1 Metal Enclosed and Pluggable Surge Arresters for Vm = 72.5kV R. B. Grund, Pfisterer Kontaktsysteme, and M.S. Zerrer, Pfisterer Kontaktsysteme Abstract—Surge arresters are a vital component for network safety. At Medium voltage networks (Vm ≤ 52kV), dry type pluggable surge arresters are known and widely used. This solution has now been taken to the next voltage level, Vm = 72.5kV. This paper discusses the general function, application in GIS and transformers, as well as testing. Fig. 1. Pluggable System Index Terms—Surge Arrester, High Voltage, Dry Type, PlugIn I. INTRODUCTION S urge arresters are a main component in securing a high voltage network. There are three types of overvoltage that can occur. [1] Voltage swells and overvoltage may occur during load rejection or earth connection faults. The duration lies between 0.1 seconds and several hours. In general the surge is of no danger to the network operation, however it is an important information for dimensioning of the arrester. Switching overvoltage occur during switching procedures and consist mostly of heavily damped oscillations with frequencies up to several kHz. Lightning overvoltage can reach very high values endangering the systems safety. In order to minimize these risks damaging the network, surge arresters are widely used. As we see a major change in replacing air insulated systems by cable systems -mainly in urban areas, places with lack of space and areas of high security level - surge arresters should meet the same expectation in reliability, lifetime and securing aspects. Therefore a pluggable, metal enclosed surge arrester was developed tested and is now available for service. II. MODULAR SETUP UTILIZING PLUGGABLE COMPONENTS Flexibility as well as modular setup and completely metal enclosed and therefore secure networks are getting more and more important. This can only be achieved by using pluggable components. These components allow separate manufacturing and testing. Such a connecting system consists of two main parts, the socket and the connector as shown in Fig. 1. The socket is fitted into a switchgear or transformer. The cable connector is fitted onto an XLPE or EPR insulated cable. The socket design includes a high voltage stress relief which is located inside the cast resin body connected to the high voltage contact element. Furthermore a capacitive voltage tap is optionally integrated in the socket. The separable connector which is plugged into the socket consists of the contact element an insulating part including the electrical stress relief and a metallic housing. The cable connector is a familiar product which is mainly used in the common sense of a cable accessory. Nevertheless most options are achieved whilst viewing the socket as an interface. An interface for testing, operation (as part of a cable system), operation (as part of an air insulated system) or as a connecting point for a surge arrester. Fig. 2. Surge arrester Size 4 Vm = 72.5kV This solution offers the flexibility and security directly at the hot spot of the equipment. The system above 72.5 kV is classified according to different sizes. These sizes do mainly refer to the cables dimensions. The interface is standardized whereas a size 4 socket complies to a size 4 connector, size 4 current testing connector, size 4 test joint and a size 4 surge arrester. 2 Fig. 3. Size Classification, Dry Type plug-in- Connector III. SETUP AND FUNCTION OF SURGE ARRESTER The dry type surge arrester consists of a contact element relevant for low resistance connection to the socket, utilizing contact lamellas. This type of contact allows a reliable interconnection for the operating idle current of the surge arrestor as well as the high impulse current in case of the surge arrestor has to secure from overvoltage. The insulation part of the plug-in system between high voltage and earthed parts is made of silicone. The main part, regarding the function of a surge arrestor are specific metal oxide resistor tablets. These MO-tablets are used as a non linear component with a very low leakage current during operation. The tablets are connected to the male part of the plug-in system and are insulated by a silicone body. This insulating body includes field controlling elements. The head armature includes a bursting disk for pressure relief and a turnable head for the re-direction of the gas, in the event of a failure according to IEC 60099-4. The housing is made of glass-fiber reinforced resin and allows enormous mechanical strength as well as protection of the silicon body against environmental conditions. The silicone body itself is protected and touch-proof. A special arrangement of the earthing path allows connecting monitoring devices or discharge counters if desired. more substituted by encapsulated systems. In the event of an Overvoltage impulse, started e.g. by a lightning, the wave is travelling at the high voltage line. The amplitude of that signal is mainly influenced by the intensity of the lightning as well as the distance between the position of the lightning stroke and the location of the transformer. Furthermore, every change of the surge impedance of the line, e.g. between the air insulated line and the underground cable, causes reflections and phase inversions of the traveling wave. This could lead to interferences, causing the amplitude to increase. This wave, travelling along the cable conductor of a cable system could hit into a transformer, causing damage if the insulating coordinates of the transformer is below the amplitude of that wave. One possibility to reduce the risk is achieved by adding a surge arrester at the connecting point between the air insulated line to the ground cable systems. This is a preferred position, because the transformers connections and the cable impedance mismatch, which usually doubles the amplitude of the incoming traveling wave. This leads to additional effort in calculating the network and the specific surge arrester due to additional influences by cable impedance, cable length, transformer impedance, as well as external sources. The optimum would be the positioning of a surge arrester directly at the transformer, possibly as near as possible to the transformer core. The pluggable solution offers this functionality, an additional socket is to be integrated in the transformer body, connected to the transformer core. The surge arrester assembled by a simple plug-in process is then being assembled and positioned directly at the so called “hot spot”. V. APPLICATION SWITCHGEAR In view of cable systems, a gas insulated switchgear is an additional connecting point for surge arresters. This demand is generally met by adding an gas insulated department including Metaloxyd tablets. One disadvantage of this well known technique is an additional need for SF6 as well as additional space requirement. As SF6 is known as the strongest green house gas[4], switchgear manufactures must reduce it to a minimum. Furthermore an additional gas compartment needs to be separated, monitored in view of moisture and must include a bursting relief. Fig. 4. Cut View of surge arrester Size 4 The arresters main insulation is pure silicone, there is no insulation liquid or insulation gas such as SF6 included. IV. APPLICATION TRANSFORMER Transformers are one of the main components with the need to be secured against overvoltage. Conventional surge arresters are positioned at an air insulated environment parallel to conventional bushings. As space saving is getting more important and due to safety issues, these air insulated switchyards are getting more and A Dry Type Plug-in surge arrester requires an additional socket in the existing compartment. Assembly of the surge arrester is a simple plug-in process. In the event of an Overvoltage at which the surge arrester blows up massive load of energy is distributed. This causes the surrounding of the MOx tablets to be affected as well. Utilizing an SF6 insulated arrester generally results in or replacement of the GIS compartment as well as the Spacers. In comparison a pluggable surge arrester can be replaced without gas works resulting in a reduced back in service time. 3 VI. TECHNICAL DATA Surge arrester are selected according to different aspects such as Highest system voltage Vm Handling of Neutral point (solid earth, …) Voltage swells and overvoltage (environment) Nominal Discharge Current Energy absorption Safety factors These factors lead to the electrical definitions of the surge arrester suitable for the network. TABLE I. MCOV RATINGS AND RESULTING RESIDUAL VOLTAGES VII. DETERMINATION OF TEMPORARY OVERVOLTAGE TIME CHARACTERISTIC (TOV) Due to networks setup and external influences, voltage swell as well as overvoltage might be unavoidable. Thermal stress on the metal oxide resistor tablets is the result. The maximum allowable limits regarding time and overvoltage can be determined according to a so called TOV- chart (Fig. 5). This information is crucial for networks operator to know the allowed limits for safe network operation. This measurement is therefore obligatory to pass a Type Test according to IEC 60099-4 [3]. Measurement is performed on a thermal equivalent consisting of a single tablet in its original configuration as shown in Fig. 6. This test configuration is thermally insulated at the top and the bottom to guarantee a thermal behavior which is equivalent or worse to the original configuration. Fig. 6. Test setup for TOV In operation an overvoltage could occur in a state of a maximum nominal thermal stress. Therefore pre-stress is part of the actual TOV measurement: The samples are preheated to 60°C (140°F). After preheating, two long duration current impulses are applied to reach the required energy according to IEC 60099-4 [3]. The time interval between the impulses has to be between 50s and 60s. Within less than 0.1s after the application of the second impulse, the temporary power-frequency overvoltage VTOV has to be applied for the duration tTOV. Then the elevated continuous operating voltage VMCOV’ has to be applied to prove the thermal stability. Power dissipation of the thermal equivalent must decrease or stay stable during application of VMCOV’. VMCOV’ is the elevated continuous operating voltage according to IEC 60099-4 [3]. This measurement is to be repeated with several pairs of VTOV and tTOV. As these values should be as high as possible it is the aim to get the values as near as possible to the physical limits without thermal runaway. To determine the overall power dissipation of the arrester during pre-stress the energy level is monitored and calculated. Vref is measured before and after each measurement block to ensure no physical damage of thermal equivalent. With several measurement pairs of VTOV and tTOV the following chart (Fig.5) is determined. 1,4 1,3 1,2 V/V C 1,1 1 0,9 continuous operating voltage Vc 0,8 0,1 1 10 100 t [s] Fig. 5. Power frequency versus TOV 1000 10000 4 VIII. REFERENCES References: [1] [2] [3] [4] ABB, Wettingen, July 1999, Application Guidelines Overvoltage Protection Prof. Hinrichsen, Siemens, February 2011, Surge Arrester Handbook IEC 60099-4, SURGE ARRESTERS - PART 4: METAL-OXIDE SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS P. Forster, P., V. Ramaswamy et al.: Changes in Atmospheric Constituents and in Radiative Forcing. In: Climate Change 2007: The Physical Science Basis. Contribution of Working Group I to the Fourth Assessment Report of the Intergovernmental Panel on Climate Change. Cambridge University Press, Cambridge und New York 2007, pg. 212 IX. BIOGRAPHIES Ruben Grund (M’1980) was born in Stuttgart. He graduated from the University of Applied Science Esslingen holding a degree of electrical Engineering. He works in the field of cable accessories focusing on Plug-able systems. Directed Research on a UHF PD diagnosis system for a corporate- sponsored doctoral student. Michael Zerrer (M’1976) was born in Kirchheim Teck . He graduated from the University of Stuttgart holding a degree of electrical Engineering. He worked in the field of automotive EMC measurement at the University of Stuttgart during his PhD. Since two years he is Head of R&D at PFISTERER.