ADCP-80-526 • Issue 1 • November 2000 PowerWorx™ Select Series™ Fuse Type Power Distribution Platform User Manual 14223-B ADC PowerWorx™ Select Series Fuse Type Power Distribution Panel (Sample Configuration Shown) Content Page INTRODUCTION ........................................................................... 3 Standards .......................................................................... 3 Important Features .................................................................... 5 Standard Configurations ................................................................ 6 Options ........................................................................... 7 Accessories ......................................................................... 7 Revision History...................................................................... 8 Trademark Information ................................................................. 8 Admonishments ...................................................................... 8 General Safety Precautions .............................................................. 8 1 GENERAL CHARACTERISTICS AND FEATURES .................................................. 9 1.1 Power Buses .................................................................. 9 1.2 Block Diagram ................................................................. 9 1.3 Bus Capacity ................................................................. 12 1.4 Bus Inputs ................................................................... 12 1.5 Bus Outputs .................................................................. 13 1.6 Fuse Panel Configuration ......................................................... 13 1.7 GMT Fuses ................................................................... 14 1.8 KLM/KTK Fuse Holders........................................................... 14 1.9 TPA Fuse Holders .............................................................. 14 (continued) 1091160 Rev A Page 1 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 Content 2 Page 1.10 Dummy Fuses................................................................. 14 1.11 Blank Modules ................................................................ 15 1.12 Chassis Ground Connection ....................................................... 15 1.13 Alarm Contact Closures .......................................................... 15 1.14 Fuse Alarm Indicators ........................................................... 16 1.15 Power-On Indicator ............................................................. 16 1.16 Fuse Designation Card and Holder ................................................... 16 1.17 Voltage Designation Label ........................................................ 17 PHYSICAL CHARACTERISTICS............................................................ 17 2.1 Material and Finish ............................................................. 17 2.2 Cooling ..................................................................... 17 2.3 Protector Cover ................................................................ 17 2.4 Weight ..................................................................... 17 2.5 Mounting .................................................................... 18 2.6 Environmental Characteristics...................................................... 18 2.7 Dimensions .................................................................. 18 3 ACCESSORIES ...................................................................... 18 4 UNPACKING AND INSPECTION ........................................................... 20 5 6 INSTALLATION ...................................................................... 20 5.1 Cable Management Bar (Optional Accessory) ........................................... 21 5.2 Mounting Brackets.............................................................. 21 5.3 Wiring Connections ............................................................. 22 5.4 Fuse Designation Pins ........................................................... 26 5.5 Fuse Designation Card Holder and Card ............................................... 26 5.6 Voltage Designation Label ........................................................ 27 5.7 Fuse Installation ............................................................... 27 TESTING THE FUSE PANEL .............................................................. 27 6.1 Quality Control ................................................................ 27 6.2 Resistance Test ............................................................... 27 6.3 Connection Polarity Test ......................................................... 27 6.4 Wiring Connections Measurements .................................................. 28 6.5 Power Indication Test ........................................................... 28 6.6 Fuse Alarm Test ............................................................... 28 7 OPERATION ........................................................................ 29 8 MAINTENANCE ...................................................................... 29 9 8.1 Inspection ................................................................... 29 8.2 Cleaning .................................................................... 29 8.3 Adjustments .................................................................. 29 8.4 Fuse Removal................................................................. 29 8.5 LED Replacement .............................................................. 30 CUSTOMER INFORMATION AND ASSISTANCE ................................................. 30 Page 2 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 INTRODUCTION This manual describes a fuse type power distribution platform that contains one or two buses (feeds) that accept input power of up to 100 Amps per bus, and provides fuse protected output power using two different types of fuses as selected from three types by the customer. This power distribution platform is designated ADC PowerWorx™ Select Series™ Fuse Type Power Distribution Platform, and is hereafter called “fuse panel.” This fuse panel is for telecommunications products used in central offices, multimedia headends, remote sites, and other locations requiring fused dc power. This fuse panel is available with several configurations of fuse types and fuse position modules. Two types of fuses, either GMT, KLM, or TPA, may be selected. KTK fuses will also fit in the KLM/KTK fuse holder, but are not currently rated for dc voltages by Underwriters Laboratories (UL). In a dual bus configuration, both the A bus and the B bus have the same type and size fuse holder modules. The maximum current that each type of fuse can provide is as follows (maximum bus current capacity is 100 Amps): • TPA type fuse; each fuse in four position module: 50 Amps • KLM type fuse; each fuse in one, two, three, four, or five position modules: 30 Amps • GMT type fuse; each fuse in four position module: 15 Amps • GMT type fuse; each fuse in five or 10 position modules: 10 Amps Two sample PowerWorx™ Select Series Fuse Type fuse panels are shown in Figures 1, 2, and 3. A description of this fuse panel, with its available options and accessories, is provided in this manual. The information necessary to install and operate the fuse panel is also provided herein. Standards The fuse panel complies with UL, Telcordia (formerly Bellcore), NEC 1999, CE, IEC, CSA, and NEBS Level 3 standards. The fuse panel design places emphasis on high reliability and simplicity of operation. Page 3 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 UL/CSA/CE LABEL VENTS BUS A KLM/KTK FUSE HOLDER (4 PER BUS) BUS A GMT FUSE HOLDER (4 POSITION) BUS B GMT FUSE HOLDER (4 POSITION) FRONT VIEW BUS B KLM/KTK FUSE HOLDER (4 PER BUS) UNIVERSAL MOUNTING BRACKETS (2), INSTALLED FOR 23-IN. (58.42 CM) RACK MOUNTING PROTECTIVE COVER PLACED OVER INPUT AND OUTPUT POWER, GROUND, AND ALARM CONTACT CONNECTIONS REAR VIEW 14224-B Figure 1. Front and Rear Views of ADC PowerWorx Select Series Fuse Type Fuse Panel with Protector Cover in Place (Fuse Panel with Dual Power Feed, Four 1-Position KLM/KTK Fuse Holders, and One 4-Position GMT Fuse Holder on Each Bus Shown) Page 4 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 BUS A GMT FUSE VALUE DESIGNATION PIN HOLDERS (1 PER POSITION) GMT FUSE HOLDER MAXIMUM CURRENT LIMIT (ON EACH FUSE HOLDER, BOTH BUSES) KLM/KTK FUSE HOLDER MAXIMUM CURRENT LIMIT (ON EACH FUSE HOLDER, BOTH BUSES) BUS B POWER-ON INDICATOR BUS A POWER-ON INDICATOR BUS B GMT FUSE VALUE DESIGNATION PIN HOLDERS (1 PER POSITION) 14225-B BUS A KLM FUSE FAILURE INDICATOR (1 PER FUSE HOLDER) BUS A GMT FUSE FAILURE INDICATOR (1 PER FUSE HOLDER) BUS B KLM FUSE FAILURE INDICATOR (1 PER FUSE HOLDER) BUS B GMT FUSE FAILURE INDICATOR (1 PER FUSE HOLDER) Figure 2. Front View of ADC PowerWorx Select Series Fuse Type Fuse Panel (Fuse Panel with Dual Power Feed, Four 1-Position KLM/KTK Fuse Holders, and One 4-Position GMT Fuse Holder on Each Bus Shown) Important Features The fuse panel provides several important features: • Self-configuring voltage capabilities to simplify installation and allow one panel to fit most dc voltage applications. • “Upside down” GMT fuse holders to make blown fuses more easily visible. • Optimally-positioned, high-brilliance fuse alarm red LED indicators that enable quick identification of blown GMT, KLM, and TPA type fuses. • Field-replaceable high-brilliance Power-On green LED indicator(s). • Easily-removable clear polycarbonate, protector cover over connectors to enhance safety and panel accessibility. • Two-post grounding to ensure robust and reliable ground connectivity. • Recess-mountable, universal mounting ears accommodate EIA or WECO 19-inch (48.26-cm) or 23-inch (58.42-cm) racks. Page 5 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 BUS B GMT FUSE VALUE DESIGNATION PIN HOLDERS (1 PER POSITION) BUS A TPA 4-POSITION FUSE HOLDER BUS A GMT 4-POSITION FUSE HOLDER BUS B GMT 4-POSITION FUSE HOLDER BUS B TPA 4-POSITION FUSE HOLDER MAXIMUM CURRENT LIMIT INDICATION FOR EACH GMT FUSE (ON EACH GMT FUSE HOLDER) BUS A GMT FUSE VALUE DESIGNATION PIN HOLDERS (1 PER POSITION) 15981-A BUS A GMT FUSE FAILURE INDICATOR (1 PER FUSE HOLDER) BUS A TPA FUSE FAILURE INDICATOR(1 PER FUSE HOLDER) MAXIMUM CURRENT LIMIT INDICATION FOR EACH TPA FUSE (ON EACH TPA FUSE HOLDER) BUS B TPA FUSE FAILURE INDICATOR (1 PER FUSE HOLDER) BUS B GMT FUSE FAILURE INDICATOR (1 PER FUSE HOLDER) BLANK PANEL (NO POWER-ON INDICATORS) Figure 3. Front View of ADC PowerWorx Select Series Fuse Type Fuse Panel (Fuse Panel with Dual Power Feed, One 4-Position TPA Fuse Holder, and One 4-Position GMT Fuse Holder on Each Bus Shown) Standard Configurations The standard configuration fuse panel has one or two power buses (feeds), with each power bus having multiple fuse holder modules with multiple fuse positions. In a two (dual) bus fuse panel, the second bus (Bus B) is a “mirror” image of the first bus (Bus A), having the same types of fuses and the same size fuse holder modules. Two different fuse types, selected from the GMT, KLM, or TPA fuse types may be used on each bus. The number of fuse positions on each bus is dependent upon the bus maximum limit of 100 Amps, the type and current value of fuses, and the width of the fuse holders. The dimensions of the fuse panel are 1.75 inches (4.45 centimeters) high, 17.12 inches (43.48 centimeters) wide, and 10.00 inches (25.41 centimeters) deep (does not include depth of protective covers, connectors, fuse holders, fuses, and visual indicators). The current capacity of each bus is 100 Amps maximum, which is marked on the fuse panel. The power dissipation of the fuse panel is 40 watts maximum at 100 A per bus. The fuse panel is capable of sensing the input voltage level and can be used with either –24 Vdc or –48 Vdc input voltages. Page 6 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 Using the universal mounting brackets included with the fuse panel, the fuse panel can be flush or recess mounted in 19-inch (48.26-cm) or 23-inch (58.42-cm) racks with WECO or EIA mounting options available. Options The fuse panel is available with the following options: • One bus or two buses • Two types of alarm contact connectors, either screw-down terminal strip connectors or wire-wrap pin block connectors • Power-On LEDs on the front of the fuse panel or no Power-On LEDs Other options are available by special order. Accessories Several accessories for the fuse panels are available (see Section 3): • Standard value GMT, KLM, and TPA fuses within the value limits in Table 1 • GMT colored fuse value designation pins (rivets) • Cable management bar kits • GMT fuse pullers • Three sizes of two-hole compression connector lugs for input power connections • Lug terminals to connect #10 AWG wire to earth ground. • Spare GMT Series type fuse value designation pin holders • Spare fuse value designation card holder kits Table 1. PowerWorx Select Series Fuse Panel Fuse Holders, Fuse Types, and Fuse Values FUSE TYPE FUSES PER AVAILABLE FUSE HOLDER MODULE FUSE HOLDER MODULE WIDTH TPA 1 to 4 in 4 position module 4.5 in. (11.43 cm) KLM 1 in 1 position module 1 or 2 in 2 position module 1 to 3 in 3 position module 1 to 4 in 4 position module 1 to 5 in 5 position module 1 to 4 in 4 position module 1.5 in. (3.81 cm) 3.0 in. (7.62 cm) 4.5 in. (11.43 cm) 6.0 in. (15.24 cm) 7.5 in. (19.05 cm) 1.5 in. (3.81 cm) 1 to 5 in 5 position module 1 to 10 in 10 position module 3.0 in. (7.62 cm) 3.0 in. (7.62 cm) GMT GMT FUSE VALUE RANGE Standard values, 3.0 Amps minimum, 50.0 Amps maximum Standard values, 5.0 Amp minimum, 30.0 Amps maximum Standard values, 0.2 Amp minimum, 15.0 Amps maximum (see 1.7) Standard values, 0.2 Amp minimum, 10.0 Amps maximum Page 7 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 Revision History ISSUE DATE Issue 1 11/2000 REASON FOR CHANGE Original Trademark Information ADC is a registered trademark of ADC Telecommunications, Inc. PowerWorx and Select Series are trademarks of ADC Telecommunications, Inc. Admonishments Important safety admonishments are used throughout this manual to warn of possible hazards to persons or equipment. An admonishment identifies a possible hazard and then explains what may happen if the hazard is not avoided. The admonishments — in the form of Dangers, Warnings, and Cautions — must be followed at all times. These warnings are flagged by use of the triangular alert icon (seen below), and are listed in descending order of severity of injury or damage and likelihood of occurrence. Danger: Danger is used to indicate the presence of a hazard that will cause severe personal injury, death, or substantial property damage if the hazard is not avoided. Warning: Warning is used to indicate the presence of a hazard that can cause severe personal injury, death, or substantial property damage if the hazard is not avoided. Caution: Caution is used to indicate the presence of a hazard that will or can cause minor personal injury or property damage if the hazard is not avoided. General Safety Precautions Caution: The fuse panel uses electrical voltage and amperage levels which, per GR-1089, may be considered an electrical hazard. Care should be exercised to assure that only qualified personnel are allowed to install, operate, maintain, or otherwise come in contact with this equipment when the fuse panel is energized. Only insulated tools should be used on energized elements of the fuse panel. Caution: All fuse panel wiring and cabling should be connected with the system office battery input off or disconnected at the office distribution panel. Caution: A replacement fuse must have exactly the same current rating as the fuse being replaced. Page 8 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 1 GENERAL CHARACTERISTICS AND FEATURES The fuse panel has the general characteristics and features defined in the following paragraphs. The rear view of the fuse panel, with the protective cover removed to show the external connectors is shown in Figures 4 and 5. Available accessories for the fuse panel are defined in Section 3. 1.1 Power Buses The fuse panel has one or two separate power buses. Each bus provides normal distribution of the input power to multiple fused output circuits using two different types of fuses, selected from GMT, KLM, or TPA types. In each bus circuit, current flows from the input to the fuse bus. When a fuse is installed in a fuse holder, the circuit is completed to the output connector. When a fuse fails, depending on the type of fuse, the following occurs: • KLM fuses: If a KLM fuse output is connected to a load, the fuse failure is sensed by a sensor, causing the alarm monitor to light a red LED indicator on the front of the fuse holder and close normally open contact closures (Form C contacts) at the alarm output connection. If a KLM fuse output is connected to a load, with no fuse installed, the corresponding sensor remains active and indicates a failure. If a KLM fuse output is not connected to a load, the corresponding sensor is inactive and no failure is indicated. Therefore, unused KLM/KTK fuse positions should not be connected to a load. • TPA fuses: The failure causes the alarm monitor to light a red LED indicator on the front of the fuse holder and close normally open contact closures (Form C contacts) at the alarm output connection. If a TPA fuse output is connected to a load, and no fuse is installed, the corresponding sensor remains inactive and no failure is indicated. • GMT fuses: The failure causes the alarm monitor to light a red LED indicator on the front of the fuse holder and close normally open contact closures (Form C contacts) at the alarm output connection. If a GMT fuse output is connected to a load, and no fuse is installed, the corresponding sensor remains inactive and no failure is indicated. 1.2 Block Diagram A block diagram of the fuse panel is shown in Figure 6. Page 9 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 BUS A AND BUS B ALARM CONTACT CONNECTOR (SCREW-DOWN BARRIER TERMINAL STRIP TYPE SHOWN) FEED B INPUT CONNECTORS (TWO HOLE COMPRESSION LUG STUD TYPE) PROTECTIVE COVER MOUNTING STANDOFFS (2 SETS) FEED A INPUT CONNECTORS (TWO HOLE COMPRESSION LUG STUD TYPE) 14226-B FEED B KLM FUSE OUTPUT CONNECTORS (SCREW-DOWN BARRIER TERMINAL STRIP) CHASSIS FEED A KLM FUSE GROUND OUTPUT CONNECTORS TERMINALS (SCREW-DOWN BARRIER FEED A GMT FUSE FEED B GMT FUSE TERMINAL STRIP) OUTPUT CONNECTORS OUTPUT CONNECTORS (SCREW-DOWN BARRIER (SCREW-DOWN BARRIER TERMINAL STRIP) TERMINAL STRIP) Figure 4. Rear View of Fuse Panel with Protector Cover Removed to Show Connectors (Fuse Panel with Dual Power Feed, One 4-Position KLM Output Connector Module Per Bus, One-4 Position GMT Output Connector Module Per Bus, and Screw-down Barrier Terminal Strip Alarm Contact Connector Shown) BUS A AND BUS B ALARM CONTACT CONNECTOR (WIRE-WRAP PIN BLOCK TYPE SHOWN) FEED B INPUT CONNECTORS (TWO HOLE COMPRESSION LUG STUD TYPE) FEED A INPUT CONNECTORS (TWO HOLE COMPRESSION LUG STUD TYPE) PROTECTIVE COVER MOUNTING STANDOFFS (2 SETS) 15982-A FEED B GMT FUSE OUTPUT CONNECTORS (SCREW-DOWN BARRIER TERMINAL STRIP) CHASSIS GROUND TERMINALS FEED B TPA FUSE OUTPUT CONNECTORS (SCREW-DOWN BARRIER TERMINAL STRIP) FEED A TPA FUSE OUTPUT CONNECTORS (SCREW-DOWN BARRIER TERMINAL STRIP) FEED A GMT FUSE OUTPUT CONNECTORS (SCREW-DOWN BARRIER TERMINAL STRIP) Figure 5. Rear View of Fuse Panel with Protector Cover Removed to Show Connectors (Fuse Panel with Dual Power Feed, One 4-Position TPA Output Connector Module Per Bus, One 4-Position GMT Output Connector Module Per Bus, and Screw-down Barrier Terminal Strip Alarm Contact Connector Shown) Page 10 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 BATTERY A RETURN A FEED A KLM FUSE ARRAY FEED A KLM SENSOR FEED A ALARM MONITOR FEED A POWER INDICATOR FEED B ALARM MONITOR FEED B POWER INDICATOR BATT 1 2 3 4 RTN 1 2 3 4 FEED A KLM FUSE ALARM INDICATOR FEED B KLM FUSE ALARM INDICATOR FEED B KLM SENSOR RETURN B BATTERY B FEED B KLM FUSE ARRAY BATT 1 2 3 4 FEED A GMT/TPA FUSE ARRAY BATT RTN 1 1 2 2 3 3 4 4 FEED A GMT/TPA FUSE ALARM INDICATOR FEED B GMT/TPA FUSE ALARM INDICATOR RTN 1 2 3 4 FEED B GMT/TPA FUSE ARRAY BATT 1 2 3 4 RTN 1 2 3 4 14227-B Figure 6. PowerWorx Select Series Fuse Panel Block Diagram (Dual Power Feed, Four-1 Position KLM/KTK Fuse Holders and One-4 Position GMT/TPA Fuse Holder on Each Bus Shown) Page 11 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 1.3 Bus Capacity The current capacity of each bus is 100 Amps maximum, which is marked above the input connectors on the rear of the fuse panel. The total current of a fuse panel with two buses is 200 Amps maximum. The power dissipation of the fuse panel is 40 watts maximum. The maximum current that each type of fuse can provide is: • TPA type fuse; each fuse in four position module: 50 Amps • KLM type fuse; each fuse in one, two, three, four, or five position modules: 30 Amps • GMT type fuse; each fuse in four position module: 15 Amps • GMT type fuse; each fuse in five or 10 position modules: 10 Amps 1.4 Bus Inputs 1.4.1 Input Voltage The fuse panel can accommodate –24 Vdc input power on both busses or –48 Vdc input power on both busses. The voltage is sensed by the fuse panel circuitry. The input voltage used with the fuse panel is required to have the following voltage characteristics: • –24 Vdc nominal, within a range of –21 Vdc to –30 Vdc • –48 Vdc nominal, within a range of –42 Vdc to –56 Vdc Fuse panels for use with other input voltage values and polarity may be available by special order. 1.4.2 Input Connectors Each bus has two (2) input connectors on the rear of the fuse panel through which input power is applied. The two input power connectors are labeled “BATT” (battery) and “RTN” (return). The input connectors are two-hole compression lugs (stud type). Each input connector has two (2) screws (studs) with nuts mounted on a tin plated copper plate(see Figures 4 and 5). Each set of two screws can accept different size 2-hole lugs which can be used with a range of wire sizes up to #2 AWG copper wire. Two 2-hole lugs per bus and one spare lug for use with #2 AWG wire (five total) are included with the fuse panel. Page 12 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 1.5 Bus Outputs 1.5.1 Output Voltage The output voltages will be the same voltage as the applied input voltage when the fuses do not fail. 1.5.2 Output Connectors Each bus has two sets of output connectors for each different type of fuses on the rear of the fuse panel through which the output power of the bus is available for connection to telecommunications equipment. The sets of output connectors are screw-down barrier terminal strips. Terminals are mounted in two barrier type terminal blocks per fuse type (see Figures 4 and 5). One of the strips is for output power; the other strip is for the power return. On the terminal strip, the terminal screw size, terminal barrier distance (width of ring or spade lug terminal) and the size of bare copper wire (insulation stripped back) to be used is dependent upon the fuse type as follows: TPA Fuse: Terminal screw size is 8-32. Maximum distance between barriers (maximum connecting terminal width) is 0.378 inch (9.601 mm). Bare wire size is #10 to #22 AWG. KLM Fuse: Terminal screw size is 8-32. Maximum distance between barriers (maximum connecting terminal width) is 0.320 inch (8.128 mm). Bare wire size is #12 to #22 AWG. GMT Fuse, four and five position module: Terminal screw size is 6-32. Maximum distance between barriers (maximum connecting terminal width) is 0.325 inch (8.255 mm). Bare wire size is #12 to #22 AWG. GMT Fuse, ten position module: Terminal screw size is 6-32. Maximum distance between barriers (maximum connecting terminal width) is 0.260 inch (6.604 mm). Bare wire size is #14 to #22 AWG. Bare wire size is #14 to #22 AWG. Combination of four TPA Fuses and 10 GMT fuses: Terminal screw size is 3-48. Maximum distance between barriers (maximum connecting terminal width) is 0.200 inch (5.080 mm). Bare wire size is #16 to #30 AWG. 1.6 Fuse Panel Configuration Two different fuse types, either GMT, KLM, or TPA, may be used on each bus. The number of fuse positions can be configured with a combination of standard size fuses of each of the two types by determining the types and number of fuses required, the size of the fuse holders, the width of the fuse panel available for mounting fuse holder modules, and the fuse values as shown in Table 1. The maximum mounting width available for mounting fuse holder modules in the single bus fuse panel is 7.50 inches (19.05 cm). The maximum mounting width available for mounting fuse holder modules in the dual bus fuse panel is 15.0 inches (38.1 cm). Page 13 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 1.7 GMT Fuses Using four position GMT fuse holder modules, up to four 15 Amp fuses can be installed sideby-side. If more than four 15 Amp fuses are installed, a space (one empty fuse position) must be placed between the four 15 Amp fuses and other 15 Amp fuses. Using five position and ten position fuse holder modules, 10 Amp fuses can be installed sideby-side without the need to have space between the fuses. Fifteen Amp fuses can be used in five position and ten position fuse holder modules, but a space (one empty fuse position) must be placed between each fuse. Each GMT fuse has a small color-coded fuse identification flag that identifies the value of the fuse that is installed. When the fuse fails, the flag moves away from the fuse to indicate the fuse failure. 1.7.1 GMT Fuse Holders GMT fuse holders are mounted on the fuse panel such that the GMT fuses install with the fuse identification flags located at the bottom of the fuse holder (upside-down position). When the flags are located at the bottom of the fuse holder, they are more visible from below when the fuse panel is installed in a location at or near the top of the rack. A fuse alarm red LED is mounted on the GMT module to allow quick identification of blown GMT fuses (see Figures 2 and 3). 1.7.2 GMT Fuse Value Designation Pin Holder The GMT fuse holder has numbered holes in the front of the fuse holder that corresponds to fuse positions in the fuse holder. The holes can be used to place color-coded pins (rivets) that identify the values of the GMT fuses (see Figures 2 and 3). 1.8 KLM/KTK Fuse Holders The KLM/KTK fuse holder modules will accept both KLM and KTK fuses. A fuse alarm red LED is mounted on the KLM/KTK fuse holder to allow quick identification of blown KLM fuses (see Figure 2). 1.9 TPA Fuse Holders The TPA fuse holder modules will accept four TPA fuses. A fuse alarm red LED is mounted on each TPA fuse holder to allow quick identification of blown TPA fuses (see Figure 3). 1.10 Dummy Fuses The fuse panel is shipped with dummy GMT fuses installed in all positions of the GMT type fuse holders and with dummy KLM fuses in all positions of the KLM/KTK fuse holders. Page 14 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 1.11 Blank Modules Space in the fuse panel that is not filled with fuse holder modules will be filled with blank modules. 1.12 Chassis Ground Connection Two #10 screws and nuts for grounding the fuse panel chassis are mounted on 0.625 inch (15.875 mm) centers (see Figures 5 and 6). This chassis ground connection can be used to attach a separate grounding conductor when mounting the fuse panel in non-grounded or nonconducting material or when required by local practice. Two crimp ring lug terminals for two #10 AWG wires are enclosed with the fuse panel. The fuse panel can be grounded using only one (1) screw. 1.13 Alarm Contact Closures The fuse panel contains circuitry that will provide three contact closures when any fuse on the bus fails or when input power to the bus is lost. These contact closures may be used as loop closures in alarm systems. The circuitry consists of alarm relays with Form C contacts that are terminated at a screwdown barrier terminal strip connector or wire-wrap pin block on the outside rear of the fuse panel. During normal operation, the normally open (NO) contacts remain open, and the normally closed (NC) contacts remain closed. When a fuse fails or power is lost, the NO contacts close, creating a connection from NO to common (C), and the NC contacts open. The current for each fuse alarm relay (set of three contacts) is 1.0 Amp maximum. 1.13.1 Alarm Contact Connection The fuse panel is available with either of two types of alarm contact connections. The two types of alarm contact connections are: • Screw-down barrier terminal strip: Six terminals with 3-48 screws are mounted in a barrier type terminal block (see Figure 4). The terminals are on 0.250 inch (6.350 mm) centers with a maximum distance between barriers (maximum connecting terminal width) of 0.200 inch (5.080 mm). The alarm terminal strip has two sets of three terminals labeled NO, C, and NC. Each set of terminals is for use with one alarm system. The terminals can also accept #16 to #30 AWG copper wire (with insulation stripped back). Wires are inserted in the terminal strip, and the screws are screwed down on the wires. • Wire-wrap terminal block: Wire-wrap pins are mounted in a terminal block for both buses (see Figure 5). The alarm terminal block has three sets of three wire-wrap pins (NO, C, NC), for use with three alarm systems. The wire-wrap pins can accept #22 to #26 AWG copper wire with insulation stripped back. Page 15 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 1.14 Fuse Alarm Indicators A visual fuse alarm indicator (red LED) mounted on the front of each fuse holder module lights when any fuse in that fuse holder module fails. The LED is not lighted when all fuses in the fuse holder module do not fail. Loss of power to a bus will cause all fuse alarm indicators corresponding to that bus to remain not lighted. 1.15 Power-On Indicator An optional power-on indicator (green LED) for each power bus mounts near the center of the front panel on the fuse panel (see Figure 2). A lighted LED indicates that power is applied to the bus input connectors. An unlighted LED indicates that power is not applied to the bus input connectors. The power-on indicator LED can easily be replaced in the field (see 8.5). The fuse panel can also be optionally configured without the power-on indicator(see Figure 3). 1.16 Fuse Designation Card and Holder Two types of fuse designation cards (see Figure 7) and a card holder are provided with the fuse panel. The card holder is intended to be attached to the fuse panel, to one of the fuse panel mounting brackets, to a part of the rack, or at a location close to the fuse panel, as desired. One of the cards should be filled out with circuit information for each of the fuses that are installed in the fuse holder and inserted in the card holder. The card holder has a pressure sensitive adhesive backing for attachment. 1.60 IN. (4.06 CM) 1.60 IN. (4.06 CM) 2.36 IN. (5.99 CM) 2.36 IN. (5.99 CM) 18 POSITION CARD 10 POSITION A AND B CARD 15983-A Figure 7. Fuse Designation Cards Page 16 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 1.17 Voltage Designation Label A voltage designation label (see Figure 8) is provided with the fuse panel. The label is intended to be filled out with the actual voltage present on the buses and placed on the fuse panel. The voltage designation label has a pressure sensitive adhesive backing for attachment. 0.38 IN. (0.96 CM) 1.00 IN. (2.54 CM) 14228-A Figure 8. Voltage Designation Label 2 2.1 PHYSICAL CHARACTERISTICS Material and Finish The fuse panel chassis and brackets are made of 16 gauge cold rolled steel. The fuse panel and brackets are finished with powder paint that is putty white color. 2.2 Cooling The fuse panel is well ventilated to allow efficient convection cooling of all components without the use of fans or blowers. A minimum of 1.75 inches (4.45 cm) of air space (one rack space) for cooling shall be provided between the top of the fuse panel and the item in the rack above the fuse panel, and between the bottom of the fuse panel and the item in the rack below the fuse panel. 2.3 Protector Cover A clear, polycarbonate protector cover is mounted on the rear of the fuse panel, over the input power connectors, the output power connectors, the chassis ground terminals, and the external alarm contact connections. To gain access to these connections and terminals, the cover is easily removed with the twist of a screw. To remove a cover, loosen the screws that attach the cover to the chassis, and pull the cover sideways and over the screws (holes are keyed for easy access). Screws do not need to be completely removed to remove the protector cover. 2.4 Weight The weight of the fuse panel is approximately 12.5 pounds (5.675 kilograms). Page 17 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 2.5 Mounting The standard (front and rear access) fuse panel can be mounted in a 19-inch (48.26-cm) rack or a 23-inch (58.42-cm) rack, using the universal fuse panel mounting brackets shipped with the panel. The mounting brackets can be flush mounted or recessed 1 inch (25.4 mm), 2 inches (50.8 mm), 3 inches (76.2 mm) or 4 inches (101.6 mm) from the front of the panel. The mounting brackets allow mounting with WECO 1.00-inch (2.54 cm) hole spacing or EIA 1.25-inch (3.18 cm) hole spacing. Two mounting brackets, eight (8) 1/4-inch (6.350 mm) 6-32 screws for attaching the brackets to the fuse panel, and four (4) 3/8-inch (9.525 mm) 12-24 screws with washers for attaching the brackets to the rack, are included with the fuse panel. 2.6 Environmental Characteristics Table 2 lists the environmental characteristics of the fuse panel. Table 2. Fuse Panel Environmental Characteristics PARAMETER Operating temperature Storage temperature Humidity range (operating) Altitude range Fire rating Earthquake design Acoustic noise Heat dissipation (fully loaded) Heat dissipation (no load) DESCRIPTION –5° C to +50° C –45° C to +85° C 0% to 95% humidity (non-condensing) –197 ft. (0.06 km) to 13,000 ft. (3.96 km) above sea level All components UL94-V1. NEBS Level 3; Zone 4 0 dBA above ambient 40watts maximum @ 100 A per bus 1 watt per bus 2.7 Dimensions The dimensions of the fuse panels are shown in Figure 9. 3 ACCESSORIES The following accessories for the PowerWorx fuse panel are available: • TPA fuses. Standard sizes from 3.0 Amp to 50.0 Amps • KLM fuses. Standard sizes from 5.0 Amp to 40.0 Amps • GMT fuses. Standard sizes from 0.2 Amp to 15.0 Amps • GMT colored, standard value, fuse value designation pins (rivets) • GMT Series type fuse value designation pin holder Page 18 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 • Cable management bar with mounting screws. Provides cable tie points. Installed at rear of fuse panel by fastening ends of bar to both sides of fuse panel. • GMT fuse puller • Three sizes of two-hole compression connector lugs for #2, #4, and #6, AWG wire for input power connections • Lug terminals to connect #10 AWG wire to earth ground. • Fuse value designation card holder kit 17.13 IN. (43.51 CM) 10.98 IN. (27.90 CM) 10.00 IN. (25.41 CM) 1.75 IN. (4.44 CM) 23.00 IN. (58.42 CM) 22.31 IN. (56.67 CM) 1.13 IN. (2.87 CM) 14229-B Figure 9. Dimensions of PowerWorx Select Series Fuse Type Fuse Panel with Protector Cover in Place and Mounting Bracket Attached for Mounting in 23 Inch (58.42 cm) Rack (Top and Front Views Shown Page 19 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 4 UNPACKING AND INSPECTION Unpack and inspect the various components as follows: 1. Inspect the exterior of the shipping container for evidence of handling that may have damaged the components in the container. 2. Unpack each container while carefully checking the contents for damage and verify with the packing slip. 3. File a claim with the commercial carrier and notify ADC Customer Service if damage is detected or if parts are missing. Save damaged cartons for inspection by the carrier. 4. Refer to the Customer Service section at the back of this manual for repair, replacement, and warranty information. 5. Save all shipping containers for use if the equipment requires return shipment at a future date. 5 INSTALLATION The following guidelines should be used when mounting the fuse panel in a rack. • Mount the fuse panel in the upper area of the rack or cabinet to reduce exposure of the power wiring. A minimum of 1.75 inches (4.45 cm) of air space (one rack space) between the top of the fuse panel and the item above the fuse panel, and between the bottom of the fuse panel and the item below the fuse panel shall be provided for cooling. • Adding a fuse panel to a rack may displace a device which may require relocation. • Use common hand tools to install the fuse panel. The use of a power screwdriver to install the self-tapping screws that attach the mounting brackets to the rack is recommended. Caution: This equipment employs electrical voltage and amperage levels which may be considered an electrical hazard. Care should be exercised to assure that only qualified personnel are allowed to install, operate, maintain, or otherwise come in contact with this equipment when the fuse panel is energized. Only insulated tools should be used on energized elements of the fuse panel. Warning: Never install telephone equipment in a wet location or during a lightning storm. When installing or modifying telephone lines, disconnect lines at the network interface before working with uninsulated lines or terminals to prevent electrical shock. Warning: Do not install fuses in fuse panel or power source until you have completed the power wiring connections. Page 20 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 5.1 Cable Management Bar (Optional Accessory) Before installing the fuse panel in the rack, mount the cable management bar (not supplied with fuse panel) on the rear of the fuse panel as shown in Figure 10. Caution: When attaching the cable management bar to the fuse panel, use only the 1/4-inch (6.350 mm) long 4-40 screws that are supplied with the cable management bar. Use of any other hardware could cause contact with internal parts of the fuse panel. The cable management bar can be recess mounted by using the mounting holes closest to the front of the fuse panel. Note: A fuse panel with the cable management bar attached may exceed the 12 inch (305 mm overall depth objective described in GR-63 COORE, 02-14. MOUNTING BRACKET INSTALLED FOR 23-IN. (58.42 CM) RACK MOUNTING ATTACH TO EITHER SET OF 3 HOLES CABLE MANAGEMENT BAR 14230-B Figure 10. Cable Management Bar Installation (Dual Power Feed Fuse Panel Shown), Rear View 5.2 Mounting Brackets Two 1-3/4-inch (4.45-cm) high universal mounting brackets are used to mount the PowerWorx Select Series fuse type fuse panel in either a 19-inch (48.26-cm) rack or a 23-inch (58.42-cm) rack. The brackets, mounting screws, and washers are provided with the fuse panel (see 2.5). See Figure 11. Caution: When attaching the mounting brackets to the fuse panel, use only the hardware supplied with the fuse panel. The flathead screws are for attaching the mounting brackets to the fuse panel. Use of any other hardware could cause contact with internal parts of the fuse panel. The slotted mounting hole pattern in the mounting brackets compensates for vertical rack differences and allows mounting the standard (front and rear access) 1-3/4-inch (4.45-cm) high fuse panel in either 1-3/4-inch (4.45 cm) high or 2-inch (5.08-cm) high rack spaces and allows mounting the 21.25-inch (53.97-cm) wide fuse panel in either 3-1/2-inch (8.89-cm) high or 3-3/4-inch (9.53 cm) high rack spaces. Page 21 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 19-IN. (48.26 CM) RACK, MOUNT ON FRAME, USE 3/8-IN. (9.525 MM) LONG SCREWS AND WASHERS (2) 23-IN. (58.42 CM) RACK, MOUNT ON FRAME, USE 3/8-IN. (9.525 MM) LONG SCREWS AND WASHERS (2) 23-IN. (58.42 CM) RACK, MOUNT ON FUSE PANEL, USE 1/4-IN. (6.350 MM) LONG FLATHEAD SCREWS (3) 19-IN. (48.26 CM) RACK, MOUNT ON FUSE PANEL, USE 1/4-IN. (6.350 MM) LONG FLATHEAD SCREWS (4) 15984-A Figure 11. Universal Mounting Brackets for Mounting PowerWorx Select Series Fuse Type Fuse Panel in 19-Inch (48.26-cm) Rack or 23-Inch (58.42-cm) Rack Install the fuse panel in the rack as shown in Figure 12 and as follows: 1. Mount the brackets to the fuse panel chassis using the eight (8) 1/4-inch (6.350 mm) 6-32 flathead screws. 2. Secure the fuse panel to the rack using the four (4)3/8-inch (9.525 mm) 12-24 screws and washers supplied with the fuse panel. Caution: Do not use any hardware other than the hardware supplied with the fuse panel by ADC. 5.3 Wiring Connections Note: Before connecting the input and output power wires, measure the resistance as defined in 6.2. Remove the protective cover from the fuse panel by loosening the four screws that attach the cover, sliding the cover to the right, and pulling it over the screws. Route and connect ground cables, power cables, and alarm cables to the fuse panel connectors according to local practice and the following subparagraphs. An example of the connections to the fuse panel is shown in Figure 13. After routing the cables, tie them to the cable management bar (if optional accessory ordered). Caution: Connect only the input voltage wire (wire labeled “BATTERY” or “BATT,” or labeled with the negative voltage polarity and/or the voltage value) – the “hot wire” – to the connector on the fuse panel labeled “BATT” (battery). Connect only the input return wire (wire labeled “RTN,” “RETURN,” or “BATTERY GROUND”) – the “ground wire” – to the connector on the fuse panel labeled “RTN” (return). If the wires are reversed, voltage could be present on the fuse panel chassis and current could flow through the unfused return wiring in the fuse panel. This condition causes damage to equipment in the rack in which the fuse panel is installed and to equipment in adjacent frames! Replace the protector cover on the fuse panel after all the wiring connections are made and before power is applied to the fuse panel. Page 22 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 14231-B Figure 12. Typical PowerWorx Select Series Fuse Type Fuse Panel Installation in Equipment Rack (With Optional Cable Management Bar), Rear View Page 23 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 FEED B, ONE TYPE OUTPUT CONNECTOR (SCREW-DOWN BARRIER TERMINAL STRIPS FOR 4 KLM FUSES SHOWN) CONNECT TO BUS B KLM FUSE OUTPUT POWER CONNECT TO BUS B KLM FUSE RETURN CHASSIS GROUND (2 CONNECTORS) COMBINED ALARM CONTACT CONNECTORS (SCREW-DOWN BARRIER TERMINAL STRIP SHOWN) CONNECT TO BATTERY BUS B* CONNECT TO RETURN BUS B** CONNECT CONNECT TO BATTERY TO RETURN BUS A* BUS A** FEED B, ONE TYPE OUTPUT CONNECTOR, (SCREW-DOWN BARRIER TERMINAL STRIPS FOR 4 GMT FUSES SHOWN) CONNECT TO T BUS B GMT FUSE OUTPUT POWER CONNECT TO BUS B GMT FUSE RETURN BUS A OUTPUT CONNECTORS ARE MIRROR IMAGE OF BUS B CONNECTORS *NOTE: CONNECT INPUT VOLTAGE WIRE LABELED "BATTERY" OR "BATT," OR LABELED WITH THE VOLTAGE POLARITY AND/OR THE VOLTAGE VALUE ("HOT" WIRE) TO THE "BATT" CONNECTOR ON THE FUSE PANEL. **NOTE: CONNECT INPUT RETURN WIRE LABELED "RTN," "RETURN," OR "BATTERY GROUND" (GROUND WIRE) TO THE "RTN" CONNECTOR ON THE FUSE PANEL. Figure 13. Fuse Panel Cabling; Select Series Fuse Type Fuse Panel, Rear View (Fuse Panel with Dual Power Feed, One 4-Position KLM/KTK Output Module and One Position GMT Output Module on Each Bus, and Screw-Down Barrier Strip Alarm Contact Connection Shown) Page 24 2000, ADC Telecommunications, Inc. 14232-B ADCP-80-526 • Issue 1 • November 2000 5.3.1 Chassis Ground Connection Mounting the fuse panel on a metal equipment rack using metal mounting brackets as described in 5.2 provides a sufficient return path to meet equipment grounding requirements. However, often a separate grounding conductor is required by local practice or local inspectors. A separate chassis grounding conductor is always needed when the fuse panel is mounted to non-grounded or non-conducting material, e.g., a plastic rack or cabinet. When the fuse panel requires separate chassis grounding, the chassis grounding conductor is sized to match the upstream protection device feeding the fuse panel. This provides an adequate return path capable of allowing the fuse to fail in the unlikely event of a battery wire to chassis fault. Connect one or both of the chassis ground connectors (labeled “C. GND”) to the equipment rack ground using the following chassis grounding recommendations: • Chassis ground conductor: Use two #10 AWG wires if using both chassis ground connectors or one #6 AWG wire if using one chassis ground. • Chassis grounding conductor connection point: Use provided #10 screws and nuts on 0.625 inch (15.875 mm) centers. Two #10 crimp ring terminals, for use with #10 AWG wires, are provided. 5.3.2 Output Power Connectors Connect the output BATT and RTN terminals for each fused circuit on each set of terminal strips. • Use wireleads with appropriate size crimp-on spade lugs or ring connectors, or use the size wire with insulation stripped back on the leads as follows (see 1.5.2): TPA Fuse: Terminal screw size is 8-32. Maximum connecting terminal width is 0.378 inch (9.601 mm). Use #10 to #22 AWG wire without lugs. KLM Fuse: Terminal screw size is 8-32. Maximum connecting terminal width is 0.320 inch (8.128 mm). Use #12 to #22 AWG wire without lugs. GMT Fuse, four and five position module: Terminal screw size is 6-32. Maximum connecting terminal width is 0.325 inch (8.255 mm). Use #12 to #22 AWG wire without lugs. GMT Fuse, ten position module: Terminal screw size is 6-32. Maximum connecting terminal width is 0.260 inch (6.604 mm). Use #14 to #22 AWG wire without lugs. Combination of four TPA Fuses and 10 GMT fuses: Terminal screw size is 3-48. Maximum connecting terminal width is 0.200 inch (5.080 mm). Use #16 to #30 AWG without lugs. • Torque the screws to approximately 9 pound-inches (1 Newton-meter). Page 25 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 5.3.3 External Alarm Contact Connections Connect each set of external alarm contacts to a system alarm as follows (see 1.13): • Screw-down barrier terminal strip: Terminal screw size is 3-48. Use wire leads with crimp-on spade lug or ring connectors that have a maximum width of 0.200 (5.080 mm) or use #16 to #30 AWG copper wire without lugs (insulation stripped back). Torque the screws to approximately 9 pound-inches (1 Newton-meter). • Wire-wrap terminal block: Wrap terminal block pins using #22 to #26 AWG copper wire with insulation stripped back. 5.3.4 Input Power Connectors Connect input power wires to the input power connectors labeled “BATT” and connect return wires to the return connectors labeled “RTN” for both buses in the fuse panel. Connect input power to the appropriate power sources in accordance with applicable local electrical codes and/or National Electrical Codes. Caution: Connect only the input voltage wire (wire labeled “BATTERY” or “BATT,” or labeled with the negative voltage polarity and/or the voltage value) – the “hot wire” – to the connector on the fuse panel labeled “BATT” (battery). Connect only the input return wire (wire labeled “RTN,” “RETURN,” or “BATTERY GROUND”) – the “ground wire” – to the connector on the fuse panel labeled “RTN” (return). Caution: Caution should be taken to not reverse input wires to the fuse panel. In the fuse panel, the internal battery (positive or negative voltage) wiring is fused, and the internal return wiring is not fused. Use the included 2-hole lugs with #2 AWG copper wire (insulation stripped back) or appropriate optional 2-hole lugs available as accessories (see Section 3) with appropriate AWG copper wire. Tighten the nuts to approximately 16 pound-inches (2 Newton-meters). 5.4 Fuse Designation Pins Insert the appropriate color-coded pins (accessory item, not supplied) in the corresponding holes in the GMT fuse holder as required. 5.5 Fuse Designation Card Holder and Card Attach the fuse designation card holder to the fuse panel, to one of the fuse panel mounting brackets, or to a part of the rack as desired by removing the backing from the back of the card holder and pressing the card holder against the mounting surface. Fill out one of the cards (see Figure 7) with circuit information as desired and insert it in the card holder. Page 26 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 5.6 Voltage Designation Label Write the voltage used in the fuse panel on the voltage designation label (see Figure 8) and attach the label to the back of the fuse panel. 5.7 Fuse Installation Replace the dummy fuses in the fuse holder(s) with the appropriate type and value fuses. Leave the dummy fuses in unused fuse positions. 6 TESTING THE FUSE PANEL Caution: This equipment employs electrical voltage and amperage levels which may be considered an electrical hazard. Care should be exercised to assure that only qualified personnel are allowed to install, operate, maintain, or otherwise come in contact with this equipment when the fuse panel is energized. Only insulated tools should be used on energized elements of the fuse panel. 6.1 Quality Control Each unit is thoroughly tested at the ADC Telecommunications factory. The following tests are recommended, however, to assure that no damage has occurred during shipping or handling. Both bus A and bus B input circuits (if applicable) need to be tested. 6.2 Resistance Test Caution: Before performing this test, verify that the input and output power is not connected to the fuse panel connectors. Measure the resistance at each bus input with a multimeter connected to the BATT and RTN input terminals. A resistance of at least 500 ohms should be read on the meter (some meters will indicate a resistance of several Megohms because their input voltage is not high enough to break down the forward conductance of the diodes used in the alarm circuit). Any resistance higher than 500 ohms is acceptable. 6.3 Connection Polarity Test To verify that the input power wires are connected to the correct terminals, measure the voltage between the input return connector (RTN) and the chassis ground using a multimeter. The voltage should be less than 2.0 Vdc. If the voltage is more than 2.0 Vdc, reverse the input power wires and measure the voltage between the input return connector (RTN) and the chassis ground again to determine that the voltage is less than 2.0 Vdc. Page 27 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 6.4 Wiring Connections Measurements Measure the torque of all input, output, chassis ground and fuse alarm relay contact connections stated in the Wiring Connections paragraphs above using a torque screwdriver that is calibrated in pound-inches (Newton-meters). 6.5 Power Indication Test After checking input resistance according to the Resistance Test above, the input power wires can be connected to the fuse panel. Upon power application, the fuse alarm indicators will not light unless no fuse is in the fuse holder or a fuse that has failed is in the fuse holder. Note: The KLM fuse positions require a load connected to the corresponding outputs to light the indicators. The fuse alarm relay should indicate an open circuit between the normally open (NO) contact and the common (C) contact at the alarm contacts. When input power is not applied, a short circuit will be indicated between these contacts. 6.6 Fuse Alarm Test 6.6.1 GMT and TPA Fuse Alarm Test Place a fuse that has failed in one of the fuse positions on each bus. The visual fuse alarm LED(s) will change from unlit to lit (red light), and the fuse alarm relay will operate. 6.6.2 KLM Fuse Alarm Test Perform the following tests: Note: The KLM fuse positions require a load connected to the corresponding outputs to light the fuse alarm indicators. 1. With the fuse panel powered, no load on the outputs, and no KLM fuses installed, observe that no fuse alarm LED is lit (no red light). Observe that the fuse alarm relay indicates an open circuit between the NO contact and the C contact at the fuse alarm contacts. 2. Connect a 10 kohm, ½ watt resistor between each KLM fuse output (labeled BATT) and return (labeled RTN). Observe that each KLM fuse alarm LED lights (red light) when the corresponding load is connected. Observe that the fuse alarm relay indicates a short circuit between the NO contact and the C contact at the fuse alarm contacts. 3. Insert a known good KLM fuse in each fuse position, one at a time, and observe that the corresponding fuse alarm LED is unlit. Page 28 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 7 OPERATION Caution: This equipment employs electrical voltage and amperage levels which may be considered an electrical hazard. Care should be exercised to assure that only qualified personnel are allowed to install, operate, maintain, or otherwise come in contact with this equipment when the fuse panel is energized. Only insulated tools should be used on energized elements of the fuse panel. All fuse panel circuits are operational as soon as power is applied to the input connectors. The alarm indicator should not light when power is applied. Operation of the fuse panel consists of removing and replacing fuses when a fuse fails. If a fuse fails, the alarm indicator lights, and the external and remote alarms are activated (if present). 8 MAINTENANCE Caution: This equipment employs electrical voltage and amperage levels which may be considered an electrical hazard. Care should be exercised to assure that only qualified personnel are allowed to install, operate, maintain, or otherwise come in contact with this equipment when the fuse panel is energized. Only insulated tools should be used on energized elements of the fuse panel. 8.1 Inspection Inspect the fuse panel periodically (every six months is recommended) for damage to the fuses, damaged or broken wires on the power outputs and the external alarm connections. Inspect for excessive dust and dirt that block the vents. 8.2 Cleaning If excessive dirt is found during the inspection, brush or wipe dust and dirt from the fuse panel with a soft bristle brush or soft cloth. Care should be taken to not damage the fuses or any wiring. 8.3 Adjustments No adjustments in the field are indicated or required. If a circuit is not operating properly, contact ADC customer assistance (see Section 9). 8.4 Fuse Removal The GMT fuses can be removed with the aid of a wire hook or tweezers-type fuse puller. A fuse puller is an available accessory. A TPA or KLM fuse may be removed by pulling the fuses straight out from the fuse holders. Page 29 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 8.5 Power-On LED Replacement The Power-On LEDs may be replaced as follows: 1. Pull LED out slowly from the front of the fuse panel. 2. Disconnect both mating terminals (quick-connects or fastons) on the wires from the tabs on the LED. 3. On the replacement LED, connect the mating terminal on the red wire to the tin tab and connect the mating terminal on the black wire to the brass tab. 9 CUSTOMER INFORMATION AND ASSISTANCE For customers wanting information on ADC products or help in using them, ADC offers the services listed below. To obtain any of these services by telephone, first dial the central ADC telephone number, then dial the extension provided below. The central number for calls originating in the U.S.A. or Canada is 1-800-366-3891. For calls originating outside the U.S.A. or Canada, dial country code “1” then dial 952-946-3000. Sales Assistance Extension 63000 • Quotation Proposals • Ordering and Delivery • General Product Information Systems Integration Extension 63000 • • • • • • • Complete Solutions (from Concept to Installation) Network Design and Integration Testing System Turn-Up and Testing Network Monitoring (Upstream or Downstream) Power Monitoring and Remote Surveillance Service/Maintenance Agreements Systems Operation BCG Technical Assistance Center Extension 63475 E-Mail: bcg_tac@adc.com • • • • • • Technical Information System/Network Configuration Product Specification and Application Training (Product-Specific) Installation and Operation Assistance Troubleshooting and Repair Product Return Department Extension 63748 E-Mail: repair&return@adc.com • ADC Return Authorization number and instructions must be obtained before returning products. Product information may also be obtained using the ADC web site at www.adc.com or by writing ADC Telecommunications, Inc., P.O. Box 1101, Minneapolis, MN 55440-1101, U.S.A. Page 30 2000, ADC Telecommunications, Inc. ADCP-80-526 • Issue 1 • November 2000 Contents herein are current as of the date of publication. ADC reserves the right to change the contents without prior notice. In no event shall ADC be liable for any damages resulting from loss of data, loss of use, or loss of profits and ADC further disclaims any and all liability for indirect, incidental, special, consequential or other similar damages. This disclaimer of liability applies to all products, publications and services during and after the warranty period. This publication may be verified at any time by contacting ADC’s Technical Assistance Center at 1-800-366-3891, extension 63475 (in U.S.A. or Canada) or 952-946-3000 (outside U.S.A. and Canada), or by writing to ADC Telecommunications, Inc., Attn: Technical Assistance Center, Mail Station #71, P.O. Box 1101, Minneapolis, MN 55440-1101, U.S.A. © 2000, ADC Telecommunications, Inc. All Rights Reserved Printed in U.S.A. Page 31