Application Notes The Effect of di/dt on SCR’s used in Reduced Voltage Starting Application Challenge Customers are applying solid state reduced voltage starters on applications with increasing motor lead lengths. This increased lead length has increased concerns of di/dt issues, especially at 4160 volts and above. Problem Power cable has a value of capacitance per metre. As the length is increased, the capacitance is increased. The voltage across a capacitor cannot be changed instantaneously, so when a step voltage is applied, a large current tries to flow instantly into the capacitor to charge it to the value of the step voltage. This rapid change in current is defined as di/dt. The step voltage comes from turning on the SCR part way through the electrical cycle. If the circuit di/dt is greater than the capability of the SCR, the SCR will not be able to spread the current across the whole silicon wafer. This causes all of the circuit current to try to go through a small portion of the silicon wafer, resulting in localized heating and melting of the gate/cathode region, and failure of the SCR. Application Solution Higher values of di/dt are caused by capacitance in the circuit. The di/dt may be avoided by removing the capacitor, or limited by installing inductors, or other components to alter the surge impedance. Inductors and capacitors in the same circuit can create a resonance, which can be stimulated by the harmonics generated during the start or stop cycles of the SMC. This can result in increased peak voltages across the SCR’s and voltage failures rather than di/dt failures. An inductor or line reactor may be used to limit the di/dt in a system, which may protect the SCR's from damage. The inductor can be wired inside the MV Dialog Plus bypass loop, such that it is only in the circuit during MV Dialog Plus operation. This keeps the inductor size smaller than inductors rated for continuous duty and eliminates the heat loss during running. For power systems without power factor correction capacitors, or where the capacitors can be disconnected from the bus while the MV Dialog Plus is not in bypass, there are no di/dt restrictions if the feeder transformer is 25 MVA or smaller. For larger transformers, restrictions may apply, depending on the impedance of the transformer. The di/dt limit is not exceeded for 30 MVA transformers >6% impedance, or for 40 MVA transformer >8% impedance. For power systems where power factor correction capacitors are on the same bus as the MV Dialog Plus, a line inductor of appropriate rating may limit the di/dt to acceptable levels. Consult the factory for cable lengths above 500m, transformers above 25 MVA, or power systems with power factor correction. Note: Reference Engineering report summary ER-042-98, and application note 1560D-2.3.19. Publication 1560D-2.3.3 - January, 1999 1