RISER DIAGRAM TO FIRE ALARM – CLOSED CONTACT CONNECTION TO 120VAC POWER SOURCE 631RFx UR1 4 COND 4 COND 4 COND 4 COND CB401B PUSH BUTTON CB401B PUSH BUTTON 4 COND ® ® 1511 EMLOCK 1511 EMLOCK CB401A PUSH BUTTON (INSIDE) NOTES: (1) ALL LOW VOLTAGE SIGNAL WIRING SHALL BE 20-GAUGE MINIMUM. THE MINIMUM INDUCTIVE LOAD (LOCK) POWER WIRE GAUGE SHALL BE DETERMINED PER THE SDC WIRE GAUGE CHART. ALL WIRING (SINGLE OR MULTI-CONDUCTOR) SHALL BE COLOR CODED WITHOUT SPLICES. A MINIMUM OF TWO SPARE CONDUCTORS IS RECOMMENDED. (2) SPECIFY VOLTAGE WHEN ORDERING PRODUCTS. VOLTAGE IS NOT SPECIFIED ON THIS WIRE DIAGRAM, BE SURE ALL PRODUCTS ARE VOLTAGE COMPATIBLE. (3) ALL WIRING MUST CONFORM TO NATIONAL, STATE AND LOCAL CODES. (4) ALWAYS CONSULT WITH THE AUTHORITY HAVING JURISDICTION (AHJ) BEFORE INSTALLATION. (5) WHERE REQUIRED BY CODE, CONNECT FAILSAFE SYSTEMS TO THE LOCAL FIRE LIFE SAFETY SYSTEM FOR EMERGENCY RELEASE. Components Qty 2 1 2 1 Description 1650lb. Magnetic Lock w/ Door Position Switch 1.5 Amp Power Supply x Universal Relay Module Emergency Access Push Button Switch System Activation Push Button Switch Part Number 1511VD 631RF x UR1 CB401B CB401AU Manufacturer SDC SDC SDC SDC Method of Operation Both doors shall be normally unlocked. System Activation: All doors must be closed to lock. Pressing the CB401A Push Button will lock all the doors. Egress: When the doors are locked, pressing the CB401A Push Button again unlocks all the doors. Emergency Release: When the doors are locked, activating either of the CB401B Emergency Push Buttons will unlock both doors. Both doors will unlock automatically via signal from the fire panel. © Security Door Controls PROJECT NAME: LOCATION.: TITLE: Solution #2 - Communicating Bath 801 Avenida Acaso Camarillo, CA 93012 t 805.494.0622 ~ f 805.494.8861 www.sdcsecurity.com NOTE: ALL WIRING MUST BE REVIEWED AND APPROVED BY THE PROJECT ENGINEER ASSIGNED TO THE LOCATION FOR IT’S CORRECTNESS AND SUITABILITY FOR THE APPLICATION IN THE WHICH THE EQUIPMENT INSTALLED AND OPERATED. ALL WIRING MUST CONFORM TO NATIONAL, STATE, AND LOCAL CODES FOR CLASS 2 FIRE PROTECTION AND CONTROL DEVICES. Comm Bath 1511 EMLock w/DPS - 631RFxUR1 SO NO.: DIST.: CONTACT: DATE: DRAWN BY: REV A DWG. NO.: Page 1 of 2 1511VD EMLOCK® Switch No: Position CB401-B PUSH BUTTON SWITCH LAMP RED EMERGENCY RELEASE UR1 NC ORG DPS RED PUSH TO UNLOCK DOOR YEL WHT NO { C Set to CR Mode SW1 SW2 SW3 SW4 off off off off A w D B 631RFxUR1 – 1.5 AMP POWER SUPPLY WITH UNIVERSAL RELAY MODULE w D NO - + PWR C NO C NO - NO C NC - NO C NC COM TRIG A TRIG B RELAY A RELAY B TO 120VAC PRIMARY VOLTAGE CONNECTION NC + POWER - DOOR 1 J1 DOOR 1 G W B + RED EMERGENCY RELEASE ORG PUSH TO UNLOCK DOOR + - C J1 NC DPS RED - STANDBY BATTERY CONNECTION CB401-B PUSH BUTTON SWITCH LAMP + - 1511VD EMLOCK® REMOVE JUMPER J1 FOR 24VDC OPERATION. REFER TO POWER SUPPLY INSTRUCTIONS FOR VOLTAGE SELECTION PROCEDURE YEL NO WHT C { (REMOVE FACTORY JUMPER ONLY IF FIRE ALARM IS USED) NO COM 24VDC OUTPUT NC + POWER - DOOR 2 J1 DOOR 2 CLOSED FIRE ALARM CONTACT NOTE: EMLOCK® DPS SHOWN WITH DOOR IN THE CLOSED POSITION. NOTES: (1) ALL LOW VOLTAGE SIGNAL WIRING SHALL BE 18-GAUGE MINIMUM. THE MINIMUM INDUCTIVE LOAD (LOCK) POWER WIRE GAUGE SHALL BE DETERMINED PER THE SDC WIRE GAUGE CHART. ALL WIRING (SINGLE OR MULTI-CONDUCTOR) SHALL BE COLOR CODED WITHOUT SPLICES. A MINIMUM OF TWO SPARE CONDUCTORS IS RECOMMENDED. CB401-AU PUSH BUTTON SWITCH LAMP RED (2) SPECIFY VOLTAGE WHEN ORDERING PRODUCTS. VOLTAGE IS NOT SPECIFIED ON THIS WIRE DIAGRAM, BE SURE ALL PRODUCTS ARE VOLTAGE COMPATIBLE. RED NC ORG (3) ALL WIRING MUST CONFORM TO NATIONAL, STATE AND LOCAL CODES. BOTHDOORS MUST BE CLOSED TO LOCK YEL WHT (4) ALWAYS CONSULT WITH THE AUTHORITY HAVING JURISDICTION (AHJ) BEFORE INSTALLATION. BATHROOM LOCK C NO PUSH TO LOCK OR UNLOCK LIGHT ONDOOR LOCKED (5) WHERE REQUIRED BY CODE, CONNECT FAILSAFE SYSTEMS TO THE LOCAL FIRE LIFE SAFETY SYSTEM FOR EMERGENCY RELEASE. ACTIVATION SWITCH (6) DOOR POSITION SWITCHES SHOWN WITH THE DOOR CLOSED © Security Door Controls 801 Avenida Acaso Camarillo, CA 93012 t 805.494.0622 ~ f 805.494.8861 www.sdcsecurity.com NOTE: ALL WIRING MUST BE REVIEWED AND APPROVED BY THE PROJECT ENGINEER ASSIGNED TO THE LOCATION FOR IT’S CORRECTNESS AND SUITABILITY FOR THE APPLICATION IN THE WHICH THE EQUIPMENT INSTALLED AND OPERATED. ALL WIRING MUST CONFORM TO NATIONAL, STATE, AND LOCAL CODES FOR CLASS 2 FIRE PROTECTION AND CONTROL DEVICES. PROJECT NAME: TITLE: Solution #2 - Communicating Bath LOCATION.: DIST.: SO NO.: Comm Bath 1511 EMLock w/DPS - 631RFxUR1 CONTACT: DATE: DRAWN BY: REV A DWG. NO.: Page 2 of 2