15-kV Live Terminal 200 Amp Mini-Switch Source

advertisement

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Bulletin

705-110

Page 1 2015

Corrosion proof nameplate is located to provide easy access for the operator

Heavy duty 11-gauge steel enclosure is all-welded construction for long life

Safety latches on the door safety barriers, front and rear, are insulating and require a positive action to remove the safety barrier

Door safety barrier removal instructions

Clear-polycarbonate door safety barriers (front and rear) allows visual inspection without removal

“Danger – Keep Out!

Hazardous Voltage”

Nontracking self-scouring

ELRIM cycloaliphatic epoxy thru-bushings and insulators

Stainless steel hinges are welded to the door & the enclosure ─ 0.375” pins are standard

Barrier lift handles are insulating and keyed to prevent rotation

Door-holder rods are stainless steel and hold the door open

100 degrees or 140 degrees

Ground lugs on each wall of the elbow compartment accept #6 - #2/0 ground cable

Superlife finish includes phosphatizing, rust-inhibiting epoxy primer and Pad-Mount

Green (Munsell 7GY 3.29/1.5) polyurethane top coat - over 5 mils dry

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

ENCLOSURE OPTIONS:

1) 0.125” #5052H32 Aluminum

2) 12-gauge #304L Stainless Steel

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Cross-kinked roof prevents standing moisture

300 Amp copper transfer bus for source isolation

Fuse mountings accept

Arc-Strangler ®

Switchblades and/or

Arc-Strangler ® fuses

Current-Limiting

Bulletin

705-110

Page 2 2015

Field-Proven Components including Elliott thru-bushings specifically designed for

"in-air" operation gives you long-term reliable service

Standard Cable Training means quick, economical installation and assures proper operation for the life of the equipment

Tamper-Resistant Enclosure meets National and Regional

Enclosure Integrity Standards and virtually eliminates the entrance of airborne contamination to reduce maintenance

Overlapping door and enclosure flanges - with other features - provide tamper resistance to meet national and regional standards

Co-ordinated padlock and penta-head or optional hex-head bolt (top and bottom) provides bolted door security with visual confirmation by supervisory personnel.

Security bolt is made captive with a stainless steel washer compressed to an oval shape to severely discourage removal.

“Fuses” compartment label is visible with doors closed

300 Amp copper bus has rounded corners and is de-burred for corona-free operation

“In-Air” Insulation eliminates leaking or contamination of insulating medium for long trouble-free operation

“In-Air” Visibility allows visual inspection of all components without the inconvenience or expense associated with equipment which must be de-energized for inspection

“In-Air” Accessibility means every connection may be checked and tightened using hot stick tools without de-energizing the equipment

Removable lift provisions with blind holes for tamper resistance

Nonferrous hardware for long life

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Glass reinforced barriers meet

NEMA GPO-3

Standards

Open bottom and terminal arrangement allows easy cable installation and maintenance

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Bulletin

705-110

Page 3 2015

Selecting Switchgear

The switchgear shown in the circuit diagrams below is rated 8.3/14.4 kV Grounded Wye Maximum Design.

Dimension drawings showing each design can be found on pages 4 through 11 of this bulletin. The continuous-current rating of the Thru-bushings is 200 amperes with an eight-hour overload rating of 300 amperes. Bus bar terminals are copper, rated 300 amperes continuous-current. Thru-bushings and insulators are cycloaliphatic epoxy with square edge skirts and extra creep for superior contamination resistance. Four ground terminals, which accept #6 through #2/0 cable, are included and are installed as shown by the drawings.

Arc-Strangler

Arc-Strangler ®

® Switchblades are interchangeable with

Fuses (Code 1 switchblades interchange with

Code 1 fuses and Code 2 switchblades interchange with

Code 2 fuses). As a result, switchblades or fuses can be installed in any combination for every design shown in this bulletin.

Arc-Strangler ® Switchblades are rated to make and break

200 amperes. Maximum fuse size is 40 amperes utilizing

Eaton’s Cooper Power Systems Arc-Strangler NX ® Current-

Limiting Fuses. Switchblade information, fuse information and available fuse sizes can be found on pages 15 and 16 of this bulletin.

These Mini-Switches may be ordered with or without

Arc-Strangler ® Switchblades and/or Arc-Strangler

The Typical Specification on pages 12, 13 and 14 describe the design, construction and available alternate switch and fuse options.

® Fuses.

EPMS-15-311S-EL2-BT/A1

EPMS-15-311S-EL2-BT/A2

EPMS-15-311S-EL2-A1/CM4

EPMS-15-311S-EL2-A2/CM5

EPMS-15-322S-EL2-BT/A1

EPMS-15-322S-EL2-BT/A2

EPMS-15-340S-EL2-A1

EPMS-15-340S-EL2-A2

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Bulletin

705-110

Page 4 2015

Cable Training and Anchor Bolt Locations

CL

Front View

Door & Door Safety

Barrier Removed

CL

Rear View

Door & Door Safety

Barrier Removed

Enclosure

2.25" X 2.25"

Galv. Square

Washer

Ø.5"

Anchor

Bolts

1.5"

Concrete Pad

Alternate #1

Enclosure

Elliott Anchor

Bracket

#6102-A81-7

Ø.5"

Anchor

Bolts

1.5"

Concrete Pad

Alternate #2

Section BB and Typical Pad Dimensions

Catalog Number Switchblade/Fuse Mounting Dim. “A”

EPMS-15-311S-EL2-BT/A1

EPMS-15-311S-EL2-BT/A2

8.3 kV (Code 1) 1.5 to 40 Amp

Arc-Strangler NX ® Fuse

15.5 kV (Code 2) 1.5 to 40 Amp

Arc-Strangler NX ® Fuse

19.625”

15.125”

When additional cable terminating space is required, a 48” or 54” high enclosure can be supplied to increase cable terminating space by

6” or 12”. To order a 48” high enclosure, suffix the catalog number “-48H”. To order a 54” high enclosure, suffix the catalog number “-54H”.

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Three-Phase – Two Ways Per Phase

200 Amp Elliott Air-Insulated Thru-Bushings

8.3/14.4 kV Grounded Wye Max Design

95 kV BIL

Bulletin

705-110

Page 5 2015

30"

"Bus" Label is Visible with Door Closed

A

A B C

Provision for

Padlock and

Security Bolt,

Top and Bottom

42"

30"

"Fuses" Label is Visible with Door Closed

C

7.5"

B

7.5"

A

CL B

7.5"

CL

7.5"

A

Front View

Door & Door Safety

Barrier Removed

B

30"

Rear View

Door & Door Safety

Barrier Removed

42"

28"

26"

Bottom

Open

Equipment

Plate

CL

2"

8.5"

40"

38"

7.5" 7.5"

8.5"

Projected

Centerline of Cables

42" 42"

34"

200 Amp

Elliott

Thru-Bushing

GPO-3

Barriers

"A"

Door Safety

Barrier

Front and Rear

CL

Section BB

ø 0.75"

Typical

Two

Ground

Provisions

Each Side

CL

Section AA

Catalog Number Switchblade/Fuse Mounting Dim. “A”

EPMS-15-311S-EL2-BT/A1

EPMS-15-311S-EL2-BT/A2

8.3 kV (Code 1) 1.5 to 40 Amp

Arc-Strangler NX ® Fuse

15.5 kV (Code 2) 1.5 to 40 Amp

Arc-Strangler NX ® Fuse

19.625”

15.125”

When additional cable terminating space is required, a 48” or 54” high enclosure can be supplied to increase cable terminating space by

6” or 12”. To order a 48” high enclosure, suffix the catalog number “-48H”. To order a 54” high enclosure, suffix the catalog number “-54H”.

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Bulletin

705-110

Page 6 2015

Cable Training and Anchor Bolt Locations

30" 30"

42"

B

7.5" 7.5"

CL

Front View

Door & Door Safety

Barrier Removed

B

"A"

6" Min.

7.5" 7.5"

CL

Rear View

Door & Door Safety

Barrier Removed

"A"

6" Min.

Enclosure

2.25" X 2.25"

Galv. Square

Washer

Ø.5"

Anchor

Bolts

1.5"

Concrete Pad

Alternate #1

Enclosure

Elliott Anchor

Bracket

#6102-A81-7

Ø.5"

Anchor

Bolts

1.5"

Concrete Pad

Alternate #2

Section BB and Typical Pad Dimensions

Catalog Number Switchblade/Fuse Mounting Dim. “A”

EPMS-15-311S-EL2-A1/CM4

EPMS-15-311S-EL2-A2/CM5

8.3 kV (Code 1) Arc-Strangler ® /8.3 kV (Code 4)

1.5 to 40 Amp Clip Mounted CL Fuse

15.5 kV (Code 1) Arc-Strangler ® /8.3 kV (Code 5)

1.5 to 140 Amp Clip Mounted CL Fuse

19.625”

15.125”

When additional cable terminating space is required, a 48” or 54” high enclosure can be supplied to increase cable terminating space by

6” or 12”. To order a 48” high enclosure, suffix the catalog number “-48H”. To order a 54” high enclosure, suffix the catalog number “-54H”.

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Three-Phase – Two Ways Per Phase

200 Amp Elliott Air Insulated Thru-Bushings

8.3/14.4 kV Grounded Wye Max Design

95 kV BIL

Bulletin

705-110

Page 7 2015

CL

Front View

Door & Door Safety

Barrier Removed

CL

Rear View

Door & Door Safety

Barrier Removed

Section BB Section AA

Catalog Number Switchblade/Fuse Mounting Dim. “A”

EPMS-15-311S-EL2-A1/CM4

EPMS-15-311S-EL2-A2/CM5

8.3 kV (Code 1) Arc-Strangler ® /8.3 kV (Code 4)

1.5 to 40 Amp Clip Mounted CL Fuse

15.5 kV (Code 1) Arc-Strangler ® /8.3 kV (Code 5)

1.5 to 140 Amp Clip Mounted CL Fuse

19.625”

15.125”

When additional cable terminating space is required, a 48” or 54” high enclosure can be supplied to increase cable terminating space by

6” or 12”. To order a 48” high enclosure, suffix the catalog number “-48H”. To order a 54” high enclosure, suffix the catalog number “-54H”.

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Bulletin

705-110

Page 8 2015

Cable Training and Anchor Bolt Locations

CL CL

Front View

Door & Door Safety

Barrier Removed

Rear View

Door & Door Safety

Barrier Removed

Enclosure

2.25" X 2.25"

Galv. Square

Washer

Ø.5"

Anchor

Bolts

1.5"

Concrete Pad

Alternate #1

Enclosure

Elliott Anchor

Bracket

#6102-A81-7

Ø.5"

Anchor

Bolts

1.5"

Concrete Pad

Alternate #2 Section BB and Typical Pad Dimensions

Catalog Number Switchblade/Fuse Mounting Dim. “A”

EPMS-15-322S-EL2-BT/A1

EPMS-15-322S-EL2-BT/A2

8.3 kV (Code 1) 1.5 to 40 Amp

Arc-Strangler NX ® Fuse

15.5 kV (Code 2) 1.5 to 40 Amp

Arc-Strangler NX ® Fuse

19.625”

15.125”

When additional cable terminating space is required, a 48” or 54” high enclosure can be supplied to increase cable terminating space by

6” or 12”. To order a 48” high enclosure, suffix the catalog number “-48H”. To order a 54” high enclosure, suffix the catalog number “-54H”.

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

B

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Bulletin

705-110

Page 9 2015

Three-Phase – Four Ways Per Phase

200 Amp Elliott Air-Insulated Thru-Bushings

8.3/14.4 kV Grounded Wye Max Design

95 kV BIL

"Bus" Label is Visible with Door Closed

48"

A "Fuses" Label is Visible with Door Closed

48"

Provision for

Padlock and

Security Bolt,

Top and Bottom

A B C C B A

48"

6.5" 6.5"

3.25"

CL

6.5"

3.25"

6.5"

A

Front View

Door & Door Safety

Barrier Removed

B

A

6.5"

B

6.5"

3.25"

C

CL

C

6.5"

3.25"

B

6.5"

A

Rear View

Door & Door Safety

Barrier Removed

CL

CL

Section BB

CL

Section AA

Catalog Number Switchblade/Fuse Mounting Dim. “A”

EPMS-15-322S-EL2-BT/A1

EPMS-15-322S-EL2-BT/A2

8.3 kV (Code 1) 1.5 to 40 Amp

Arc-Strangler NX ® Fuse

15.5 kV (Code 2) 1.5 to 40 Amp

Arc-Strangler NX ® Fuse

19.625”

15.125”

When additional cable terminating space is required, a 48” or 54” high enclosure can be supplied to increase cable terminating space by

6” or 12”. To order a 48” high enclosure, suffix the catalog number “-48H”. To order a 54” high enclosure, suffix the catalog number “-54H”.

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Bulletin

705-110

Page 10 2015

Cable Training and Anchor Bolt Locations

CL CL

Front View

Door & Door Safety

Barrier Removed

Rear View

Door & Door Safety

Barrier Removed

Enclosure

2.25" X 2.25"

Galv. Square

Washer

Ø.5"

Anchor

Bolts

1.5"

Concrete Pad

Alternate #1

Enclosure

Elliott Anchor

Bracket

#6102-A81-7

Ø.5"

Anchor

Bolts

1.5"

Concrete Pad

Alternate #2 Section BB and Typical Pad Dimensions

Catalog Number Switchblade/Fuse Mounting Dim. “A”

EPMS-15-340S-EL2-A1

EPMS-15-340S-EL2-A2

8.3 kV (Code 1) 1.5 to 40 Amp

Arc-Strangler NX ® Fuse

15.5 kV (Code 2) 1.5 to 40 Amp

Arc-Strangler NX ® Fuse

19.625”

15.125”

When additional cable terminating space is required, a 48” or 54” high enclosure can be supplied to increase cable terminating space by

6” or 12”. To order a 48” high enclosure, suffix the catalog number “-48H”. To order a 54” high enclosure, suffix the catalog number “-54H”.

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Bulletin

705-110

Page 11 2015

Three-Phase – Four Ways Per Phase

200 Amp Elliott Air-Insulated Thru-Bushings

8.3/14.4 kV Grounded Wye Max Design

95 kV BIL

CL

Front View

Door & Door Safety

Barrier Removed

CL

Rear View

Door & Door Safety

Barrier Removed

CL

CL

Section BB

CL

Section AA

Catalog Number Switchblade/Fuse Mounting Dim. “A”

EPMS-15-340S-EL2-A1

EPMS-15-340S-EL2-A2

8.3 kV (Code 1) 1.5 to 40 Amp

Arc-Strangler NX ® Fuse

15.5 kV (Code 2) 1.5 to 40 Amp

Arc-Strangler NX ® Fuse

19.625”

15.125”

When additional cable terminating space is required, a 48” or 54” high enclosure can be supplied to increase cable terminating space by

6” or 12”. To order a 48” high enclosure, suffix the catalog number “-48H”. To order a 54” high enclosure, suffix the catalog number “-54H”.

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Typical Specification - Page 1 of 3

Bulletin

705-110

Page 12 2015

General

The switchgear shall be 15 kV Class, 95 kV BIL,

200 ampere continuous current, suitable for use on

8.3/14.4 kV grounded wye max design systems. The switchgear shall be constructed for connection to the utility system with bolt-on cable terminals and stress-relief devices

(Elastimold ® modular terminators, Joslyn PS terminators or equal to be supplied by the user). The switchgear shall be designed for and contain switch and fuse mountings that accept both Eaton’s Cooper Power Systems Arc-Strangler ®

Switchblades and Arc-Strangler NX ® Fuses. A door safety barrier shall be provided inside the door(s) as recommended in IEEE Standard C2 (National Electrical Safety Code) Rule

381G. Tamper resistance shall meet the Enclosure Security requirements of IEEE Standard C57.12.28 (Pad-Mounted

Equipment—Enclosure Integrity). Together, the tamper resistance and the door safety barrier(s) shall resist unauthorized entry, protect authorized and unauthorized persons, and provide positive safety features when installed in areas accessible to the general public. The switchgear shall be constructed for outdoor installation in areas subject to heavy precipitation and in areas with windblown contamination. The equipment shall be “air-insulated” and completely assembled prior to shipment.

Enclosure Construction

The enclosure shall be tamper-resistant, all-welded construction utilizing 11-gauge minimum sheet steel. Corner plates and braces shall be used as necessary to assure rigidity.

The enclosure top shall be cross-kinked to provide watershed and rigidity. The enclosure shall be open bottom with a 1-inch flange inside, all around. The door(s) shall be furnished with a stainless steel door holder that will latch the door open

100 degrees and 140 degrees and resist accidental closing.

Door(s) shall be provided with provisions for padlocking and a recessed penta-head (or hex-head) security bolt to prevent unauthorized entry (coordinated to prevent installation of the padlock until the security bolt is tightened when closing the door(s ) and to prevent a wrench from operating the security bolt until the padlock is removed when opening the door(s)) . The security bolt shall be made captive with a stainless steel washer compressed to an oval shape to severely discourage removal.

Hinges shall be stainless steel (with stainless steel pins not less than 0.3125-inch diameter) and shall be welded to both the enclosure and the door(s) to maintain door alignment for the life of the equipment. The enclosure shall be nonventilated to minimize the entrance of airborne contamination, insects, rodents or reptiles. The protective finish shall include necessary grinding, cleaning and phosphatizing, two-component rustinhibiting epoxy primer and a Pad-Mount Green two-component polyurethane top coat finish ( Munsell color 7GY 3.29/1.5).

The primer and top coat shall be electronically monitored during application to insure proper ratio and mixing of each component. Total average thickness of paint (after curing) shall

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296 be not less than 5 mils. The protective coating shall meet the

Enclosure Coating System requirements of IEEE Standard

C57.12.28 (Pad-Mounted Equipment—Enclosure Integrity).

Removable lift provisions, adequate to withstand handling with normal utility equipment, shall be provided on the outside of the enclosure. Threaded openings for lift provision bolts shall be blind holes to prevent the entrance of wire or other foreign objects into the enclosure when lift provisions are removed.

Switches

Alternate 1: Switch provisions shall be Code 1 to accept Eaton’s Cooper Power Systems 200 ampere loadbreak 8.3 kV and 15.5 kV (short) Arc-Strangler ®

Switchblades. When specified, switchblades shall be supplied in the switchgear. An available option is a holder for each switchblade that will allow storage (and retrieval) of the

Arc-Strangler ® Switchblade with hot-line tools. Switchblade storage shall not interfere with opening or closing the door(s).

Alternate 2: Switch provisions shall be Code 2 to accept Eaton’s Cooper Power Systems 200 ampere loadbreak 15.5 kV (long) Arc-Strangler ® Switchblades.

When specified, switchblades shall be supplied in the switchgear. An available option is a holder for each switchblade that will allow storage (and retrieval) of the

Arc-Strangler ® Switchblade with hot-line tools. Switchblade storage shall not interfere with opening or closing the door(s).

Bus and Fuse Mountings

Bus shall be copper with all burrs and sharp corners removed prior to installation. Fuse clips and/or fuse hinges shall be keyed to prevent rotation and to maintain alignment.

Positive pressure shall be assured by use of stainless steel fasteners and lock washers or compression washers at all connection points. All connections shall provide direct contact of current-carrying parts and shall not depend on current transfer through fastener thread-to-thread contact. Fuses and their blown-fuse indicators shall be visible (when the fuse compartment door(s) are open) without removal of the clearpolycarbonate door safety barrier to allow easy identification of blown fuses without de-energizing or removing the fuse from service. Electrical components shall be “air-insulated” and positioned to allow visual inspection of all internal connections and components without removing the clear-polycarbonate door safety barrier , de-energizing or removing the equipment from service.

Alternate 1: Fuse mountings shall be Mounting Code 1 to accept 1.5 amp to 40 amp (max), 8.3 kV Eaton’s Cooper

Power Systems Arc-Strangler NX ® current-limiting fuses.

Spare-fuse storage is optional. When specified, a spare-fuse holder shall be provided for each fuse position that will allow storage (and retrieval) of the Arc-Strangler ® fuse with hot-line tools. Spare-fuse storage shall not interfere with opening or closing the doors.

Alternate 2: Fuse mountings shall be Mounting Code 2

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Typical Specification - Page 2 of 3

Bulletin

705-110

Page 13 2015 to accept 1.5 amp to 40 amp (max), 15.5 kV Eaton’s Cooper

Power Systems Arc-Strangler NX ® current-limiting fuses.

Spare-fuse storage is optional. When specified, a spare-fuse holder shall be provided for each fuse position that will allow storage (and retrieval) of the Arc-Strangler ® closing the doors.

fuse with hot-line tools. Spare-fuse storage shall not interfere with opening or

Bushings and Terminals

Bushings shall be 200 ampere Elliott #1351-215TB,

15 kV class (8.3 kV to ground) Air-Insulated Live-Terminal

Thru-Bushings, 95 kV BIL, for use with 8.3/14.4 kV systems.

The bushings shall be pressure-molded cycloaliphatic epoxy with a 0.75-inch diameter copper conductor that is drilled and tapped 0.375-inch – 16UNC x 1-inch deep on both ends to provide for connection of the bus and/or live parts. Integral shielding shall be provided to eliminate partial discharge caused by off-center mounting and mounting holes that may have sharp edges or burrs. Bushings shall mount in a 3.125-inch diameter opening and bolt in place to allow field replacement with standard tools. The bushing mounting bolts shall be self-locking stainless steel serrated-flange hex-head bolts that “cut” through the enclosure protective finish to ground the integral shielding of each bushing. To assure adequate strength for apparatus support, the bushing shall withstand a minimum cantilever loading of 250 pounds for five minutes without damage. Each bushing shall be tested in free air, mounted in a grounded steel plate not less than 10 inches x

10 inches and shall meet the requirements for 15 kV devices in accordance with the test values of IEEE Standard 386 (latest revision), including 100 percent production testing.

“Bushing-Style” Thru-Insulators

Insulators shall be Elliott #1351-025TI, 25 kV class

(15.2 kV to ground) Air-Insulated “Bushing-Style”

Thru-Insulators, 125 kV BIL, for use with 8.3/14.4 kV or

15.2/26.3 kV systems.

The insulators shall be nontracking, self-scouring, nonweathering pressure-molded cycloaliphatic epoxy with cast-in-place brass inserts. The brass inserts shall be drilled and tapped 0.375-inch – 16UNC x 1-inch deep to provide for connection of the bus and/or live parts. The skirts shall be square-edge design to provide 17 inches or more leakage distance for superior contamination resistance.

Surface damage to insulators shall expose material of the same composition and characteristics so insulators with minor surface damage will not require replacement. The insulators shall provide adequate thermal cycle withstand to assure trouble-free field service in the most severe climatic conditions established by in-house testing and field-operating experience. Insulators shall mount in a 3.125-inch diameter opening and bolt in place to allow field replacement with standard tools. To assure adequate strength for apparatus support, the insulator shall withstand a minimum cantilever loading of 600 pounds for five minutes without damage. The

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296 insulator mounting bolts shall be self-locking stainless steel serrated-flange hex-head bolts.

Insulators

The switch and bus insulators shall be nontracking, self-scouring, nonweathering pressure-molded cycloaliphatic epoxy with cast-in-place brass inserts. The skirts shall be square-edge design to provide 14 inches or more leakage distance for superior contamination resistance. Surface damage to insulators shall expose material of the same composition and characteristics so insulators with minor surface damage will not require replacement. The insulators shall provide adequate thermal cycle withstand to assure trouble-free field service in the most severe climatic conditions established by in-house testing and field-operating experience.

The insulators shall be 15 kV class, 95 kV BIL and produced by a manufacturer with ten or more years experience with cycloaliphatic epoxy.

Barriers

Phase and ground barriers shall be provided to assure correct phase-to-phase and phase-to-ground clearances for proper operation at rated voltage. These barriers shall be glass-reinforced polyester (NEMA GPO-3 class material) not less than 0.1875-inch thick.

A removable insulating barrier with a “DANGER – Keep

Out! – Hazardous voltage” sign, Elliott #7203-D2003-309, shall be located inside the door(s) as recommended in Rule

381G of IEEE Standard C2 (National Electrical Safety Code).

The door safety barriers shall be constructed of 0.25-inch clear-polycarbonate (Lexan or equal) and shall completely close the door opening and be provided with a non-conductive safety latch requiring a positive action to remove the barrier.

Handles and other hardware extending through this door safety barrier shall be nonconductive material. Handles shall be keyed to prevent rotation for secure handling. Complete visual inspection of the internal components shall be possible without removing the door safety barrier .

Grounding Provisions

Four high-conductivity bronze eyebolt-type ground lugs, which accept #6 through #2/0 copper conductor, shall be installed on the inside walls of the enclosure (located on each side of each door opening in an accessible position as shown on the drawings).

Accessory Equipment

A corrosion proof nameplate with permanent thermal transfer printing shall be installed inside one door on the switch

(or bus) compartment. It shall be located at the top corner farthest from the live equipment when the door is open. The nameplate will provide Type of Equipment, Model Number,

Amps Continuous, kV Maximum, BIL, Serial Number, Job

Number, Date Manufactured and Weight of Equipment.

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Typical Specification - Page 3 of 3

Bulletin

705-110

Page 14 2015

The enclosure shall be labeled in near proximity of the locking provisions with a pressure-sensitive vinyl label using letters not less than 0.375-inch nor more than 0.625-inch high. The label shall indicate the type of equipment behind the access (switch, fuses, bus, etc.).

When specified, mounting provisions for distribution-class metal-oxide-varistor surge arresters shall be provided at each source-side switch terminal.

When specified, four anchor-bolt brackets, Elliott

#6102-A81-7 or approved equal, shall be supplied with each switchgear to provide a means of clamping the equipment to the concrete pad.

Packaging

Each switchgear shall be bolted to a solid-top wood pallet

(to prevent the forks of a forklift truck from entering the open bottom of the equipment) to prevent hidden damage. The equipment shall be wrapped with 0.125-inch thick polyethylene foam or other suitable material to minimize damage to the finish during shipment.

Drawings

When specified, drawings shall be furnished for each switchgear that include:

1) enclosure dimensions and location of components.

2) proposed pad dimensions and location of anchor bolts.

15-kV Thru-Bushings

“B” Series (bolt in) for Air-Insulated Service

200 Amp Thru-Bushing #1351-215TB

Thru-Insulator #1351-025TI

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Bulletin

705-110

Page 15 2015

NX ® Hinge-Style Arc-Strangler ® Switchblade

Ratings

The Arc-Strangler used on NX ®

® loadbreaking device

switchblades meets all the requirements of IEEE Standard C37.47. It has a continuous-current rating of 200 amps, its momentary and closing-in rating is 18,000 amps, and its loadbreaking ability is five operations at 200 amps at 80% power factor. At smaller current levels, more operations are possible.

Two-hundred amp switchblades with integral Arc-Strangler ® loadbreaking devices are available for use in NX ® fuse mountings.

They are completely interchangeable with

NX ® fuses of the same code number so that, as system needs change, switches can be substituted for fuses and vice versa without any alteration to the mounting.

Pullring

Arc-Strangler ®

Sleeve

Voltage

(kV)

8.3

15.5

15.5

Ratings and Dimensions

Rating

Continuous and Loadbreak

Current (amp)

200

200

200

Description

Blade

Short 15 kV Blade

Long 15 kV Blade

Mounting

Code

Number*

1

1

2

*Code number of mounting must match code number of fuse or switchblade.

Dimension

A

(in.)

13.3125

13.3125

17.8125

Catalog

Number

FA1B1

FA4B1

FA3B1

Switchblade

Hinge

8.875”

A

NX ® Fuses with Arc-Strangler ® Loadbreaking Device

NX ® current-limiting fuses up to 15.5 kV can be ordered with an integral Arc-Strangler ® loadbreaking device. These units have the same operating characteristics as the basic clip style fuse, along with loadbreaking capabilities.

A B

See Page 20

C

Latch Spring

Actuator Spring

Core

Fuse Conductor

Arc-Strangler ®

Sleeve

Plastic

Accessory Latch

Replaces the

Latch Spring

Blown-Fuse

Indicator

Button

Arc-Strangler ® loadbreaking device with optional accessory latch.

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com

15-kV Live Terminal 200 Amp Mini-Switch

Source-Isolated Pad-Mounted Switchgear

40 Amp (Max) Arc-Strangler NX ® Fuses

Bulletin

705-110

Page 16 2015

NX ® Fuses With Arc-Strangler ® Loadbreaking Device

Features

Eaton’s Cooper Power Systems NX fuses with Arc-Strangler

®

® loadbreaking device offer:

Safe loadbreaking . The Arc-Strangler ® loadbreak quickly extinguishes load-current arcs drawn between the mounting contacts and the fuse conductor during loadbreaking operation.

Prevention from accidental closing .

The Arc-Strangler ® loadbreaking device must be cocked before the fuse can be closed into the mounting.

NEMA standard hookstick operation .

Both the pullring and the hinge accept the standard distribution-class hookstick.

The hinge is made with a slot for the hookstick, making fuse removal from— and replacement in—the mounting easy.

Blown-fuse indication . A red button is clearly visible after the fuse has operated.

High-voltage warning . The big warning label (readable when the fuse is hanging open) warns personnel of possible danger.

Optional latch . A plastic latch that gives a positive indication that the device is armed is available as an accessory (See

Page 15).

Operating Principles

The Arc-Strangler ® loadbreaking device is a springloaded sliding sleeve that cuts off the arc drawn between the mounting contacts and the fuse conductor when the fuse is opened while load current is flowing. A pullring at the top of the fuse

(for hookstick operation) and a hinge at the bottom complete the loadbreak device.

The Arc-Strangler ® loadbreak is complete in itself—no auxiliary loadbreaking tool is required and no additional loadbreaking switch in series is necessary. All current magnitudes through the continuous-current rating of the fuse can be interrupted positively and safely under proper conditions.

The loadbreaking assembly includes a stationary core and a sliding molded sleeve that covers the contacts on opening the hinged assembly. The sleeve is made of high-quality material that gives off small quantities of arc-quenching gases under the heat of the arc.

Voltage

(kV)

50,000 amps Symmetrical Interrupting Rating

Rating

Continuous

Current

(amp)

Mounting

Code

Number*

For Single and Parallel Unit Hinge Style Mountings

Fuse

Diameter

(In.)**

8.3

5.5

4.3

15.5

20

25

30

40

8

10

12

18

40

50

65

75

1.5

3

4.5

6

18

20

25

30

6

8

10

12

50

65

75

100

18

25

35

45

20

25

30

40

8

10

12

18

1.5

3

4.5

6

*Code number of mounting must match code number of fuse or switchblade.

**All 2 -in. diameter fuses have magniformed end fittings with stamped hinge.

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

1.125

1.125

1.125

1.125

2

2

2

2

1.125

1.125

1.125

2

2

2

2

2

1.125

1.125

1.125

2

1.125

1.125

1.125

1.125

1.125

2

2

2

2

2

2

2

2

2

2

2

1.125

1.125

1.125

2

Description

1.125-in. diameter

hinged fuse

Voltage

Rating

(kV)

4.3, 5.5,

and 8.3

15.5

4.3, 5.5,

Dimensions

Mounting

Code

Number*

1

2

A

(in.)

13.3125

17.8125

See Page 15

B

(in.)

8.875

8.875

2-in. diameter

hinged fuse

and 8.3

15.5

1

2

13.3125

18

8.9375

9.125

*Code number of mounting must match code number of fuse or switchblade.

NX ® and Arc-Strangler ® are registered trademarks of Eaton in the U.S. and other countries

Elliott Industries, Inc.

© Copyright 2015

1509 Hamilton Road

Phone 318-746-3296

Catalog

Number

FA2A40

FA2A50

FA2A65

FA2A75

FA3A1

FA3A3

FA3A4

FA3A6

FA3A8

FA3A10

FA3A12

FA3A18

FA3A20

FA3A25

FA3A30

FA3A40

FA1A18

FA1A25

FA1A35

FA1A45

FA1A50

FA1A65

FA1A75

FA1A100

FA2A6

FA2A8

FA2A10

FA2A12

FA2A18

FA2A20

FA2A25

FA2A30

FA4A1

FA4A3

FA4A4

FA4A6

FA4A8

FA4A10

FA4A12

FA4A18

FA4A20

FA4A25

FA4A30

FA4A40

C

(in.)

1.375

1.375

2.4375

2.4375

Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd.

Bossier City, LoUiSiAna 71111

Fax 318-741-1127 sales@elliott-industries.com

www.elliott-industries.com