TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards Transmission Planning (TPL) VEC-008 Control Document Electric Generation and Transmission Planning Criteria Please refer questions about this document to the Electric Reliability Compliance Department (812-491-4012 or 812-491-5878). Non-Public ComplySMART© Page 1 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards TABLE OF CONTENTS 1 Introduction ..................................................................................................... 6 1.1 1.2 2 Purpose ................................................................................................................. 6 Roles and Responsibilities ................................................................................... 6 Electric Generation and Transmission Planning Procedure ...................... 7 2.1 Model Usage ........................................................................................................ 7 2.1.1 Transmission Performance Planning Models (up to 10 years) ...................... 7 2.1.2 AFC Planning models (0-3 years) .................................................................. 7 2.1.3 Operational models (current and next season) ............................................... 8 2.2 Model Development ............................................................................................. 8 2.3 Model Evaluation Criteria .................................................................................. 10 2.3.1 Contingencies ............................................................................................... 10 2.3.2 Performance ................................................................................................. 12 2.3.3 SOL and IROL Determination ..................................................................... 13 2.4 Study Results...................................................................................................... 14 3 Cross References ........................................................................................... 16 4 Appendices ..................................................................................................... 17 4.1 Appendix A: Table 1 – Steady State & Stability Performance Planning Events17 4.2 Appedix B: Table 1 – Steady State & Stability Performance Extreme Events . 20 4.3 Appendix C: Table 1 – Steady State & Stability Performance Footnotes (Planning Events and Extreme Events) ......................................................................................... 21 Non-Public ComplySMART© Page 3 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards Revision Table Revision Number 0 Revision Date 07/23/08 Effective Date 07/28/08 Revised By Summary of Changes Name R. Tabor 1 04/09/09 04/10/09 R. Tabor 2 01/12/10 01/26/10 R. Tabor 3 03/10/10 04/05/10 M. Rose 4 10/05/10 11/23/10 M. Rose 5 10/27/11 11/15/11 R. Collins 6 03/01/12 04/10/12 R. Collins 7 05/13/13 05/23/13 K. Sims 8 08/31/13 08/31/13 9 10/22/13 11/01/13 J. Biggerstaff J. Biggerstaff Revised document into new format, added sections to address NERC FAC and TPL standards Updated Annual Review Table Standardized document formatting. Added 3H Reference to VEC-014 and ratings. Added 4.3 SOL & IROL Determination Updated reference tables to latest reports Added verbiage to cover TPL-001 & TPL-002 for Transmission Performance Planning Models (up to 10 years) under 2 Model Usage, 2.1. Added Section F under Study Results • Made content changes based on self-certification. See redline(s). • Made content changes based on annual or self-certification review. See redline(s) and summary of document changes. • Made content changes based on annual or self-certification review. See redline(s) and summary of document changes. • Made content changes based on annual or self-certification review. See redline(s) and summary of document changes. • Revised MISO document link under section 2.1.2 • Revised first paragraph of section 2.3.1. Contingencies based on Director Review. Non-Public ComplySMART© Page 4 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards Revision Number 10 Revision Date 03/24/14 Effective Date 04/07/14 Revised By Summary of Changes K. Barr • 11 07/07//14 12/10/14 K. Barr • 12 11/06/15 12/18/15 K. Barr • Non-Public ComplySMART© Made content changes based on annual or self-certification review. See redline(s) and summary of document changes. Inserted references based on annual or self-certification review. See redline(s) and summary of document changes. Made content changes based on annual or self-certification review. See redline(s) and summary of document changes. Page 5 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards 1 Introduction 1.1 Purpose The major functions of and guidelines for Vectren electric transmission system planning are as follows: a. Developing a transmission system capable of delivering voltage of constant magnitude, duration and frequency at levels which meet our customers’ needs during normal conditions and during a system contingency or set of contingencies, and having established normal (pre-contingency) operating procedures in place; b. Optimizing the system configuration such that costs (capital and operating) are minimized while obtaining the above major function and providing a plan for system upgrades to meet performance requirements; c. Determining the near and long term Available Flowgate Capacity (AFC) of Vectren electric transmission facilities for imports, exports, and flow-through transmission service reservations of other areas in conjunction with the Midcontinent Independent System Operator (MISO); d. Performing transmission planning over a ten-year planning horizon; e. Performing an annual assessment of the electric transmission system; f. Developing selection criteria by which the transmission system configuration is analyzed and performance evaluated; g. Modeling and studying projected firm transfers over the range of forecast system demands; h. Performing analysis of reactive power resources to ensure adequate reserves exist and are available to meet system performance criteria; and i. Meeting NERC and RF Electric Reliability Compliance Standards for Transmission Planning (applicable MOD and TPL standards). 1.2 Roles and Responsibilities System Engineering is responsible for building models pursuant to steady state, short circuit, and dynamic modeling and simulation pursuant to NERC Reliability Standards MOD-010 and MOD-012 and pursuant to VEC-014 and VEC-008 as stated in the above Purpose statement. Vectren also conducts simulation studies on these models annually pursuant to the applicable TPL standards. Midcontinent Independent System Operator (MISO) functions as Vectren’s Reliability Coordinator (RC) and Planning Authority (PA). Non-Public ComplySMART© Page 6 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards 2 Electric Generation and Transmission Planning Procedure 2.1 Model Usage 2.1.1 Transmission Performance Planning Models (up to 10 years) Models will be developed to cover critical system conditions and study years as deemed appropriate. These include peak and off peak near-term (year 1 to 5) and long-term (year 6 to 10) models used for system growth, generator interconnections, transmission interconnections, Load Serving Entity (LSE) interconnections, and other studies as needed. The models are to be complete, including existing facilities at or above 69 kV. The models may include distribution circuits and substations as desired. Facilities included may be uncommitted, but should represent, at a minimum, required upgrades, and may include optimistic planned facilities. The models will be analyzed with More Probable, Less Probable and Extreme Contingency events. The planning horizon may be incremented further to consider future additions of any available long-term transmission and/or generation plans. Longer term models may also be required to study identified marginal conditions, proposed generation additions, unavailability of long lead time equipment, or other conditions that require longer lead time solutions. 2.1.2 AFC Planning models (0-3 years) Models will be developed for determining the Available Flowgate Capability (AFC) of facilities and impacts of both Firm and Non-Firm transmission service requests. These models are to be developed with the Bulk Electric System (all 100 kV and above existing and planned facilities) and certain 69 kV facilities, as required for proper transmission system modeling. All committed facilities will be included for study periods in the future. Uncommitted facilities will not be included. These models will be analyzed with the More Probable and Less Probable Contingency events. Vectren reviews models and identifies the most limiting contingencies for the Vectren system or that significantly impact the Vectren system: a. Facilities that show up as contingency overloads for the transfer studies; and b. Binding constraints identified by MISO in the real-time market. Non-Public ComplySMART© Page 7 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards Facilities identified to be limits by Vectren are submitted as flowgates to MISO for inclusion in their flowgate monitoring tool. See the MISO Regional Transmission Organization (RTO) Reliability Plan. This plan can be found on the MISO Web site https://www.misoenergy.org/Library/Repository/Procedure/MISO%20Reliabil ity%20Plan.pdf Upon request, Vectren will provide flowgates to Transmission Service Providers that work within Vectren’s Transmission Planning Area and to adjacent Transmission Planners. 2.1.3 Operational models (current and next season) Models will be developed for analyzing switching procedures, planned transmission and generation outages, and contingencies for the current system configuration. These models are also used for optimizing the system operation and reducing losses. These models are to be complete, including all existing and planned facilities at or above 69KV. These models may include distribution circuits and substations as desired. The models will be available and current for the upcoming season. These models will be analyzed with More Probable, Less Probable and Extreme Contingency events. 2.2 Model Development The Models have four critical elements that must be balanced to result in a viable solution: A) the load, B) the generation, C) the system voltage, and D) the net interchange. These are all tested against the equipment ratings and connectivity. a. The peak forecasted real and reactive load is obtained from the Vectren Integrated Resource Plan (IRP) and from other municipal and Local Balancing Area’s load forecasts for each year. This load includes all transmission and distribution losses. Losses for the distribution system will remain in the model load. The model load will be reduced uniformly equal by the calculated value of the transmission losses. Exceptions to this rule apply to identified non-conforming loads (e.g. Alcoa, General Electric, Toyota, Waupaca). The modeled load represents the expected steady state and dynamic behavior of loads that could impact the study area. Off-peak or seasonal loads are calculated based on the peak forecast load for that period. Interruptible load will be defined for operational or AFC models, but will not be used for long-range planning. It is the intent for long-range planning to serve all loads and not to utilize interruptible load, since its long-term availability is uncertain. For stability analysis, the system load is represented by a dynamic load model which models the expected Non-Public ComplySMART© Page 8 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards dynamic load behavior of loads and considers the behavior of induction motor loads. b. The maximum available generation is also obtained from the IRP. Generation resources (supply or demand side) will be dispatched as required to meet the system load demand plus the system losses based a merit order dispatch set by Vectren Power Supply. Sensitivity studies are normally conducted to represent market based dispatch to determine if import capability is available in lieu of running peaking turbines and select generation outages. Off-peak models are used for export studies to determine the amount of export capability. Capacity Benefit Margin (CBM) is studied upon request from a Load Serving Entity (LSE) or Distribution Provider (DP). Automatic Reserve Sharing (ARS) provides the capacity for the short-term and is controlled by the generation dispatch by MISO. Studies for ARS are not normally conducted unless specifically initiated by a request. c. The bus voltages at generation plants are typically set to operate at or near 1.05 per unit of nominal voltage. Plant bus voltages are normally limited by the generator terminal voltages on the high end and the auxiliary bus voltages on the low end. d. Long-term committed power transfers will also be included in the models as needed and coordinated with the interchanging party. Contingency analysis may require model imports of an additional 300MW for an outage of the largest unit, or 570MW for the two largest units. Imports may also be used for additional capacity and reserves during peak load. No generating unit will be modeled above its rated capacity. Additional studies will be conducted by adjusting the generation to determine the maximum import and export capability of the transmission system. e. Alcoa Warrick Operations generation and load is significant and is modeled in the Vectren Control Area in MISO and RF models. Warrick has a transfer-trip relaying scheme to automatically shed load (2 pot lines) for a trip of any of their generators. Warrick generation and load is not included in the Vectren contingency analysis. Vectren does not plan its system to directly support Warrick operations. Studies at Alcoa Warrick Operations will be performed and coordinated with Alcoa separately. f. Models will include all reactive resources as applicable (generators, capacitors, etc.). g. Models will include, at a minimum, planned outages of six months or more of any bulk electric equipment for the demand levels and time periods being studied. Non-Public ComplySMART© Page 9 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards h. Applicable Ratings of all facilities will be included in the model. Ratings are defined per VEC-014 Transmission and Generation System Facility Ratings. i. Sensitivity case(s) are developed to demonstrate the impact of changes to the basic assumptions used in the model. To accomplish this, the sensitivity analysis in the Planning Assessment must vary one or more of the following conditions by a sufficient amount to stress the System within a range of credible conditions that demonstrate a measurable change in System response. i. ii. iii. iv. v. vi. vii. Real and reactive forecasted Load. Expected transfers. Expected in service dates of new or modified Transmission Facilities. Reactive resource capability. Generation additions, retirements, or other dispatch scenarios. Controllable Loads and Demand Side Management. Duration or timing of known Transmission outages. j. Steady state, short circuit, and dynamic equipment characteristics and system simulation modeling data is maintained in System Engineering electronic files and is used to create the appropriate Vectren system models for the various study horizons. k. Models are initially solved utilizing the automatic operation of load tap changing (LTC) transformers and switched capacitors to reflect an optimized base case. 2.3 Model Evaluation Criteria 2.3.1 Contingencies Our rationale for selected steady state contingencies is to include the entire Vectren System and the facilities 3 buses, at a minimum, into all neighboring control areas. Single contingencies include all facilities at or above 69kV and double contingencies at 100kV or above internal to Vectren and all 69kV or above ties. Our rationale for selected dynamics contingencies is close in faults at power plants. Select 69kV facilities may be included for sensitivity studies. The only exception is at Alcoa. Vectren planning models normally exclude Alcoa Warrick operations contingencies for facility studies and for AFC studies. Alcoa is a large aluminum smelter and rolling mill with normally self-sufficient generation resources located on site. Improvements at Alcoa will be studied and coordinated with Alcoa separately. The monitored elements will include the entire Vectren System, Alcoa facilities, and three buses, at a minimum, into all neighboring control areas. This should identify Non-Public ComplySMART© Page 10 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards any problems induced into Alcoa and the other control areas that may be caused by our system. Special contingencies will be included in the appropriate severity category to model the effects of existing and planned protection systems and control devices (including any backup or redundant systems) and also to include any concerns or conditions identified by Transmission System Operations (TSO). The effects of existing and planned protection systems to be studied include the removal of all elements protected by that protection system, the tripping of generators when the generator bus voltage (or high side of the GSU bus voltage) is less than the known or assumed generator steady state voltage limit (or voltage ride-through capability), the tripping of all appropriate elements when relay loadability limits are exceeded, successful and unsuccessful high speed reclosing (in instances where high speed reclosing is utilized), tripping of transmission elements when transient swings causes protection system operation based on generic relay models, and any other effects as deemed appropriate by Vectren’s System Engineering. During the contingency analysis simulations, the models are solved allowing the automatic operation of load tap changing (LTC) transformers. The operation of the switched capacitors on Vectren’s system is a manual process; therefor the automatic operation of the switched capacitors is disabled during the simulation solution. For the purpose of evaluating the transmission system, the following contingency events are tested for both steady state and dynamic performance per the NERC TPL requirements: No Contingencies: a. Normal system conditions per NERC Category P0 on the table found in Appendix A. More Probable Contingencies: a. Sudden outage of any transmission facility (circuit, transformer, generator, etc.) for normal system configuration per NERC Category P1 and P2 on the table found in Appendix A. Vectren studies all Category B contingencies in order to ensure studying the most severe. Less Probable Contingencies: a. Sudden outage of multiple transmission facilities (circuit, transformer, generator, etc.) while the transmission system is reconfigured for any other generator rated 200 MVA or more out of service. Non-Public ComplySMART© Page 11 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards b. Additional NERC Category P3 through P7 contingencies as described on the table found in Appendix A. Extreme Contingencies: Extreme contingencies are not expected to be caused by an electrical disturbance, but rather are expected to be caused by a tornado, earthquake, ice storm, or other catastrophic event. Mitigation measures may include the following: redesign, modifications to substations, the use of ring busses, breaker-and-a-half busses, or primary and secondary alternate busses to reduce the possibility of an extreme contingency at that Substation. Extreme Contingencies include: a. Outage of a bus and any associated transformers at any substation with three or more lines at 100 kV or above. b. Additional NERC Extreme Events contingencies as described in the table found in Appendix B. 2.3.2 Performance Acceptable operating performance for the above contingencies is as follows: For No Contingencies: The system is stable and all facility loadings are within normal ratings and all bus voltages are within normal limits. For More Probable Contingencies: After a sudden outage; however, before any operator directed system adjustments are made, the system is stable and all facility loadings are within normal ratings and all bus voltages are within normal limits. Any loss of radial load is restored through routine operator directed switching procedures, if possible. For Less Probable Contingencies: After a sudden outage; however, before any operator directed system adjustments are made, the system is stable, all facility loadings are within Emergency ratings and all bus voltages are within Emergency limits. Any loss of load is restored through routine operator directed switching procedures, if possible. For Extreme Contingencies: After a sudden multiple event outage; the remaining system is stable without voltage collapse or loss of system integrity. The Vectren System may contain an Island, or even be an Island itself to protect the Bulk Electric System. Extreme Contingencies are used to ensure regional system stability, to identify Non-Public ComplySMART© Page 12 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards weaknesses in the Vectren system, and to develop system restoration procedures. The system will not be designed to completely eliminate the effects of an extreme contingency, but the extreme contingencies should be analyzed and steps should be taken to minimize both the probability of occurrence and the resulting impact. 2.3.3 SOL and IROL Determination All components of the BES facilities have a thermal and voltage rating. In addition to these ratings, the system will be studied to determine if there are any additional voltage or power stability issues which may further limit the system. The System Operating Limits (SOLs) will be developed to operate facilities within these ratings. MISO has determined that Vectren does not have any IROLs. Vectren also reviews system studies for potential IROLs through cascading analysis. If a contingency occurs that results in a facility over 125% of its emergency rating, or less than 90% voltage PU for generating facility, that facility will be outaged. The simulation will be solved and again any facilities over 125% of its emergency rating, or under 90% voltage PU for a generating facility, will be outaged. Cascading occurs when more than two facilities, in a series, are outaged using this process. This process will continue until no facilities exceed this criterion to determine how many facilities will be affected and outaged. This will be the determination of the extent of cascading. If the initial post-contingent overloaded or undervoltaged BES facility is subsequently outaged, and additional BES facilities are overloaded to over 125% of their emergency rating or below 90% voltage PU for a BES generating facility, an IROL will be developed and coordinated with MISO and other impacted systems. Non-Public ComplySMART© Page 13 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards 2.4 Study Results Written study results will be presented in as clear and concise manner as possible depending on the analysis being performed. The study results document all assumptions made during the analysis, including the rationale behind the model system conditions and year selection, and provide a summary of all contingencies studied and the level of performance indicated by the model. The study results include a reactive power resources review to indicate that adequate reactive resources are available to meet system performance. If reactive resources are found to be inadequate, a recommended plan will be provided as outlined in the next paragraph. If the performance of the system does not meet requirements throughout the planning horizons, a recommended corrective action plan including any system upgrades will be provided. The written corrective action plan will include a schedule for implementation with required in-service dates of facilities and with consideration for expected lead times for equipment delivery and construction timelines. Corrective action plans are not necessarily created to address deficiencies observed in a single sensitivity study, however they are created if the same deficiency is identified in multiple sensitivity studies throughout the assessment. These corrective action plans are reviewed in subsequent planning assessments for continued validity and implementation status. An annual review is completed for each type of model listed in the “Model Usage” section. Steady state, short circuit, and stability simulations will be performed if changes to the bulk electric system conditions warrant analyses. Changes to the bulk electric system that warrant such an analyses may include changes to generation, transmission lines 100kv and above, or significant load change. System Engineering will review subsequent annual assessments (where sufficient lead time exists) to evaluate the continuing need for identified system facilities. Detailed implementation plans are not needed. In instances where simulations were not performed due to lack of system changes as described above, studies from past years are assessed to support the current planning assessment, given that they are less than 5 calendar years old. The short circuit portion of the analysis is used to determine whether circuit breakers have adequate interrupting capability for faults that they will be expected to interrupt. Any instance where a breaker’s interrupting capability is found to be inadequate is documented in the corrective action plan along with the actions needed to achieve the required system performance. These corrective action plans are reviewed in subsequent planning assessments for continued validity and implementation status. For the stability portion of the assessment, any instant where the system fails to meet the performance requirements described in the MISO Business Practices Manual 020 (including acceptable damping, transient voltage response, etc.) will be considered to show signs of instability, and these instances will be documented and addressed in Non-Public ComplySMART© Page 14 TRANSMISSION PLANNING Revision Number 12 VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards corrective action plans. These corrective action plans are reviewed in subsequent planning assessments for continued validity and implementation status. The study results and corrective action plans will be documented and provided to Vectren’s Reliability Coordinator (RC), Transmission Service Provider (TSP) and Transmission Planning Coordinator (PC) annually. Vectren’s RC and TSP is Midcontinent Independent System Operator (MISO). The study results will be submitted by e-mail to MISO Real Time Operations (RTO), but any resulting projects from the study will be submitted through the MISO WebTool. Vectren’s PC is also MISO. The study results are e-mailed to MISO’s Transmission Planners for inclusion in the MISO Transmission Expansion Plan (MTEP), but all projects resulting from the study will be submitted through the Model On Demand (MOD) software. The MTEP is posted publically and provided annually to the RRO. Vectren also provides the study results to RF and upon request subject to confidentiality requirements. The study results and corrective action plans will be provided to Vectren TSO on a timely basis for their review and inclusion into the planning process for reliable operation of the transmission system during the study period. Non-Public ComplySMART© Page 15 Revision Number 12 TRANSMISSION PLANNING VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards 3 Cross References Documents Cross Reference Table Document Name VEC-014 Transmission and Generation System Facility Ratings MISO RTO Reliability Plan MISO Transmission Expansion Plant (MTEP) MOD-010 MOD-012 Non-Public ComplySMART© References To Document Name 1.2 Roles and Responsibilities; 2.2 Model Development 2.1.2 AFC Planning models (0-3 years) 2.4 Study Results 1.2 Roles and Responsibilities 1.2 Roles and Responsibilities Page 16 Revision Number 12 TRANSMISSION PLANNING VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards 4 Appendices 4.1 Appendix A: Table 1 – Steady State & Stability Performance Planning Events Table 1 – Steady State & Stability Performance Planning Events Steady State & Stability: a. The System shall remain stable. Cascading and uncontrolled islanding shall not occur. b. Consequential Load Loss as well as generation loss is acceptable as a consequence of any event excluding P0. c. Simulate the removal of all elements that Protection Systems and other controls are expected to automatically disconnect for each event. d. Simulate Normal Clearing unless otherwise specified. e. Planned System adjustments such as Transmission configuration changes and re-dispatch of generation are allowed if such adjustments are executable within the time duration applicable to the Facility Ratings. Steady State Only: f. Applicable Facility Ratings shall not be exceeded. g. System steady state voltages and post-Contingency voltage deviations shall be within acceptable limits as established by the Planning Coordinator and the Transmission Planner. h. Planning event P0 is applicable to steady state only. i. The response of voltage sensitive Load that is disconnected from the System by end-user equipment associated with an event shall not be used to meet steady state performance requirements. Stability Only: j. Transient voltage response shall be within acceptable limits established by the Planning Coordinator and the Transmission Planner. Category Initial Condition Event1 Fault Type2 BES Level3 Interruption of Firm Transmission Service Allowed 4 P0 No Contingency Normal System None N/A EHV, HV No P1 Single Contingency Normal System Loss of one of the following: 1. Generator 2. Transmission Circuit 3. Transformer 5 4. Shunt Device 6 3Ø EHV, HV No Non-Public ComplySMART© Page 17 NonConsequential Load Loss Allowed No 9 No 12 Revision Number 12 TRANSMISSION PLANNING VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards 5. Single Pole of a DC line SLG 1. Opening of a line 7 section w/o a fault N/A EHV 2. Bus Section Fault P2 Single Contingency Normal System SLG P4 Multiple Contingency (Fault plus stuck 10 breaker ) Loss of generator unit followed by System 9 adjustments Normal System SLG 4. Internal Breaker Fault 8 (Bus-tie Breaker) SLG Loss of one of the following: 1.Generator 2. Transmission Circuit 5 3. Transformer 6 4. Shunt Device 3Ø 5. Single pole of a DC line SLG Loss of multiple elements caused by a stuck breaker10 (non-Bus-tie Breaker) attempting to clear a Fault on one of the following: 1.Generator 2. Transmission Circuit 3. Transformer5 4. Shunt Device6 5. Bus Section Non-Public HV EHV 8 3. Internal Breaker Fault (non-Bus-tie Breaker) P3 Multiple Contingency EHV, HV No 9 No No 9 No Yes No 9 12 Yes No HV Yes Yes EHV, HV Yes Yes EHV, HV No 9 No EHV No 9 No HV Yes 12 SLG ComplySMART© Page 18 Yes Revision Number 12 TRANSMISSION PLANNING VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards 6. Loss of multiple elements caused by a stuck breaker10 (Bus-tie Breaker) attempting to clear a Fault on the associated bus P5 Multiple Contingency (Fault plus relay failure to operate) Normal System P6 Multiple Contingency (Two overlapping singles) Loss of one of the following followed by System adjustments.9 1.Transmission Circuit 2. Transformer5 3. Shunt Device6 4. Single pole of a DC line P7 Multiple Contingency (Common Structure) Normal System EHV, HV Yes EHV No HV Yes Yes 3Ø EHV, HV Yes Yes 4. Single pole of a DC line SLG EHV, HV Yes Yes The loss of: 1. Any two adjacent (vertically or horizontally) circuits on common 11 structure 2. Loss of a bipolar DC line SLG EHV, HV Yes Yes Delayed Fault Clearing due to the failure of a nonredundant relay13 protecting the Faulted element to operate as designed, for one of the following: 1.Generator 2. Transmission Circuit 3. Transformer5 4. Shunt Device6 5. Bus Section Loss of one of the following: 1. Transmission Circuit 5 2. Transformer 6 3. Shunt Device Non-Public SLG 9 Yes No SLG ComplySMART© Page 19 Revision Number 12 TRANSMISSION PLANNING VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards 4.2 Appedix B: Table 1 – Steady State & Stability Performance Extreme Events Table 1 – Steady State & Stability Performance Planning Events Steady State & Stability For all extreme events evaluated: a. Simulate the removal of all elements that Protection Systems and automatic controls are expected to disconnect for each Contingency. b. Simulate Normal Clearing unless otherwise specified. Steady State Stability 1. Loss of a single generator, Transmission Circuit, single pole of a DC Line, 1. With an initial condition of a single generator, Transmission circuit, single shunt device, or transformer forced out of service followed by another single pole of a DC line, shunt device, or transformer forced out of service, apply a generator, Transmission Circuit, single pole of a different DC Line, shunt 3Ø fault on another single generator, Transmission circuit, single pole of a device, or transformer forced out of service prior to System adjustments. different DC line, shunt device, or transformer prior to System adjustments. 2. Local area events affecting the Transmission System such as: 2. Local or wide area events affecting the Transmission System such as: a. Loss of a tower line with three or more circuits.11 a. 3Ø fault on generator with stuck breaker10 or a relay failure13 resulting in b. Loss of all Transmission lines on a common Right-of-Way11. Delayed Fault Clearing. c. Loss of a switching station or substation (loss of one voltage level plus b. 3Ø fault on Transmission circuit with stuck breaker10 or a relay failure13 resulting in Delayed Fault Clearing. transformers). c. 3Ø fault on transformer with stuck breaker10 or a relay failure13 resulting in d. Loss of all generating units at a generating station. Delayed Fault Clearing. e. Loss of a large Load or major Load center. d. 3Ø fault on bus section with stuck breaker10 or a relay failure13 resulting in 3. Wide area events affecting the Transmission System based on System Delayed Fault Clearing. topology such as: a. Loss of two generating stations resulting from e. 3Ø internal breaker fault. conditions such as: f. Other events based upon operating experience, such as consideration of i. Loss of a large gas pipeline into a region or multiple regions that have initiating events that experience suggests may result in wide area significant gas-fired generation. disturbances ii. Loss of the use of a large body of water as the cooling source for generation. iii. Wildfires. iv. Severe weather, e.g., hurricanes, tornadoes, etc. v. A successful cyber attack. vi. Shutdown of a nuclear power plant(s) and related facilities for a day or more for common causes such as problems with similarly designed plants. b. Other events based upon operating experience that may result in wide area disturbances. Non-Public ComplySMART© Page 20 Revision Number 12 TRANSMISSION PLANNING VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards 4.3 Appendix C: Table 1 – Steady State & Stability Performance Footnotes (Planning Events and Extreme Events) Table 1 – Steady State & Stability Performance Footnotes (Planning Events and Extreme Events) 1. If the event analyzed involves BES elements at multiple System voltage levels, the lowest System voltage level of the element(s) removed for the analyzed event determines the stated performance criteria regarding allowances for interruptions of Firm Transmission Service and NonConsequential Load Loss. 2. Unless specified otherwise, simulate Normal Clearing of faults. Single line to ground (SLG) or three-phase (3Ø) are the fault types that must be evaluated in Stability simulations for the event described. A 3Ø or a double line to ground fault study indicating the criteria are being met is sufficient evidence that a SLG condition would also meet the criteria. 3. Bulk Electric System (BES) level references include extra-high voltage (EHV) Facilities defined as greater than 300kV and high voltage (HV) Facilities defined as the 300kV and lower voltage Systems. The designation of EHV and HV is used to distinguish between stated performance criteria allowances for interruption of Firm Transmission Service and Non-Consequential Load Loss. 4. Curtailment of Conditional Firm Transmission Service is allowed when the conditions and/or events being studied formed the basis for the Conditional Firm Transmission Service. 5. For non-generator step up transformer outage events, the reference voltage, as used in footnote 1, applies to the low-side winding (excluding tertiary windings). For generator and Generator Step Up transformer outage events, the reference voltage applies to the BES connected voltage (high-side of the Generator Step Up transformer). Requirements which are applicable to transformers also apply to variable frequency transformers and phase shifting transformers. 6. Requirements which are applicable to shunt devices also apply to FACTS devices that are connected to ground. 7. Opening one end of a line section without a fault on a normally networked Transmission circuit such that the line is possibly serving Load radial from a single source point. 8. An internal breaker fault means a breaker failing internally, thus creating a System fault which must be cleared by protection on both sides of the breaker. 9. An objective of the planning process should be to minimize the likelihood and magnitude of interruption of Firm Transmission Service following Contingency events. Curtailment of Firm Transmission Service is allowed both as a System adjustment (as identified in the column entitled ‘Initial Condition’) and a corrective action when achieved through the appropriate re-dispatch of resources obligated to re-dispatch, where it can be demonstrated that Facilities, internal and external to the Transmission Planner’s planning region, remain within applicable Facility Ratings and the re-dispatch does not result in any Non-Consequential Load Loss. Where limited options for re-dispatch exist, sensitivities associated with the availability of those resources should be considered. 10. A stuck breaker means that for a gang-operated breaker, all three phases of the breaker have remained closed. For an independent pole operated (IPO) or an independent pole tripping (IPT) breaker, only one pole is assumed to remain closed. A stuck breaker results in Delayed Fault Clearing. Non-Public ComplySMART© Page 21 Revision Number 12 TRANSMISSION PLANNING VEC-008 Electric Generation and Transmission Planning Criteria This document is compliant with NERC Transmission Planning Standards 11. Excludes circuits that share a common structure (Planning event P7, Extreme event steady state 2a) or common Right-of-Way (Extreme event, steady state 2b) for 1 mile or less. 12. An objective of the planning process is to minimize the likelihood and magnitude of Non-Consequential Load Loss following planning events. In limited circumstances, Non-Consequential Load Loss may be needed throughout the planning horizon to ensure that BES performance requirements are met. However, when Non-Consequential Load Loss is utilized under footnote 12 within the Near-Term Transmission Planning Horizon to address BES performance requirements, such interruption is limited to circumstances where the Non-Consequential Load Loss meets the conditions shown in Attachment 1. In no case can the planned Non-Consequential Load Loss under footnote 12 exceed 75 MW for US registered entities. The amount of planned Non-Consequential Load Loss for a non-US Registered Entity should be implemented in a manner that is consistent with, or under the direction of, the applicable governmental authority or its agency in the non-US jurisdiction. 13. Applies to the following relay functions or types: pilot (#85), distance (#21), differential (#87), current (#50, 51, and 67), voltage (#27 & 59), directional (#32, & 67), and tripping (#86, & 94). Non-Public ComplySMART© Page 22