Technical Data Emergency Power Failure ON Device WRE-9242/WRE-9242-G PART No. DESCRIPTION WRE-9242 Power Failure ON Device for WR61xx Relays n n WRE-9242-G Power Failure ON Device for Satellite Panel Relays n n n SPECIFICATION The Emergency Power Failure ON Device is used to switch ON two emergency relays in the event of a power failure. Upon power failure, the device will automatically switch ON two relays that are powered by utility or generator feed. This ensures that circuits will be energized if normal power is lost. The WRE-9242 switches WR-61xx series HID Latching Relays in a Douglas Lighting Control Panel. The WRE-9242-G switches the top two 704L relays in a Douglas Satellite Panel. The Emergency Power Failure ON Device mounts inside the Class 2 section of the Lighting Control Panel (WRE-9242) or the Satellite Panel (WRE-9242-G). CONNECTIONS for WRE-9242 Emergency Power Panel Power: 24VAC 250mA Class 2 Low Voltage device. n Outputs WRE-9242 Two outputs provided for Douglas WR61xx Series HID Latching Relays. WRE-9242-G Two outputs provided for Douglas 704L Latching Relays in Satellite Panels. n n Relay Interface Each of the unit's two relay outputs sends a relay ON pulse when the input 24VAC power is interrupted. n Environment Indoors, stationary, non-vibrating, noncorrosive atmosphere and noncondensing humidity. Ambient operating temperature: +15° to +120°F (-10° to +50°C) n n The WRE-9242 mounts inside the relay panel on DIN rail. It connects directly to the 2 relays controlling the emergency lighting circuits and to the transformer as shown in the schematic. Emergency Lighting Loads Inputs Normal Power Panel Relay Panel DIMENSIONS & MOUNTING Transformer 24VAC W B Blue N Relays n N Red WRE-9242 Red A B n E F G H n Blue n Utility Power Generator or AC Inverter Satellite Panel The WRE-9242 or WRE-9242-G Interface is a sealed plastic package with screw wire terminals built into it. The unit mounts onto standard 35mm DIN rail. A small 2" DIN rail piece is included for mounting. Locate the WRE-9242 in the relay panel near the relays and transformer. Locate the WRE-9242-G in the Satellite Panel on the backpan in the area above the horizontal voltage barrier. WR-9242-G CONNECTIONS for WRE-9242-G Satellite Panel Relays Red A B E F G H W B Net A Net B Net A Net B 2 Com 1 Black Yell ow Black Black Yell ow 35mm DIN Rail - LonW orks FTT-10 S ignal - D ata Signal is polarity insensitive - Tw o pairs of t erminals provided for con ven ien ce. Service Switch Service LED WINK LED Photo Sensors LonW orks Controls - Con nect Doug las WPS-55 27 or WPS- 5533 Phot o Se nsors. - Use syst em soft wa re to set set- points a nd desir ed actio n for photo se nsors. Please re fer to user manua l for ope ration of these contro ls. Reset Switch Press and hol d for 5 seconds to clear all set tings and restore fact ory default s. Locator B uzzer To help loca te Satellite pan els installed in plen ums, u se system softwar e to make this buzze r bee p. WSP-2718 Satellite Panel Control Card 1 2 1" 3 4 5 6 8 2.5" 9 3 4 5 6 7 8 9 10 10 1 2 White Blue 24VAC Blue Return 7 Power 24VAC Transformer N Blue Utility Power 2 2 24VAC WRE-9242-G Relay 1 Relay 2 1 Photo Sensors 1 2 24 VD C Power & 24VDC Inputs - Con nect 24 VDC Occupa ncy de tectors to these term ni als. - Dou glas WRM-51 04 det ector can also be conn ected to the se input s. - See user m anual fo r con nection diagr ams a nd ho w to pro gram setting s for occupa ncy dete ction. Transformer Red Terminal Block 24 VD C 24 VDC Inputs Power Source 1 Data Signal Normal Power Panel Blue N +24v Red WRE-9242 or WRE-9242-G The WRE-9242-G mounts inside the Satellite Panel on DIN rail in the area above the horizontal voltage barrier. Relays 1 and 2 (top two relays) control the emergency circuits. The WRE-9242G connects directly to the 4-position terminal block near the relays and to the transformer as shown in the schematic. Emergency Lighting Loads Emergency Power Panel Terminal Block Generator or AC Inverter www.DouglasLightingControls.com Screw Terminals 2.7"