{1. DOOR IS NOT SHOWN. FOR INFORMATION SEE
DETAIL ED.231.
2. FOR CABLING SCHEMATIC SEE DETAIL NO. ED.211.
3. INSTALL GROUND WIRE BETWEEN EQUIPMENT
GROUNDING BAR AND DOOR GROUNDING LUG.
INSTALL GROUND LUG ON PROVIDED ENCLOSURE
DOOR TAB.
4. VERIFY THE OPENING AND CLOSING OF THE
ENCLOSURE. DO NOT INTERFERE WITH MILLWORK,
LIGHT FIXTURES, CEILING GRID, ETC.
5. NEW CONSTRUCTION: CISCO SWITCH PROVIDED
AND INSTALLED BY OWNER. (PER CPS OPERATIONS ITS
AGREED ALLOWANCE)
6. EXISTING SCHOOL: 24 OR 48-PORT CISCO SWITCH
WILL BE PURCHASED AND INSTALLED BY ITS.}
1
{WALL MOUNTED EQUIPMENT CABINET (CONCENTRATOR ENCLOSURE)
2
FIBER OPTIC PATCH PANEL WITH 6 LC CONNECTORS AND SIDE RAILS FOR PULL-OUT
ACCESS.
3
4
5
QUADRUPLEX ISOLATED GROUND (IG) RECEPTACLE (ORANGE) MOUNTED IN REAR OF
CABINET IN LEFT HAND CORNER, CONDUIT SHALL BE PLACED IN CORNER OF
CONCENTRATOR BEHIND MOUNTING RAIL SO AS NOT TO INTERFERE WITH EQUIPMENT.
PROVIDE ONE IG 20A, 120 V, 1-PHASE, DEDICATED, ISOLATED GROUND CIRCUIT.
8
5
8
9
5
TMGB
6
OSP CABLE
NOTES:
PLACE A #6 AWG INSULATED GROUND
APPLICABLE TO SERVE SPECIFIC REQUIREMENTS
PER THE SCHOOL.
GROUND ALL CONDUITS TO TMGB.
PLACE GROUND WIRE IN SEPARATE 3/4" CONDUIT
WHEN ENDING TERMINATION POINT IS AT OTHER
LOCATION THAN MDF.
COPPER EQUIPMENT GROUND BUS, PROVIDE WITH ENCLOSURE.
11
VSV
SSS
CATEGORY 6 UTP 48 PORT PATCH PANEL.
24-PORT OR 48-PORT CISCO NETWORK SWITCH. 48-PORT SWITCH TO BE USED IN TCE/QCE
CONFIGURATIONS. SEE NOTES 5 & 6.
6
8
2
4
WIRE MANAGER PANEL
3
VSS
3
CHICAGO
PUBLIC
SCHOOLS
ALL GROUNDING WIRE IS TO BE GREEN IN COLOR
VIA MANUFACTURERS WIRE JACKET. (COLOR
TAPE IS NOT ALLOWED)
CABLE
PROTECTOR
BLOCK
4
9
10
KEYED NOTES
NOTES:
1
CPS
ENCLOSURE DOOR GROUNDING LUG, ONE ON EACH VERTICAL SIDE ADDED TO DOOR, (SEE
NOTE 3)
19" WIDE EQUIPMENT RACKS (RACK NOT SHOWN ON RIGHT HAND SIDE)
DEPARTMENT OF FACILITIES
VENTILATION LOUVERS TO BE PROVIDED ON BOTH SIDE PANELS (LOUVERS ARE NOT
SHOWN) WITH LOUVER OPENINGS FACING DOWNWARD.
CAPITAL IMPROVEMENT PROGRAM
24/25 PAIR VOICE RISER BACKBONE CABLE. CATEGORY 5E 110 RACK MOUNTED 100 PAIR
PANEL (LEVITON ITEM 010-41DR2-100 OR APPROVED EQUAL). }
10
CCE - CLASSROOM CONCENTRATOR ENCLOSURE (1 ROOM).
SCE - SHARED CLASSROOMS CONCENTRATOR ENCLOSURE (2 ROOMS)
TCE - THREE CLASSROOMS CONCENTRATOR ENCLOSURE (3 ROOMS)
QCE - FOUR CLASSROOMS (QUAD) CONCENTRATOR ENCLOSURE (4 ROOMS)
KEYED NOTES:
11
VSS
1
2
3
4
5
6
7
ELECTRICAL
SCALE: 1/XX"=1'-0"
8
GROUNDING BUSHINGS W/INSULATED LINER
4" X 1/4" X 12" WALL MOUNTED TMGB
#6 AWG INSULATED GROUND WIRE TO OVERHEAD RACKING
PLACE A #6 AWG INSULATED GROUND WIRE TO THE MDF PANEL EQUIPMENT GROUND
ONE #6 AWG INSULATED GROUND WIRE TO EACH RACK/CABINET.
3/4" X 3/16" X 19" GROUND BAR
#6 AWG INSULATED GROUND TO COMMUNICATIONS CABLE(OSP) PROTECTOR BLOCK
#6 AWG INSULATED GROUND TO CONDUIT'S GROUNDING BUSHING
LOOP 24" LENGTH OF
TO 110 PATCH PANEL
XX
THE CONCENTRATOR
ELECTRICAL
SCALE: 1/XX"=1'-0"
MMTV, VOICE AND DATA
BACKBONE CABLES
TO MDF ROOM IN
1 1/2" C. MIN.
(1) 4PR CAT 5E UTP
OR SURFACE RACEWAY
CABLE FOR VOICE
(YELLOW)
SEE PLANS
(1) 4PR CAT 5E UTP
CABLE FOR VOICE
(YELLOW)
(1) 4PR CAT 6 UTP
CABLE FOR DATA
TO 110 PATCH PANEL -
(AQUA) TO FIBER SHELF IN MDF
(1) 24/25 PR RISER - CAT 5E
1
(1) 4PR CAT 6 UTP
(BLUE)
(BLUE)
(1) 6-STRAND FIBER OPTIC CABLE
CABLE FOR DATA
2
DISTRIBUTION RACK #2. PROVIDE
(2) 4PR CAT 6 UTP
IN SEPARATE, 1" MINIMUM DIAMETER
CABLE FOR DATA
CONDUIT.
(BLUE)
NOTES:
{1. FOR EQUIPMENT LAYOUT OF CCE/SCE/TCE/QCE SEE SHEET
NO. ED.201.
2. EACH DATA OUTLET STATION SHALL HAVE A 20A, 120V,
1-PHASE, DUPLEX RECEPTACLE ADJACENT TO IT. THESE DUPLEX
RECEPTACLES, SHALL BE ISOLATED GROUND (IG) (ORANGE) TYPE
AND SHALL BE CONNECTED TO IG PANELBOARDS.
3. INSTALL GROUND WIRE BETWEEN EQUIPMENT GROUNDING
BAR AND DOOR GROUNDING LUG. INSTALL GROUND LUG ON
PROVIDED ENCLOSURE DOOR TAB.
4. NEW CONSTRUCTION CISCO SWITCH PROVIDED AND
INSTALLED BY OWNER. (PER CPS OPERATIONS / ITS AGREED
ALLOWANCE)
5. EXISTING SCHOOL: 24 OR 48-PORT CISCO SWITCH WILL BE
PURCHASED AND INSTALLED BY ITS. }
4
REVISIONS
DATE
NO.
DESCRIPTION
FIBER PATCH CORD
DATA UTP PATCH
CORD
KEYED NOTES
{WALL
MOUNTED EQUIPMENT CABINET (CONCENTRATOR
1
ENCLOSURE)
9
6
03-11-2014
ISSUED FOR BID
02-11-2014
ISSUED FOR 100%
01-31-2014
ISSUED FOR 75%
01-13-2014
ISSUED FOR 60%
DRAWN BY:
FIBER OPTIC PATCH PANEL WITH 6 LC CONNECTORS AND SIDE RAILS
2 PULL-OUT ACCESS.
FOR
SCALE:
SEE SHEET
WIRE MANAGER PANEL
JOB:
2013044
3
CATEGORY
6 UTP 48-PORT PATCH PANEL.
FILE:
QUADRUPLEX
ISOLATED GROUND RECEPTACLE MOUNTED IN REAR
4
OF CABINET (NOT SHOWN)
5
24-PORT
OR 48-PORT CISCO NETWORK SWITCH SEE NOTES 4 AND 5.
10
COPPER EQUIPMENT GROUND BAR, PROVIDED WITH ENCLOSURE.
NO. 6 AWG GROUND
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
VOICE JACK
DATA JACK
DATA JACK
VOICE JACK
DATA JACK
DATA JACK
(WHITE)/
(ORANGE)
(TYPICAL)
(ORANGE)
(TYPICAL)
RJ45
DATA JACK
(ORANGE)
(TYPICAL)
(ORANGE)
(TYPICAL)
RJ45
DATA JACK
(WHITE)/
CABLE
(ORANGE)
(ORANGE)
TEACHER
CLASSROOM
STATION
PRINTER
WORK STATION
OUTLET
(1) LOCATION
(1) LOCATION
(UP TO 6 LOCATIONS
CLASSROOM "A"
#6 AWG INSULATED GROUND WIRE TO THE ALT. CURRENT (AC)
OUTLET TO PROVIDE EQUIPMENT GROUND.
8
TEACHER
CLASSROOM
STATION
PRINTER
(1) LOCATION
(1) LOCATION
SEE PLANS)
WORK STATION
OUTLET
(UP TO 6 LOCATIONS
SEE PLANS)
6
ENCLOSURE
GROUNDING LUG, ONE ON EACH VERTICAL SIDE ADDED
TO DOOR. SEE NOTE 3.
{CCE - CLASSROOM CONCENTRATOR ENCLOSURE (1 ROOM).
SCE - SHARED CLASSROOMS CONCENTRATOR ENCLOSURE (2 ROOMS)
TCE - THREE CLASSROOMS CONCENTRATOR ENCLOSURE (3 ROOMS)
QCE - FOUR CLASSROOMS (QUAD) CONCENTRATOR ENCLOSURE (4 ROOMS).}
24/25 PAIR VOICE RISER BACKBONE CATEGORY 5E 110 RACK MOUNT
WIRING PANEL TO 110 PATCH PANEL IN MDF ROOM.}
8
9
WARNIG:SBETO-CNAIGBULDMTERIASOMYBEPRSNTIHBULDG.ANSETOMGNPLAISVBENTHSCOLFREVIWUPONQST.ERONMAYDISTUBEO-CNTAIGMERLSUNTHAPERSOILCNDASBETOWRK CNDUTSHWORKINACDEWTHSPCIFAON()TIEDHPROJCTUMENSADICOPLNEWTHIOSDPARMENTFHLRUESANDGLTIO.
10
SHEET TITLE
CLASSROOM "B"
CLASSROOM "C" AND "D" SAME AS CLASSROOM "A OR B"
ELECTRICAL DETAILS
XX
SCALE: 1/XX"=1'-0"
ELECTRICAL
DRAWING NO.
{WARNING: ASBESTOS-CONTAINING BUILDING MATERIALS ARE OR MAY BE PRESENT IN THIS BUILDING. AN ASBESTOS MANAGEMENT PLAN IS AVAILABLE IN THE SCHOOL FOR REVIEW UPON REQUEST. NO PERSON MAY DISTURB ASBESTOS-CONTAINING MATERIALS UNLESS THAT PERSON IS A LICENSED ASBESTOS WORKER OR CONDUCTS SUCH WORK IN ACCORDANCE WITH SPECIFICATIONS(S) CONTAINED IN THE PROJECT DOCUMENTS AND IN COMPLIANCE WITH ILLINOIS DEPARTMENT OF HEALTH RULES AND REGULATIONS.}