Installation Instructions

advertisement
RAZOR RZR SERIES
DIE CAST ALUMINUM LED EXIT SIGNS
INSTALLATION AND OPERATING
INSTRUCTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. Do not use outdoors.
2. Do not mount near gas or electric heaters.
3. Equipment should be mounted in locations and at heights where it will not
readily be subject to tampering by unauthorized personnel.
4. The use of accessory equipment not recommended by the manufacturer
may cause an unsafe condition.
5. Do not use this equipment for other than intended use.
6. Supply connections must be made either inside the junction box for surface
mount or the splice box in the recessed mount backbox.
7. Install using recommended junction box only.
8. Servicing of this equipment should be performed by qualified service
personnel.
SAVE THESE INSTRUCTIONS
3161 State Road • Bensalem • PA 19020 U•S•A
Telephone: (215) 244-4204 • Fax: (215) 244-4208
Page 1
INSTALLATION OF MASTER SIGN
Before installing unit, disconnect power at breaker panel
TOP OR END
CANOPY MOUNT
Ceiling
4X No. 6 screws
Attaches Power
Supply Mounting
Plate to Masonry
Box
Sign to Power
Supply
connection
Canopy
attaches to
sign with 2x
No. 8 screws
AC Power
Connection
Part No. M210076
4 gang masonry box 2-1/2”d x 3-3/4” h
Typical: Crouse - Hinds TP685
(mounting by others)
Power Supply mounted to
Mounting Plate
Low Voltage 4.8VDC connection to REMOTE
SIGN (if required). Maximum run of 2 conductor
wiring (by others): 50 ft. = AWG 22
100 ft. = AWG 18
300 ft. = AWG 12
Single or Double Face Sign
Disassemble housing using
1/16” Allen wrench
Canopy attaches to
Mounting Plate with
2X No. 8 screws
Removable Lens
WALL MOUNT
Power Supply
Mounted to
Back Plate
Power
Input
4X No. 6 screws
Attaches Back Plate
to Masonry Box
2x Set Screws
(tighten on Back Plate
mounting pins while
holding Faceplate
flush to wall)
Low Voltage
4.8VDC
connection to
REMOTE
UNIT
(if required)
Wall
Back Plate
2x Set Screws (tighten on Faceplate
mounting pins while holding Faceplate flush
to wall)
Connect power input wires to feed wires in junction box as per local code.
Black lead for 120V or Orange lead for 277V CAP UNUSED LEAD
White lead for neutral
Green/Yellow lead for Ground.
REAPPLY POWER AND NOTIFY THE AUTHORITY HAVING J U R I S D I C T I O N
Page 2
DIRECTIONAL INDICATORS
Determine which directional indicator(s)
are to be removed. Knock out as shown
in the attached diagram. For the rear
face on a double face sign, remove the
tape and punch out the indicator(s).
For front, die-cast face, knock
out desired directional indicator(s)
supporting Faceplate as shown
All units, except Remotes, mount to a 4 gang masonry box supplied. Box
must be mounted flush with wall surface. Remotes can be mounted to a
standard 4” octagon J Box (supplied by others).
INSTALLATION OF REMOTE SIGN
Low Voltage 4.8VDC
connection to
MASTER UNIT
(supplied by
contractor)
Knockouts in Back Plate
for attachment to wall by
screws (supplied by others)
Color Diffuser, Lens and
Lens Reflector line up with
square notch on the left hand
side.
Back Plate
2x Set Screws
(tighten on Back Plate
mounting pins while
holding Faceplate
flush to wall)
Wall
Maximum run of 2
conductor wiring:
50 ft. = AWG 22
100 ft. = AWG 18
300 ft. = AWG 12
Low Voltage
4.8VDC Leads
from REMOTE
2x Set Screws
(tighten on Faceplate
mounting pins while
holding Faceplate
flush to wall)
Lens Reflector
Removable
Lens
Faceplate
Color Diffuser
LED Array PC Board
Page 3
SECURITY SHIELD INSTALLATION
SINGLE FACE
WALL MOUNT
4x Vandal
Resistant
Screws
Fasten Security Shield
to housing unused
tapped holes with
socket wrench, using 4
Vandal Resistant screws
supplied.
DOUBLE FACE
CANOPY MOUNT
2x Canopy to
Sign Mounting
Screws
2x Canopy to
Back Box
Mounting
Screws
Page 4
8x Vandal
Resistant
Screws
RECESSED PENDANT SWIVEL ASSEMBLY
Secure recessed Back Box into ceiling using means supplied by others. Run
wires up Pendant Rod and secure Rod to Pendant Adapter on fixture using 2
mounting nuts supplied.
Interconnect wires to power supply and install Swivel Ball, Swivel Bracket and
Swivel Bracket.
Recessed Back Box
3-3/4 x 7-1/2
2-1/2 deep
Opening:
3-3/4 x 7-1/2
Ceiling
(4x) Mounting Screws
(Trim Plate to Back Box)
(2x) Mounting Screws
(Swivel Bracket to Trim Plate)
Swivel Ball
Trim Plate Cover
8-3/4 x 6
Swivel Bracket
Swivel Cover
(Snaps on to Swivel Bracket)
Pendant Rod
(Specify Length)
(2x) Mounting Nuts
(2x) Mounting Screws
(Pendant Adapter to Razor Sign)
Pendant Adapter
Page 5
TWO CIRCUIT INPUT OPTION (AC VERSIONS ONLY)
For AC versions with two circuit input, connect the input power from the main input to the
leads marked MAIN, and from the backup input to the leads marked BACKUP. Note
that the main and backup voltages can be either 120V or 277V. They do not have to be
the same voltage. Connect to the Black lead for 120V or Orange lead for 277V, and
White lead for Neutral. Cap off the unused leads.
FLASHER / FIRE ALARM / BUZZER OPTIONS
Battery Backup Emergency signs that are equipped with the FLASH IN EMERGENCY
MODE OPTION or BUZZER IN EMERGENCY MODE option will automatically
flash/beep in the emergency mode but not flash/beep on AC operation. AC Only exit
signs that are equipped with the flash or buzzer options will flash/beep continuously while
power is supplied.
AC Only and Battery Backup Emergency signs that are equipped with the FIRE ALARM
SIGNAL MODE FLASH or BUZZER options will automatically flash/beep in both AC and
emergency modes upon application of a fire alarm signal to the YELLOW 18 AWG leads.
The fire alarm signal can be either AC or DC of either polarity, and range from 12 to 24
volts. The current draw from the fire alarm signal is less than 10 milliamps.
Units that include one of the above options, are intended for installation in locations
where such features are permitted by local codes.
Flasher Rate: 60 per minute
Duty Cycle: 50 percent
DIAGNOSTICS
For units with Self-Testing / Self-Diagnostics option, refer to Operating Instructions.
Battery back-up units without Self-Testing / Self-Diagnostics option include a battery
diagnostics system which indicates, via flashing of the indicator light, that the battery
needs replacement. If flashing occurs after a new installation, check that the battery plug
is properly inserted into the circuit board connector.
TEST FOR BATTERY BACKUP WITHOUT SELF-TEST / SELF-DIAGNOSTICS
To test Battery backup units, use test switch to simulate AC power outage. The indicator
light will go out, and the sign will remain lit, indicating transfer to emergency mode; and
remain lit on battery power until switch is released. Release of switch will automatically
restore AC/battery charge mode, with indicator light on. Testing for longer periods is best
accomplished by turning off AC circuit power. Signs should be tested in accordance with
National Electric Code and NFPA 101 Life Safety Code requirements which specify
monthly testing for 30 seconds and yearly testing for 90 minutes. Note that the batteries
will take some time to reach full charge after a prolonged test, and that the unit cannot
provide full duration operation should a real power outage occur before the batteries have
had an opportunity to reach full charge. It is recommended that long duration tests be
limited to once yearly, and be conducted when the area will be unoccupied afterwards.
Page 6
SELF-TESTING / SELF DIAGNOSTIC OPERATING INSTRUCTIONS
This unit meets the requirements of NFPA 101 for Periodic Testing of Emergency
Lighting Equipment. It provides visual indication of unit malfunctions including:
Battery Fault
Charger Fault
Transfer Fault
Lamp Fault
STATUS INDICATIONS SHOWN ON FOLLOWING PAGE
SELF-TEST
The unit will perform a self-test and diagnostic function at least once every 28
days. The self-test will disable the charger and turn on the LEDs for 5 minutes to
check the lamp load and battery. The test will be performed only if the battery is
fully charged. If not, the test will automatically reschedule. The charger function
is monitored continuously.
USER-TEST
A User-Test may be performed at any time the status display is continuous green.
On initial power-up, it could take up to 72 hours for the status display to reach
continuous green.
With a fully charged battery, pressing the test switch momentarily will initiate a 30
second test. Pressing the test switch continuously for 4 seconds and releasing it
will initiate a 90 minute test.
Either test can be cancelled by pressing the test switch again for 1 second.
REMOTE LAMP OPERATION
The self-diagnostic system “learns” the lamp load when the unit reaches its first
full charge. It is therefore necessary to have any remote lamps already
connected when first applying AC power. Subsequent self-tests and user-tests
will compare the actual lamp load to the “learned” value.
If the remote lamp load is changed once it has been learned, it is necessary to
disconnect AC power at the circuit breaker panel and unplug the internal battery.
Once these are reconnected, the unit will “learn” the new lamp load.
INFRA RED REMOTE TESTING
To activate TRANSMITTER, remove tab from back of device.
The USER-TEST can be performed up to 20 feet away using the optional “INFRA
RED REMOTE TESTING TRANSMITTER”. By aiming the TRANSMITTER at the
legend face, and pushing either the “30 SECOND” or “90 MINUTE” button for 1
second, all the “TEST SWITCH” functions can be performed.
Page 7
STATUS INDICATIONS
STATUS DISPLAY
FUNCTION
ACTION
Continuous Green
Battery in
Float/Trickle Charge
None
Continuous Red
Battery High Charging
Wait for Green Status
Flashing Green
In Test Mode
Wait for
Test to Complete
Alternate Red and Green
Red
One Blink ON / Pause
Insufficient Charge
for User Test
Transfer System Failure
Wait for Full Charge
Factory Service
Red
Two Blinks ON / Pause
Battery Failure
Check Connections
Replace Battery
Red
Three Blinks ON / Pause
Charger Failure
Factory Service
Red
Four Blinks ON / Pause
Lamp Failure
Check Remote
Connection /
Factory Service
BATTERY REPLACEMENT
To replace battery, disconnect branch circuit, detach unit from junction box, and cut plastic
strap securing battery inside power supply chassis. Unplug battery connector from Printed
Circuit assembly. Replace battery only with part number B310013.
This product contains Ni-Cd batteries. Used Ni-Cd batteries may not be disposed of in the
municipal solid waste stream. Ni-Cd batteries must be recycled or disposed of properly.
For information on local recycling drop-off points, phone toll free 1-800-BATTERY.
Page 8
Z410067