Padmount Switchgear Service Information VFI Tester Operating Instructions Figure 1. VFI Tester. S285-10-7 030052KM Contents Safety Information ..................................................... 2 Description of Tester ................................................. 5 Hazard Statement Definitions ................................ 2 Operating Procedures .............................................. 6 Safety Instructions .................................................. 2 Control Tests .......................................................... 8 Product Information .................................................. 3 SCADA Accessory Tests ........................................12 Introduction ............................................................ 3 External Flux-Shift Tripper Tests ............................17 Acceptance and Initial Inspection .......................... 3 Battery Test ............................................................18 Handling and Storage ............................................ 3 Service Information ...................................................19 Quality Standards ................................................... 3 Appendices ................................................................20 Description ............................................................. 3 LCD Message Screens ..........................................20 Specifications ............................................................ 4 Control Board Reference Illustrations ....................21 New • July 2004 Printed in USA 1 VFI Tester Operating Instructions ! SAFETY FOR LIFE ! SAFETY FOR LIFE SAFETY FOR LIFE Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our “Safety For Life” mission. SAFETY INFORMATION The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: • Is thoroughly familiar with these instructions. • Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. • Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. • Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Safety Instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER: Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high and low voltage lines and equipment. G103.3 ! WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling, or maintenance can result in death, severe personal injury, and equipment damage. ! G101.0 Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. ! WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. ! CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. ! CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. 2 WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury, and equipment damage. G102.1 ! WARNING: Power distribution equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install, or maintain power distribution equipment can result in death, severe personal injury, and equipment damage. G122.2 ! ! S285-10-7 SAFETY FOR LIFE PRODUCT INFORMATION Introduction Quality Standards Service Information S285-10-7 provides operating instructions for the VFI Tester device use in conjunction with Cooper Power Systems Padmounted VFI switchgear. Before operating this device, carefully read and understand the contents of this manual. ISO 9001:2000-Certified Quality Management System For additional information, refer to the following applicable service information bulletins: • S285-10-1 Kyle ® Type VFI, Oil-Insulated, Vacuum Fault Interrupter; Installation, Operation, and Maintenance Instructions • S285-10-2 Kyle ® Type VFI, SF6-Insulated, Vacuum Fault Interrupter; Installation, Operation and Maintenance Instructions. • S285-15-1 Kyle ® Type Shrubline VFI, Vacuum Fault Interrupter; Installation, Operation and Maintenance Instructions. • S285-75-1 Kyle ® Tri-Phase, TPG, and TPG with SCADA Electronic Control Installation and Operation Instructions. Read This Manual First Read and understand the contents of this manual and follow all locally approved procedures and safety practices before operating this equipment. Additional Information These instructions cannot cover all details or variations in the equipment, procedures, or process described, nor provide directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user's purpose, please contact your Cooper Power Systems Representative. Acceptance and Initial Inspection This test set is in good condition at the factory and when accepted by the carrier for shipment. Upon receipt, inspect the test set thoroughly for damage and loss of parts incurred during shipment. If damage or missing parts are discovered, file a claim immediately with the carrier. Handling and Storage Be careful during handling and storage of the Type VFI Tester to minimize the possibility of damage. If the tester is to be stored for any length of time prior to use, provide a clean, dry storage area. Description The VFI tester is a current injection device designed to simulate Fault Current for verification of minimum trip values and time current characteristics of Tri-phase and TPG electronic control boards utilized in Kyle type VFI padmounted switchgear. Three internal flux-shift trippers enable confirmation of the presence of sufficient levels of energy upon the control board for operation of padmounted VFI flux-shift trippers. The on-board flux-shift trippers also enable selfchecking of the VFI tester prior to general control testing. Further flux-shift tripper capability enables verification of operation of the flux-shift trippers within the VFI unit under test, external to the VFI tester. The tester has the capability to perform the following operational tests: • Minimum-Trip Tests • Time Current Curve Characteristic Tests • Control Operation Test • Instantaneous Trip Test • Time-Current Curve Characteristics Modifier • Limited Testing of SCADA accessory board functions including verification of the minimum trip multiplier function and inrush restraint feature. • Battery Test • Flux-Shift Tripper Tests Test settings are adjusted via a series of rotary, toggle, and push button switches on the front panel of the tester. Banana jacks on the front panel facilitate connection of a Fluke or equivalent multimeter for verification of fault current injection values. Simulated phase and ground fault currents may be set in the range of 4-900 A by using the millampere reading of the digital multimeter as directly equivalent to reading the primary fault current in amperes. A two-line, 16 character LCD display provides tester status, TCC trip times, and battery test information. The VFI Tester is fan cooled and features thermal protection circuitry which disables the tester if the internal temperature exceeds 65°C. Additional overload protection is provided by an automatic time-out circuit which limits testing to 5 minutes during unsupervised tests. The VFI tester requires 120 Vac, single phase power for operation. Inboard power is protected by a 8 A resettable circuit breaker and is controlled by a large, illuminated rocker type switch on the front panel. A three conductor power cable is furnished with the tester. 3 VFI Tester Operating Instructions SPECIFICATIONS Input Weight AC Input: 120 Vac ±10% 60 Hz, single phase, circuit breaker protected at 8 A. 15.87 kg (35 lbs) - cables excluded Output Temperature Range 4-900 mA actual, simulating 4-900 A fault current levels. Continuously adjustable, through multiple ranges with coarse and fine control. Operating Range: 0° to 50°C Instrumentation LCD Display Storage Range: -20°C to 65°C CAUTION: Equipment misoperation. This device must be operated in dry environments only. So not operate it in rain, snow, or sleet. Failure to comply can result in equipment misoperation and possible personal injury. G141.0 ! 16 character, 2-line LCD display. Current Measurement Auxiliary Output: Banana jacks on the front of the tester panel provide the means for connecting an external, user-provided, multimeter for measurement of simulated fault current levels produced by tester unit. Accuracy is dependent upon the calibration standards and procedures employed during calibration of the user supplied multimeter. 120 Vac, 3 A GFI duplex outlet provides 120 Vac threewire supply power for operation of low wattage devices such as auxiliary measurement equipment, notebook computers and supplementary lighting. Protective Circuits NOTE: Overloading of the 3 A rated GFI protected convenience outlet will result in complete shutdown of the VFI tester device. Ground Fault Protection Interface Cables Ground fault sensing capabilities enables automatic shut down of the tester upon detection of a ground fault current within the tester or through the 120 Vac convenience outlet on the tester front panel. A set of two interface cables are provided with each VFI tester unit. Each cable is 4.6 m (15 ft.) in length with connectors appropriate for the type of control and VFI unit specified at time of order. Internal Thermal Cutoff VFI Tester automatically shuts off upon exceeding 65°C (149°F) internal temperature. Cutoff resets upon internal temperature cooling to below 50°C(122°F). Side-Hinged VFI units with TPG controls utilize cable set 6A00393601. All VFI units with Tri-Phase controls and Top-Hinged VFI units with TPG controls utilize cable set 6A00393501. Automatic Shutdown An automatic timer circuit turns off the tester if any control test exceeds five minutes in duration. 14-pin female to 14-pin male Interrupter Interface Cable Side-Hinged VFI w/TPG Cable Set Part No. 6A00393601 AC Power Cord 19-pin male to 14-pin female Control Interface Cable A 2.3 m (7.5 ft.) 3-conductor power cord is provided. Carrying Case 14-pin female to 18-pin recessed male Interrupter Interface Cable The VFI tester is housed in a high impact case with detachable cover, and has a compartment for storing the power cord and interconnecting cables. Dimensions (Approximate) 318 mm (12.5”) High 432 mm (17”) Wide 432 mm (17”) Deep All VFI w/Tri-Phase and Top-Hinged VFI w/TPG Cable Set Part No. 6A00393501 19-pin male to 18-pin female Control Interface Cable Figure 2. Kyle® VFI Tester Cable Set Options 4 ! S285-10-7 SAFETY FOR LIFE DESCRIPTION OF TESTER 16 TO INTERRUPTER B 1 A K L C J P M D H N E F VFI EXTERNAL TRIPPERS G INTERNAL TRIPPERS 15 Tester TO CONTROL CONTROL TEST AØ BØ M L U K J T H CØ S G A N V B C P D R F 14 E CURRENT 2 METER JACKS TEST SELECT 13 PHASE SELECT A-PHASE TRIPPER 17 12 3 B-PHASE TRIPPER BATTERY CONNECTOR ON 18 30A 4 BATTERY TEST ON ON 19 60A 24 ON 20 21 120A 23 11 ON C-PHASE TRIPPER 240A 10 TRIPPER TEST 2X 22 4-30A 1X 4-30A 25 5 TEST 6 RESET 9 CONTROL TEST INPUT POWER 120 VAC CONVENIENCE OUTLET 120 VAC Power Systems 8 7 Figure 3. VFI Tester Front Panel TABLE 1 Description and Functionality of VFI Tester Front Panel Features Item No. (Figure 3) Description Purpose and Use 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 VFI Cable Connector Multi-meter Connection Jacks Battery Test Terminals Battery Test Switch Power Switch AC Power Receptacle Cooling Fan Intake Port Cooling Fan Exhaust Port GFI Convenience Outlet Tripper Test Switch C-Phase Flux Shift Tripper B-Phase Flux Shift Tripper A-Phase Flux Shift Tripper Control Cable Receptacle Phase Select Switch Testing Mode Selector Switch 17 18 19 20 21 22 23 24 25 LED Display 30 A Current Adder Switch 60 A Current Adder Switch 120 A Current Adder Switch 240 A Current Adder Switch 1X/2X Current Multiplier Switch 4-30 A Fault Current Rheostat 4-30 A Rheostat Enable Switch Fault Test Switch Interface for External VFI Switch Connector Cable Measurement of Injection Current Levels Interface for Battery Test cable Initiates battery test Energizes 120 Vac input to tester Interface for 120Vac Power Cable Unit Cooling Unit Cooling 120 Vac, 3 A Ground Fault Protected Outlet for auxiliary power for meters, etc. Verification of Internal Tripper Operation Actuates when control board under test issues trip signal Actuates when control board under test issues trip signal Actuates when control board under test issues trip signal Interface for Tri-Phase/TPG Control Test Cable Selection of phase to be tested Selection of either external test of flux-shift trippers within VFI unit under test, internal self-check of flux-shift trippers within VFI tester, or general Tri-phase/TPG Control Test Mode Displays Test Data and Tester Status Information Operation of switch adds 30 A of test current to total output of Tester Unit Operation of switch adds 60 A of test current to total output of Tester Unit Operation of switch adds 120 A of test current to total output of Tester Unit Operation of switch adds 240 A of test current to total output of Tester Unit Multiplies Designated Current Levels by a factor of two Provides variable adder of 4-30 A Fault Current Level to total output of Tester Unit Enables operation of 4-30 A Fault Current Rheostat (Item 23) Initiates injection of simulated fault current to VFI control 5 VFI Tester Operating Instructions OPERATING PROCEDURES Tester operating procedures have been grouped three functional groups; Control Tests, Flux-Shift Tripper Tests, and Battery Tests. Each group of tests is preceded by pre-test setup instructions which specify any required settings for the tester and the device under test. Verify these settings before starting any tests. Upon completion of testing, return the control settings to the desired operating conditions before returning the control to service. NOTE: A 5 K ohm resistor is required to complete certain procedures detailed in this bulletin. For specific information regarding the operation and adjustment of Kyle ® Tri-Phase and TPG Controls refer to Service Information Bulletin S285-75-1, Kyle Tri-Phase, TPG, and TPG w/SCADA Electronic Control Installation and Operation Instructions. WARNING: Hazardous voltage. Always use a shotgun stick when working with this equipment. Failure to do so could result in contact with high voltage, which will cause death or severe personal injury. ! G108A.0 WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury, and equipment damage. G102.1 ! 4. Connect the 19-pin male/14-pin female control interface cable (Item 2) to the VFI Tester at the Control port. WARNING: Hazardous voltage. Open the switch associated with the control before attempting to disconnect its control cable. Failure to do so can result in contact with high voltage pulse (300 V peak) from the CT protection circuit, which can cause death or severe personal injury. T287.0 ! 5. Break the connection between the control and VFI unit by disconnecting the VFI control cable (Item 3) from the male receptacle located on the outside of the TPG control enclosure. 6. Connect the 14-pin male connector end of the tester interrupter interface cable (Item 1) to the 14-pin female end of the padmount cable (Item 3) originating from the front plate of the VFI unit under test. 7. Connect the 14-pin female connector end of the VFI tester control interface cable (Item 2) to the male receptacle of the TPG control enclosure. 8. Proceed with the testing procedures as detailed in this service bulletin. To return the unit under test to service: 1. Verify that the VFI Switches under test are in the open position. 2. Turn off the VFI tester. CAUTION: Equipment misoperation. This device must be operated in dry environments only. So not operate itw in rain, snow, or sleet. Failure to comply can result in equipment misoperation and possible personal injury. G141.0 ! Testing In-Service VFI Units The following procedures must be followed if an in-service VFI padmounted switchgear unit is to be tested with the VFI tester apparatus. 14-pin female connector at cable end 14-pin male connector at cable end TPG Control Enclosure Item 3 VFI Control Cable Side-Hinged Units with TPG Controls 1. Open the VFI Switches 2. Attach the power cable to the VFI tester and plug it into a grounded, three-prong 120 Vac outlet. Item 1 Interrupter Interface Cable Item 2- Control Interface Cable VFI TO INTERRUPTER EXTERNAL TRIPPERS INTERNAL TRIPPERS TO CONTROL Tester CONTROL TEST Afl Bfl Cfl 19-pin male connector at cable end CURRENT IMPORTANT: This device must be connected to a properly grounded, 3-wire 120 Vac power source to ensure safe and reliable operation. Do not operate it using a “floating” power source such as a portable generator. METER JACKS TEST SELECT PHASE SELECT A-PHASE TRIPPER B-PHASE TRIPPER BATTERY CONNECTOR 14-pin female connector at cable end ON ON ON ON 30A 60A 120A 240A C-PHASE TRIPPER BATTERY TEST ON 2X 4-30A TRIPPER TEST 1X 4-30A TEST RESET CONTROL TEST INPUT POWER 120 VAC 3. Connect the 14-pin female/14-pin male interrupter interface cable (Item 1) to the VFI Tester at the interrupter port. Refer to Figure 4 for steps 3 through 8. 6 Power Systems CONVENIENCE OUTLET 120 VAC Figure 4. Connection of the VFI Tester to side-hinged VFI units with TPG controls. ! S285-10-7 SAFETY FOR LIFE 3. Disconnect the 14-pin female connector end of the tester control interface cable (Item 2) from the TPG control enclosure. Refer to Figure 4 for steps 3 through 8. 4. Disconnect the 14-pin male connector end of the VFI tester interrupter interface cable (Item 1) from the 14pin female end of the VFI control cable (Item 3) originating from the front plate of the VFI unit under test. CAUTION: Equipment misoperation. The capacitors upon the Tri-phase and TPG boards will retain a charge of 20 Vdc upon completion of control testing. Apply a 5 k ohm resister between ground and the P1-7, P1-5, and P1-3 board terminals for 10 seconds prior to returning the control to service. Failure to comply can result in false tripping activity by the control upon reinstallation. T318.0 5. Reconnect the VFI control cable (Item 3) to the receptacle located upon the TPG control enclosure housing. IMPORTANT: Always wear a grounding wrist strap to control static electricity before handling circuit boards. Attach wrist strap to ground terminal located upon the front plate of the VFI unit. Failure to use this strap may result in circuit board damage. 5. Break the connection between the control and VFI unit by carefully disconnecting the internal VFI control wiring harness (Item 3) at the control. 6. Connect the 18-pin male connector end of the VFI tester interrupter interface cable (Item 1) to the 18pin female end of the VFI control wire harness (Item 3). 7. Connect the 18-pin female connector end of the tester control interface cable (Item 2) to the 18-pin male header of the Tri-Phase/TPG board. 8. Proceed with the testing procedures as detailed within this service bulletin. To return the unit under test to service: 6. Disconnect the interrupter and control interface cables (Items 1 and 2) from the VFI tester and store the cables in the storage compartment located in the cover of the VFI tester. 1. Verify that the VFI Switches under test are in the open position. 7. Close the VFI switches. 3. Disconnect the 18-pin female connector end of the tester control interface cable (Item 2) from the 18-pin male header of the Tri-Phase/TPG board. Refer to Figure 5 for steps 3 through 7. Top-Hinged VFI Units with TPG Controls/All Tri-Phase Controls 1. Open the VFI Switches. 2. Attach the power cable to the VFI tester and plug it into a grounded, three-prong 120 Vac outlet. 2. Turn off the VFI tester. 4. Disconnect the 18-pin male connector end of the tester interrupter interface cable (Item 1) from the 18pin female end of the VFI control wire harness (Item 3). IMPORTANT: This device must be connected to a properly grounded, 3-wire 120 Vac power source to ensure safe and reliable operation. Do not operate it using a “floating” power source such as a portable generator. 3. Connect the 14-pin female/18-pin male interrupter interface cable (Item 1) to the VFI Tester at the interrupter port. Refer to Figure 5 for steps 3 through 8. 4. Connect the 19-pin male/18-pin female control interface cable (Item 2) to the VFI Tester at the control port. WARNING: Hazardous voltage. Open the switch associated with the control before attempting to disconnect its control cable. Failure to do so can result in contact with high voltage pulse (300 V peak) from the CT protection circuit, which can cause death or severe personal injury. T287.0 ! CAUTION: Equipment damage. Use care while disconnecting and reconnecting cables to the TriPhase/TPG control. Do not misalign male and female connectors or allow the full weight of the tester cable to be transferred to the Tri-Phase/TPG board. Failure to comply can result in damage to the board header and possible equipment misoperation. T319.0 Tri-Phase/ TPG Board 18-pin male header Item 3 VFI Control Wire Harness 18-pin female connector 18-pin female connector 18-pin recessed male connector VFI TO INTERRUPTER B A L C M D P N E F EXTERNAL TRIPPERS INTERNAL TRIPPERS TO CONTROL Tester M L U T CONTROL TEST Afl Bfl A N V S P R Cfl CURRENT METER JACKS TEST SELECT Item 2 Control Interface Cable PHASE SELECT A-PHASE TRIPPER Item 1 Interrupter Interface Cable B-PHASE TRIPPER BATTERY CONNECTOR ON ON ON ON 30A 60A 120A 240A C-PHASE TRIPPER BATTERY TEST ON 2X 4-30A TRIPPER TEST 1X 4-30A TEST RESET CONTROL TEST INPUT POWER 120 VAC Power Systems CONVENIENCE OUTLET 120 VAC Figure 5. Connection of VFI Tester to top-hinged VFI units with TPG controls and all VFI units with Tri-Phase controls. 7 VFI Tester Operating Instructions CAUTION: Equipment misoperation. The capacitors upon the Tri-phase and TPG boards will retain a charge of 20 Vdc upon completion of control testing. Apply a 5 k ohm resister between ground and the P1-7, P1-5, and P1-3 board terminals for 10 seconds prior to returning the control to service. Failure to comply can result in false tripping activity by the control upon reinstallation. T318.0 Note: Once a control test is initiated, pressing and releasing the control test button a second time will result in the test being aborted. Battery tests can not be conducted during a control test. Initial Tester Setup 5. Reconnect the VFI control wire harness (Item 3) to the 18-pin male receptacle located upon the Triphase/TPG control. Refer to Figure 3 for identification of individual VFI Tester switches and other features referenced within the following setup procedures. 6. Disconnect the interrupter and control interface cables (Items 1 and 2) from the VFI tester and store the cables in the storage compartment located in the cover of the VFI tester. 1. Connect the VFI tester to the VFI Padmount unit following the procedures described in the TESTING INSERVICE VFI UNITS section of this service bulletin. 7. Close the VFI switches. 2. Connect external multi-meter to the multi-meter tester connection jacks and set external meter to appropriate current measurement range. 3. Energize the tester by setting the power switch to ON. Control Tests The VFI tester enables testing and verification of minimum trip timing values for each phase of the VFI unit. Testing at nominal test current values of 150, 300 and 1000 percent of minimum trip current levels verifies Triphase/TPG board response at current levels typically requiring slow, medium and fast trip operations. Current Adder Switches ON ON ON ON 30A 60A 120A 240A Conduct Internal Flux-Shift Tripper Test The internal VFI Tester flux-shift trippers should be tested for correct operation at the beginning of every control testing session. Failure to verify the correct operation of the internal flux-shift trippers prior to a control test could result in an erroneous assessment of control performance, in the event of a malfunction of the internal VFI Tester flux-shift trippers. Verify the internal flux-shift trippers are operational with the following procedure: 1. Depress all three internal flux-shift trippers. Refer to Figure 3 for steps 1 through 8. ON 2X 2. Place the Test Selector Switch into the INTERNAL TRIPPERS position. 4-30A 1X 3. Place the Phase Selector Switch into the A-PHASE position. 4-30A Rheostat Enable Switch 4-30A Rheostat 4-30A 1X/2X Current Multiplier Switch CONTROL TEST Figure 6. VFI Tester Current Adjustment Switches Test current values are set by selectively closing a group of toggle switches controlling a stepped network of resistors within the VFI tester unit (Figure 6). Placing the 4-30 A toggle switch into the ON position enables operation of a 4-30 A fine adjustment rheostat for precise adjustment of test current levels. Pressing the Control Test button of the VFI tester initiates injection of simulated fault current into the Tri-Phase/TPG control board and concurrently begins measurement of the accrued time between test initialization and and issuance of a trip signal. Upon issuance of a trip signal, the flux-shift tripper of the respective phase being tested 8 should operate as the LCD display indicates the accrued trip-time interval. 4. Press and release the Tripper Test button. The APhase flux-shift tripper on the VFI tester should operate immediately. 5. Place the Phase Selector Switch into the B-PHASE position. 6. Press and release the Tripper Test button to initiate the test. The B-Phase flux-shift tripper on the VFI tester should operate immediately. 7. Place the Phase Selector Switch into the C-PHASE position. 8. Press and release the Tripper Test button to initiate the test. The C-Phase flux-shift tripper on the VFI tester should operate immediately. 8. Depress all of the flux-shift trippers on the VFI tester. Upon completion of the internal Flux-Shift Tripper Test, complete the initial set-up procedure as follows: 1. Place the Test Select switch into the CONTROL TEST position. 2. Place the Phase Select switch into the A-PHASE position. ! S285-10-7 SAFETY FOR LIFE Initial Tri-phase/TPG Control Setup IMPORTANT: Always wear a grounding wrist strap to control static electricity before handling circuit boards. Attach wrist strap to ground terminal located upon the front plate of the VFI unit. Failure to use this strap may result in circuit board damage. Refer to Figures 9 and 10 for locations of individual control switches referenced within the following procedures. 1. Set the minimum trip levels on A-phase, B-phase, and C-phase to 50 A. 2. Set the control board for Single Phase/Independent Trip. Instantaneous Trip Test - Ground (TPG only) Setup: 1. Verify that the settings of the tester and control are as described in the Initial Tester Setup and Initial Triphase/TPG Control Setup sections of this bulletin. 2. Place the Ground Trip Block switch on the control board in the OFF position. 3. Place the Ground Instantaneous Trip switch on the control board into the ON position. Test Procedure: 3. Set the Ground Trip level to 50 A (TPG only). 1. Set the minimum trip levels on A-, B-, and C-phase to 690 A while maintaining the Ground Trip level setting at 50 A. 4. Set the Ground Trip Block Switch in the ON position (TPG only). 2. Turn the 4-30 A rheostat adjusting knob fully counterclockwise. Instantaneous Trip Test - Phase Setup 1. Verify that the settings of the tester and control are as described in the Initial Tester Setup and Initial Triphase/TPG Control Setup sections of this bulletin. 2. Place the Phase Instantaneous Trip switch on the control board into the ON position. Test Procedure VFI Tester Operation: 1. Place the 4-30 A and 30 A Fault Current toggle switches into the ON position. 2. Turn the 4-30 A rheostat adjusting knob fully counterclockwise. 3. Press and release the Control Test button to initiate flow of simulated fault current to the control. 4. Slowly turn the 4-30 A rheostat adjusting knob clockwise while monitoring the current value on the multimeter. Verify that the A-Phase flux-shift tripper on the VFI tester operates when the fault current exceeds 50 A. 5. Place the Phase Select switch into the B-PHASE position. 3. Place the Phase Select Switch into the A-PHASE position. 4. Turn the 4-30 A rheostat adjusting knob fully counterclockwise. 5. Press and release the Control Test button to initiate flow of simulated fault current to the control. 6. Slowly turn the 4-30 A rheostat adjusting knob clockwise while monitoring the current value on the multimeter. 7. Verify that the A-Phase, B-Phase, and C-Phase fluxshift trippers on the VFI tester operate when the fault current exceeds 50 A. 8. Depress the flux-shift trippers for all three phases. 9. Place the Phase Select Switch to the B-PHASE position. 10. Repeat steps 2 through 7. 11. Place the Phase Select Switch to the C-PHASE position. 12. Repeat steps 2 through 7. 13. Return the minimum trip levels on A-Phase, BPhase, and C-Phase on the control board to 50 A. 6. Repeat steps 2 through 4. 14. Place the Ground Trip Block switch on the control board to the ON position. 7. Place the Phase Select switch into the C-PHASE position. 15. Place the Ground Instantaneous Trip switch on the control board into the OFF position. 8. Repeat steps 2 through 4. Time Current Curve (TCC) Trip Test Phase 9. Return the Phase Instantaneous Trip switch on the control board into the OFF position. CAUTION: Equipment misoperation. The capacitors upon the Tri-phase and TPG boards will retain a charge of 20 Vdc upon completion of control testing. Apply a 5 k ohm resister between ground and the P1-7, P1-5, and P1-3 board terminals for 10 seconds prior to returning the control to service. Failure to comply can result in false tripping activity by the control upon reinstallation. T318.0 Setup – 150% of minimum trip - Phase: 1. Verify that the settings of the tester and control are as described in the Initial Tester Setup and Initial Triphase/TPG Control Setup sections of this bulletin. 2. Place the 4-30 A and 60 A Fault Current switches on the VFI tester into the ON position. All other Fault Current switches should be in the OFF position. 9 VFI Tester Operating Instructions 3. Place the Phase Select Switch on the VFI tester into the A-PHASE position. 6. Press and release the Control Test button to terminate flow of simulated fault current to the control. 4. Set the minimum trip level for A-Phase on the control board to 690 A. This prevents the control from issuing a trip signal when calibrating the fault current. 7. Set the minimum trip level for A-Phase on the control board to 50 A. 5. Press and release the Control Test button to initiate flow of simulated fault current to the control. 6. While monitoring the fault current on the multimeter, adjust the 4-30 A rheostat adjusting knob until the multimeter reads 75 mA ± 5 mA. 7. Press and release the Control Test button to terminate flow of simulated fault current to the control. 8. Set the minimum trip level for A-Phase on the control board to 50 A. Test Procedure – 150% of minimum trip - Phase: The Phase Minimum-Trip test is performed as follows: 1. Press and release the Control Test button to initiate flow of simulated fault current to the control. 2. Upon operation of the flux-shift tripper record the time displayed on the LCD, and compare it with the 150% entry in Table 2 for the timing card that is used in the control board. 3. Place the Phase Select switch into the B-PHASE position. Repeat steps 2 and 3. 4. Place the Phase Select Switch on the VFI tester into the C-PHASE position. Repeat steps 2 and 3. Test Procedure – 300% of minimum trip - Phase: 1. Press and release the Control Test button to initiate flow of simulated fault current to the control. 2. Upon operation of the flux-shift tripper record the time displayed on the LCD, and compare it with the 300% entry in Table 2 for the timing card that is used in the control board. 3. Place the Phase Select switch into the B-PHASE position. Repeat steps 2 and 3. 4. Place the Phase Select Switch on the VFI tester into the C-PHASE position. Repeat steps 2 and 3. Setup – 1000% of minimum trip - Phase: 1. Place the 4-30 A, 240 A Fault Current switches on the VFI tester into the ON position, and the 1X/2X Fault Current switch on the VFI tester into the 2X position. All other Fault Current switches should be in the OFF position. 2. Place the Phase Select Switch on the VFI tester into the A-PHASE position. 3. Set the minimum trip level for A-Phase on the control board to 690 A. This prevents the control from issuing a trip signal when calibrating the fault current. 4. Press and release the Control Test button to initiate flow of simulated fault current to the control. Setup – 300% of minimum trip - Phase: 1. Place the 4-30 A and 120 A Fault Current switches on the VFI tester into the ON position. All other Fault Current switches should be in the OFF position. 2. Place the Phase Select Switch on the VFI tester into the A-PHASE position. 3. Set the minimum trip level for A-Phase on the control board to 690 A. This prevents the control from issuing a trip signal when calibrating the fault current. 4. Press and release the Control Test button to initiate flow of simulated fault current to the control. 5. While monitoring the fault current on the multimeter, adjust the 4-30 A rheostat adjusting knob until the multimeter reads 150 mA ± mA. 5. While monitoring the fault current on the multimeter, adjust the 4-30 A rheostat adjusting knob until the multimeter reads 500 mA ± 35 mA. 7. Press and release the Control Test button to terminate flow of simulated fault current to the control. 8. Set the minimum trip level for A-Phase on the control board to 50 A. Test Procedure – 1000% of minimum trip - Phase: 1. Press and release the Control Test button to initiate flow of simulated fault current to the control. 2. Upon operation of the flux-shift tripper record the time displayed on the LCD, and compare it with the TABLE 2 Acceptable Control Response Time Range for TCC Tests Acceptable Control Response Time Range for TCC Tests Percentage of Test Current EF Curve KF Curve TF Curve H Curve F Curve 150% 3.484-6.461 sec 16.632-43.509 sec 23.696-47.054 sec 2.023-3.182 sec 2.200-3.361 sec 300% 0.532-0.838 sec 0.586-0.895 sec 1.645-2.863 sec 0.441-0.726 sec 0.476-0.762 sec 1000% 0.058-0.087 sec 0.038-0.070 sec 0.193-0.279 sec 0.032-0.052 sec 0.112-0.132 sec * NOTE: These timing ranges represent ± 10% in current or time, or ±10ms, whichever is greater. 10 ! S285-10-7 SAFETY FOR LIFE 300% entry in Table 2 for the timing card that is used in the control board. 3. Set the minimum trip level on the A-, B-, and CPhases of the control board to 690 A. 3. Place the Phase Select switch into the B-PHASE position. Repeat steps 2 and 3. 4. Place the 4-30 A and 120 A Fault Current switches on the VFI tester into the ON position. All other Fault Current switches should be in the OFF position. 4. Place the Phase Select Switch on the VFI tester into the C-PHASE position. Repeat steps 2 and 3. Ground-Minimum Trip Test – TPG Only Setup – 150% of minimum trip - Ground (TPG Only): 1. Verify that the settings of the tester and control are as described in the Initial Tester Setup and Initial Triphase/TPG Control Setup sections of this bulletin. 5. Press and release the Control Test button to initiate flow of simulated fault current to the control. 6. While monitoring the fault current on the multimeter, adjust the 4-30 A rheostat adjusting knob until the multimeter reads 150 mA ± 10 mA. 7. Press and release the Control Test button to terminate flow of simulated fault current to the control. 2. Place the Ground Trip Block switch on the control board into the OFF position. 8. Set the minimum trip level for Ground on the control board to 50 A. 3. Set the minimum trip level on the A-, B-, and CPhases of the control board to 690 A. Test Procedure – 300% of minimum trip – Ground (TPG only): 4. Place the 4-30 A and 60 A Fault Current switches on the VFI tester into the ON position. All other Fault Current switches should be in the OFF position. 5. Press and release the Control Test button to initiate flow of simulated fault current to the control. 6. While monitoring the fault current on the multimeter, adjust the 4-30 A rheostat adjusting knob until the multimeter reads 75 mA ± 5 mA. 7. Press and release the Control Test button to terminate flow of simulated fault current to the control. 8. Set the minimum trip level for Ground on the control board to 50 A. Test Procedure – 150% of minimum trip – Ground (TPG only) 1. Place the Phase Select Switch on the VFI tester into the A-PHASE position. 2. Press and release the Control Test button to initiate flow of simulated fault current to the control. 3. When the control board issues a trip signal, the A-, Band C-Phase flux-shift trippers should operate, and the timer will stop. 4. Record the time displayed on the LCD, and compare it with the 150% entry in Table 2 for the timing card that is used in the control board. 5. Depress the flux-shift trippers for all three phases. 6. Place the Phase Select switch into the B-PHASE position. 7. Repeat steps 2 through 5. 8. Place the Phase Select switch into the C-PHASE position. 9. Repeat steps 2 through 5. Setup – 300% of minimum trip – Ground (TPG only): 1. Verify that the settings of the tester and control are as described in the Initial Tester Setup and Initial Triphase/TPG Control Setup sections of this bulletin. 2. Place the Ground Trip Block switch on the control board into the OFF position. 1. Place the Phase Select Switch into the A-PHASE position. 2. Press and release the Control Test button to initiate flow of simulated fault current to the control. 3. When the control board issues a trip signal, the APhase, B-Phase, and C-Phase flux-shift trippers should operate, and the timer will stop. 4. Record the time displayed on the LCD, and compare it with the 300% entry in Table 2 for the timing card that is used in the control board. 5. Depress the flux-shift trippers for all three phases. 6. Place the Phase Select switch into the B-PHASE position. 7. Repeat steps 2 through 5. 8. Place the Phase Select switch into the C-PHASE position. 9. Repeat steps 2 through 5. Setup – 1000% of minimum trip - Ground: (TPG only) 1. Verify that the settings of the tester and control are as described in the Initial Tester Setup and Initial Triphase/TPG Control Setup sections of this bulletin. 2. Place the Ground Trip Block switch on the control board into the OFF position. 3. Set the minimum trip level on the A-, B-, and CPhases of the control board to 690 A. 4. Place the 4-30 A, and 240 A Fault Current switches on the VFI tester into the ON position, and the 1X/2X Fault Current switch on the VFI tester into the 2X position. All other Fault Current switches should be in the OFF position. 5. Press and release the Control Test button to initiate flow of simulated fault current to the control. 6. While monitoring the fault current on the multimeter, adjust the 4-30 A rheostat adjusting knob until the multimeter reads 500 mA ± 35 mA. 7. Press and release the Control Test button to terminate flow of simulated fault current to the control. 8. Set the minimum trip level for Ground on the control board to 50 A. 11 VFI Tester Operating Instructions Test Procedure – 1000% of minimum trip – Ground (TPG only): 1. Place the Phase Select Switch into the A-PHASE position. 2. Press and release the Control Test button to initiate flow of simulated fault current to the control. 3. When the control board issues a trip signal, the APhase, B-Phase, and C-Phase flux-shift trippers should operate, and the timer will stop. 4. Record the time displayed on the LCD, and compare it with the 1000% entry in Table 2 for the timing card that is used in the control board. 5. Depress the flux-shift trippers for all three phases. 6. Place the Phase Select switch into the B-PHASE position. 7. Repeat steps 2 through 5. 8. Place the Phase Select switch into the C-PHASE position. 9. Repeat steps 2 through 5. CAUTION: Equipment misoperation. The capacitors upon the Tri-phase and TPG boards will retain a charge of 20 Vdc upon completion of control testing. Apply a 5 k ohm resister between ground and the P1-7, P1-5, and P1-3 board terminals for 10 seconds prior to returning the control to service. Failure to comply can result in false tripping activity by the control upon reinstallation. T318.0 SCADA Board Tests –TPG 4. Place the 30 A Fault Current switch into the ON position. Place all of the other Fault Current switches into the OFF position. 5. Reset the target by pressing the Control Test button, waiting 5 seconds, and then pressing the Control Test button again. The A-Phase Fault Target should now be black. 6. Place the Phase Select switch into the B-PHASE position. 7. Repeat steps 1 and 2. 8. After the B-Phase flux-shift tripper operates, verify that the B-Phase Fault Target on the SCADA board is orange. 9. Place the 30 A Fault Current toggle switch into the ON position. Place all of the other Fault Current switches into the OFF position. 10. Reset the target by pressing the Control Test button, waiting 5 seconds, and then pressing the Control Test button again. The B-Phase Fault Target should now be black. 11. Place the Phase Select switch into the C-PHASE position. 12. Repeat steps 1 and 2. 13. After the C-Phase flux-shift tripper operates, verify that the C-Phase Fault Target on the SCADA board is orange. 14. Place the 30 A Fault Current switch into the ON position. Place all of the other Fault Current switches into the OFF position. Refer to Figure 11 for identification of individual SCADA accessory board components referenced within the following procedures. 15. Reset the target by pressing the Control Test button, waiting 5 seconds, and then pressing the Control Test button again. The C-Phase Fault Target should now be black. IMPORTANT: Always wear a grounding wrist strap to control static electricity before handling circuit boards. Attach wrist strap to ground terminal located upon the front plate of the VFI unit. Failure to use this strap may result in circuit board damage. 16. Place the Ground Trip Block switch into the OFF position (TPG only). 17. Set the minimum trip levels on A-phase, B-phase, and C-phase to 690 A. 18. Reset the flux-shift trippers. Fault Target Test 19. Repeat steps 1 and 2. Setup 20. After all three of the flux-shift trippers operate, verify that the Ground Fault Target on the SCADA board is orange. 1. Verify that the settings of the tester and control are as described in the Initial Tester Setup and Initial Triphase/TPG Control Setup sections of this bulletin. 2. Place the Phase Instantaneous Trip switch on the control board into the ON position. Test Procedure 1. Place the 60 A Fault Current switch into the ON position. Place all of the other Fault Current switches into the OFF position. 2. Press and release the Control Test button to initiate the test. 3. After the A-Phase flux-shift tripper operates, verify that the A-Phase Fault Target on the SCADA board is orange. 12 21. Place the 30 A Fault Current switch into the ON position. Place all of the other Fault Current switches into the OFF position. 22. Press and release the Control Test button, wait 5 seconds, then press and release the Control Test button again. The C-Phase Fault Target should now be black. 23. Place the Ground Trip Block switch into the ON position (TPG only). 24. Reset the flux-shift trippers. ! SAFETY FOR LIFE Emergency Minimum Trip Multiplier Test S285-10-7 Control Setup – 5X minimum trip multiplier test (250 A) 1. Verify that the settings of the tester and control are as described in the Initial Tester Setup and Initial Triphase/TPG Control Setup sections of this bulletin. 1. Set the emergency trip multiplier switches for APhase, B-Phase, and C-Phase for ‘5X’ (.8X + 3.2X +1X default). TPG Control Setup – 2X minimum trip multiplier test (100 A) Test Procedure – 5X minimum trip multiplier test 250 A) 1. Place the Phase Instantaneous Trip switch into the ON position. 1. Place the 4-30 A and 240 A Fault Current switches on the VFI tester into the ON position. All other Fault Current switches should be in the OFF position. 2. Set the emergency trip multiplier switches for APhase, B-Phase, and C-Phase for 2X (.2X + .8X +1X default). 2. Turn the 4-30 A rheostat adjusting knob fully counterclockwise. Test Procedure – 2X minimum trip multiplier test (100 A) 3. Place the Phase Select Switch on the VFI tester into the A-Phase position. 1. Place the 4-30 A, 30 A, and 60 A Fault Current toggle switches on the VFI tester into the ON position. All other Fault Current switches should be in the OFF position. 4. Press and release the Control Test button to initiate flow of simulated fault current to the control. 2. Turn the 4-30 A rheostat adjusting knob fully counterclockwise. 3. Place the Phase Select Switch on the VFI tester into the A-PHASE position. 4. Press and release the Control Test button to initiate flow of simulated fault current to the control. 5. Slowly turn the 4-30 A rheostat adjusting knob clockwise while monitoring the current value on the multimeter. Verify that the A-Phase flux-shift tripper on the VFI tester operates when the fault current exceeds 100 A (2X the minimum trip setting of 50 A). 6. Turn the 4-30 A rheostat adjusting knob fully counterclockwise. 7. Place the Phase Select Switch on the VFI tester into the B-PHASE position. 8. Press and release the Control Test button to initiate flow of simulated fault current to the control. 9. Slowly turn the 4-30 A rheostat adjusting knob clockwise while monitoring the current value on the multimeter. Verify that the B-Phase flux-shift tripper on the VFI tester operates when the fault current exceeds 100 A (2X the minimum trip setting of 50 A). 10. Turn the 4-30 A rheostat adjusting knob fully counterclockwise. 11. Place the Phase Select Switch on the VFI tester into the C-PHASE position. 12. Press and release the Control Test button to initiate flow of simulated fault current to the control. 13. Slowly turn the 4-30 A rheostat adjusting knob clockwise while monitoring the current value on the multimeter. Verify that the C-Phase flux-shift tripper on the VFI tester operates when the fault current exceeds 100 A (2X the minimum trip setting of 50 A). 5. Slowly turn the 4-30 A rheostat adjusting knob clockwise while monitoring the current value on the multimeter. Verify that the A-Phase flux-shift tripper on the VFI tester operates when the fault current exceeds 250 A (5X the minimum trip setting of 50 A). 6. Turn the 4-30 A rheostat adjusting knob fully counterclockwise. 7. Place the Phase Select Switch on the VFI tester into the B-Phase position. 8. Press and release the Control Test button to initiate flow of simulated fault current to the control. 9. Slowly turn the 4-30 A rheostat adjusting knob clockwise while monitoring the current value on the multimeter. Verify that the B-Phase flux-shift tripper on the VFI tester operates when the fault current exceeds 250 A (5X the minimum trip setting of 50 A). 10. Turn the 4-30 A rheostat adjusting knob fully counterclockwise. 11. Place the Phase Select Switch on the VFI tester into the C-Phase position. 12. Press and release the Control Test button to initiate flow of simulated fault current to the control. 13. Slowly turn the 4-30 A rheostat adjusting knob clockwise while monitoring the current value on the multimeter. Verify that the C-Phase flux-shift tripper on the VFI tester operates when the fault current exceeds 250 A (5X the minimum trip setting of 50 A). CAUTION: Equipment misoperation. The capacitors upon the Tri-phase and TPG boards will retain a charge of 20 Vdc upon completion of control testing. Apply a 5 k ohm resister between ground and the P1-7, P1-5, and P1-3 board terminals for 10 seconds prior to returning the control to service. Failure to comply can result in false tripping activity by the control upon reinstallation. T318.0 13 VFI Tester Operating Instructions Inrush Restraint Tests 1. Verify that the settings of the tester and control are as described in the Initial Tester Setup and Initial Triphase/TPG Control Setup sections of this bulletin. Control Setup – 2X minimum trip multiplier during inrush (100 A), 1 second reset time 1. Set the Phase Instantaneous Trip switch into the ON position. 2. Place the Inrush Restraint switch into the ON position. 17. Depress the B-Phase flux-shift tripper. 18. Place the 120 A Fault Current switch into the OFF position. 19. Place the Phase Select Switch on the VFI tester into the C-PHASE position. 20. Press and release the Control Test button to initiate flow of simulated fault current to the control. 21. Verify that the C-Phase flux-shift tripper on the VFI tester operates after 1 second ± 10%. 22. Depress the C-Phase flux-shift tripper. 3. Place the Ground Trip Block During Inrush switch into the ON position. 23. Place the 120 A Fault Current switch into the ON position. 4. Set the A-Phase, B-Phase, and C-Phase Inrush Restraint Minimum Trip Multiplier switches for 2X (1X + 1X default setting). 24. Press and release the Control Test button to initiate flow of simulated fault current to the control. 5. Set the Reset Time switches for 1 seconds (.5 sec + .5 sec default setting). 6. Place the 4-30 A, 30 A, and 60 A Fault Current switches on the VFI tester into the ON position. All other Fault Current switches should be in the OFF position. Test Procedure – 2X minimum trip multiplier during inrush (100 A), 1 second reset time 1. Place the Phase Select Switch on the VFI tester into the A-PHASE position. 2. Press and release the Control Test button to initiate flow of simulated fault current to the control. 3. Verify that the A-Phase flux-shift tripper on the VFI tester operates after 1 second ± 10%. 4. Depress the A-Phase flux-shift tripper. 5. Place the 120 A Fault Current switch into the ON position. 6. Press and release the Control Test button to initiate flow of simulated fault current to the control. 7. Verify that the A-Phase flux-shift tripper on the VFI tester operates immediately. 8. Depress the A-Phase flux-shift trippers. 9. Place the 120 A Fault Current switch into the OFF position. 10. Place the Phase Select Switch on the VFI tester into the B-PHASE position. 11. Press and release the Control Test button to initiate flow of simulated fault current to the control. 12. Verify that the B-Phase flux-shift tripper on the VFI tester operates after 1 second ± 10%. 13. Depress the B-Phase flux-shift trippers. 14. Place the 120 A Fault Current switch into the ON position. 15. Press and release the Control Test button to initiate flow of simulated fault current to the control. 16. Verify that the B-Phase flux-shift tripper on the VFI tester operates immediately. 14 25. Verify that the C-Phase flux-shift tripper on the VFI tester operates immediately. 26. Depress the C-Phase flux-shift tripper. 27. Place the 120 A Fault Current switch into the OFF position. Control Setup – 5X minimum trip multiplier during inrush (250 A), 3 second reset time 1. Set the A-Phase, B-Phase, and C-Phase Inrush Restraint Minimum. Trip Multiplier switches for 5X (4X + 1X default setting). 2. Set the Reset Time switches for 3 seconds (.5 sec + 2 sec + .5 sec default setting). 3. Place the 240 A Fault Current switch on the VFI tester into the ON position. All other Fault Current switches should be in the OFF position. Test Procedure – 5X minimum trip multiplier during inrush (250 A), 3 second reset time 1. Place the Phase Select Switch on the VFI tester into the A-PHASE position. 2. Press and release the Control Test button to initiate flow of simulated fault current to the control. 3. Verify that the A-Phase flux-shift tripper on the VFI tester operates after 3 seconds ± 10%. 4. Depress the A-Phase flux-shift tripper. 5. Place the 30 A Fault Current switch into the ON position. All other Fault Current switches should be in the OFF position. 6. Press and release the Control Test button to initiate flow of simulated fault current to the control. 7. Verify that the A-Phase flux-shift tripper on the VFI tester operates immediately. 8. Depress the A-Phase flux-shift tripper. 9. Place the 120 A Fault Current switch into the OFF position. 10. Place the Phase Select Switch on the VFI tester into the B-PHASE position. 11. Press and release the Control Test button to initiate flow of simulated fault current to the control. ! S285-10-7 SAFETY FOR LIFE 12. Verify that the B-Phase flux-shift tripper on the VFI tester operates after 1 second ± 10%. 13. Depress the B-Phase flux-shift tripper. 14. Place the 30 A Fault Current switch into the ON position. All other Fault Current switches should be in the OFF position. 15. Press and release the Control Test button to initiate flow of simulated fault current to the control. 16. Verify that the B-Phase flux-shift tripper on the VFI tester operates immediately. 17. Depress the B-Phase flux-shift tripper. 4. Verify that the A-Phase, B-Phase, and C-Phase fluxshift trippers on the VFI tester all operate within 50 ms of the fault current being applied. SCADA Board Customer Connections Tests (TPG only) The following materials are required for SCADA board testing; small flat-blade screwdriver; Fluke 87 Multimeter or equivalent; 3” jumper wire; Ac power cord with wire ends stripped. 1. Verify that the settings of the tester and control are as described in the Initial Tester Setup and Initial Triphase/TPG Control Setup sections of this bulletin. 18. Place the 120 A Fault Current switch into the OFF position. Minimum Trip Multiplier Enable Readback Status Test 19. Place the Phase Select Switch on the VFI tester into the C-PHASE position. 1. Place the Minimum Trip Multiplier switch into the INCREASED position. Refer to Figure 11. 20. Press and release the Control Test button to initiate flow of simulated fault current to the control. 2. Using the multimeter, verify continuity between pin 8 and 18 of the Customer Connections Terminal Block. 21. Verify that the C-Phase flux-shift tripper on the VFI tester operates after 3 seconds ± 10%. 3. Place the Minimum Trip Multiplier switch into the NORMAL position. Refer to Figure 11. 22. Depress the C-Phase flux-shift tripper. 4. Using the multimeter, verify non-continuity between pins 8 and 18 of the Customer Connections Terminal Block. 23. Place the 30 A Fault Current switch into the ON position. All other Fault Current switches should be in the OFF position. Ground Trip Block Enable Readback Status Test 24. Press and release the Control Test button to initiate flow of simulated fault current to the control. 1. Place the Ground Trip Block switch into the ON position. 25. Verify that the C-Phase flux-shift tripper on the VFI tester operates immediately. 2. Using the multimeter, verify continuity between pin 8 and 17 of the Customer Connections Terminal Block. 26. Depress the C-Phase flux-shift tripper. 3. Place the Minimum Trip Multiplier switch into the NORMAL position. 27. Place the 120 A Fault Current switch into the OFF position. Control Setup – Ground Fault Trip during Inrush test 1. Set the minimum trip levels on A-Phase, B-Phase, CPhase, and Ground to 50 A. 2. Place the Ground Trip Block switch into the OFF position. 3. Place the Phase and Ground Instantaneous Trip switches into the ON position. 4. Place the Ground Trip Block During Inrush switch into the OFF position. 5. Place the Inrush Restraint switch into the ON position. 6. Set the A-Phase, B-Phase, and C-Phase Inrush Restraint Minimum Trip Multiplier switches for 5X (4X + 1X default setting). Test Procedure – Ground Fault Trip during Inrush test 1. Place the 120 A Fault Current switch on the VFI tester into the ON position. All other Fault Current switches should be in the OFF position. 4. Using the multimeter, verify non-continuity between pins 8 and 17 of the Customer Connections Terminal Block. Target Readback Status Test Setup 1. Place the Phase Instantaneous Trip switch on the control board into ON position. Test Procedure 1. Place the 60 A Fault Current toggle switch into the ON position. Place all of the other Fault Current switches into the OFF position. 2. Press and release the Control Test button to initiate flow of simulated fault current to the control. 3. After the A-Phase flux-shift tripper operates, verify continuity between pins 8 and 9 of the Customer Connections Terminal Block. 2. Place the Phase Select Switch on the VFI tester into the A-PHASE position. 4. Using a jumper wire, temporarily jumper pins 13 and 14 of the Customer Connections Terminal Block. This will reset all of the fault targets. Verify non-continuity between pins 8 and 9 of the Customer Connections Terminal Block. 3. Press and release the Control Test button to initiate flow of simulated fault current to the control. 5. Place the Phase Select switch into the B-PHASE position. 15 VFI Tester Operating Instructions 6. Press and release the Control Test button to initiate flow of simulated fault current to the control. 7. After the B-Phase flux-shift tripper operates, verify continuity between pins 8 and 10 of the Customer Connections Terminal Block. 8. Using a jumper wire, temporarily jumper pins 13 and 14 of the Customer Connections Terminal Block. This will reset all of the fault targets. Verify non-continuity between pins 8 and 10 of the Customer Connections Terminal Block. 9. Place the Phase Select switch into the C-PHASE position. 10. Press and release the Control Test button to initiate flow of simulated fault current to the control. 11. After the C-Phase flux-shift tripper operates, verify continuity between pins 8 and 11 of the Customer Connections Terminal Block. 12. Using a jumper wire, temporarily jumper pins 13 and 14 of the Customer Connections Terminal Block. This will reset all of the fault targets. Verify non-continuity between pins 8 and 11 of the Customer Connections Terminal Block. 13. Place the Ground Trip Block switch into the OFF position (TPG only). Remote Trip Test Setup 1. Place the remote trip power selector switch into the 125 VDC/120 VAC position. 2. Using a power cord, apply 120 Vac to pins 6 and 7 of the Customer Connections terminal block located upon the SCADA board. Connect the hot wire to pin 6. Connect the neutral wire to pin 7. IMPORTANT: The TPG/SCADA board accessory is a polarity dependent device. Do not connect a hot wire to the terminal 7 of the customer connections terminal block of the SCADA board. Failure to comply will result in damage to the SCADA board. Refer to the connections decal found within the control enclosure for additional information. 3. Plug the other end of the power cord into the accessory outlet on the VFI tester. Test Procedure 1. Reset the flux-shift trippers on VFI tester. 2. Using a jumper wire, jumper pins 1 and 4 of the Customer Connections Terminal Block. 15. Reset the flux-shift tripper. 3. Using another jumper wire, momentarily jumper pins 5 and 15 of the Customer Connections Terminal Block. The A-Phase flux-shift tripper on the VFI tester should operate. 16. Press and release the Control Test button to initiate flow of simulated fault current to the control. 4. Remove the jumper wire from pins 1 and 4 of the Customer Connections terminal block. 17. After all three of the flux-shift trippers operate, verify continuity between pins 8 and 12 of the Customer Connections Terminal Block. 5. Using the jumper wire, jumper pins 2 and 4 of the Customer Connections terminal block. 14. Set the minimum trip levels on A-phase, B-phase, and C-phase to 690 A. 18. Using a jumper wire, temporarily jumper pins 13 and 14 of the Customer Connections Terminal Block. This will reset all of the fault targets. Verify non-continuity between pins 8 and 12 of the Customer Connections Terminal Block. 6. Using another jumper wire, momentarily jumper pins 5 and 15 of the Customer Connections Terminal Block. The B-Phase flux-shift tripper on the VFI tester should operate. 7. Remove the jumper wire from pins 2 and 4 of the Customer Connections Terminal Block. 19. Place the Ground Trip Block switch into the OFF position (TPG only). 8. Using the jumper wire, jumper pins 3 and 4 of the Customer Connections Terminal Block. 20. Reset the flux-shift tripper. 9. Using another jumper wire, momentarily jumper pins 5 and 15 of the Customer Connections Terminal Block. The C-Phase flux-shift tripper on the VFI tester should operate. Ground Trip Block Enable Test 1. Verify non-continuity between pins 8 and 17 of the Customer Connections Terminal Block. 2. Using a jumper wire, jumper pins 15 and 16 of the Customer Connections Terminal Block. 3. Verify continuity between pins 8 and 17 of the Customer Connections Terminal Block. 4. Remove the jumper wire between pins 15 and 16 of Customer Connections Terminal Block. 5. Verify non-continuity between pins 8 and 17 of the Customer Connections Terminal Block. 16 10. Remove the jumper wire from pins 3 and 4 of the Customer Connections Terminal Block. 11. Reset the flux-shift trippers. ! S285-10-7 SAFETY FOR LIFE External Flux-Shift Tripper Tests The External Flux-Shift Tripper Test verifies the operation of the flux-shift trippers contained within the VFI switchgear under test. It should be used as a final diagnostic procedure only after verifying the control is operating correctly through administration of the control tests detailed in the Operating Procedures section of this service bulletin. IMPORTANT If service conditions allow, the VFI unit should be removed from service by disconnecting all sources of system voltage. If it is not possible to remove the VFI device from service by disconnecting all sources of system voltage, follow the procedures and safety precautions detailed in the TESTING IN-SERVICE VFI UNITS section found on page 6 of this service bulletin. WARNING: Hazardous voltage. Disconnect all source and tap elbows prior to conducting an external flux-shift tripper test. Failure to comply can result in possible contact with high voltage resulting in death or severe personal injury. T320.0 ! WARNING: Hazardous voltage. Always use a shotgun stick when working with this equipment. Failure to do so could result in contact with high voltage, which will cause death or severe personal injury. 10. Place the Phase Selector switch into the B-PHASE position. 11. Press the Tripper Test button. The B-Phase flux-shift tripper in the padmount unit should operate immediately. 12. Place the Phase Selector switch into the C-PHASE position. 13. Press the Tripper Test button. The C-Phase flux-shift tripper in the padmount unit should operate immediately. 14. De-energize the tester by setting the power switch to OFF. 15. Disconnect the 14-pin male connector end of the tester interrupter interface cable (Item 1) from the 14pin female end of the padmount cable (Item 2) originating from the front plate of the VFI unit under test. 16. Reconnect the VFI control cable (Item 2) to the receptacle located upon the TPG control enclosure. 17. Disconnect the interrupter and control interface cable (Item 1) from the VFI tester and store the cable in the storage compartment located in the cover of the VFI tester. 18. Using a hotstick, close in all three phases on the padmount unit. ! G108A.0 Side-Hinged Units with TPG Controls 1. Remove the padmount unit from service. 2. Attach the power cable to the VFI tester and plug it into a grounded, three-prong 120 Vac outlet. 14-pin male connector at cable end TPG Control Enclosure Item 2 VFI Control Cable 3. Connect the 14-pin female/14-pin male interrupter interface cable (Item 1) to the VFI Tester at the interrupter port. Refer to Figure 7 for steps 3 through 17. 4. Break the connection between the control and VFI unit by disconnecting the VFI control cable (Item 2) from the male receptacle located on the outside of the TPG control enclosure. Item 1 Interrupter Interface Cable VFI TO INTERRUPTER EXTERNAL TRIPPERS INTERNAL TRIPPERS TO CONTROL Tester CONTROL TEST Afl Bfl Cfl CURRENT METER JACKS TEST SELECT PHASE SELECT A-PHASE TRIPPER 5. Connect the 14-pin male connector end of the tester interrupter interface cable (Item 1) to the 14-pin female end of the padmount cable (Item 2) originating from the front plate of the VFI unit under test. B-PHASE TRIPPER BATTERY CONNECTOR 14-pin female connector at cable end ON ON ON ON 30A 60A 120A 240A C-PHASE TRIPPER BATTERY TEST ON 2X 4-30A TRIPPER TEST 1X 4-30A TEST 6. Place the Phase Test Selector switch on the VFI tester into the EXTERNAL TRIPPERS position. 7. Place the Phase Selector switch into the A-PHASE position. 8. Energize the tester by setting the power switch to ON. 9. Press the Tripper Test button. The A-Phase flux-shift tripper in the padmount unit should operate immediately. RESET CONTROL TEST INPUT POWER 120 VAC Power Systems CONVENIENCE OUTLET 120 VAC Figure 7. Connection of the VFI Tester to side-hinged VFI units with TPG controls for External Flux-shift Tripper Test. 17 VFI Tester Operating Instructions Top-Hinged VFI Units with TPG Controls/All Tri-Phase Controls 1. Remove the padmount unit from service. 2. Attach the power cable to the VFI tester and plug it into a grounded, three-prong 120 Vac outlet. 3. Connect the 14-pin female/18-pin male interrupter interface cable (Item 1) to the VFI Tester at the interrupter port. Refer to Figure 8 for steps 3 through 17. WARNING: Hazardous voltage. Open the switch associated with the control before attempting to disconnect its control cable. Failure to do so can result in contact with high voltage pulse (300 V peak) from the CT protection circuit, which can cause death or severe personal injury. T287.0 ! CAUTION: Equipment damage. Use care while disconnecting and reconnecting cables to the TriPhase/TPG control. Do not misalign male and female connectors or allow the full weight of the tester cable to be transferred to the Tri-Phase/TPG board. Failure to comply can result in damage to the board header and possible equipment misoperation. T319.0 16. Carefully reconnect the internal VFI control wiring harness (Item 2) to the control board header. 17. Disconnect the 18-pin male connector end of the VFI tester interrupter interface cable (Item 1) from the VFI tester. 18. Using a hotstick, close in all three phases on the padmount unit. 4. Break the connection between the control and VFI unit by carefully disconnecting the internal VFI control wiring harness (Item 2) at the control. CAUTION: Equipment damage. Use care while disconnecting and reconnecting cables to the TriPhase/TPG control. Do not misalign male and female connectors or allow the full weight of the tester cable to be transferred to the Tri-Phase/TPG board. Failure to comply can result in damage to the board header and possible equipment misoperation. T319.0 5. Connect the 18-pin male connector end of the VFI tester interrupter interface cable (Item 1) to the 18-pin female end of the VFI control wire harness (Item 2). Tri-Phase/ TPG Board Item 2 VFI Control Wire Harness 18-pin female connector 18-pin recessed male connector VFI TO INTERRUPTER B A L C M D P N E F EXTERNAL TRIPPERS INTERNAL TRIPPERS TO CONTROL Tester M L U T CONTROL TEST Afl Bfl A N V S P R Cfl CURRENT METER JACKS TEST SELECT PHASE SELECT A-PHASE TRIPPER 6. Place the Phase Test Selector switch on the VFI tester into the EXTERNAL TRIPPERS position. 7. Place the Phase Selector switch into the A-PHASE position. Item 1 Interrupter Interface Cable ON ON ON ON 30A 60A 120A 240A C-PHASE TRIPPER BATTERY TEST ON 2X 4-30A TRIPPER TEST 1X 4-30A TEST RESET CONTROL TEST INPUT POWER 120 VAC 8. Energize the tester by setting the power switch to ON. 9. Press the Tripper Test button. The A-Phase flux-shift tripper in the padmount unit should operate immediately. B-PHASE TRIPPER BATTERY CONNECTOR Power Systems CONVENIENCE OUTLET 120 VAC Figure 8. Connection of the VFI Tester to top-hinged VFI units with TPG controls and all VFI units for external Flux-shift Tripper Test. 10. Place the Phase Selector switch into the B-PHASE position. 11. Press the Tripper Test button. The B-Phase flux-shift tripper in the padmount unit should operate immediately. 12. Place the Phase Selector switch into the C-PHASE position. 13. Press the Tripper Test button. The C-Phase flux-shift tripper in the padmount unit should operate immediately. 14. De-energize the tester by setting the power switch to OFF. 15. Disconnect the 18-pin male connector end of the VFI tester interrupter interface cable (Item 1) from the 18-pin female end of the VFI control wire harness (Item 2). 18 Battery Test Refer to Figure 3 for identification of individual VFI Tester switches and other features referenced within the following procedure. The VFI tester features an LCD screen, battery connection terminal,0 and push button for verifying the battery condition under load. The procedure for conducting a battery test is as follows: 1. Disconnect and remove the 15 Vdc lithium battery from the control. 2. Connect the 15 Vdc lithium battery to the battery test terminals located on the front panel of the VFI tester. 3. Press and release the Battery Test button. ! SAFETY FOR LIFE S285-10-7 4. If the battery passes the test, the LCD display of the tester will display the ‘Battery Good’ message. Batteries passing the battery test may be placed back into service. 5. If the battery fails the test, the LCD display of the tester will display the ‘Replace Battery’ message. Replace the exhausted battery with a new, equivalent battery. Exhausted batteries should be disposed of in an environmentally responsible manner. Consult local regulations regarding proper battery disposal. Note: Control tests can not be conducted during a battery test. SERVICE INFORMATION VFI Tester units have no user serviceable components. Do not attempt to perform any service or maintenance on these units. Factory Authorized Service Centers Factory authorized service centers are located throughout the continental United States to provide maintenance, repair, and testing services for Kyle Products. For further information, contact your Cooper Power Systems sales representative. 19 VFI Tester Operating Instructions APPENDIX A TABLE 2 LCD Message Screens Screen No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 20 Screen Text VFI Tester Revision XX.xx Test Aborted Thermal Shutdown Description Initial Screen on Power-up. Shows the current firmware version. Displayed when VFI tester is shut off during an over-temperature condition. Tester Ready to Resume Testing Displayed after VFI tester has cooled down from an overtemperature condition. Initializing Battery Test Displayed when VFI tester verifies battery condition Verify Battery Connection Displayed if battery voltage measured during initialization is below 0.5V Test in Progress Time Remaining X Sec Displayed while battery load test is in progress. Test Complete Replace Battery Displayed after battery load test, if battery failed test. Test Complete Battery Good Displayed after battery load test, if battery passed test Control Test: XXX.xxx Seconds Displayed during a control test. Shows the elapsed time of the test. Test Stopped Seconds: XXX.xxx Displayed if user manually stops the control test Control Test Timed Out Displayed if the control test exceeded 5 minutes A-Phase Trip: XXX.xxx Seconds Indicates elapsed time between initialization of the A-Phase control test and execution of a trip command by the VFI control board. B-Phase Trip: XXX.xxx Seconds Indicates elapsed time between initialization of the B-Phase control test and execution of a trip command by the VFI control board. C-Phase Trip: XXX.xxx Seconds Indicates elapsed time between initialization of the C-Phase control test and execution of a trip command by the VFI control board. A-, B-Phase Trip: XXX.xxx Seconds Indicates only A- and B-Phase tripped during 3-phase trip test. Conduct single-phase trip test of C-phase to verify control and flux-shift tripper operation. A-, C-Phase Trip: XXX.xxx Seconds Indicates only A- and C-Phase tripped during 3-phase trip test Conduct single-phase trip test of B-phase to verify control and flux-shift tripper operation. B-, C-Phase Trip: XXX.xxx Seconds Indicates only B- and C-Phase tripped during 3-phase trip test Conduct single-phase trip test of A-phase to verify control and flux-shift tripper operation. A, B, C Phase Trip: XXX.xxx Seconds Indicates elapsed time between initialization of ganged, A-, B-, and C-phase control test and execution of a trip command by the VFI control board. ! S285-10-7 SAFETY FOR LIFE APPENDIX B Phase Minimum Trip Dip Switches Instantaneous Trip Dip Switches Independent or 3-phase Trip Selector Switch Figure 9. Kyle® Tri-Phase Board. 040001KM 21 VFI Tester Operating Instructions Phase Minimum Trip Ground Minimum Trip Dip Switch Phase Instantaneous Trip Dip Switch Ground Trip Block Switch Ground Instantaneous Trip Dip Switch Independent or 3-phase Trip Selector Switch Figure 10. Kyle® TPG Board. 22 040002KM ! S285-10-7 SAFETY FOR LIFE Minimum Trip Multiplier Switch Inrush Restraint Reset Time Dip Switch SCADA Fault Targets Minimum Trip Multiplier Dip Switches Inrush Restraint Dip Switch Ground Trip Block During Inrush Switch Figure 11. Optional SCADA Board Accessory-TPG only 23 040003KM 23 VFI Tester Operating Instructions ! SAFETY FOR LIFE ©2005 Cooper Power Systems or its affiliates. Kyle® is a registered trademark of Cooper Power Systems or its affiliates. KA2048-627 Rev: 00 1045 Hickory Street Pewaukee, WI 53072 www.cooperpower.com KDL 1/05