DC POWER SYSTEM
DCPS
12KW WITH DISTRIBUTION
The La Marche DCPS system offers a complete DC power solution
in a compact package configuration (4RU). DCPS system can be
installed in standard 19 or 23 inch rack or cabinet.
La Marche DC system utilizes high efficiency rectifiers, a highly
intelligent system controller, I/O interface board for alarms/
sensors, and a load/battery distribution panel. This complete DC
system offers battery management with low voltage disconnect,
remote monitoring, remote configuration and configurable alarm
contacts.
The compact design of the system reduces space requirements and
installation cost. The system is configured with 48V/50A high
efficiency rectifiers to provide a rated output current up to 200A.
The DC distribution section is comprised of 16 pluggable load
breakers and 2 battery breakers.
Standard Features
Universal AC Input
Hot-Swappable Rectifiers Provide Easy Installation
and Maintenance
Rectifier Efficiency Exceeds 96% (Lower Energy
Consumption)
Rectifier Hibernation Management Mode (Increases
System Efficiency)
Intelligent Battery Management and Protection Modes
Site Environment Monitoring and Remote Management
(Through Dry Contacts, Serial Interface or Ethernet
Interface)
16 Pluggable Load Breakers, 2 Battery Breakers and
LVBD (Low Voltage Battery Disconnect)
50A Rectifier
(56A @ 53.3V)
UL Recognized
Controller
La Marche Mfg. (A U.S. Company)
Specifications subject to change without notice
P25-DSDCPS4-1
ECN 21098
4/16
106 Bradrock Drive, Des Plaines, IL 60018
Tel: 847.299.1188 Fax: 847.299.3061
sales@lamarchemfg.com
www.lamarchemfg.com
Specifications
RECTIFIER
Input Voltage
85-300 VAC, Single Phase
Input Frequency
45-66 Hz
Maximum Input Current
17A
Output Voltage
42-58 VDC, Nominal: 54 VDC
Efficiency
Rated Power
>96%
56A @ 53.3V (176-300 VAC)
Linearly derated to 23A @ 53.3V (85-175 VAC)
4.1” x 11.1” x 1.6” (1RU)
105 x 281 x 40.8mm
Dimensions (W x D x H)
DC DISTRIBUTION
CONTROLLER
MECHANICAL
ENVIRONMENTAL
www.lamarchemfg.com
Weight
≤4.4lb (≤2kg)
Cooling Mode
Forced Air Cooling
Power Factor
≥0.99
THD
≤5%
Maximum Capacity
220A @ Nominal
Battery Breakers
2 x up to 200A Breakers
Load Breakers
A group: 8 x up to 100A Breakers
B group: 8 x up to 100A Breakers
Low Voltage Battery Disconnect
Adjustable
Surge Protection Device (SPD)
10kA/20kA, 8/20µs
Display Mode
LCD
Available Signal Input
6 Digital Inputs, 1 Door Sensor, 1 Water Sensor, 1 Smoke
Sensor, 2 Temperature Sensors, 1 Battery Temperature Sensor,
1 Temperature/Humidity Sensor
Alarm Output
8 Dry Contact Outputs
Communication Ports
RS232/485, Fast Ethernet (FE)
Overall Dimensions
(W x D x H)
19” x 17.7” x 7” (4RU)
482.6 x 450 x 178mm
Weight (without rectifiers)
≤50.7lb (≤23kg)
Cooling
Natural Cooling
Mounting
19” or 23” Rack
Terminal
Rear Access
Protection Level
IP20
Operating Temperature
-40 to 65°C (-40 to 149°F)
Storage Temperature
Operating Humidity
Altitude
-40 to 70°C (-40 to 158°F)
5%-95% (Non-Condensing)
Up to 6,562ft (Derate Operating Temperature by 1°C/656ft
for 6,562ft-13,123ft)
2
CONTROLLER (DCSC)
Controller Front Panel
La Marche’s DC System Control (DCSC) is an intelligent
module that monitors and manages La Marche DC power
systems. The controller provides the system with Battery
Management, Energy Conservation, Rectifier Management,
Intelligent Battery Hibernation Mode, Battery Testing,
Battery Charging, and Current Limiting controls.
System configuration settings and real-time parameters can be
accessed either locally (through a two-line LCD display), or
remotely (through a Web User Interface).
Communication Ports
Communication
Ports
FE port
RS485/RS232 port
Communication
Parameter
Communication
Protocol
10/100M
auto-adaptation
HTTPS and SNMP
Baud rate:
9600 bit/s
Master/slave
protocols
NOTE: All ports are protected by a security mechanism
(1) Run Indicator
(2) Minor Alarm Indicator
(3) Major Alarm Indicator
(4) Control Buttons
(5) USB port
DCU I/O INTERFACE MODULE
(6) RS485/RS232 Port
(7) Handle
(8) Locking Latch
(9) Fast Ethernet (FE) Port
(10) LCD
DCU Port Description
Equipped with the I/O module (DCU), the controller
supports configurable digital inputs, alarm dry-contacts and
site sensor ports for environment management and alarms
reporting. The DCU I/O module provides the ability to add
multiple sensors for: ambient temperature, humidity, water,
door status, smoke and battery temperature.
Port Type
Sensor Port
The dry-contacts alarm are configurable and can be
customized upon the DC system’s requirements. All alarms
can be easily configured and monitored remotely through the
WebUI (Web User Interface). See page 4 for details.
Dry Contact Input
NOTE: For details about
the signal definitions, see
the power system user manual
Dry Contact Output
NOTE: For details about
the alarms associated with dry
contact outputs, see the power
system user manual
Communication Port
3
Silk Screen
Description
TEM-HUM
Ambient Temp. and humidity sensor
WATER
Water Sensor
TEMP1
Ambient Temperature Sensor 1
TEMP2
Ambient Temperature Sensor 2
GATE
Door Status Sensor
SMOKE
Smoke Sensor
BTEMP
Battery Temperature Sensor
DIN1
Dry Contact Input 1
DIN2
Dry Contact Input 2
DIN3
Dry Contact Input 3
DIN4
Dry Contact Input 4
DIN5
Dry Contact Input 5
DIN6
Dry Contact Input 6
ALM1
Dry Contact Output 1
ALM2
Dry Contact Output 2
ALM3
Dry Contact Output 3
ALM4
Dry Contact Output 4
ALM5
Dry Contact Output 5
ALM6
Dry Contact Output 6
ALM7
Dry Contact Output 7
ALM8
Dry Contact Output 8
COM
RS485 Port
Controller Features
DETECTION
BATTERY MANAGEMENT
AC Input Voltage
Battery Hibernation
AC Input Current
Battery Control
AC Frequency
Battery Charging
DC Output Voltage
Total Load Current
Battery Test
Battery Current Limiting
Total Battery Current
Battery Current
Battery Temperature Compensation
.
Battery High Temperature Protection
Battery Temperature
Ambient Temperature
Multi-Mode & Multi-Level Disconnecting Protection
Battery Imbalance Detection
Ambient Humidity
ENERGY
CONSERVATION MANAGEMENT
Battery Capacity Calculation/Backup Time Calculation
Rectifier Hibernation
ALARM
RECTIFIER MANAGEMENT
Internal Fault
Rectifier Operation Information
Rectifier Power-On/Off Control
AC Phase Failure
Rectifier Overvoltage Protection
AC/DC Overvoltage/Undervoltage
Load/Battery Fuse Break
Battery Discharging
Sequential Rectifier Startup
Low Voltage Battery Disconnect (LVBD)
MECHANICAL
Battery Temperature High/Very High/Low/Very Low
Rectifier Output Voltage and Current Limit
Overall Dimensions: 7.6” x 1.6” x 3.9”
(W x D x H)
194.3 x 40.8 x 99mm
Weight: 3.3lb (1.5kg)
Rectifier Failure
Natural Cooling
No Redundant Rectifiers
Rectifier Communication Failure
AC/DC Surge Protection Device (SPD) Failure
Web User Interface
The Web User Interface allows for a secure password protected remote access to the DC system for monitoring and control
purposes. The WebUI provides system’s running parameters, active alarms and configurations. Various settings can be configured
using the WebUI. Settings include: alarm parameters and configurations, rectifier management, battery management and
communications settings.
The WebUI provides flexible alarm configuration settings that includes a PLC (Programmable Logic Controller) programming
tool.
www.lamarchemfg.com
4
DC RECTIFIER (DCR)
The DCR50 rectifier converts AC power to DC power and
utilizes high performance features, such as high efficiency
(>96%), high power density, walk-in start, complete
protection and low noise. The output voltage of the rectifiers
can be adjusted through the DCSC controller. The
rectifier is hot swappable, providing easy installation and
maintenance.
Rectifier
Max. Amp
Input Voltage
Output Voltage
Max Input Current
DCR50
56A @ 53.3 VDC
85-300 VAC
42-58 VDC
< 17 A
Performance for 50 Amp Rectifiers
Output Feature
55
50
45
40
10 15
20 25
30 35
40
45 50
55
60 65
Current / A
100
98
96
94
92
90
88
86
84
82
80
3500
Power/W
Voltage/V
60
5
Power Derating Curve
Efficiency Curve
3000
2500
2000
1500
1000
20%
40%
60%
80%
100%
500
40
50
Load Rate
55
65
75
Temperature/℃
DC DISTRIBUTION PANEL (DCD)
The DC distribution section is comprised of:
• 16 pluggable Load Breakers (0 – 100 Amp)
• 2 pluggable Battery Breakers (Up to 200 Amp)
• LVBD circuit
All breakers are equipped with a trip detection
alarm, and can be sized based on the system
requirements.
Available Breaker Current Ratings:
1A, 2A, 3A, 5A, 10A, 15A, 20A, 25A, 30A, 35A, 40A
50A, 60A, 70A, 80A, 100A, 125A, 150A, 200A
Breaker Positions Required:
- 100A
= 1 Position
1A
= 2 Positions
125A - 200A
5
www.lamarchemfg.com
MECHANICAL
DCPS Front View
(1) Distribution DCD
7.00”
(2) Controller DCSC
(3) I/O Board DCU
(4) Open slots for rectifiers
(rectifiers sold separately)
17.70”
DCPS Top View without the Top Cover
(1) Return positive busbar
19.00”
(2) Wiring terminals for
DC output power cables
(3) Wiring terminals for battery
cables
17.70”
Ordering Information
Model
Number
Description
Max. Number
in One System
Available
Range
DCPS-200
Complete system without rectifiers or breakers
---
---
DCR50
50Amp DC rectifiers
4
---
P4-ALELB-xxD1B
Plug in bullet type breakers
16
Up to 100A
P4-ALELB-xxD1B
Plug in bullet type breakers
2
125A, 150A
P4-ACELB-200D1B
Plug in bullet type breakers
2
200A