HVAC Right Sizing Program Subcontractor’s field guide 0 GLOSSARY Procedures for HVAC Design and Installation Pg. 2 Details for an HVAC system: Materials, Fabrication, Design, and Installation Pg. 4 HVAC System Testing Protocols Pg. 11 Appendix A, Test-In Checklist Pg. 26 Appendix B, Test-Out Checklist Pg. 28 Appendix C, CEC Compliance Forms Pg. 30 Appendix D, CEC Code Clarification Letters Pg. 51 1 PROCEDURES FOR HVAC SYSTEM DESIGN AND INSTALLATION The goal for a HVAC system is to provide proper airflow, heating, and cooling to each room. This document sets out key criteria that describe a quality system, and key design and installation considerations that should be met to achieve this goal. The following pages contain more detailed information on design, fabrication, installation, and performance testing. Criteria for a Quality HVAC System An HVAC system should: 1. Be properly sized to provide correct airflow, and meet room-by-room calculated heating and cooling loads, 2. Be installed so that the static air pressure drop across the handler is within manufacturer and design specifications, 3. Have sealed supply ductwork that will provide proper airflow, 4. Be installed with a return system sized to provide correct return airflow, 5. Have sealed return ductwork that will provide proper airflow to the fan, and avoid air entering the HVAC system from polluted zones (e.g., fumes from autos and stored chemicals, and attic particulates), 6. Have balanced airflows between supplies and return systems to maintain neutral pressure in the home, 7. Minimize duct air temperature gain or loss between the air handler and room registers, and between return registers and the air handler, 8. Be properly charged with refrigerant, 9. Have proper CVA, burner operation and proper draft. Procedures to Design and Install an Air Distribution System The following steps should be followed in the design and installation of the HVAC system to ensure efficiency and comfort: 1. Determine room-by-room loads and air-flows using ACCA Manual J calculation procedures (or substantially equivalent), 2. Layout duct system on floor plan, accounting for the direction of joists, roof hips, firewalls, and other potential obstructions. Determine register locations and types, duct lengths, and connections required to produce layout given construction constraints, 3. Size duct system according to ACCA Manual D calculation procedures (or substantially equivalent), 4. Size HVAC equipment to sensible load using ACCA Manual S procedures (or substantially equivalent), 5. Install equipment and ducts according to design specifications, using installation requirements and procedures from the Uniform Mechanical Code, the Air Diffusion Council, SMACNA, 2 California Residential Energy Efficiency Standards (Title 24), and manufacturers’ specifications. Using these procedures, the duct system should be substantially air tight, 6. Charge the system appropriately, and verify charge with the evaporator superheat method or sub-cooling method, 7. Check for proper furnace burner operation and firebox drafting, 8. Test the system to ensure that it performs properly by determining that the system is properly sized, it does not leak substantially, and has proper air handler fan flow, and proper plenum static pressures. 3 Details for an HVAC System: Materials, Fabrication, Design and Installation MINIMUM MATERIALS SPECIFICATIONS The following are minimum materials specifications recommended to achieve a substantially tight installation that will last: All Materials Shall have a minimum performance temperature ratings per UL181 (ducts), UL181A (closure systems for rigid fiberglass ducts), UL181B (closure systems for flexible ducts) and/or UL 181BM (mastic); Butyl-back tape may also be used to seal ducts, ductboard and metal, Shall have a flame spread rating of no more than 25 and a maximum smoke developed rating of 50 (ASTM E 84). Factory-Fabricated Duct Systems All factory-fabricated duct systems shall include UL 181 listed ducts with approved closure systems including collars, connections and splices, All pressure-sensitive and heat-activated tapes used in the manufacture of rigid fiberglass ducts shall be UL 181A listed, All pressure-sensitive tapes and mastics used in the manufacture of flexible ducts shall be UL 181B (tape) or UL 181BM (mastic) listed. Field-Fabricated Duct Systems Ducts: - Factory-made ducts for field-fabricated duct systems shall be UL 181 listed. Mastic sealants and mesh: - Sealants shall be UL 181BM listed, non-toxic, and water resistant, - Sealants for interior applications shall pass ASTM tests C 731 (extrudability after aging) and D 2202 (slump test on vertical surfaces), - Sealants and meshes shall be rated for exterior use, - Sealants for exterior applications shall pass ASTM tests C 731, C 732 (artificial weathering test), and D 2202. Pressure-sensitive tapes: - Cloth-backed, rubber-adhesive tapes (typical duct tape) shall not be used even if UL 181B rated, - Tape used for flex-duct shall be UL 181B listed or be aluminum-backed butyl adhesive tape (15 mil. minimum), - Tape used for duct board shall be UL 181A listed and so indicated with a UL 181A mark or aluminum-backed butyl adhesive tape (15 mil. minimum). 4 Draw bands: - Shall be either stainless-steel worm-drive hose clamps or UV-resistant nylon duct ties, - Shall have a minimum performance temperature rating of 165 degrees Fahrenheit (continuous, per UL 181A-type test) and a minimum tensile strength rating of 50 pounds, - Shall be tightened as recommended by the manufacturer with an adjustable tensioning tool. 5 DESIGN, FABRICATION, AND INSTALLATION The following are design, fabrication, and installation guidelines that, if carefully followed, will provide a duct installation that is substantially airtight and that will provide proper airflow to each room of the house: General Issues Ducts, plenums, and fittings should be constructed of galvanized metal, duct board, or flexible duct. Building cavities may not be used as a duct or plenum without a sealed duct board or metal liner, The air handler box should be airtight, Air filters should be easily accessible for replacement, and evaporator coils should be easily accessible for cleaning, Ducts should be configured and supported so as to prevent use of excess material, prevent dislocation or damage, and prevent constriction of ducts below their rated diameter, Flexible duct bends should not be made across sharp corners or have incidental contact with metal fixtures, pipes, or conduits that can compress or damage the ductwork, Flexible ducts should not have bends that exceed 90º unless specified in the design, Sheet metal collars and sleeves should be beaded to hold draw-bands. DESIGN HVAC SYSTEM Loads and CFM Calculation ACCA Manual J Load Calculation or equivalent required, Calculate heat loss and heat gain for each room, Total room loads to determine system requirements. Lay Out Air Distribution System Lay out duct system on floor plan and determine register positions and duct paths to optimize room air circulation and minimize actual duct length as well as equivalent lengths of fittings, bends, etc., Duct paths must account for locations and directions of joists, roof hips, firewalls, and other potential obstructions, Duct paths must be planned to avoid sharp turns of flexduct that will kink the duct. Size Air Distribution System ACCA Manual D Duct Design or equivalent required, Calculate correct cfm for each room and total for building for both supply and return, Size ducts according to Manual J loads, Manual D airflows, and final layout on plans, Choose registers to optimize air distribution and duct static pressure, Size and locate returns to optimize airflow per ACCA methods, For return-filter grills, calculate minimum return filter area per ACCA methods. 6 Select System ACCA Manual S Residential Equipment Selection or equivalent required. ACCA, 1515 16th St., NW, Washington, DC 20036, From Manual J loads and Manual D cfm, determine appropriate equipment Equipment should be sized to sensible loads, Equipment sensible capacity should not be more than 15% larger than the total sensible design load (as specified in Manual S). FABRICATE AND INSTALL AN AIRTIGHT DUCT SYSTEM All Duct Types All joints and seams of duct systems and their components should be sealed with mastic, mastic and embedded mesh, aluminum-backed butyl adhesive tape (15 mil. minimum), or pressure-sensitive tape approved for use by the duct manufacturer and meeting UL181 specifications, excluding cloth-backed rubber-adhesive tapes (“approved tape”); cloth-backed rubber-adhesive tapes shall not be used to attach or seal ducts, Junctions of collars to distribution boxes and plenums should be sealed with mastic, All sealants should be used in strict accordance with manufacturer’s installation instructions and within sealants moisture and temperature limitations, All tapes used as part of duct system installation should be applied to clean, dry surfaces and sealed with manufacturer’s recommended amount of pressure or heat. If oil is present, taped surfaces should be prepared with a cleaner / degreaser prior to application, 7 Flexible Ducts Flexible ducts should be joined by a metal sleeve, collar, coupling, or coupling system. At least 2 inches of the beaded sleeve, collar, or coupling must extend into the inner core while allowing a 1-inch attachment area on the sleeve, collar, or coupling for the application of tape, The inner core should be mechanically fastened to all fittings, preferably using draw-bands installed directly over the inner core and beaded fitting. If beaded sleeves and collars are not used, then the inner core should be fastened to the fitting using #8 screws equally spaced around the diameter of the duct, and installed to capture the wire coil of the inner liner (3 screws for ducts up to 12” diameter, and 5 screws for ducts over 12” diameter), The inner core should be sealed to the fitting with mastic or approved tape, Tape used for sealing the inner core should be applied with at least 1 inch of tape on the duct lining, 1 inch of tape on the fitting of flange, and wrapped at least three times, The outer sleeve (vapor barrier) should be sealed at connections with a drawband and/or three wraps of approved tape, The vapor barrier should be complete. All holes, rips, and seams must be sealed with mastic or approved tape. Metal Ducts and Plenums Metal-to-metal connections should be cleaned and sealed in accordance with manufacturer’s specifications, Openings greater than 1/16 inch should be sealed with mastic and mesh, or butyl adhesive tape, Openings less than 1/16 inch should be sealed with mastic or UL-181A listed tape, Special attention should be paid to collar connections to duct-board and/or sheet metal; seal around the connection with mastic, Connections between collars and distribution boxes should be sealed with mastic, At least three equally spaced #8 screws should be used to mechanically fasten round ducts (3 screws for ducts up to 12” diameter, and 5 screws for ducts over 12” diameter), Crimp joints should have a contact lap of at least 1½ inches, Square or rectangular ducts should be mechanically fastened with at least one screw per side 8 Duct Board Duct board connections should be sealed with adhesive, mastic, or UL 181A listed pressuresensitive or heat-activated tape in accordance with manufacturer’s specifications. Duct Support Supports should be installed per manufacturer’s specifications or per UMC requirements, Supports for flexible ducts should be spaced at no more than 4-foot intervals, Flexible ducts should be supported by strapping having a minimum width of 1½ inches at all contact points with the duct, Supports should not constrict the inner liner of the duct, Flexible ducts should have maximum of ½ inch sag per foot between supports, Flexible ducts may rest on ceiling joists or truss supports as long as they lie flat and are supported at no more than 4-foot intervals. Boots After mechanically attaching the register boot to floor, wall, or ceiling, all openings between the boot and floor, wall, or ceiling should be sealed with caulk, mastic, or butyl-adhesive tape, 9 Air Handler Openings greater than 1/16 inch should be sealed with mastic and mesh, or butyl adhesive tape, Openings less than 1/16 inch should be sealed with mastic or UL 181A listed tape, Unsealed access doors should be sealed with UL 181A listed tape. 10 HVAC SYSTEM TESTING PROTOCOLS The following are testing requirements and procedures that must be followed to ensure that the HVAC system has been properly installed. The tests are designed to determine whether: 1. Ducts, plenum, and air handler are tight; a. A rough system, including both supply and return but without the air handler, should not leak more than 4% of nominal fan flow (cfm leakage measured with HVAC system pressurized to 25 Pa), b. For finished installation, including supply and return ducts, the air handler, condeser and finished registers, measured leakage must be less than 6% of nominal fan flow (cfm leakage measured with HVAC system pressurized to 25 Pa), or less than 15% of nominal fan flow for equipment change-outs only, c. Duct leakage can be determined using a pressurization or depressurization technique; for details, see ASHRAE Standard 152P, California Energy Commission ACM Manual Appendix F, Minneapolis Duct Blaster™ manual, or other commercially available duct pressurization or depressurization devices, d. Duct leakage to outside space can be determined with the house pressurization or LBL simplified technique. 2. Cooling Coil Airflow is as designed; a. Airflow must be greater than 350 cfm/ton, 3. Fan Watt Draw requirements are met; a. Fan Watt Draw must be equal to or better than .58w per cfm 4. Refrigerant Charge is adequate; a. For systems with fixed metering devices use evaporator superheat method: i. Cooling coil airflow must be greater than 350 cfm/ton, ii. Refrigerant system evacuation must be complete; iii. In hot, dry climates be cautious to be within range of superheat charging chart or use an approved method. b. For systems with thermostatic expansion valves use the sub-cooling method. PROCEDURES 1. Duct Testing (using 1 of the 3 following methods) a. Total Duct Leakage (brand new systems and change-outs), CF6R- MECH-20-HERS or CF6R-MECH-21-HERS i. The objective of this procedure is for an installer to determine or a rater to verify the total leakage of a new or altered duct system. The total duct leakage shall be 11 determined by pressurizing the entire duct system to plus 25 Pa with respect to outside. The following procedure shall be used for the fan pressurization tests: 1. Verify that the air handler, supply and return plenums and all the connectors, transition pieces, duct boots and registers are installed. The entire duct system shall be included in the total leakage test, 2. For newly installed or altered ducts, verify that cloth backed rubber adhesive duct tape has not been used and if a platform or other building cavity used to house the air distribution system has been newly installed or altered, it contains a duct or is ducted with duct board or sheet metal, 3. Seal all the supply and return registers except for one return register or the system fan access, 4. Attach the duct blaster to the duct system at the return, 12 5. Install a static pressure probe at a supply register, 6. Pressurize the ducts with the duct blaster to produce a +25 Pa pressure in the duct system, 7. Record the flow from the manometer; this is the leakage flow at +25 Pa, 8. Divide the leakage flow by the total fan flow determined by the cooling method (400cfm X ton) or the heating method (21.7x BTU output in thousands) to find a percentage, 9. If the leakage flows percentage is less than 15% for change-outs or 6% for whole new systems, it passes 13 b. Duct Leakage to Outside (change-out only), CF6R-MECH-21-HERS i. The objective of this test is to determine the duct leakage to outside. This measurement is used to verify that duct systems are entirely located within conditioned space. The procedure is also used to provide an alternate leakage measurement where it is likely that some of the total duct leakage is to within the conditioned space. The duct leakage to outside shall be determined by pressurizing the ducts and the conditioned space of the house to 25 Pa with respect to outside. The following procedure shall be used for the fan pressurization test of leakage to outside: 1. Seal all the supply and return registers except one return register or the fan access door, 2. Attach the duct blaster to the duct system at the unsealed register or access door, 3. Install a static pressure probe at a supply register, 4. Attach a blower door to an external doorway, 5. If any ducts are located in an unconditioned basement, all doors or accesses between the conditioned space and the basement shall be closed, and at least one operable door or window (if it exists) between the basement and outside shall be open during the test, 6. If the ducts are located in a conditioned basement, any door between the basement and the remaining conditioned space shall be open, and any basement doors or windows to outside must be closed during the test. 7. Adjust the blower door fan to provide +25 Pa pressure in the conditioned space with respect to outside, 8. Adjust the duct blaster to maintain zero pressure (plus or minus 0.5Pa) between the ducts and the conditioned space, and adjust the blower door fan to maintain +25 Pa pressure in the conditioned space with respect to outside. This step may require several iterations, 14 9. Record the flow from the Duct blast Manometer (this is the duct leakage at +25 Pa. To verify ducts in conditioned space compare this flow to the criterion, 10. Where the criterion is a percentage of total flow, divide the leakage flow by the total fan flow determined by by the cooling method (400cfm X ton) or the heating method (21.7x BTU output in thousands) to find a percentage. 11. If the leakage flow percentage is less than 10%, the system passes. c. Leakage Reduction Test (change-out only), CF6R-MECH-21-HERS i. For altered existing duct systems that do not pass the Total Leakage or Leakage to Outside tests, the objective of this test is to show that the original leakage is reduced through duct sealing. The following procedure shall be used: 1. Use the procedure of the total duct leakage test to measure the leakage before commencing duct sealing, 2. After sealing is complete use the same procedure to measure the leakage after duct sealing, 3. Subtract the sealed leakage from the original leakage and divide the remainder by the original leakage. If the leakage reduction is 60 percent or greater of the original leakage, the system passes. 2. Cooling Coil Airflow (using 1 the 3 following methods), CF6R-MECH-22-HERS a. Cooling Coil Airflow with a flow hood i. The fan flow measurement shall be performed using the following procedures: 1. All registers shall be fully open, and the air filter shall be installed, 2. Turn on the system fan at the cooling speed and measure the fan flow at the return grille(s) with a calibrated flow capture hood to determine the total system return fan, 3. The system fan flow (cfm) shall be the sum of the measured return flows. 15 b. Cooling Coil Airflow with Plenum Pressure Matching Method i. The fan flow measurement shall be performed using the following procedures: 1. If the duct blaster is to be connected to the air handler outside the conditioned space, then the door or access panel between the conditioned space and the air handler location shall be opened, 2. With the system fan on at the maximum speed used in the installation (the cooling speed when air conditioning is present), measure the pressure difference (in Pa) between the supply plenum and the conditioned space (Psp). Psp is the target pressure to be maintained during the fan flow tests, 3. Place the pressure probe in the Supply Pressure Measurement Location described below: 4. Adjust the probe to achieve the highest pressure and then firmly attach the probe to ensure that it does not move during the fan flow test, 5. If the duct blaster is to be connected to the air handler at the access, block the return duct system from the plenum upstream of the air handler fan and the duct blaster. Filters are often located in an ideal location for this blockage, 6. Attach the duct blaster to the duct system at the air handler or alternatively at the inlet to the return from the conditioned space with the grille and filter removed, 7. Turn on the system fan and the duct blaster, and adjust the pressure until the pressure between supply plenum and conditioned space matches Psp, 8. Record the flow through the duct blaster’s monometer (cfm) - this is the diagnostic fan flow. In some systems, system fan and duct blaster combinations may not be able to produce enough flow to reach Psp. In this 16 case record the maximum flow (Qmax) and pressure (Pmax) between the supply plenum and the conditioned space. The following equation shall be used to correct measured system flow and pressure (Qmax and Pmax) to operating condition at operating pressure (Psp). Air Handler Flow Qah = Qmax x (Psp/Pmax) ^0.5 c. Cooling Coil Airflow with the Flow Grid Measurement: i. The fan flow measurement shall be performed using the following procedures: 1. With the system fan on at the maximum speed used in the installation (the cooling speed when air conditioning is present), measure the pressure difference (in Pascal) between the supply plenum and the conditioned space (Psp), 2. Place the pressure probe in the Supply Pressure Measurement Location described in the previous section, 3. Adjust the probe to achieve the highest pressure and then firmly attach the probe to ensure that it does not move during the fan flow test, 4. The flow grid shall be attached at a point where all the fan air flows through the flow grid, 5. Re-measure the system operating pressure with the flow grid in place. 6. Measure the airflow through the flow grid (Qgrid) and the test pressure (Ptest), 7. The following equation for air handler flow shall be used to correct flow through the flow grid and pressure (Qgrid and Ptest) to operating condition at operating pressure (Psp). Qah = Qmax x (Psp/Ptest) ^0.5 3. Fan Watt Draw (Using 1 of the 2 following methods), CF6R-MECH-22-HERS a. Fan Watt Draw using a portable watt meter i. The air handler watt draw measurement shall be performed using the following procedures: 1. All registers shall be fully open, and the air filter shall be installed, 2. Turn on the system fan at the maximum speed used in the installation (usually the cooling speed when air conditioning is present,) 3. Measure the fan watt draw (Wfan). b. Fan Watt Draw using the Utility Revenue Meter i. The air handler watt draw measurement shall be performed using the following procedures: 1. All registers shall be fully open, and the air filter shall be installed, 17 2. Turn on the system fan at the maximum speed used in the installation (usually the cooling speed when air conditioning is present) and turn off every circuit breaker except the one exclusively serving the air handler, 3. Record the Kh factor on the revenue meter, count the number of full revolutions of the meter wheel over a period exceeding 90 seconds, 4. Record the number of revolutions (Nrev) and time period (trev, seconds). 5. Compute the air handler watt draw (Wfan) using the following formula: Air Handler Fan Watt Draw Wfan = (Kh x Nrev x 3600) / trev 6. Return all circuit breakers to their original positions. 4. Refrigerant Charge (using 1 of the 2 following methods) a. Standard Procedure, CF6R-MECH-25-HERS i. Under this procedure, required refrigerant charge is calculated using the Superheat Charging Method for Fixed Metering Devices and the Subcooling Charging Method for Thermostatic Expansion Valves (TXV) and Electronic Expansion Valves (EXV). The method also checks airflow across the evaporator coil to determine whether the charge test is valid using the Temperature Split Method, ii. The standard procedure detailed in this section shall be completed when the outdoor temperature is 55°F or higher after the HVAC installer has installed and charged the system in accordance with the manufacturer’s specifications. If the outdoor temperature is between 55°F and 65°F the return dry bulb temperature shall be maintained above 70°F during the test. All HERS rater verifications are required to use this standard procedure, iii. Measurements require four (4) temperature sensors with a response time that produces the accuracy specified within 15 seconds of immersion in a bath at least 40º F different from the surrounding conditions, iv. Measurements require one (1) cotton wick for measuring wet-bulb temperatures, v. Measurements require at two (2) pipe temperature sensors that produce the accuracy within 15 seconds of being applied to a pipe at least 40º F different from the surrounding conditions, 18 vi. There shall be two labeled temperature measurement access holes, one in the supply plenum and one in the return plenum. The temperature measurements shall be taken at the following locations: vii. The standard charge measurement shall be performed using the following procedure: 1. If the condenser air entering temperature is less than 65ºF, establish a return air dry bulb temperature sufficiently high that the return air dry bulb temperature will be not less than 70ºF prior to the measurements at the end of the 15-minute period in step 2, 2. Connect the refrigerant gauges to the service ports, taking normal precautions to not introduce air into the system, 3. Turn the cooling system on and let it run for 15 minutes to stabilize temperatures and pressures before taking any measurements. While the system is stabilizing, proceed with setting up the temperature sensors, 4. Attach one pipe temperature sensor to the suction line near the suction line service valve and attach one pipe temperature sensor to the liquid line near the liquid line service valve, 5. Attach a temperature sensor to measure the condenser entering air dry-bulb temperature. The sensor shall be placed so that it records the average condenser air entering temperature and is shaded from direct sun, 19 6. Be sure that all cabinet panels that affect airflow are in place before making measurements. The temperature sensors shall remain attached to the system until the final charge is determined, 7. Place wet-bulb temperature sensor (cotton wick) in water to ensure it is saturated when needed. Do not get the dry-bulb temperature sensors wet, 8. Insert the dry-bulb temperature sensor in the supply plenum at the "Title 24 – Supply Temperature Access" detailed in the previous diagram in this section, 9. At 12 minutes, insert a dry-bulb temperature sensor and a wet-bulb temperature sensor into the return plenum at the "Title 24 – Return Temperature Access" detailed the previous diagram in this section, 10. At 15 minutes when the return plenum wet-bulb temperature has stabilized, using the temperature sensors already in place, measure and record the return (evaporator entering) air dry-bulb temperature (Treturn, db) and the return (evaporator entering) air wet-bulb temperature (Treturn, wb), 11. Using the dry-bulb temperature sensor already in place, measure and record the supply (evaporator leaving) air drybulb temperature (Tsupply, db), 12. Using the refrigerant gauge or saturation temperature measurement sensor already attached, measure and record the evaporator saturation temperature (Tevaporator, sat) from the low side gauge, 13. Using the refrigerant gauge or saturation temperature measurement sensor already attached, measure and record the condenser saturation temperature (Tcondenser, sat) from the high side gauge, 14. Using the pipe temperature sensor already in place, measure and record the suction line temperature (Tsuction), 15. Using the pipe temperature sensor already in place, measure and record the liquid line temperature (Tliquid), 16. Using the dry-bulb temperature sensor already in place, measure and record the condenser (entering) air dry-bulb temperature (Tcondenser, db). viii. The following steps describe the calculations to determine if the system meets the required refrigerant charge and metering device function using the measurements described in the section above: 1. Fixed Metering Device Calculations; The Superheat Charging Method is used only for systems equipped with fixed metering devices. These include capillary tubes and piston-type metering devices: a. Calculate Actual Superheat as the suction line temperature minus the evaporator saturation temperature. Actual Superheat = Tsuction, – Tevaporator, sat. 20 b. Determine the Target Superheat using the tables below using the return air wet-bulb temperature (Treturn, wb) and condenser air drybulb temperature (Tcondenser, db). 21 22 c. If a dash mark is read from the table above, the target superheat is less than 5°F. Note that a valid refrigerant charge verification test cannot be performed under these conditions. The usual reason for a target superheat determination of less than 5°F is that outdoor conditions are too hot and dry. One of the following is needed so a target superheat value can be obtained from the referenced tables: i. turn on the space heating system and/or open the windows to warm up indoor temperature, OR ii. retest at another time when conditions are different, d. Repeat the measurement procedure as necessary to establish the target superheat. Allow system to stabilize for 15 minutes before the final measurements are taken, e. Calculate the difference between actual superheat and target superheat (Actual Superheat – Target Superheat). In order to allow for inevitable differences in measurements, the Pass/Fail criteria are different for the Installer and the HERS Rater, f. For the Installer, if the difference is between minus 5°F and plus 5°F, then the system passes the required refrigerant charge criterion, g. For the HERS Rater inspecting the system, if the difference is between minus 6°F and plus 6°F, then the system passes the required refrigerant charge criterion, h. For the Installer, if the difference is greater than plus 5°F, then the system does not pass the required refrigerant charge criterion and the Installer shall add refrigerant. Adjust refrigerant charge and check the measurements as many times as necessary to pass the test. After the final adjustment has been made, allow the system to run 15 minutes before completing the final measurement procedure, i. For the Installer, if the difference is between minus 5°F and minus100°F, then the system does not pass the required refrigerant charge criterion, the Installer shall remove refrigerant. Adjust refrigerant charge and check the measurements as many times as necessary to pass the test. After the final adjustment has been made, allow the system to run 15 minutes before completing the final measurement procedure. 2. Variable Metering Device Calculations; The Sub-cooling Charging Method is used only for systems equipped with variable metering devices. These include Thermostatic Expansion Valves (TXV) and Electronic Expansion Valves (EXV). Since variable metering devices are constant superheat valves, measuring the superheat determines whether they are working properly. 23 a. Calculate Actual Sub-cooling as the condenser saturation temperature minus the liquid line temperature, Actual Subcooling = Tcondenser, sat – Tliquid. b. Determine the Target Sub-cooling specified by the manufacturer. c. Calculate the difference between actual sub-cooling and target subcooling, Actual Sub-cooling – Target Sub-cooling d. In order to allow for inevitable differences in measurements, the Pass/Fail criteria are different for the Installer and the HERS Rater, e. For the Installer, If the difference is between minus 3°F and plus 3°F, then the system passes the required refrigerant charge criterion, f. For the HERS Rater inspecting the system, if the difference is between minus 4°F and plus 4°F, then the system passes the required refrigerant charge criterion, g. For the Installer, if the difference is greater than plus 3°F, then the system does not pass the required refrigerant charge criterion and the Installer shall remove refrigerant. Adjust refrigerant charge and check the measurements as many times as necessary to pass the test. After the final adjustment has been made, allow the system to run 15 minutes before completing the final measurement procedure, h. For the Installer, if the difference is between minus 3°F and minus 100°F, then the system does not pass the required refrigerant charge criterion, the Installer shall add refrigerant. Adjust refrigerant charge and check the measurements as many times as necessary to pass the test. After the final adjustment has been made, allow the system to run 15 minutes before completing the final measurement procedure, i. Calculate Actual Superheat as the suction line temperature minus the evaporator saturation temperature, Actual Superheat = Tsuction, – Tevaporator, sat. j. If possible, determine the Superheat Range specified by the manufacturer, k. In order to allow for inevitable differences in measurements, the Pass/Fail criteria are different for the Installer and the HERS Rater, l. For the Installer, if the superheat is within the manufacturer’s superheat range, then the system passes the metering device criterion. If the manufacturer’s specification is not available and the superheat is 24 between 4°F and 25°F, then the system passes the metering device criterion. m. For the HERS Rater inspecting the system, if the superheat is between 3°F and 26°F, then the system passes the metering device criterion. 3. Minimum Airflow a. For the refrigerant test to be valid, a minimum airflow of 300cfm/ton has to be present, b. This value can be measured using any of the Cooling Coil Airflow testing methods described in previous sections. b. Weigh-in procedure, CF6R-MECH-23-HERS i. Under this procedure, the required refrigerant charge is calculated using the WeighIn Charging Method, ii. There shall be two labeled temperature measurement access holes, one in the supply plenum and one in the return plenum, as described in the diagram present in the Standard Measurement procedure section. iii. HVAC installers who must complete system installation verification when the outdoor temperature is below 55°F shall use this alternate procedure in conjunction with installing and charging the system in accordance with the manufacturer’s specifications, iv. HERS Raters shall not use this procedure to verify compliance, v. Split system air conditioners come from the factory already charged with the standard charge indicated on the nameplate, vi. The manufacturer supplies the charge proper for the application based on their standard liquid line length, vii. It is the responsibility of the HVAC installer to ensure that the charge is correct for each air conditioner and to adjust the charge based on liquid line lengths different from the manufacturer's standard. 25 APPENDIX A Test-In Checklist 26 TEST IN CHECKLIST DUCT LAYOUT □ □ □ □ □ □ No sharp bends No collapsed ducts Insulation present, R-Value:_________ No un-ducted chases Sealed joints Support straps every 4 feet of duct or less FURNACE □ Sealed penetrations Refrigerant lines Condensation lines Blower access door □ Sealed seams □ Sealed joints COIL □ Sealed seams □ Sealed penetrations Refrigerant lines Condensation lines □ Sealed joints PLENUMS □ Dampers present □ Sealed joints □ Sealed seams SUPPLY/ RETURN CANS □ Sealed flange □ Sealed to drywall DIAGNOSTIC TESTING □ Duct leakage Ton/ BTUs:______ □ Cooling Coil Airflow CFM:______ CFM25:______ %Leakage:______ COMPLIANCE DOCUMENTATION □ CF1R-ALT-HVAC (Climate Zone 10-15) □ Confirm Home Owner submittal of Residential HVAC Rebate Reservation □ Confirm Home Owner submittal of Residential HVAC Rebate Application 27 APPENDIX B Test-Out Checklist 28 TEST OUT CHECKLIST DUCT LAYOUT □ □ □ □ □ □ No sharp bends No collapsed ducts Insulation present; R-Value:_______ No un-ducted chases Sealed joints Support straps every 4 feet of duct or less □ Sealed penetrations Refrigerant lines Condensation lines Blower access door Sealed seams Sealed joints FURNACE □ □ COIL □ Sealed seams Sealed penetrations Refrigerant lines Condensation lines Sealed joints □ □ □ Dampers present Sealed joints Sealed seams □ □ PLENUMS SUPPLY/ RETURN CANS □ □ Sealed flange Sealed to drywall DIAGNOSTIC TESTING □ Duct Leakage □ Cooling Coil Airflow □ □ Refrigerant Charge Fan Watt Draw Ton/BTUs:______ CFM25:______ %Leakage:______ %Leakage Reduction: Test in% - Test Out% = ________ CFM:______ Airflow increase: Test Out CFM - Test In CFM = _______ COMPLIANCE DOCUMENTATION □ □ □ □ CF6R-MECH-04 (Equipment Installed) CF6R-MECH-20-HERS OR CF6R-MECH-21-HERS (For the Duct Leakage) CF6R-MECH-22-HERS (For Cooling Coil Airflow and Fan Watt Draw) SPLIT SYSTEMS ONLY CF6R-MECH-25 OR 26-HERS (For Refrigerant Charge) SPLIT SYSTEMS ONLY 29 APPENDIX C CEC Compliance Forms 30 (ENFORCEMENT AGENCY CAN CUSTOMIZE WITH LETTERHEAD/SEAL) 2008 Building Energy Efficiency Standards Residential HVAC Alterations Climate Zones 10 to 15 BUSINESS AND PROFESSIONS CODE, SECTION 7110 Willful or deliberate disregard and violation of the building laws, including the California Building Code, and local permit requirements constitutes a cause for disciplinary action from the Contractors State License Board working in conjunction with the local building department. This action may consist of fines up to $5,000 per violation or suspension/revocation of a contractor’s license. WHEN IS A PERMIT REQUIRED? A written construction permit shall be obtained from the enforcement agency prior to the erection, construction, reconstruction, installation, relocation, or alteration of any mechanical system, except as permitted in Appendix Chapter 1, Section 112.2 of the 2007 California Mechanical Code. Projects requiring permits include, but are not limited to: • New HVAC installation • Relocation of an existing HVAC unit • HVAC Changeout • Adding or replacing more than 40ft ducting • Replacement of furnace, coil, FAU, or condenser in unconditioned space 2008 BUILDING ENERGY EFFICIENCY STANDARDS (Title 24, Part 6) REQUIREMENTS INCLUDE: 1. Heating equipment must have a minimum 78% AFUE (Exception: Wall & floor furnaces; room heaters). 2. Central air conditioners & heat pumps less than 65,000 Btu/hr must have a minimum 13 SEER. 3. Newly installed or replaced ducts must have a minimum insulation value of R-4.2. When more than 40 ft of ducting will be installed or replaced, the duct insulation value must be R-6 (CZ 10-13), or R-8 (CZ 14 and 15). 4. A setback type thermostat (24 hr clock with four set points) is required for all alterations. 5. New or replacement ducts must meet the mandatory requirements of Section 150(m): • All joints and openings in the in the HVAC system must be sealed. • Only UL 181, UL 181A, or UL 181B approved tapes or mastic shall be used to seal duct openings. • Connections of metals ducts and the inner core of flex ducts shall be mechanically fastened. Flex ducts must be connected using a metal sleeve/coupling. • Flex ducts that are suspended must be supported every 4ft. max for horizontal runs with no more than 2” of sag between supports and 6 ft. max for vertical runs. WHEN IS HERS VERIFICATION REQUIRED AND WHAT FORMS ARE REQUIRED? HERS verification is required for all HVAC alterations in Climate Zone 10-15. A HERS rater is a special inspector for the building department. The building inspector may also request to be on site to witness testing by the contractor and/or HERS rater. The installer picks one of the four options on the CF-1R-ALT-HVAC Form that describe the work being conducted. Each option lists the forms required to be at the job site for final inspection. • CF-6R Forms shall be completed and submitted by the installing contractor for final inspection.* • CF-4R Forms shall be completed, registered with an approved HERS Provider (cannot be completed by hand), and submitted by the HERS Rater for final inspection effective January 1, 2010. DESCRIPTION OF HERS TESTS BELOW (Full descriptions found in Residential Appendix RA3 and Residential Manual) Duct sealing – The installer is to insure leakage of the HVAC system is less than 6% for new air conditioning system (new equipment and all new ducts) or 15%, 60% reduction, seal all accessible leaks, etc. for alterations to existing HVAC systems. When the contractor uses the option to seal all accessible leaks, all easily movable objects must be moved to seal existing ducting. New ducting installed by the contractor is not allowed to have any leaks even if it is no longer accessible. In example 3 of the CF-1R “all new ducts” means that all the ducting was changed. The original boots, plenums, etc. do not need to be changed. Cooling Coil Airflow (CCA) – There are two different minimum air flow requirements that must be met. These are 300 CFM and 350 CFM. The minimum 300 CFM per ton of cooling is required in order to conduct a refrigerant charge test. For new HVAC systems (new equipment and new ducts) the HVAC system must move a minimum 350 CFM of air for each ton of cooling. Refrigerant Charge (RC) – The installer is required to verify the charge is correct. If the outside temperature is below 55 degrees then the weigh in method must be used by the installer. When the weigh in method is used the HERS rater must retest when the temperature is 55 and above. A charge indicator display (CID) can be used in place of conducting an RC, manufacturers are currently developing this device. Temperature Measurement Access Holes (TMAH) – Installer must drill and mark holes to measure temperature split. Hole for the placement of a Static Pressure Probe (HSPP) or Permanently installed Static Pressure Probe (PSPP) – Either the installer must drill and mark holes to measure static pressure or a permanently installed pressure probe must be installed and marked. Saturation Temperature Measurement Sensors (STMS) – Permanently installed type K thermocouple are installed on the indoor and outdoor coil so that the HERS rater can verify charge without attaching gauges. Instructions are found in Ch 4 of the Res. Manual. Fan Watt Draw (FWD) – Installer verifies that the furnace fan watt draw is less than 0.58 Watts/CFM. NOTE: The CF-6R-MECH-04 is required for all HVAC alterations. * For Final inspection ALL compliance forms (CF-1Rs, CF-6Rs, and CF-4Rs) shall be registered with an approved HERS Provider for building permit applications submitted on or after October 1, 2010. Simplified Prescriptive Certificate of Compliance: 2008 Residential HVAC Alterations CF-1R-ALT-HVAC Climate Zones 10 to 15 Site Address: Enforcement Agency: Date: Permit #: Conditioned Floor Equipment Type1 List Minimum Efficiency2 Duct insulation requirement Area Thermostat Packaged Unit Over 40 ft of ducts added or Setback Furnace AFUE____ COP______ replaced in unconditioned space Served by system (If not already Indoor Coil SEER_____ HSPF ____ present, must be R 6 (CZ 10-13) ________ sf Condensing Unit EER _____ Resistance installed) R 8 (CZ 14-15) Other ________ 1. Equipment Type: Choose the equipment being installed; if more than one system, use another CF-1R-ALT-HVAC for each system. 2. Minimum Equipment Efficiencies: 13 SEER, 78% AFUE, 7.7HSPF for typical residential systems. HERS VERIFICATION SUMMARY Listed below are four HVAC alteration Options. The installer decides what work is being done and picks one of the appropriate Options. Each Option lists the HERS measures that must be conducted. A copy of the forms shall be left on site for final inspection and a copy given to the homeowner. At final, the inspector verifies that the work listed on this form was in fact the work completed by the installer. The inspector also verifies that each appropriate CF-6R and registered CF-4R forms (no hand filled CF-4Rs allowed) are filled out and signed. Beginning October 1, 2010, a registered copy of the CF-1R and CF-6R shall also be on site for final inspection. 1. HVAC Changeout • All HVAC Equipment replaced Required Forms: CF-6R forms: MECH-04, MECH-21-HERS and (for split systems) MECH-25-HERS CF-4R forms: MECH-21 and (for split systems) MECH-25 • Condenser Coil and /or CF-6R forms: MECH-21-HERS and (for split systems) MECH-25-HERS • Indoor Coil and /or CF-4R forms: MECH-21 and (for split systems) MECH-25 • Furnace For Split Systems: Duct leakage < 15 percent; RC, CCA ≥ 300 CFM/ton(Minimum Air Flow Requirement), TMAH For Packaged Units: Duct leakage < 15 percent Exempted from duct leakage testing if: 1. Duct system was documented to have been previously sealed and confirmed through HERS verification, or 2. Duct systems with less than 40 linear feet in unconditioned space, or 3. Existing duct systems are constructed, insulated or sealed with asbestos 2. New HVAC System • Cut in or Changeout with new ducts: (all new ducting and all new equipment) Required Forms: CF-6R forms: MECH-04, MECH-20-HERS,and (for split systems) MECH-22-HERS, and MECH-25-HERS CF-4R forms: MECH-20, and (for split systems) MECH-22, and MECH-25 For Split Systems: Duct leakage < 6 percent; RC, CCA ≥ 350 CFM/ton, FWD, TMAH, STMS, and either HSPP or PSPP. For Packaged Units: Duct leakage < 6 percent 3. New Ducts with Replacement Required Forms: CF-6R forms: MECH-04, MECH-20-HERS,and (for split systems) MECH-25-HERS • Includes replacing or installing all new ducting and/or outdoor condensing unit and/or indoor coil and/or furnace. Not all equipment changed. CF-4R forms: MECH-20 and (for split systems) MECH-25 For Split Systems: Duct leakage < 6 percent, RC, CCA ≥ 300 CFM/ton, TMAH For Packaged Units: Duct leakage < 6 percent 4. New Ducting over 40 feet Required Forms: • Includes adding or replacing more than 40 CF-6R forms: MECH-04, MECH-21-HERS linear feet of duct in unconditioned space. CF-4R forms: MECH-21 For split system or packaged units: Duct leakage < 15 percent EXCEPTION: Existing duct systems constructed, insulated or sealed with asbestos. Contractor (Documentation Author's /Responsible Designer's Declaration Statement) • I certify that this Certificate of Compliance documentation is accurate and complete. • I am eligible under Division 3 of the California Business and Professions Code to accept responsibility for the design identified on this Certificate of Compliance. • • I certify that the energy features and performance specifications for the design identified on this Certificate of Compliance conform to the requirements of Title 24, Parts 1 and 6 of the California Code of Regulations. The design features identified on this Certificate of Compliance are consistent with the information documented on other applicable compliance forms, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with the permit application. Name: Signature: Company: Date: Address: License: City/State/Zip: Phone: 2008 Residential Compliance Forms July 2010 Mandatory Measures Summary MF-1R Residential Site Address: (Page 1 of 3) Enforcement Agency: Date: NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF-1R, CF-1R-ADD, or CF-1R-ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated into the permit documents and the applicable features shall be considered by all parties as minimum component performance specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF-1R Form with plans. DESCRIPTION Building Envelope Measures: §116(a)1: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage. §116(a)4: Fenestration products (except field-fabricated windows) have a label listing the certified U-Factor, certified Solar Heat Gain Coefficient (SHGC), and infiltration that meets the requirements of §10-111(a). §117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed. §118(a): Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on CF-6R Form. §118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(i) when the installation of a Cool Roof is specified on the CF-1R Form. *§150(a): Minimum R-19 insulation in wood-frame ceiling or equivalent U-factor. §150(b): Loose fill insulation shall conform with manufacturer’s installed design labeled R-Value. *§150(c): Minimum R-13 insulation in wood-frame wall or equivalent U-factor. *§150(d): Minimum R-13 insulation in raised wood-frame floor or equivalent U-factor. §150(f): Air retarding wrap is tested, labeled, and installed according to ASTM E1677-95(2000) when specified on the CF-1R Form. §150(g): Mandatory Vapor barrier installed in Climate Zones 14 or 16. §150(l): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance rate is no greater than 2.0 perm/inch and shall be protected from physical damage and UV light deterioration. Fireplaces, Decorative Gas Appliances and Gas Log Measures: §150(e)1A: Masonry or factory-built fireplaces have a closable metal or glass door covering the entire opening of the firebox. §150(e)1B: Masonry or factory-built fireplaces have a combustion outside air intake, which is at least six square inches in area and is equipped with a with a readily accessible, operable, and tight-fitting damper and or a combustion-air control device. §150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of the building, are prohibited. Space Conditioning, Water Heating and Plumbing System Measures: §110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy Commission. §113(c)5: Water heating recirculation loops serving multiple dwelling units and High-Rise residential occupancies meet the air release valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5. §115: Continuously burning pilot lights are prohibited for natural gas: fan-type central furnaces, household cooking appliances (appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and spa heaters. §150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA. §150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c). §150(j)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped with insulation having an installed thermal resistance of R-12 or greater. §150(j)1B: Unfired storage tanks, such as storage tanks or backup tanks for solar water-heating system, or other indirect hot water tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the tank. §150(j)2: First 5 feet of hot and cold water pipes closest to water heater tank, non-recirculating systems, and entire length of recirculating sections of hot water pipes are insulated per Standards Table 150-B. §150(j)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot water tank shall be insulated to Table 150-B and Equation 150-A. §150(j)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table 123-A. §150(j)3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. §150(j)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in conditioned space. 2008 Residential Compliance Forms August 2009 Mandatory Measures Summary MF-1R Residential Site Address: (Page 2 of 3) Enforcement Agency: Date: §150(j)4: Solar water-heating systems and/or collectors are certified by the Solar Rating and Certification Corporation. Ducts and Fans Measures: §150(m)1: All air-distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections 601, 602, 603, 604, 605 and Standard 6-5; supply-air and return-air ducts and plenums are insulated to a minimum installed level of R-4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct-closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used §150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. §150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and draw bands. §150(m)7: Exhaust fan systems have back draft or automatic dampers. §150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers. §150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material. §150(m)10: Flexible ducts cannot have porous inner cores. §150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in Section 4 of that Standard. Pool and Spa Heating Systems and Equipment Measures: §114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating or a pilot light. §114(b)1: Any pool or spa heating equipment shall be installed with at least 36” of pipe between filter and heater, or dedicated suction and return lines, or built-up connections for future solar heating §114(b)2: Outdoor pools or spas that have a heat pump or gas heater shall have a cover. §114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or programmed to run only during off-peak electric demand periods. §150(p): Residential pool systems or equipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150(p). Residential Lighting Measures: §150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies contained in Table 150-C and is not a low efficacy luminaire as specified by §150(k)2. §150(k)3: The wattage of permanently installed luminaires shall be determined as specified by §130(d). §150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than 20 kHz. §150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line-voltage socket or line-voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a medium screw-base socket. §150(k)6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150(k). §150(k)7: All switching devices and controls shall meet the requirements of §150(k)7. §150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy. EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant sensor, dimmer, energy management system (EMCS), or a multi-scene programmable control system; and all permanently installed luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a manual-on occupant sensor. §150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated cabinet. §150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms shall be high efficacy. 2008 Residential Compliance Forms August 2009 Mandatory Measures Summary MF-1R Residential Site Address: (Page 3 of 3) Enforcement Agency: Date: EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual-on occupant sensor certified to comply with the applicable requirements of §119. EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a manual-on occupant sensor. §150(k)11: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual-on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site is not required to comply with §150(k)11. §150(k)12: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between the luminaire housing and ceiling. §150(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor, and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor luminaires used to comply with Exception1 to §150(k)13 may be controlled by a temporary override switch which bypasses the motion sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not be high efficacy luminaires. §150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw-base socket, and consume no more than five watts of power as determined according to §130(d). §150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable requirements of Sections 130, 131, 134, and 146 §150(k)16: Permanently installed lighting in the enclosed, non-dwelling spaces of low-rise residential buildings with four or more dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by an occupant sensor(s) certified to comply with the applicable requirements of §119. 2008 Residential Compliance Forms August 2009 INSTALLATION CERTIFICATE Space Conditioning Systems, Ducts and Fans CF-6R-MECH-04 (Page 1 of 2) Site Address: Enforcement Agency: Permit Number: Space Conditioning Systems Heating Equipment Equip Type (packageheat pump) CEC Certified Mfr. Name and Model Number ARI Reference Number 2 # of Identical Systems Efficiency (AFUE, etc.)1, 3 (≥CF-1R value)4 Duct Location (attic, crawlspace, etc.) Duct R-value Heating Load (Btu/hr) Heating Capacity (Btu/hr) Duct Location (attic, crawlspace, etc.) Duct R-value Cooling Load (Btu/hr) Cooling Capacity (Btu/hr) Cooling Equipment Equip Type (package heat pump) CEC Certified Mfr. Name and Model Number ARI Reference Number 2 # of Identical Systems Efficiency (SEER and EER) 1, 3 (≥CF-1R value) 4 1. If project is new construction, see Footnotes to Standards Table 151-B and Table 151-C for duct ceiling alternative compliance. 2. ARI Reference Number can be found by entering the equipment model number at http://www.aridirectory.org/ari/ac.php# 3. Listed efficiency on this page must be greater than or equal ( ≥ ) to the value shown on the CF-1R form. 4. When CF-1R is reference it is also applicable to the CF-1R, CF-1R-AA or CF-1R-ALT ALL BOXES MUST BE CHECKED TO BE A VALID FORM §110-§113: HVAC equipment is certified by the California Energy Commission. §150(h): Heating and/or cooling loads calculated in accordance with ASHRAE, SMACNA, or ACCA. §150(i): Setback Thermostat on all applicable heating and/or cooling systems meet the requirements of §112(c). §150(j)2: Pipe insulation for cooling system refrigerant suction, chilled water and brine lines meets minimum requirements of Table 150-B and includes a vapor retardant or is enclosed entirely in conditioned space. 2008 Residential Compliance Forms August 2009 INSTALLATION CERTIFICATE Space Conditioning Systems, Ducts and Fans Site Address: CF-6R-MECH-04 (Page 2 of 2) Enforcement Agency: Permit Number: Ducts and Fans §150(m): Duct and Fans 1. All air-distribution system ducts and plenums installed, sealed and insulated to meet the requirements of CMC Sections 601, 602, 603, 604, 605 and Standard 6-5; supply-air and return-air ducts and plenums are insulated to a minimum installed level of R-4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct-closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used; and 1. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. 2D. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and draw bands. 7. Exhaust fan systems have back draft or automatic dampers. 8. Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers. 9. Protection of Insulation. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material. 10. Flexible ducts cannot have porous inner cores. DECLARATION STATEMENT • I certify under penalty of perjury, under the laws of the State of California, the information provided on this form is true and correct. • I am eligible under Division 3 of the Business and Professions Code to accept responsibility for construction, or an authorized representative of the person responsible for construction (responsible person). • I certify that the installed features, materials, components, or manufactured devices identified on this certificate (the installation) conforms to all applicable codes and regulations, and the installation is consistent with the plans and specifications approved by the enforcement agency. • I reviewed a copy of the Certificate of Compliance (CF-1R) form approved by the enforcement agency that identifies the specific requirements for the installation. I certify that the requirements detailed on the CF-1R that apply to the installation have been met. I will ensure that a completed, signed copy of this Installation Certificate shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Installation Certificate is required to be included with the documentation the builder provides to the building owner at occupancy. • Company Name: (Installing Subcontractor or General Contractor or Builder/Owner) Responsible Person's Name: CSLB License: 2008 Residential Compliance Forms Responsible Person's Signature: Date Signed: Position With Company (Title): August 2009 INSTALLATION CERTIFICATE Duct Leakage Test – Completely New or Replacement Duct System Site Address: Enforcement Agency: CF-6R-MECH-20-HERS (Page 1 of 2) Permit Number: Enter the Duct System Name or Identification/Tag: Enter the Duct System Location or Area Served: Note: Submit one Installation Certificate for each duct system that must demonstrate compliance in the dwelling. This certificate is required for compliance for completely new duct systems installed in new dwelling construction, and also for completely new or replacement duct systems in existing dwellings. For existing dwellings, a completely new or replacement duct system can also include existing parts of the original duct system (e.g., register boots, air handler, coil, plenums, etc.) if those parts are accessible and they can be sealed. Duct Leakage Diagnostic Test – completely new or replacement duct system Enter a value for the Allowed Leakage (CFM) for the duct system leakage verification. The value entered must be the Verified Low Leakage Ducts in Conditioned Space criteria or one of the three calculated leakage rates described below. Verified Low Leakage Ducts in Conditioned Space (VLLDCS) Compliance Credit. If compliance credit Allowed for verified low leakage ducts in conditioned space is shown in the special features section of the CF-1R, the Leakage leakage to outside test method must be used to verify duct leakage (refer to RA3.1.4.3.4), and 25 CFM must be (CFM) entered for Allowed Leakage. Allowed leakage calculation – (select one calculation method from this section). Use 6% (leakage factor = 0.06) for calculations if tested at “final” or 4% (leakage factor = 0.04) if tested at “rough.” When utilizing Low Leakage Air Handler (LLAH) credit, the allowed duct leakage may be specified by the CF-1R to be less than 6%, in which case the user-specified leakage rate must be used in the calculations below. For example, if the user-specified leakage (specified as a percentage of fan airflow) is reported on the CF-1R as 3%, then use a leakage factor of 0.03 in the calculations below. Cooling system method: Nominal capacity of condenser in Tons x 400 x leakage factor = (CFM) Heating system method: Output Capacity in Thousands of Btu/hr x leakage factor = 21.7 x (CFM) Measured airflow method (RA3.3): Enter measured fan flow in CFM here (CFM) x leakage factor = Enter value for Actual leakage (CFM) in the right column, from measurement using applicable duct leakage pressurization test procedure from Reference Residential Appendix RA3.1(CFM @ 25 Pa). Actual Leakage (CFM) List Actual Leakage from duct leakage test (CFM) Pass if Actual Leakage is less than Allowed Leakage Pass For complete replacement of duct systems only, if the 6 percent leakage rate criteria cannot be met, a smoke test should be performed to verify that the excess leakage is coming only from a pre-existing furnace cabinet (air handler cabinet), and not from other accessible portions of the duct system. A HERS rater must verify the installation (No sampling allowed). List Actual Leakage from smoke test(CFM) Pass if all accessible leaks (except for existing air handler) are sealed using smoke Pass Fail Fail Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms August 2009 INSTALLATION CERTIFICATE Duct Leakage Test – Completely New or Replacement Duct System Site Address: Enforcement Agency: CF-6R-MECH-20-HERS (Page 2 of 2) Permit Number: Compliance Method This dwelling was: (select one of the following two choices): Tested at Final Tested at Rough-in (requires installer to complete the visual inspection at final construction stage described below) Visual Inspection at Final Construction Stage (if applicable) After installing the interior finishing wall and verifying that the above rough-in tests was completed, the following procedure must be performed: For all supply and return registers, verify that the spaces between the register boot and the interior finishing wall are properly sealed. If the house rough-in duct leakage test was conducted without an air handler installed, inspect the connection points between the air handler and the supply and return plenums to verify that the connection points are properly sealed. Inspect all joints to ensure that no cloth backed rubber adhesive duct tape is used. Outside air (OA) ducts for Central Fan Integrated (CFI) ventilation systems, shall not be sealed/taped off during duct leakage testing. CFI OA ducts that utilize controlled motorized dampers, that open only when OA ventilation is required to meet ASHRAE Standard 62.2, and close when OA ventilation is not required, may be configured to the closed position during duct leakage testing. All supply and return register boots must be sealed to the drywall New duct installations cannot utilize building cavities as plenums or platform returns in lieu of ducts. Mastic and draw bands must be used in combination with Cloth backed, rubber adhesive duct tape to seal leaks at duct connections. DECLARATION STATEMENT • I certify under penalty of perjury, under the laws of the State of California, the information provided on this form is true and correct. • I am eligible under Division 3 of the Business and Professions Code to accept responsibility for construction, or an authorized representative of the person responsible for construction (responsible person). • I certify that the installed features, materials, components, or manufactured devices identified on this certificate (the installation) conforms to all applicable codes and regulations, and the installation is consistent with the plans and specifications approved by the enforcement agency. • I understand that a HERS rater will check the installation to verify compliance, and that that if such checking identifies defects, I am required to take corrective action at my expense. I understand that Energy Commission and HERS provider representatives will also perform quality assurance checking of installations, including those approved as part of a sample group but not checked by a HERS rater, and if those installations fail to meet the requirements of such quality assurance checking, the required corrective action and additional checking/testing of other installations in that HERS sample group will be performed at my expense. I reviewed a copy of the Certificate of Compliance (CF-1R) form approved by the enforcement agency that identifies the specific requirements for the installation. I certify that the requirements detailed on the CF-1R that apply to the installation have been met. I will ensure that a completed, signed copy of this Installation Certificate shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Installation Certificate is required to be included with the documentation the builder provides to the building owner at occupancy. I will ensure that all Installation Certificates will come from a HERS provider data registry for multiple orientation alternatives, and beginning October 1, 2010, for all low-rise residential buildings. • • Company Name: (Installing Subcontractor or General Contractor or Builder/Owner) Responsible Person's Name: CSLB License: Responsible Person's Signature: Date Signed: Is this installation monitored by a Third Party Quality Control Program (TPQCP)? Yes No Position With Company (Title): Name of TPQCP (if applicable): Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms August 2009 INSTALLATION CERTIFICATE Duct Leakage Test – Existing Duct System CF-6R-MECH-21-HERS (Page 1 of 2) Site Address: Enforcement Agency: Permit Number: Enter the Duct System Name or Identification/Tag: Enter the Duct System Location or Area Served: Note: Submit one Installation Certificate for each duct system that must demonstrate compliance in the dwelling. This installation certificate is required for compliance for alterations and additions in existing dwellings to space conditioning systems and duct systems. Note: For existing dwellings, a completely new or replacement duct system can also include existing parts of the original duct system (e.g., register boots, air handler, coil, plenums, etc.) if those parts are accessible and they can be sealed. For a completely new or replacement duct system installed in an existing dwelling, use the Installation Certificate titled "Duct Leakage Test – Completely New or Replacement Duct System." Duct Leakage Diagnostic Test – Existing Duct System Select one compliance method from the following four choices. Option 1. Measured leakage less than 15% of Fan Airflow. Option 2. Measured leakage to outside less than 10% of Fan Airflow. Option 3. Reduce leakage by 60% or more, and conduct smoke test to seal all accessible leaks. Option 4. Fix all accessible leaks using smoke test, and HERS rater must verify. Note: (One of Options 1, 2 or 3 must be attempted before utilizing Option 4.) Determine nominal Fan Airflow using one of the following three calculation methods. Cooling system method: Size of condenser in Tons x 400 = CFM Heating system method: 21.7 x Heating Output Capacity (kBtuh) = Measured system airflow using RA3.3 airflow test procedures: 1 Option 1 used then: Allowed leakage = Fan Airflow Actual leakage = 2 Option 2 used then: Allowed leakage = Fan Airflow Actual leakage to outside = Initial leakage CFM CFM Pass if Actual leakage is less than Allowed leakage Pass Fail x 0.10 = CFM CFM Pass if Actual leakage to outside is less than Allowed leakage Pass Fail CFM Final leakage after sealing all accessible leaks using smoke test = (Leakage reduction 4 CFM x 0.15 = Option 3 used then: Initial leakage prior to start of work= 3 CFM - Final leakage / Initial leakage CFM = Leakage reduction CFM ) x 100% = % Reduction Pass if % Reduction > 60% Option 4 used then: All accessible leaks repaired using smoke test. HERS rater must verify (No sampling). Pass Fail Pass if all accessible leaks have been sealed using Smoke Test Pass Fail Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms March 2010 INSTALLATION CERTIFICATE Duct Leakage Test – Existing Duct System Site Address: CF-6R-MECH-21-HERS (Page 2 of 2) Enforcement Agency: Permit Number: Outside air (OA) ducts for Central Fan Integrated (CFI) ventilation systems, shall not be sealed/taped off during duct leakage testing. CFI OA ducts that utilize controlled motorized dampers, that open only when OA ventilation is required to meet ASHRAE Standard 62.2, and close when OA ventilation is not required, may be configured to the closed position during duct leakage testing. All supply and return register boots must be sealed to the drywall if smoke test is utilized for compliance – applies to duct leakage compliance option 3 (leakage reduction by 60%) and option 4 (fix all accessible leaks) described above. New duct installations cannot utilize building cavities as plenums or platform returns in lieu of ducts. Mastic and draw bands must be used in combination with cloth backed rubber adhesive duct tape to seal leaks at all new duct connections. DECLARATION STATEMENT • I certify under penalty of perjury, under the laws of the State of California, the information provided on this form is true and correct. • I am eligible under Division 3 of the Business and Professions Code to accept responsibility for construction, or an authorized representative of the person responsible for construction (responsible person). • I certify that the installed features, materials, components, or manufactured devices identified on this certificate (the installation) conforms to all applicable codes and regulations, and the installation is consistent with the plans and specifications approved by the enforcement agency. • I understand that a HERS rater will check the installation to verify compliance, and that that if such checking identifies defects, I am required to take corrective action at my expense. I understand that Energy Commission and HERS provider representatives will also perform quality assurance checking of installations, including those approved as part of a sample group but not checked by a HERS rater, and if those installations fail to meet the requirements of such quality assurance checking, the required corrective action and additional checking/testing of other installations in that HERS sample group will be performed at my expense. • I reviewed a copy of the Certificate of Compliance (CF-1R) form approved by the enforcement agency that identifies the specific requirements for the installation. I certify that the requirements detailed on the CF-1R that apply to the installation have been met. • I will ensure that a completed, signed copy of this Installation Certificate shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Installation Certificate is required to be included with the documentation the builder provides to the building owner at occupancy. I will ensure that all Installation Certificates will come from a HERS provider data registry for multiple orientation alternatives, and beginning October 1, 2010, for all low-rise residential buildings. Company Name: (Installing Subcontractor or General Contractor or Builder/Owner) Responsible Person's Name: CSLB License: Responsible Person's Signature: Date Signed: Is this installation monitored by a Third Party Quality Control Program (TPQCP)? Yes No Position With Company (Title): Name of TPQCP (if applicable): Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms March 2010 INSTALLATION CERTIFICATE HSPP/PSPP Installation; Cooling Coil Airflow & Fan Watt Draw Test Site Address: Enforcement Agency: CF-6R-MECH-22-HERS (Page 1 of 2) Permit Number: As many as 4 systems in the dwelling can be documented for compliance using this form. Attach an additional form(s) for any additional systems in the dwelling as applicable. Hole for the placement of a Static Pressure Probe (HSPP), and Permanently installed Static Pressure Probe (PSPP) in the supply plenum When the Certificate of Compliance (CF1R )indicates Cooling Coil Airflow or Fan Watt Draw verification are required, HSPP or PSPP are required to be installed in each air handler in the dwelling. Procedures for installing HSPP and PSPP are described in Reference Residential Appendix RA3.3. This measure requires verification by a HERS rater. Select one method from the two choices below for compliance with the HSPP/PSPP requirement for this dwelling. 1/4 inch (6 mm) hole labeled and located downstream of the evaporator coil in the supply HSPP plenum as shown in the figure in Section RA3.3.1.1. 1/4 inch (6 mm) hole equipped with a permanently installed pressure probe, labeled and located downstream of the evaporator coil in the supply plenum as shown in the figure in PSPP Section RA3.3.1.1. System Name or Identification/Tag System Location or Area Served Confirm that a HSPP or PSPP has been installed on the air handler per the requirements of RA3.3.1.1. Enter Pass or Fail Cooling Coil Airflow Verification When the Certificate of Compliance indicates Cooling Coil Airflow verification is required, the procedures for measuring the cooling coil airflow must be performed as specified in Reference Residential Appendix RA3.3. Results of the cooling coil airflow diagnostic test must be entered in the table below. This measure requires verification by a HERS rater. Select one method from the three choices below for compliance with the Cooling Coil Airflow test requirement for this dwelling. Diagnostic Fan Flow Using Plenum Pressure Matching according to the procedures in RA3.3.3.1.1 Diagnostic Fan Flow Using Flow Grid Measurement according to the procedures in RA3.3.3.1.2 Diagnostic Fan Flow Using Flow Capture Hood according to the procedures in RA3.3.3.1.3 System Name or Identification/Tag System Location or Area Served Nominal Cooling Capacity (ton) of the outdoor unit. Enter the minimum airflow requirement from the CF-1R (CFM/ton). Calculate the target minimum airflow for the test by multiplying the CFM/ton criteria specified on the CF-1R by the nominal cooling capacity of the outdoor unit (ton). Target (CFM) Enter the diagnostically tested airflow (CFM). Tested (CFM) The system complies if Tested (CFM) is equal or greater than Target (CFM). Enter Pass or Fail Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms March 2010 INSTALLATION CERTIFICATE HSPP/PSPP Installation; Cooling Coil Airflow & Fan Watt Draw Test Site Address: Enforcement Agency: CF-6R-MECH-22-HERS (Page 2 of 2) Permit Number: Fan Watt Draw Verification When the Certificate of Compliance indicates Fan Watt Draw verification is required, the procedures for measuring the Fan Watt Draw must be performed as specified in Reference Residential Appendix RA3.3. Results of the Fan Watt Draw diagnostic test must be entered in the table below. This measure requires verification by a HERS rater. Note: Fan watt draw must be measured simultaneously with cooling coil airflow. The fan watt draw measurement and cooling coil airflow measurement must simultaneously meet or exceed their target criteria specified by the CF-1R for the dwelling. Select one method from the two choices below for compliance with the Fan Watt Draw test requirement for this dwelling. Portable Watt Meter Measurement according to the procedures in RA3.3.3.3.1 Utility Revenue Meter Measurement according to the procedures in RA3.3.3.3.2 System Name or Identification/Tag System Location or Area Served Enter the air handler Tested (CFM) from the cooling coil airflow test table above. Enter the fan watt draw requirement from the CF-1R (Watt/CFM). Calculate the target maximum Watt draw for the test by multiplying the Watt/CFM criteria specified on the CF-1R by the air handler Tested (CFM). Target (Watt) Enter the diagnostically tested Watt draw (Watt). Tested (Watt) The system complies if Tested (Watt) is less than or equal to Target (Watt) Enter pass or Fail DECLARATION STATEMENT • I certify under penalty of perjury, under the laws of the State of California, the information provided on this form is true and correct. • I am eligible under Division 3 of the Business and Professions Code to accept responsibility for construction, or an authorized representative of the person responsible for construction (responsible person). • I certify that the installed features, materials, components, or manufactured devices identified on this certificate (the installation) conforms to all applicable codes and regulations, and the installation is consistent with the plans and specifications approved by the enforcement agency. • I understand that a HERS rater will check the installation to verify compliance, and that that if such checking identifies defects, I am required to take corrective action at my expense. I understand that Energy Commission and HERS provider representatives will also perform quality assurance checking of installations, including those approved as part of a sample group but not checked by a HERS rater, and if those installations fail to meet the requirements of such quality assurance checking, the required corrective action and additional checking/testing of other installations in that HERS sample group will be performed at my expense. • I reviewed a copy of the Certificate of Compliance (CF-1R) form approved by the enforcement agency that identifies the specific requirements for the installation. I certify that the requirements detailed on the CF-1R that apply to the installation have been met. • I will ensure that a completed, signed copy of this Installation Certificate shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Installation Certificate is required to be included with the documentation the builder provides to the building owner at occupancy. I will ensure that all Installation Certificates will come from a HERS provider data registry for multiple orientation alternatives, and beginning October 1, 2010, for all low-rise residential buildings. Company Name: (Installing Subcontractor or General Contractor or Builder/Owner) Responsible Person's Name: CSLB License: Responsible Person's Signature: Date Signed: Is this installation monitored by a Third Party Quality Control Program (TPQCP)? Yes No Position With Company (Title): Name of TPQCP (if applicable): Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms March 2010 INSTALLATION CERTIFICATE Refrigerant Charge Verification - Standard Measurement Procedure Site Address: Enforcement Agency: CF-6R-MECH-25-HERS (Page 1 of 5) Permit Number: Note: If installation of a Charge Indicator Display (CID) is utilized as an alternative to refrigerant charge verification for compliance, a MECH-24 Certificate (instead of this MECH-25 Certificate) should be used to demonstrate compliance with the refrigerant charge verification requirement. TMAH and STMS are not required for compliance, when a CID is utilized for compliance. As many as 4 systems in the dwelling can be documented for compliance using this form. Attach an additional form(s) for any additional systems in the dwelling as applicable. Temperature Measurement Access Holes (TMAH) and Saturation Temperature Measurement Sensors (STMS) Procedures for installing TMAH are specified in Reference Residential Appendix RA3.2. If refrigerant charge verification is required for compliance, TMAH are also required for compliance. STMS are only required for completely new or replacement space-conditioning systems that utilize prescriptive compliance method. TMAH - Access Holes in Supply and Return Plenums of Air Handler System Name or Identification/Tag System Location or Area Served 1 Yes No 2 Yes No Yes to 1 and 2 is a pass. 5/16 inch (8 mm) access hole upstream of evaporative coil in the return plenum and labeled according to Figure in Section RA3.2.2.2.2. 5/16 inch (8 mm) access hole downstream of evaporative coil in the supply plenum and labeled according to Figure in Section RA3.2.2.2.2. Enter Pass or Fail 9 Pass 9 Fail STMS - Sensor on the Evaporator Coil System Name or Identification/Tag The sensor is factory installed, or field installed according to manufacturer's specifications, or is installed by methods/specifications approved by the Executive Director. The sensor wire is terminated with a standard mini plug suitable for connection to a 4 Yes No digital thermometer. The sensor mini plug is accessible to the installing technician and the HERS rater without changing the airflow through the condenser coil 5 Yes No The sensor measures the saturation temperature of the coil within 1.3 degrees F Yes to 3, 4, and 5 is a pass. Enter 9 N/A 9 Pass 9 Fail N/A if STMS are not applicable. Otherwise enter Pass or Fail 3 Yes No STMS - Sensor on the Condenser Coil System Name or Identification/Tag The sensor is factory installed, or field installed according to manufacturer's specifications, or is installed by methods/specifications approved by the Executive Director. The sensor wire is terminated with a standard mini plug suitable for connection to a 7 Yes No digital thermometer. The sensor mini plug is accessible to the installing technician and the HERS rater without changing the airflow through the condenser coil 8 Yes No The sensor measures the saturation temperature of the coil within 1.3 degrees F Yes to 6, 7, and 8 is a pass. Enter 9 N/A 9 Pass 9 Fail N/A if STMS are not applicable. Otherwise enter Pass or Fail 6 Yes No Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms August 2009 INSTALLATION CERTIFICATE Refrigerant Charge Verification - Standard Measurement Procedure Site Address: Enforcement Agency: CF-6R-MECH-25-HERS (Page 2 of 5) Permit Number: Standard Charge Measurement Procedure (for use if outdoor air dry-bulb is above 55 oF) Procedures for determining Refrigerant Charge using the Standard Charge Measurement Procedure are available in Reference Residential Appendix RA3.2. As many as 4 systems in the dwelling can be documented for compliance using this form. Attach an additional form(s) for any additional systems in the dwelling as applicable. • The system should be installed and charged in accordance with the manufacturer’s specifications before starting this procedure. • The system must meet minimum airflow requirements as prerequisite for a valid refrigerant charge test. • If outdoor air dry-bulb is 55 °F or below, the installer must use the RA3.2.3 Alternate Charge Measurement Procedure (Weigh-In Charging Method). If the Weigh-In Method is used, the dwelling cannot be included in a sample group for HERS verification compliance. Space Conditioning Systems System Name or Identification/Tag System Location or Area Served Outdoor Unit Serial # Outdoor Unit Make Outdoor Unit Model Nominal Cooling Capacity (ton) Date of Verification Calibration of Diagnostic Instruments Date of Refrigerant Gauge Calibration (must be re-calibrated monthly) Date of Thermocouple Calibration (must be re-calibrated monthly) Measured Temperatures (°F) System Name or Identification/Tag Supply (evaporator leaving) air dry-bulb temperature (Tsupply, db) Return (evaporator entering) air dry-bulb temperature (Treturn, db) Return (evaporator entering) air wet-bulb temperature (Treturn, wb) Evaporator saturation temperature (Tevaporator, sat) Condensor saturation temperature (Tcondensor, sat) Suction line temperature (Tsuction) Liquid Line Temperature (Tliquid) Condenser (entering) air dry-bulb temperature (Tcondenser, db) Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms July 2010 INSTALLATION CERTIFICATE Refrigerant Charge Verification - Standard Measurement Procedure Site Address: Enforcement Agency: CF-6R-MECH-25-HERS (Page 3 of 5) Permit Number: Minimum Airflow Requirement Temperature Split Method Calculations for determining Minimum Airflow Requirement for Refrigerant Charge Verification. The temperature split method is specified in Reference Residential Appendix RA3.2. System Name or Identification/Tag Calculate: Actual Temperature Split = Treturn, db - Tsupply, db Target Temperature Split from Table RA3.2-3 using Treturn, wb and Treturn, db Calculate difference: Actual Temperature Split – Target Temperature Split = Passes if difference is between -3°F and +3°F or, upon remeasurement, if between -3°F and -100°F Enter Pass or Fail Note: Temperature Split Method Calculation is not necessary if actual Cooling Coil Airflow is verified using one of the airflow measurement procedures specified in Reference Residential Appendix RA3.3. If actual cooling coil airflow is measured, the value must be equal to or greater than the Calculated Minimum Airflow Requirement in the table below. Calculated Minimum Airflow Requirement (CFM) = Nominal Cooling Capacity (ton) X 300 (cfm/ton) System Name or Identification/Tag Calculated Minimum Airflow Requirement (CFM) Measured Airflow using RA3.3 procedures (CFM) Passes if measured airflow is greater than or equal to the calculated minimum airflow requirement. Enter Pass or Fail Superheat Charge Method Calculations for Refrigerant Charge Verification. This procedure is required to be used for fixed orifice metering device systems System Name or Identification/Tag Calculate: Actual Superheat = Tsuction – Tevaporator, sat Target Superheat from Table RA3.2-2 using Treturn, wb and Tcondenser, db Calculate difference: Actual Superheat – Target Superheat = System passes if difference is between -5°F and +5°F Enter Pass or Fail Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms August 2009 INSTALLATION CERTIFICATE Refrigerant Charge Verification - Standard Measurement Procedure Site Address: Enforcement Agency: CF-6R-MECH-25-HERS (Page 4 of 5) Permit Number: Subcooling Charge Method Calculations for Refrigerant Charge Verification. This procedure is required to be used for thermostatic expansion valve (TXV) and electronic expansion valve (EXV) systems. System Name or Identification/Tag Calculate: Actual Subcooling = Tcondenser, sat – Tliquid Target Subcooling specified by manufacturer Calculate difference: Actual Subcooling – Target Subcooling = System passes if difference is between -3°F and +3°F Enter Pass or Fail Metering Device Calculations for Refrigerant Charge Verification. This procedure is required to be used for thermostatic expansion valve (TXV) and electronic expansion valve (EXV) systems. System Name or Identification/Tag Calculate: Actual Superheat = Tsuction – Tevaporator, sat Enter allowable superheat range from manufacturer's specifications (or use range between 4°F and 25°F if manufacturer's specification is not available) System passes if actual superheat is within the allowable superheat range Enter Pass or Fail Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms August 2009 INSTALLATION CERTIFICATE Refrigerant Charge Verification - Standard Measurement Procedure Site Address: Enforcement Agency: CF-6R-MECH-25-HERS (Page 5 of 5) Permit Number: Standard Charge Measurement Summary: System shall pass both refrigerant charge criteria, metering device criteria (if applicable), and minimum cooling coil airflow criteria based on measurements taken concurrently during system operation. If corrective actions were taken, all applicable verification criteria must be re-measured and/or recalculated. System Name or Identification/Tag System meets all refrigerant charge and airflow requirements. Enter Pass or Fail Residential Appendix RA3.2.2 requires that if the outdoor temperature is between 55°F and 65°F the return air dry bulb temperature shall be maintained above 70°F during the Standard Charge Measurement Procedure. The signature of the Responsible Person in the declaration statement below certifies this requirement has been met for all applicable system verifications reported on this certificate. DECLARATION STATEMENT • I certify under penalty of perjury, under the laws of the State of California, the information provided on this form is true and correct. • I am eligible under Division 3 of the Business and Professions Code to accept responsibility for construction, or an authorized representative of the person responsible for construction (responsible person). • I certify that the installed features, materials, components, or manufactured devices identified on this certificate (the installation) conforms to all applicable codes and regulations, and the installation is consistent with the plans and specifications approved by the enforcement agency. • I understand that a HERS rater will check the installation to verify compliance, and that that if such checking identifies defects, I am required to take corrective action at my expense. I understand that Energy Commission and HERS provider representatives will also perform quality assurance checking of installations, including those approved as part of a sample group but not checked by a HERS rater, and if those installations fail to meet the requirements of such quality assurance checking, the required corrective action and additional checking/testing of other installations in that HERS sample group will be performed at my expense. • I reviewed a copy of the Certificate of Compliance (CF-1R) form approved by the enforcement agency that identifies the specific requirements for the installation. I certify that the requirements detailed on the CF-1R that apply to the installation have been met. • I will ensure that a completed, signed copy of this Installation Certificate shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Installation Certificate is required to be included with the documentation the builder provides to the building owner at occupancy. I will ensure that all Installation Certificates will come from a HERS provider data registry for multiple orientation alternatives, and beginning October 1, 2010, for all low-rise residential buildings. Company Name: (Installing Subcontractor or General Contractor or Builder/Owner) Responsible Person's Name: CSLB License: Responsible Person's Signature: Date Signed: Is this installation monitored by a Third Party Quality Control Program (TPQCP)? Yes No Position With Company (Title): Name of TPQCP (if applicable): Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms March 2010 INSTALLATION CERTIFICATE Refrigerant Charge Verification - Alternate Measurement Procedure Site Address: Enforcement Agency: CF-6R-MECH-26-HERS (Page 1 of 2) Permit Number: As many as 4 systems in the dwelling can be documented for compliance using this form. Attach an additional form(s) for any additional systems in the dwelling as applicable. Temperature Measurement Access Holes (TMAH) and Saturation Temperature Measurement Sensors (STMS) Procedures for installing TMAH are specified in Reference Residential Appendix RA3.2. If refrigerant charge verification is required for compliance, TMAH are also required for compliance. STMS are only required for completely new or replacement space-conditioning systems that utilize prescriptive compliance method. TMAH - Access Holes in Supply and Return Plenums of Air Handler System Name or Identification/Tag System Location or Area Served 1 Yes No 2 Yes No Yes to 1 and 2 is a pass. 5/16 inch (8 mm) access hole upstream of evaporative coil in the return plenum and labeled according to Figure in Section RA3.2.2.2.2. 5/16 inch (8 mm) access hole downstream of evaporative coil in the supply plenum and labeled according to Figure in Section RA3.2.2.2.2. Enter Pass or Fail 9 Pass 9 Fail STMS - Sensor on the Evaporator Coil System Name or Identification/Tag The sensor is factory installed, or field installed according to manufacturer's specifications, or is installed by methods/specifications approved by the Executive Director. The sensor wire is terminated with a standard mini plug suitable for connection to a 4 Yes No digital thermometer. The sensor mini plug is accessible to the installing technician and the HERS rater without changing the airflow through the condenser coil 5 Yes No The sensor measures the saturation temperature of the coil within 1.3 degrees F Yes to 3, 4, and 5 is a pass. Enter 9 N/A 9 Pass 9 Fail N/A if STMS are not applicable. Otherwise enter Pass or Fail 3 Yes No STMS - Sensor on the Condenser Coil System Name or Identification/Tag The sensor is factory installed, or field installed according to manufacturer's specifications, or is installed by methods/specifications approved by the Executive Director. The sensor wire is terminated with a standard mini plug suitable for connection to a 7 Yes No digital thermometer. The sensor mini plug is accessible to the installing technician and the HERS rater without changing the airflow through the condenser coil 8 Yes No The sensor measures the saturation temperature of the coil within 1.3 degrees F Yes to 6, 7, and 8 is a pass. Enter 9 N/A 9 Pass 9 Fail N/A if STMS are not applicable. Otherwise enter Pass or Fail 6 Yes No Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms August 2009 INSTALLATION CERTIFICATE Refrigerant Charge Verification - Alternate Measurement Procedure Site Address: Enforcement Agency: CF-6R-MECH-26-HERS (Page 2 of 2) Permit Number: Alternate Charge Measurement Procedure (for use if outdoor air dry-bulb is below 55 °F) Procedures for Determining Refrigerant Charge using the Alternate Method are available in Reference Residential Appendix RA3.2. As many as 4 systems in the dwelling can be documented for compliance using this form. Attach an additional form(s) for any additional systems in the dwelling as applicable. • The alternative charge measurement procedure requires that the system shall be installed and charged in accordance with the manufacturer’s specifications for refrigerant charge using the weigh-in charging method. • Installer verification of line lengths and charge adjustment calculation must be documented on CF-6R before starting this procedure. • If outdoor air dry-bulb is 55 °F or above, installer must use the Standard Charge Measure Procedure. Weigh-In Charging Method for Refrigerant Charge Verification System Name or Identification/Tag System Location or Area Served Actual liquid line length (ft) Manufacturer’s Standard liquid line length (ft) Calculate: difference in length (ft) = Actual length – Standard length Manufacturer’s correction factor (ounces per foot) Calculate: charge adjustment = correction factor X difference in length Alternate Charge Measurement Summary: System refrigerant charge has been adjusted to meet the manufacturer's specifications based on actual line length Enter Pass or Fail DECLARATION STATEMENT • I certify under penalty of perjury, under the laws of the State of California, the information provided on this form is true and correct. • I am eligible under Division 3 of the Business and Professions Code to accept responsibility for construction, or an authorized representative of the person responsible for construction (responsible person). • I certify that the installed features, materials, components, or manufactured devices identified on this certificate (the installation) conforms to all applicable codes and regulations, and the installation is consistent with the plans and specifications approved by the enforcement agency. • I understand that a HERS rater will check the installation to verify compliance, and that that if such checking identifies defects, I am required to take corrective action at my expense. I understand that Energy Commission and HERS provider representatives will also perform quality assurance checking of installations, including those approved as part of a sample group but not checked by a HERS rater, and if those installations fail to meet the requirements of such quality assurance checking, the required corrective action and additional checking/testing of other installations in that HERS sample group will be performed at my expense. I reviewed a copy of the Certificate of Compliance (CF-1R) form approved by the enforcement agency that identifies the specific requirements for the installation. I certify that the requirements detailed on the CF-1R that apply to the installation have been met. I will ensure that a completed, signed copy of this Installation Certificate shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Installation Certificate is required to be included with the documentation the builder provides to the building owner at occupancy. I will ensure that all Installation Certificates will come from a HERS provider data registry for multiple orientation alternatives, and beginning October 1, 2010, for all low-rise residential buildings. • • Company Name: (Installing Subcontractor or General Contractor or Builder/Owner) Responsible Person's Name: CSLB License: Responsible Person's Signature: Date Signed: Position With Company (Title): Registration Number: ___________________________ Registration Date/Time: __________________ HERS Provider: ____________ 2008 Residential Compliance Forms August 2009 APPENDIX D CEC Code Clarification Letters 51 STATE OF CALIFORNIA – NATURAL RESOURCES AGENCY ARNOLD SCHWARZENEGGER, Governor CALIFORNIA ENERGY COMMISSION 1516 NINTH STREET SACRAMENTO, CA 95814-5512 www.energy.ca.gov Guidelines for Residential HERS Compliance Documentation Registered on or After October 1, 2010 – Newly Constructed Buildings and Additions Starting January 1, 2010, the 2008 Building Energy Efficiency Standards required all compliance documentation for newly constructed low-rise residential buildings requiring HERS verification and demonstrating compliance under the multiple orientation alternative to be registered with the appropriate HERS Provider. On October 1, 2010, this requirement was extended to all low-rise residential buildings requiring HERS field verification. To ensure compliance with this regulation, please follow these guidelines for newly constructed dwellings and additions: • Look for and review a registered Certificate(s) of Compliance (CF-1R) submitted with the building plans. A registered CF-1R will have a HERS Provider’s watermark and a unique 12-digit registration number followed by 13 zeros located at the bottom of each page (see registration number guide and example registered CF-6R on the following pages). • Look for and review an electronically signed and registered Installation Certificate(s) (CF-6R) posted by the installing contractor at the building site. The first 12 digits of its 21-digit registration number (followed by four zeros) will match the associated CF-1R’s registration number. • At final inspection, look for and review an electronically signed and registered Certificate(s) of Field Verification and Diagnostic Testing (CF-4R) posted at the building site by a certified HERS rater. The first 20 digits of its 25-digit registration number will match the associated CF-1R’s registration number. • At final inspection, verify that the work listed on the CF-1R has actually been completed and that the installed equipment matches what is listed on the CF-6R posted at the building site. • You may verify that any registered compliance document is valid by searching for it on the appropriate HERS Provider’s website using the document’s registration number. (Currently CalCERTS [www.calcerts.com] is the only HERS Provider certified for newly constructed residential buildings and additions.) If the submitted CF-1R, 6R, or 4R does not exactly match the version posted on the provider’s website, or if there is no electronic version available, its validity should be questioned. To combat fraud, the California Energy Commission recommends that building department personnel use the HERS Providers’ websites to perform random verification checks of registered compliance documents. (See HERS Providers’ website information on next page.) September 29, 2010 Registration Number Guide Note: Only capitalized alpha digits are used, to avoid confusion with the number Zero "0", the letter "O" is not used, and to avoid confusion with the number One "1", the letter "I" is not used. HERS Providers Approved for Newly Constructed Buildings, Additions, Alterations, and New Solar Homes Partnership Programs CalCERTS – www.calcerts.com Approved for Alterations Only CBPCA – www.cbpca.org September 29, 2010 Example Registered CF-6R from CalCERTS HERS Provider watermark Registration Number 210-N0001972A-M2000005B-0000 For more information, visit www.energy.ca.gov/title24 and www.energyvideos.com, or call the Energy Standards Hotline at (800) 772‐3300. September 29, 2010 STATE OF CALIFORNIA – THE RESOURCES AGENCY ARNOLD SCHWARZENEGGER, Governor CALIFORNIA ENERGY COMMISSION 1516 NINTH STREET SACRAMENTO, CA 95814-5512 www.energy.ca.gov Guidelines for Residential HERS Compliance Documentation Registered on or After October 1, 2010 – HVAC Alterations Starting October 1, 2010, all required energy compliance forms for residential HVAC alterations shall be registered with an approved HERS provider when HERS field verification and/or testing is required. This will include the CF-1R-ALT-HVAC form (or CF-1R-ALT form), all required CF6R-MECH-HERS forms, and all required CF-4R forms. To help simplify verification that all of these forms are registered when required, please follow these guidelines: • The CF-1R-ALT-HVAC form (or CF-1R-ALT form) shall be completed by hand, signed, and submitted along with the building permit application by the individual applying for the permit. This form will not be registered at the time of permit application. • For the final inspection, the building inspector shall verify that the following energy compliance forms are completed and signed by the installing contractor (or homeowner if the homeowner installed the HVAC equipment and/or ducting), and that the forms are registered by an approved HERS provider: ¾ CF-1R-ALT-HVAC form (or CF-1R-ALT form) ¾ ALL required CF-6R-MECH-HERS forms ¾ ALL required CF-4R forms NOTE: The CF-1R-ALT-HVAC form identifies which CF-6R-MECH-HERS forms and CF4R forms are required depending on climate zone and the type of HVAC alteration. • After the final inspection, the installing contractor shall provide a copy of the registered energy compliance forms to the homeowner. HERS Providers currently approved for alterations: CalCERTS – www.calcerts.com CBPCA – http://thecbpca.org For more information regarding residential HVAC alterations, required energy compliance forms, or the registration of forms, please visit the newly developed 2008 Energy Standards Online Learning Center at www.energyvideos.com, or contact the Energy Standards Hotline at (800) 772-3300. Guidance for Enforcement Agencies Regarding Approval Procedure for Weigh-In Method With winter temperatures upon us and without an approved alternative procedure to verify refrigerant charge when temperatures are below 55°F there have been reports of HERS raters conducting verification of refrigerant charge using an unapproved method in order to close permits due to pressure by contractors. In other cases, some enforcement agencies are issuing final building permits on the condition provided in RA 2.4.4 (quoted below). There doesn’t appear to be a formalized process to ensure that the HERS rater provide the verification required by the Standards after the final building permit has been issued. The following guidance has been developed to ensure that the HERS rater has been contracted to complete the verification process when outdoor temperatures are 55°F or above and the building permit was approved conditionally. From RA 2.4.4 If necessary to avoid delay of approval of dwelling units completed when outside temperatures are below 55°F, the enforcement agency may approve compliance credit for refrigerant charge and airflow measurement when installers have used the alternate charging and airflow measurement procedure described in Section RA3.2. This approval will be on the condition that installers provide a signed agreement to the builder with a copy to the enforcement agencies to return to correct refrigerant charge and airflow if the HERS rater determines at a later time when the outside temperature is above 55°F that correction is necessary. When the Alternate Charge Measurement Procedure (weigh-in method) is used for refrigerant charge measurement due to outdoor temperatures being below 55°F, the enforcement agency may final on the CF-6R on the condition that the installer provides a signed agreement to the builder or homeowner with a copy to the enforcement agency to return to correct refrigerant charge and airflow if the HERS rater determines that correction is necessary (per RA 2.4.4). The enforcement agency should verify a written agreement is in place between the installer and a certified HERS rater that documents that the HERS rater will measure the refrigerant charge using the Standard Charge Measurement Procedure when outdoor temperatures are 55°F or above and complete and register the required compliance documentation. This written agreement should be signed by both the installer and the HERS rater and contain the project address and homeowner’s/builder’s name, the HERS rater’s and Installer’s names, and specify how the HERS rater will be paid for performing the verification. This agreement should be submitted to the enforcement agency instead of a CF-4R before the final permit for the project is issued. Therefore, in cases where the Alternate Charge Measurement Procedure is used for refrigerant charge measurement, the enforcement agency may final the permit after receiving the CF-1R, CF-6R, and the written agreement between the HERS rater and installer detailed above. No CF-4R will be required at that time, but the HERS rater will provide the registered CF-4R to the homeowner when the verification is complete and the CF-4R is registered. For questions or clarification, contact the Energy Commission’s Building Standards Hotline at (800) 772-3300.