A75MD Data Sheet

advertisement
A75MD
Mine Battery Charger (SCR)
SCR Technology Mine Battery Charger
The La Marche model A75MD mine battery charger product line utilizes microprocessor controlled SCR charging
technology. The A75MD comes with a Vacuum Fluorescent Display (VFD) which is bright with clear contrast and
functions normally from -40°C to 80°C, making them ideal for outdoor use.
This charger features automatic AC line voltage compensation, current limiting, controlled I-E-I charging cycle and more.
The I-E-I charge cycle provides constant current start charge rate followed by constant voltage and completing with
constant current finish rate. The constant current finish rate can be terminated either by DV/DT or time to assure full
charge.
The rugged A75MD is specially designed for the mining market to perform reliably under severe conditions such as
moisture, corrosive atmosphere and rugged handling. The unit is convection cooled utilizing a 180°C class H insulation
system and powder coat paint for durable finish.
Standard Features
.
.
.
.
.
.
.
.
.
.
.
.
AC Input Voltages:
- North America 480/575, 3 Phase, 60 Hertz
- South Africa 995/1100, 3 Phase, 50 Hertz
- Norway 525/1050, 3 Phase, 50 Hertz
- China 660/695, 3 Phase, 50 Hertz
Microprocessor Controlled I-E-I Charge Cycle
VFD Display
Digital Display Indicates:
.
Limited 5 year Warranty
- DC Volts
- DC Amps
- Amp Hours Returned
- Elapsed Time on Charge
- Error Codes
Optional Accessories
Automatic Start / Stop Circuitry
Programmable Entry of Battery AH Rating
05D
Data Logging
Smart DV/DT Termination
21M
Manual Start & Stop Push Bottons
Battery Equalize Switch
21N
External 120 VAC Power Outlet Panel (3KVA)
Single Controls Plate (Plug & Play)
093
Tropicalization (Magnetics Only)
12 Hour Override Timer
184
Ground Integrity System (PA SPEC) (128VDC)
Operating Temperature 0° to 50°C (32° to 122° F)
18J
Ground Integrity System (PA SPEC) (240VDC)
LED Indications:
- ON Charge
- 80% Complete
- Equalize Mode
- Failure Mode
Specifications subject to change without notice
P25-DSA75MD-1
ECN 19603
07-12
.
La Marche Mfg. (A U.S. Company)
106 Bradrock Drive, Des Plaines, IL 60018
Tel: 847.299.1188 Fax: 847.299.3061
sales@lamarchemfg.com
www.lamarchemfg.com
DC Output
240 VDC
120L
128 VDC
64 L
Model Number
Battery
Amp- Hour
Capacity 100%
AC Input Draw*
Overall Dimensions
WXDXH
Case
No.
Shipping
Weight
Amp
(Max)
Volts
(8hr recharge @
High Selectable Rate)
480 VAC
575 VAC
A75MD-150-64L
153
128
850
45 - 58
35 - 48
26L
A75MD-210-64L
216
128
1200
54 - 70
45 - 58
A75MD-270-64L
270
128
1500
70 - 90
58 - 74
A75MD-360-64L
360
128
2000
89 - 115
73 - 95
CF**
CF
CF
A75M-210-120L 153
A75MD-150-120L
240
850
74 - 96
62 - 80
26P
108.00” X 39.00” X 25.25”
2,305
1,047.7
lbs
kgs
72.00” X 37.00” X 25.25”
1,180
536.4
26L
72.00” X 37.00” X 25.25”
1,340
609.1
26L
72.00” X 37.00” X 25.25”
1,545
702.3
CF
A75MD-210-120L
216
240
1200
101 - 130
82 - 107
26P
108.00” X 39.00“ X 25.25”
2,610
1,186.4
A75MD-270-120L
270
240
1500
130 - 168
100 - 130
26S
108.00” X 45.00” X 25.25”
2,980
1,354.5
All above models designed for optimal performance at 60Hz. **Consult factory for units designed specificaly at 50HZ. Please consult factory for availability of other DC cell range.
*AC Current Draws based @ 100% load. Maximun Current Draws is typically 105% of ratings shown.
Selectable Output Ratings in DC Amps
Cell
Rating
64 or 120
150
64 or 120
210
64 or 120
270
64
360
Output Amp
144 (800)
144 (800)
216 (1200) 270 (1500) 101 (560)
153 (850)
216 (1200)
270 (1500)
360 (2000)
FRONT PANEL
Model Number Nomenclature
A75MD - 210 - 64L - ( ) - ( ) - 3 - ( )
Model Number
DC Amps
Battery Cell
When ordering, please specify:
(Lead Acid)
Special Frequency
When Required *
AC Voltage(s) Code
- La Marche Model Number
AC Phase Code
- Input Voltage, Frequency, Phase
Factory Assigned
Accessory Code
- Number and Type of Battery Cells
AC Voltage Codes
60Hz
Special Frequency Code
5-50Hz
AC Phase Code
C - 480
ZB - 525
E - 575
P - 660
*60Hz standard unless
Special code is entered
3 - Three Phase
X - 695
H - 995
ZC - 1050
Y - 1100
Ordering Information
- Allows Rechange Time from Full
Discharge (where applicable)
- Optional Accessories
Download