Intelligent Ballast Installation Instructions

advertisement
Intelligent Ballast Installation Instructions
Installing a Ballast
Note: The Fulham Co., Inc. CF-DA-UNV-XXX-TX-X is a program-start, dimmable florescent ballast. The wiring must be per the diagram provided. The
lamp holders must be of the 2-wire, non-shunted variety. Not using the proper
lamp holder will result in improper operation, i.e. no lamp start or flashing.
Note: The Fulham Co., Inc. CF-DA-UNV-XXX-TX-X is dimmable by either DALI
or 0-10 florescent controls. The control wiring must be positioned in accordance with (IAW) the NEC guidelines for control wiring in a luminaire.
Note: The Fulham Co., Inc. CF-DA-UNV-XXX-TX-X is a multi-function ballast
as it can drive 1, 2 or 3 lamp configuration fixtures. Reference Figure 9, Figure 10, and Figure 11 for the attached lamp table pertaining to the configuration you are using.
STEP 1: Position the luminaire in a manner to facilitate easy access
to the ballast chamber.
STEP 2: Install the ballast in the designated mounting area.
• A) Do not stand the ballast off by using a spacer.
• B) Mount the ballast against the metal surface of the fixture.
• C) Do not over tighten the mounting hardware as this will cause the ballast
to become loose during shipment to the customer. Ref Figure 1.
Figure 1
STEP 3: Attach the lamp holder wires to the ballast IAW the attached wiring diagram.
• A) It is recommended to use proper color coded wires to facilitate ease of
identification in the event of a ballast failure. Ref Figure 2.
Figure 2
STEP 4: Remove a Ballast ID sticker from the ballast (white numbers
on clear sticker) located at the Line voltage end of the ballast, ref Figure 3. Place the sticker at one end of the fixture in such a manner as to
make it visible from the user environment, ref Figure 4.
Figure 3
Figure 4
STEP 5: Attach the Line and Neutral wires from one half of the ballast
wiring quick disconnect to the Line(black) Neutral(white) WAGO style
stab connectors on the ballast. Ref Figure 5.
Figure 5
STEP 6: Attach the RJ-12 6p-6c ballast control wire to the RJ connector at the Line end of the ballast.
• A) Run this wire through a separate punch out from the line voltage punch
out IAW the NEC for Luminaires. Ref Figure 6.
• This figure is for
demonstration
purposes only. Ensure
control wire is fitted
through a grommet at
the metal punch-out to
protect the wire.
Figure 6
• B) Secure the bulk of the control wire to the outside of the fixture to ease
installation in the field. Ref Figure 7.
• This figure is for
demonstration
purposes only. Ensure
control wire is fitted
through a grommet at
the metal punch-out to
protect the wire.
Figure 7
STEP 7: Complete assembly of your luminaire as per your MFG guideline.
Appendix A - Wiring Diagram
v.1.3
• CF-DA-UNV-3XX-T8-W
Wiring Diagram for 1
lamp, 2 lamp, and 3
lamp configuration.
Figure 8
• CF-DA-UNV-XXX-TX-L
Wiring Diagram for 1
lamp, 2 lamp, and 3
lamp configuration.
Figure 9
Appendix B - Lamp Table CF-DA-UNV-XXX-TX-X
Figure 10 • CF-DA-UNV-332-T8-W
CF-DA-UNV-317-T8-W
Lamp Table.
v.1.3
Figure 11 • CF-DA-UNV-254-T5-L Lamp Table.
Figure 12 • CF-DA-UNV-332-T8-L Lamp Table.
Download