dB
DB
DC
DEMARC
DISC
DIST
DL
DVR
DWG
DECIBEL
DIRCT BURIAL
DIRECT CURRENT
DEMARCATION
DISCONNECT
DISTRIBUTION
DAMP LABEL
DIGITAL VIDEO RECORDER
DRAWING
E
EA
EC
EGC
EH
ELEC
ELEV
EM
EMT
EOL
EPO
EQUIP
ER
EWC
EXISTING TO REMAIN
EACH
ELECTRICAL CONTRACTOR OR EMPY CONDUIT
EQUIPMENT GROUNDING CONDUCTOR
ELECTRICALLY HELD
ELECTRIC OR ELECTRICAL
ELEVATOR
EMERGENCY
ELECTRIC METALLIC TUBING
FIRE ALARM END OF LINE RESISTOR
EMERGENCY POWER OFF
EQUIPMENT
EXISTING TO BE RELOCATED
ELECTRIC WATER COOLER
F
FA
FACP
FAAP
FBO
FC
FDR
FLA
FLEX
FLR
FLUOR
FO
FU
FUSE
FIRE ALARM
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
FURNISHED BY OTHERS
FOOTCANDLES
FEEDER
FULL LOAD AMPERES
FLEXIBLE CONDUIT
FLOOR
FLUORESCENT
FIBER OPTIC
FUSE OR FUSED
G, GND
GA
GALV
GC
GEN
GFI,GFCI
GRC
GROUND
GUAGE
GALVANIZED
GENERAL CONTRACTOR
GENERATOR
GROUND FAULT CIRCUIT INTERRUPTER
GALVANIZED RIGID CONDUIT
HV
HD
HH
HID
HOA
HP
HPF
HPS
HZ
HORIZONTAL CROSS CONNECT
HEAVY DUTY
HAND HOLE
HIGH INTENSITY DISCHARGE
HAND-OFF-AUTOMATIC
HORSEPOWER
HIGH POWER FACTOR
HIGH PRESSUR SODIUM
HERTZ (CYCLES/SECOND)
IC
ID
IDF
IG
IMC
INCAND
TBB
TC
TEL
TELCOM
TEMP
TGB
TMGB
TO
TR
TS
TTB
TTC
TB
TYP
J-BOX
JUNTION BOX
KILOAMPERE INTERRUPTING CAPACITY
THOUSAND OF CIRCULAR MILLS
KILOVOLT
KILOVOLT-AMPER
KILOWATT
KILOWATT-HOUR
LAN
LCL
LED
LFC
LML
LPF
LTG
LV
LOCAL AREA NETWORK
LONG CONTINUOUS LOAD
LIGHT EMITTING DIODE
LIQUIDTIGHT FLEXIBLE CONDUIT
LARGEST MOTOR LOAD
LOW POWER FACTOR
LIGHTING
LOW VOLTAGE
UNDER COUNTER
UNDER GROUND
UNDERWRITER LABORATORIES
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER SUPPLY
UNSHIELDED TWISTED PAIR
V
VA
VAR
VFD
VP
VOLT
VOLT-AMPERE
REACTIVE VOLT-AMPERS
VARIABLE FREQUENCY DRIVE
VAPOR PROOF
W
W/
W/O
WCR
WH
WHM
WP
WPL
WT
WATT
WITH
WITHOUT
WITHSTAND CURRENT RATING
WATT HOUR
WATT HOUR METER
WEATHERPROOF
WEATHERPROOF LOCKABLE ENCLOSURE
WATERTIGHT
XFMR
XP
TRANSFORMER
EXPLOSION PROOF
X
X
X
X
X
X
X
SPECIAL RECEPTACLE
RECESSED 2'x2' FLUORESCENT FIXTURE
SPECIAL RECEPTACLE
2'x2' FLUORESCENT FIXTURE (SURFACE MOUNTED)
SINGLE RECEPTACLE (EMERGENCY CIRCUIT)
DIRECT/INDIRECT 2'x2' FLUORESCENT FIXTURE
DUPLEX RECEPTACLE (EMERGENCY CIRCUIT)
HP
PROVISION FOR UTILITY METER
FOURPLEX RECEPTACLE (EMERGENCY CIRCUIT)
GROUND
SPECIAL RECEPTACLE (EMERGENCY CIRCUIT)
X
X
X
X
1'x4' FLUORESCENT FIXTURE (SURFACE MOUNTED)
FLUORESCENT RECESSED COVE FIXTURE
DUPLEX RECEPTACLE, HALF SWITCHED
MOTOR
WALL MOUNTED FLUORESCENT FIXTURE
CLOCK OUTLET
EXISTING CONDUIT INTERCEPTOR
WALL MOUNTED HID FIXTURE
SINGLE SWITCHED DUPLEX RECEPTACLE
MULTIPLE CONDUCTOR LUG
TV
X
TV
STRIP LIGHT
TELEVISION OUTLET
FEEDER IDENTIFIER SYMBOL
J
J
J
J
J
J
J
J
WALL MOUNTED STRIP LIGHT
JUNCTION BOX
NON-FUSED DISCONNECT SWITCH
PENDANT MOUNTED STRIP LIGHT
SYSTEMS FURNITURE FEED
DISCONNECT SWITCH W/ AMP FUSE AND AMP FRAME
TRACK LIGHT
CIRCUIT BREAKER DISCONNECT
POWER POLE
COMBINATION MAGNETIC STARTER AND CIRCUIT BREAKER
DISCONNECT
PLUG MOLD
TO
CONTACTOR
XXXA
3P
2.
THE DISCONNECTING MEANS FOR ALL MECHANICAL EQUIPMENT SHALL BE
ACCESSIBLE AND HAVE THE CLEARANCE IN FRONT AS REQUIRED BY NEC AMENDMENTS.
3.
ALL CEILING ATTACHED OBJECTS AND FLOOR ATTACHED EQUIPMENT INCLUDING
BUT NOT LIMITED TO PENDANT LIGHTING FIXTURES, CHANDELIERS, GENERAL LIGHTING,
MULTIPLE RACEWAYS, GENERATORS, TRANSFORMERS, ELECTRICAL SWITCHGEAR, AND
SWITCHBOARDS SHALL BE INSTALLED IN ACCORDANCE WITH SUPPORTING OBJECTS FOR
SEISMIC ZONE AS REQUIRED BY STATE AND LOCAL CODES AND PER STRUCTURAL
ENGINEERS RECOMMENDATIONS.
4.
ALL SWITCHGEAR, SWITCHBOARDS AND TRANSFORMERS SHALL HAVE A 4 INCH
HOUSE KEEPING PAD. UNDER NO CONDITION SHALL THE HIGHEST SWITCH OR BREAKER
EXCEED 6'-6" AFF.
5.
DATA GIVEN ON THE DRAWINGS IS AS EXACT AS COULD BE SECURED. ABSOLUTE
ACCURACY IS NOT GUARANTEED AND THE CONTRACTOR SHALL OBTAIN AND VERIFY
EXACT LOCATIONS, MEASUREMENTS, LEVELS, SPACE REQUIREMENTS, POTENTIAL
CONFLICTS WITH OTHER TRADES, ETC. AT THE SITE AND SHALL SATISFACTORILY ADAPT
HIS WORK TO ACTUAL CONDITIONS AT THE BUILDINGS. THE DRAWINGS ARE
DIAGRAMMATICAL IN NATURE AND SHALL NOT BE SCALED. HOWEVER THIS DOES NOT
RELIEVE ANY SUB-CONTRACTOR FROM COORDINATING HIS WORK WITH ALL OTHER
TRADES AND FROM ADJUSTING HIS WORK AS REQUIRED BY THE ACTUAL CONDITIONS OF
THE PROJECT. THE CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING COSTS TO
BECOME THOROUGHLY FAMILIAR WITH THE ACTUAL CONDITIONS OF THE PROJECT.
6.
COORDINATE AND ADJUST ALL WORK BETWEEN TRADES AND EXISTING
CONDITIONS IN ORDER TO ACCOMPLISH A NEAT, INTEGRATED AND EFFICIENT
INSTALLATION WHICH INCLUDE BUT ARE NOT LIMITED TO:
a.
EXAMINE THE CONTRACT DOCUMENTS OF ALL TRADES (IE. THE
ARCHITECTURAL REFLECTED CEILING PLAN, MECHANICAL HVAC DRAWINGS,
ELECTRICAL LIGHTING PLAN, FIRE PROTECTION PLAN, ETC.).
WALL SCONCE
b.
COORDINATE NECESSARY EQUIPMENT, FIXTURES, ETC. SO THAT THE
FINAL INSTALLATION IS COMPATIBLE WITH THE MATERIALS AND EQUIPMENT OF
THE OTHER TRADES.
PENDANT
SINGLE POLE THERMAL OVERLOAD SWITCH
SURFACE MOUNTED DOWNLIGHT
NON-FUSED DISCONNECT SWITCH
SURFACE MOUNTED WALL WASHER
MOLDED CASE CIRCUIT BREAKER
c.
THIS CONTRACTOR SHALL ASSIST THE DIVISION 15 CONTRACTOR IN
PREPARING SHOP DRAWINGS FOR COORDINATING INSTALLATION OF ALL WORK
(IE. LOCATING ALL LIGHTING FIXTURES IN CEILING WITH CEILING CLEARANCES,
RACEWAYS, CABLE TRAY, PIPING, EQUIPMENT FOR CLEARANCE THROUGHOUT).
RECESSED DOWNLIGHT
FUSED DISCONNECT SWITCH
G
1.
ALL EXPOSED RACEWAYS ARE TO BE INSTALLED PARALLEL OR PERPENDICULAR
TO WALLS OR STRUCTURAL MEMBERS SUCH THAT THEY FOLLOW STRUCTURAL SURFACE
CONTOURS AND SHALL BE INSTALLED SUCH THAT THEY DO NOT OBSTRUCT
PASSAGEWAYS OR ACCESS TO EQUIPMENT. MULTIPLE RACEWAYS SHOULD BE
INSTALLED GROUPED TOGETHER. THE LOCATION OF PUBLICLY VISIBLE RACEWAYS SHALL
BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION. (EXTRA TIME SHOULD BE
ALLOWED FOR THIS REVIEW AND APPROVAL.)
WALL MOUNTED LIGHT
GROUNDING BUS BAR
MAGNETIC MOTOR STARTER
MOLDED CASE CIRCUIT BREAKER WITH GROUND FAULT
RECESSED WALL WASH DOWNLIGHT
ENCLOSED CIRCUIT BREAKER
d.
THE ELECTRICAL DRAWINGS INDICATE THE ELECTRICAL
REQUIREMENTS FOR A SIGNIFICANT PORTION OF THE MECHANICAL AND
PLUMBING SYSTEMS. ADDITIONAL MECHANICAL AND PLUMBING EQUIPMENT IS
INDICATED ON THE DIVISION 15 DRAWINGS. REFER TO MECHANICAL DRAWINGS
AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. PROVIDE COMPLETE
WIRING AND FUSIBLE DISCONNECTING MEANS FOR ALL MECHANICAL AND
PLUMBING EQUIPMENT UNLESS OTHERWISE NOTED.
RECESSED LINEAR WALL WASH
MAGNETIC MOTOR STARTER
SHUNT TRIP CIRCUIT BREAKER
RECESSED STEP LIGHT
PANEL BOARD
DRAWOUT AIR CIRCUIT BREAKER
SITE POLE LIGHT - 1 HEAD
LIGHTING CONTROL PANEL / CONTROL PANEL
NON-FUSED SWITCH
EXTERIOR POST TOP OR BOLLARD
EMERGENCY POWER OFF PUSHBUTTON
FUSED SWITCH
FUSED DISCONNECT SWITCH W/ GROUND
SHUNT TRIP
G
STARTER CIRCUIT BREAKER
T
BUZZER / DOORBELL
EMERGENCY BATTERY PACK
MOTOR
WALL MOUNTED EXIT SIGN
b.
"INSTALL" MEANS TO "SET IN PLACE, CONNECT AND PLACE IN FULL
OPERATIONAL ORDER".
VFD
SELECTOR SWITCH
WALL SWITCH
SUPERSCRIPTS:
2 - 2 POLE SWITCH
3 - 3 WAY SWITCH
4 - 4 WAY SWITCH
K - KEY OPERATED
LV - LOW VOLTAGE
P - PILOT LIGHT
G - COMBINATION SWITCH AND DEAD-FRONT GFCI
VARIABLE FREQUENCY DRIVE
PB
PULL-BOX. SIZE BY CODE OR SPECIFICATION, UON
T
K
CEILING MOUNTED EXIT SIGN
TERMINAL CABINET, SIGNAL SYSTEM
STARTER NON-FUSED SWITCH
TRANSFORMER
KIRK KEY
PAD MOUNTED TRANSFORMER
ENCLOSED CAPACITOR
SINGLE POLE TOGGLE SWITCH
(LOWER CASE LETTERS DENOTES MULTIPLE SWITCHES)
a,b
ELECTRICAL MANHOLE
E
D
DIGITAL DISPLAY METER W/ CENTRAL REPORTING
WALL DIMMER LIGHT SWITCH
GROUND SENSING RELAY
SPECIAL RECEPTACLE MODIFIERS
ENGINE GENERATOR SET W/ NEUTRAL GROUND, ENGINE
STARTING CONTACTS AND MAIN CIRCUIT BREAKER
LETTER
NON-FUSED DISCONNECT SWITCH IN SEPERATE ENCLOSURE
MOLDED CASE CIRCUIT BREAKER IN SEPERATE ENCLOSURE
VFD
VARIABLE FREQUENCY DRIVE
RATING
NEMA
NOTES
A
125V, 1~, 30A, 2P, 3W
5-30R
WITH 5-30P PLUG
B
250V, 1~, 20A, 2P, 3W
6-20R
WITH 6-20P PLUG
C
250V, 1~, 30A, 2P, 3W
6-30R
WITH 6-30P PLUG
D
250V, 1~, 50A, 2P, 3W
6-50R
WITH 6-50P PLUG
F
125/250V, 1~, 20A, 3P, 4W
14-20R
WITH 14-20P PLUG
G
125V, 1~, 20A, 2P, 3W DUPLEX
5-20R
GROUND FAULT
INTERRUPTING
SURGE ARRESTOR
H
125/250V, 1~, 30A, 3P, 4W
14-30R
WITH 14-30P PLUG
IG
125V, 1~, 20A, 2P, 3W
5-20R
ISOLATED GROUND WITH
INTEGRAL TRANSISENT
VOLT. SUPPRESSOR
ISOLATION TRANSFORMER
1
L
125V, 1~, 20A, 2P, 3W LOCKING
L5-20R
WITH L5-20P PLUG
1
LA
125V, 1~, 30A, 2P, 3W
L5-30R
WITH L5-30P PLUG
M
250V, 3~, 20A, 3P, 4W
15-20R
WITH 15-20P PLUG
N
250V, 3~, 30A, 3P, 4W
15-30R
WITH 15-30P PLUG
P
250V, 3~, 50A, 3P, 4W
15-50R
WITH 15-50P PLUG
R
250V, 3~, 60A, 3P, 4W
15-60R
WITH 15-60P PLUG
S
125V, 1~, 20A, 2P, 3W
5-20R
"SAFETY-TYPE"
W
480V, 3~, 60A, 3P, 4W
ANNOTATION LEGEND
SYMBOL
1
XXXX
AA-1,3,5
KEYED NOTE TAG
WP
IEC 309-1&2
(NOT NEMA)
125V, 1~, 20A, 2P, 3W DUPLEX
5-20R
DETAIL TAG
HOMERUN TO SWITCHBOARD OR MOTOR
CONTROL CNETER. SIZED PER SINGLE LINE
DIAGRAM OR SCHEDULE.
2
d.
"EQUIVALENT" MEANS "MEETS THE SPECIFICATIONS OF THE
REFERENCE PRODUCT OR ITEM IN ALL SIGNIFICANT ASPECTS." SIGNIFICANT
ASPECTS SHALL BE DETERMINED BY THE ENGINEER.
e.
"WORK BY OTHER(S) (CONTRACTOR): "RE:
DIVISION", AND SIMILAR
EXPRESSIONS MEANS WORK TO BE PERFORMED UNDER THE CONTRACT
DOCUMENTS, BUT NOT NECESSARILY UNDER THE DIVISION OR SECTION OF THE
WORK ON WHICH THE NOTE APPEARS. IT IS THE CONTRACTORS SOLE
RESPONSIBILITY TO COORDINATE THE WORK OF THE CONTRACT BETWEEN
HIS/HER SUPPLIERS, SUBCONTRACTORS, AND EMPLOYEES. IF CLARIFICATION IS
REQUIRED, CONSULT ARCHITECT BEFORE START OF WORK.
8.
"FIRESTOPPING" REQUIREMENT. ALL PENETRATIONS THROUGH RATED WALLS AND
FLOORS SHALL BE SEALED WITH MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF
FLAMES AND HOT GASSES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST
STANDARD SPECIFIC FOR FIRE STOPS ASTM-E-814. ALL PENETRATIONS SHALL MEET F
AND T RATINGS AS REQUIRED BY THE BUILDING CODE.
9.
ALL ELECTRICAL CONDUIT CROSSING BUILDING SEISMIC SEPARATION OR
EXPANSION JOINTS SHALL BE PROVIDE WITH APPROVED FLEXIBLE CONNECTORS. REFER
TO THE ARCHITECTURAL PLANS FOR ALL EXPANSION JOINT LOCATIONS.
SHADED SYMBOLS DENOTE EMERGENCY FIXTURES
GENERAL NOTES FOR REMODEL
FIRE ALARM
SYMBOL
CLG
DESCRIPTION
WALL
SPEAKER
SPEAKER WITH STROBE
STROBE
M
MASS NOTIFICATION STROBE
RTS
RTS
PIN & SLEEVE ON 15 DEG.
ANGLE BACK BOX
WITH MATCHING PLUG
BR
BT
THE NEMA NUMBER WITH THE "L" PREFIX INDICATES THE LOCKING
TYPE RECEPTACLE AND PLUG.
CO
S
TV
1.
OBTAIN STRUCTURAL ENGINEERS APPROVAL PRIOR TO ANY CORE DRILLING OF AN
EXISTING SUSPENDED SLAB. X-RAY THE SLAB TO AVOID RE-BAR, ETC.
2.
THE INFORMATION ON THE DEMOLITION DRAWINGS REGARDING EXISTING
CONDITIONS WAS OBTAINED LARGELY FROM FIELD OBSERVATIONS AND DISCUSSIONS
WITH FACILITY PERSONNEL. PROVIDE A SURVEY OF THE EXISTING BUILDING, AND
VERIFICATION OF THE EXISTING CONDITIONS.
3.
REFER TO THE ARCHITECTURAL DEMOLITION FLOOR PLANS AND REFLECTED
CEILING PLANS, TO ESTABLISH THE COMPLETE SCOPE OF WORK.
4.
PROVIDE THE REQUIRED NEW CONDUIT, CONDUIT INTERCEPTIONS, JUNCTION
BOXES, PULL BOXES, NEW CONDUCTORS, ETC. TO ACCOMPLISH THE WORK, INTEGRATE
THE NEW WORK WITH THE EXISTING WHERE INDICATED. MAINTAIN THE CONTINUITY AND
OPERATION OF THE EXISTING SYSTEMS IN THE AREAS ADJACENT TO THE REMODELED
AREAS.
REMOTE INDICATOR LIGHT
SMOKE DETECTOR
GROUND FAULT
INTERRUPTING WITH
IN-USE WEATHERPROOF
COVER
THE NUMBER OF WIRES INDICATED INCLUDES THE GROUND.
"PROVIDE" MEANS TO "FURNISH AND INSTALL".
WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
KEY NOTES:
1
c.
10.
WHERE DISCONNECTS ARE INDICATED ON DRAWINGS CONTRACTOR SHALL
PROVIDE FINAL CONNECTION TO EQUIPMENT BEING SERVED BY DISCONNECT.
E
IDENTIFIES DINGLE OR MULTIWIRE BRANCH
CIRCUITS (THREE CIRCUITS SHOWN) IN
HOMERUN TO PANEL AA.
WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH
(LOWER CASE LETTERS DENOTES DUAL LEVEL SWITCHING)
ab
M
DESCRIPTION
PANELBOARD NAME TAG
CEILING MOUNTED DUAL TECH OCCUPANCY SENSOR
2
AUTOMATIC TRANSFER SWITCH
TRANSFORMER (DELTA TO GROUND WYE)
DEFINITIONS:
a.
"FURNISH" MEANS TO "SUPPLY" AND USUALLY REFERS TO AN ITEM OF
EQUIPMENT.
THERMOSTAT
STARTER FUSED SWITCH
7.
IN GROUND WELL LIGHT
DOUBLE PUSH-BUTTON STATION
#
SHT.
TYPICAL 9'-0" CEILING OR HIGHER
PARABOLIC 2'x4' FLUORESCENT FIXTURE
RECESSED 1'x4' FLUORESCENT FIXTURE
M
TELECOMMUNICATIONS BONDING BACKBONE
TIME CLOCK
TELEPHONE
TELECOMMUNICATIONS
TEMPORARY OR TEMPERATURE
TELECOMMUNICATIONS GROUND BUSS
MAIN TELECOMMUNICATIONS GROUND BUS
THERMAL OVERLOAD
TAMPER RESISTANT OR TELECOMMUNICATIONS ROOM
TIME SWITCH
TELEPHONE TERMINAL BOARD
TELEPHONE TERMINAL CABINET OR CLOSET
TELEVISION
TYPICAL
UC
UG
UL
UON
UPS
UTP
X
BRANCH CIRCUIT PANELBOARD W/ FEED THROUGH GUTTER
AND MAIN CIRCUIT BREAKER
G
INTERCOM OR INTERMEDIATE CROSS-CONNECT
INSIDE DIAMETER
INTERMEDIAT DISTRIBUTION FRAME
ISOLATED GROUND
INTERMEDIATE GRADE METALLIC CONDUIT
INCANDESCENT
KAIC
KCMIL
KB
KVA
KW
KWH
BRANCH CIRCUIT PANELBOARD W/ FEED THROUGH GUTTER
XXXX
POLE
PUBLIC ACCESS
PUSH BUTTON OR PULL BOX
PRIVATE BRANCH EXCHANGE
PHOTOELECTRIC
POWER FACTOR
PHASE
PANEL
PAIRS
PRIMARY
PROXIMITY
POTENTIAL TRANSFORMER
PAN, TILT, ZOOM CAMERA
POLYVINYL CHLORIDE
POWER
SECURITY CONTROL PANEL
SECONDARY OR SECOND
SECTION
SHEET
SINGLE-MODE FIBER OPTIC
SERVICE PROVIDER
SURGE PROTECTION DEVICE
SINGLE POLE, DOUBLE THROW
SINGLE POLE, SINGLE THROW
SHUNT TRIP
SHIELDED TWISTEED PAIR
STANDARD
SYSTEM
SWITCH
SWITCHBOARD
2'x4' FLUORESCENT FIXTURE (SURFACE MOUNTED)
DIRECT/INDIRECT 2'x4' FLUORESCENT FIXTURE
P
PA
PB
PBX
PE
PF
PH
PNL
PR
PRI
PROX
PT
PTZ
PVC
PWR
SCP
SEC
SECT
SHT
SMFO
SP
SPD
SPDT
SPST
ST
STP
STD
SYS
SW
SWBD
RECESSED 2'x4' FLUORESCENT FIXTURE
DUPLEX RECEPTACLE
BRANCH CIRCUIT PANELBOARD W/ MAIN CIRCUIT BREAKER
XXXX
ON CENTER
OUTSIDE DIAMETER
OWNER FURNISHED, CONTRACTOR INSTALLED
OWNER FURNISHED, OWNER INSTALLED
OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
OUTSIDE PLANT
EXIXISTING TO BE REMOVED
RELOCATED EXISTING
RECEPTACLE
REQUIRED
RIGID GALVANIZED STEEL
ROOM
RIGID METALLIC CONDUIT
RIGID NON-METALLIC CONDUIT
REVOLUTIONS PER MINUTE
FLOOR WALL
FOURPLEX RECEPTACLE
OC
OD
OFCI
OFOI
OSHA
OSP
R
RE
REC
REQ'D
RGS
RM
RMC
RNC
RPM
DESCRIPTION
BRANCH CIRCUIT PANELBOARD
XXXX
NEUTRAL
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NON-FUSED
NATIONAL FIRE PROTECTION ASSOCIATION
NOT IN CANTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
QUARTZ RESTRIKE
CLG
SYMBOL
SINGLE RECEPTACLE
N
NC
NEC
NEMA
NF
NFPA
NIC
NL
NO
NTS
QR
STUB
XXXX
DESCRIPTION
BEAM SMOKE DETECTOR - RECEIVER
BEAM SMOKE DETECTOR - TRANSMITTER
ELEVATOR LOBBY SMOKE DETECTOR
5.
EXISTING BRANCH CIRCUIT CONDUITS MAY BE REUSED FOR THE NEW WORK.
UNDER THESE CONDITIONS, PROVIDE ALL NEW CONDUCTORS. CONDUCTOR FILL PER
CODE. IN CEILING SPACES, REMOVE ANY EXISTING CONDUITS THAT ARE NOT REUSED.
6.
WHERE THE ARCHITECTURAL DRAWINGS INDICATE THAT AN EXISTING PARTITION
IS TO BE REMOVED, DISCONNECT AND REMOVE EXISTING ELECTRICAL AND SIGNAL
DEVICES, OUTLET BOXES, CONDUIT AND CONDUCTORS. REMOVE CONDUCTORS BACK TO
THE LAST ELECTRICAL OR SIGNAL DEVICE TO REMAIN ACTIVE. REFER TO THE DEMO AND
MODERNIZATION DRAWINGS FOR THE SCOPE OF THIS WORK.
HEAT DETECTOR
7.
ALL REMOVED LIGHTING FIXTURES, RECEPTACLE OUTLETS, SECURITY, PUBLIC
ADDRESS AND FIRE ALARM DEVICES SHALL BE RETURNED TO THE OWNER AS DIRECTED.
DUCT DETECTOR
8.
WHERE THE ELECTRICAL DRAWINGS INDICATE THAT A DEVICE, OF ANY TYPE, IS
TO BE REMOVED FROM A PARTITION THAT REMAINS, DISCONNECT AND REMOVE THE
DEVICE AND OUTLET BOX. REMOVE THE CONDUCTORS BACK TO THE LAST DEVICE TO
REMAIN ACTIVE. CAP THE CONDUIT IN THE PARTITION AND ABANDON. AT THE TOP OF
THE PARTITION, INTERCEPT AND CAP THE CONDUIT IN THE CEILING SPACE AT THE FIRST
ACCESSIBLE COUPLING.
CARBON MONOXIDE DETECTOR
WALL MOUNTED SILENT HORN
PUEBLO COUNTY SCHOOL DISTRICT 70
CONDUIT
COMMUNITY ANTENNA TV (CABLE TV)
CABINET
CAMERA
CIRCUIT BREAKER
CERTIFIED BALLAST MANUFACTURERS
CLOSED CIRCUIT TELEVISION
CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
COMPACT FLUORESCENT LAMP
CIRCUIT
CEILING
CONDUIT ONLY
COAXIAL
COMBINATION
CONDUCTOR
CONTRACTOR OR CONTINUATION
CURRENT TRANSFORMER
COPPER
SYMBOL
Pueblo West High School Additions + Renovations
C
CATV
CAB
CAM
CB
CBM
CCTV
CFCI
CFL
CKT
CLG
CO
COAX
COMB
COND
CONT
CT
CU
DESCRIPTION
Revisions
BARE COPPER
BELOW FINISHED CEILING
BELOW FINISHED GRADE
BREAKER
BUILDING
SYMBOL
MAGNETIC
MAXIMUM
MECHANICAL CONTRACTOR OR MAIN CROSS
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOTOR CIRCUIT PROTECTORR
MAIN DISTRIBUTION FRAME
MAIN DISTRIBUTION PANEL
MECHANICAL
MANUFACTURER
MOTOR GENERATOR
MANHOLE OR METAL HALIDE
MINIMUM
MAIN LUGS ONLY
MULTIMODE FIBER OPTIC
MAIN POINT OF ENTRY
MAIN SWITCHBOARD
MAIN TERMINAL BOARD
MOUNTED
MOUNTING HEIGHT
MOTOR
MEDIUM VOLTAGE
37-13102-00
09.12.2013
BC
BFC
BFG
BKR
BLDG
MAG
MAX
MC
MCB
MCC
MCP
MDF
MDP
MECH
MFR
MG
MH
MIN
MLO
MMFO
MPOE
MSB
MTB
MTD
MTG
MTR
MV
GENERAL ELECTRICAL REQUIREMENTS
ELECTRICAL LEGEND
AMPERE
ABOVE COUNTER OR ALTERNATING CURRENT
AMERICANS WWITH DISABILITIES ACT
AMPERE FUSE/FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMPERE INTERRUPTING CAPACITY
ALUMINUM
ALTERNATE
ANNUNCIATOR
AMERICAN NATIONAL STANDARDS INSTITUTE
AVAILABLE RMS SYMMETRICAL AMPERES
AMPERE SWITCH
AMPERE TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AUXILIARY
AMERICAN WIRE GAUGE
LIGHTING
E0.0
A,AMP
AC
ADA
AF
AFF
AFG
AIC
AL
ALT
ANN
ANSI
ARS
AS
AT
ATS
AUTO
AUX
AWG
ANNOTATION LEGEND
ONE-LINE SYMBOLS
ABBREVIATIONS
661 W Capistrano Ave
Pueblo West, CO 81007
ABBREVIATIONS
PULL STATION
SYMBOL
TOP OF CABINET
FAAP
W
18" (1'-6") UON
42" (3'-6") UON
54" (4'-6") UON
64" (5'-4") UON
72" (6'-0") UON
78" (6'-6") UON
84" (7'-0") UON
(SINGLE OR
GANGED,
ALL TYPES)
80" (6'-8") TO BOTTOM OF STROBE OR 6"
BELOW CEILING TO TOP OF STROBE,
WHICHEVER IS LOWER.
TOP OF CABINET
96" (8'-0") UON
DESCRIPTION
DH
FACP
NOTE: ALL DEVICES INDICATED
TO BE INSTALLED AT DIFFERENT
MOUNTING HEIGHTS AND LOCATED
WITHIN ONE STUD SPACE FROM
EACH OTHER SHALL ALIGN
VERTICALLY, ON THE SAME SIDE
OF THE STUD. WHERE WALL
MOUNTED TELEPHONES OCCUR OVER
LIGHT SWITCHES, VOLUME CONTROLS,
ETC. OFFSET ONE STUD SPACE.
FINISHED FLOOR
TYPICAL DEVICE MOUNTING HEIGHTS
MAGNETIC DOOR HOLDER
BRANCH CIRCUIT HOMERUN TO PANELBOARD
NUMBER OF ARROWS INDICATE NUMBER OF
PANEL LEGS. NUMERAL INDICATES CIRCUIT
BREAKER NUMBER.
TAMPER SWITCH
CONCEALED CONDUIT IN WALL OR CEILING
ROTATING BEACON
FLOW SWITCH
CONDUIT BELOW GRADE OR BELOW SLAB
IM
INPUT MODULE
CONDUIT CAP
FR
FIRE ALARM ADDRESSABLE RELAY
CONDUIT CONTINUATION
CONDUIT UP
CONDUIT DOWN
ALARM BELL
F
ROLL DOWN FIRE DOOR
FAAP
FIRE ALARM ANNUNCIATION PANEL
FACP
FIRE ALARM CONTROL PANEL W/ AUTONOMOUS CONTROL UNIT
FATC
FIRE ALARM TERMINAL CABINET
LOC
LOCAL OPERATOR CONSOLE
NO SCALE
NOTES:
1.
HEIGHTS SHOWN ARE TYPICAL TO CENTERLINE OF BOX
UNLESS OTHERWISE NOTED.
2.
MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL
ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE.
3.
CONTRACTOR SHALL ENSURE THAT MOUNTING HEIGHTS
COMPLY WITH CURRENT ADA REQUIREMENTS.
4.
WHEREVER DEVICES ARE INDICATED TO BE ABOVE
DOORS, DEVICE SHALL BE CENTERED BETWEEN TOP OF
DOOR TRIM AND CEILING LINE.
5.
ALL ABOVE COUNTER (DESIGNATED BY "AC") DEVICES
SHALL BE MOUNTED 6" ABOVE COUNTER TO CENTER OF
DEVICE OR A MAXIMUM OF 44" (3'-8") TO TOP OF DEVICE.
VERIFY HEIGHTS WITH ARCHITECT.
BENJAMIN TALPOS
9/11/2013 11:51:16 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
TOP OF CABINET
FIRE FIGHTERS PHONE JACK
9.
WHERE THE DRAWINGS INDICATE THAT AND EXISTING CONDUIT (BRANCH CIRCUIT
OR FEEDER) IS TO BE INTERCEPTED, FOR PURPOSES OF EXTENDING TO A NEW
LOCATION, ALWAYS REMOVE THE EXISTING CONDUCTORS AND PROVIDE NEW
CONDUCTORS BETWEEN POINTS OF CONNECTION. WHEN THIS WORK REQUIRES
REMOVING AN EXISTING WIRING DEVICE (RECEPTACLE OR SWITCH) AT A LOCATION THAT
REMAINS, PROVIDE A NEW WIRING DEVICE AND PLATE.
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
RACEWAY LEGEND
M
Architecture Engineering Planning Interiors
TV
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
FIRE SERVICE PHONE
TYPICAL 8'-0" CEILING
(E)14
GENERAL NOTES:
(E)15
1. ALL ELECTRICAL DEVICES AND LIGHT FIXTURES
SHOWN DASHED ARE TO BE DISCONNECTED AND
REMOVED. INCLUDING ALL ASSOCIATED CONDUIT AND
CONDUCTORS BACK TO THE SOURCE OR LAST DEVICE
TO REMAIN ACTIVE. MAINTAIN CONTINUITY FOR
EXISTING DEVICES TO REMAIN.
(E)29
2. EXISTING DEVICE AND LIGHT FIXTURE QUANTITIES
AND LOCATIONS WERE TAKEN FROM EXISTING
DRAWINGS AND SITE OBSERVATIONS. CONTRACTOR
SHALL FIELD VERIFY ALL DEVICES AND CIRCUITING.
(E)28
3. WHEN REMODELING WORK INTERFERES WITH
CIRCUITS THAT WOULD OTHERWISE BE UNTOUCHED,
CONTRACTOR SHALL REWORK CIRCUITS AS
REQUIRED.
(E)27
661 W Capistrano Ave
Pueblo West, CO 81007
(E)26
(E)25
(E)24
(E)23
(E)12
(E)13
(E)L
(E)K.9
C1
TK
(E)
KEYNOTE LEGEND
Q
1
EXISTING PUMP TO BE REPLACED. DISCONNECT AND
REMOVE ALL CONDUCTORS BACK TO SOURCE.
PROTECT CONDUIT FOR RE-USE.
(E)J
(E)K
R
(E)H.5
CH
(E)H
CD.2
(E)G
C9
C8
C7
(E)EE
MSB
RA
(E)
P-11 1
T
(E)CC.8
D
1 P-4
(E)
CJ
(E)
(E)
TSDP
R8
(E)
EM1
(E)
TEM2
CR2G
(E)CC
B3.1
(E)
CC5
SDP
EM2
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
P-12 1
(E)
(E)E
CR2H
(E)BB.1
CR1E
(E)BB
(E)D
CG
(E)C.4
B5.1
KEY PLAN
BC
JJJ
(E)C
(E)AA
D
(E)AA1
RB
XX
CR2F
CR1D
(E)B
B
A
E
C
1
ED0.1
DEMO CRAWL SPACE POWER
PLAN - AREA B
1/8" = 1'-0"
CR2E
BE
BENJAMIN TALPOS
(E) 11
(E) 12
(E) 13
B2
BD
VV
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
Architecture Engineering Planning Interiors
B4.9
9/11/2013 11:51:23 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
B2.1
ED0.1
(E)DD
1 P-3
Revisions
(E)
DP1
(E)F
PUEBLO COUNTY SCHOOL DISTRICT 70
(E)11
37-13102-00
09.12.2013
(E)10
DEMO ELECTRICAL PLAN, CRAWL SPACE - AREA B
C1.1
(E)21
Pueblo West High School Additions + Renovations
(E)22
GENERAL NOTES:
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10 A11
1. ALL ELECTRICAL DEVICES AND LIGHT FIXTURES
SHOWN DASHED ARE TO BE DISCONNECTED AND
REMOVED. INCLUDING ALL ASSOCIATED CONDUIT AND
CONDUCTORS BACK TO THE SOURCE OR LAST DEVICE
TO REMAIN ACTIVE. MAINTAIN CONTINUITY FOR
EXISTING DEVICES TO REMAIN.
A12
(E)1
(E)2
(E)2.1
2. EXISTING DEVICE AND LIGHT FIXTURE QUANTITIES
AND LOCATIONS WERE TAKEN FROM EXISTING
DRAWINGS AND SITE OBSERVATIONS. CONTRACTOR
SHALL FIELD VERIFY ALL DEVICES AND CIRCUITING.
(E)2.6
3. WHEN REMODELING WORK INTERFERES WITH
CIRCUITS THAT WOULD OTHERWISE BE UNTOUCHED,
CONTRACTOR SHALL REWORK CIRCUITS AS
REQUIRED.
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10 A11
A12
AJ
AJ
AI
AI
661 W Capistrano Ave
Pueblo West, CO 81007
(E)K.9
(E)J
(E)G.7
AG
AF
AE
AE
(E)G
(E)G
KEYNOTE LEGEND
1
AD
EXISTING EXTERIOR EGRESS LIGHT TO BE
RELOCATED, PROTECT DURING DEMOLITION.
AD
(E)F
(E)E.9
AC
AC
(E)
(E)E.5
AB
(E)4-AA
AB
AA
AA
(E)4-A
(E)4-B
(E)4-C
(R)
(E)4-1
(E)
(E)
(E)
(E)
(E)
(ER)
(E)
(E)
(E)
(E)
(ER)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)4-1
DH
(E)
(E)
(E)E
(E)
(E)
(E)
1
(E)
DH
(E)
DH
(E)
(E)E.5
(E)4-D
(R)
(E)
MED
(E)D
(E)C.9
(E)
DH
(E)4-2
(E)C.4
(E)C.4
(E)C
1RN
ED1.1
(E)
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
(E)B
(E)4-B
(E)4-C
(E)4-D
Architecture Engineering Planning Interiors
(E)4-A
(E)A
KEY PLAN
D
B
A
E
C
1
ED1.1
BENJAMIN TALPOS
9/11/2013 11:51:28 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
(E)4-3
1ST FLOOR DEMO POWER PLAN
- AREA A
1/8" = 1'-0"
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
AF
DEMO POWER PLAN, FIRST LEVEL - AREA A
(E)G.5
Revisions
AG
PUEBLO COUNTY SCHOOL DISTRICT 70
AH
37-13102-00
09.12.2013
AH
Pueblo West High School Additions + Renovations
(E)G.9
GENERAL NOTES:
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10 A11
1. ALL ELECTRICAL DEVICES AND LIGHT FIXTURES
SHOWN DASHED ARE TO BE DISCONNECTED AND
REMOVED. INCLUDING ALL ASSOCIATED CONDUIT AND
CONDUCTORS BACK TO THE SOURCE OR LAST DEVICE
TO REMAIN ACTIVE. MAINTAIN CONTINUITY FOR
EXISTING DEVICES TO REMAIN.
A12
(E)1
(E)2
(E)2.1
(E)2.6
2. EXISTING DEVICE AND LIGHT FIXTURE QUANTITIES
AND LOCATIONS WERE TAKEN FROM EXISTING
DRAWINGS AND SITE OBSERVATIONS. CONTRACTOR
SHALL FIELD VERIFY ALL DEVICES AND CIRCUITING.
3. WHEN REMODELING WORK INTERFERES WITH
CIRCUITS THAT WOULD OTHERWISE BE UNTOUCHED,
CONTRACTOR SHALL REWORK CIRCUITS AS
REQUIRED.
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10 A11
A12
AJ
AJ
AI
AI
661 W Capistrano Ave
Pueblo West, CO 81007
(E)K.9
(E)J
(E)G.7
(E)G.5
AE
(E)G
(E)G
KEYNOTE LEGEND
1
AD
AD
(E)F
(E)E.9
AC
AC
(E)E.5
AB
(E)4-AA
AB
AA
AA
(E)4-A
(E)4-B
(E)4-C
(E)4-D
(E)4-1
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)E.5
(E)
(E)
(E)
(E)E
(E)4-1
(ER)
(E)
(E)
1
(ER)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)D
(E)C.9
(E)
(E)4-2
(E)C.4
(E)C
2RN
ED1.5
(E)
(E)B
2RE
(E)4-A
1
ED1.5
BENJAMIN TALPOS
9/11/2013 11:51:32 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
(E)4-3
(E)A
2ND FLOOR DEMO POWER PLAN
- AREA A
1/8" = 1'-0"
(E)C.4
EXISTING EXTERIOR EGRESS LIGHT TO BE
RELOCATED, PROTECT DURING DEMOLITION.
(E)4-B
(E)
2RS
(E)4-C
(E)4-D
(E)
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
AE
Revisions
AF
Architecture Engineering Planning Interiors
AF
DEMO POWER PLAN, SECOND LEVEL - AREA A
AG
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
AG
PUEBLO COUNTY SCHOOL DISTRICT 70
AH
37-13102-00
09.12.2013
AH
Pueblo West High School Additions + Renovations
(E)G.9
GENERAL NOTES:
1. ELECTRICAL CONTRACTOR SHALL COORDINATE
EXACT LOCATION OF ALL MECHANICAL AND PLUMBING
EQUIPMENT WITH MECHANICAL AND PLUMBING
CONTRACTORS. REFER TO MECHANICAL AND PLUMBING
EQUIPMENT SCHEDULES FOR ALL MECHANICAL AND
PLUMBING EQUIPMENT ELECTRICAL CONNECTIONS.
(E)1
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10 A11
(E)2
(E)2.1
2. ALL EXPOSED CONDUIT SHALL BE ROUTED
PERPENDICULAR, PARALLEL, AND TIGHT TO COLUMNS
AND BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE
COORDINATED WITH ENGINEER AND ARCHITECT PRIOR
TO INSTALLATION. NO ADDITIONAL COST TO OWNER
WILL BE ALLOWED FOR RELOCATING CONDUIT DUE TO
THE LACK OF COORDINATION WITH ARCHITECT.
(E)2.6
3. ALL BACK BOXES SHALL BE FLUSH MOUNTED UNLESS
NOTED OTHERWISE. ALL VERTICAL SECTIONS OF
CONDUIT SHALL BE CONCEALED. CONTRACTOR SHALL
COORDINATE INSTALLATION OF CONDUIT AND BACK
BOXES IN CONCRETE, MASONRY AND GYP. WALLS.
A12
4. PROVIDE A 120V CONNECTION TO EACH CLOCK USING
3/4"C, 2#12 & 1#12 GND. FIRST FLOOR CLOCKS SHALL BE
CIRCUITED TO 1RNA1-28, AND SECOND FLOOR CLOCKS
SHALL BE CIRCUITED TO 2RNA2-24. SEE TECHNOLOGY
DRAWINGS FOR QUANTITY AND LOCATIONS.
661 W Capistrano Ave
Pueblo West, CO 81007
(E)K.9
AJ
AI
AHU
23
TO
UH
(E)J
5-1
5
AF
MWA
7
5
AE
RBW- 7
SE
5-1
(E)G
KEYNOTE LEGEND
TO
1
RBW- 11
GWH
AD
2
1
CRAC
RP
1RNA1- 31
TO
5-1
4
(E)F
(E)E.9
TO
4
AC
RBW- 5
SP
5-1
TO
CRAC
3
5-4
G
(E)4-B
G
TO
(E)4-A
(E)E.5
TO
(E)4-AA
3
5
6
7
ERW- 9
1RNA1- 33
1RNA1- 35
3
1
CONNECTION TO ELEVATOR MOTOR USING 1-1/4"C,
3#4 & 1#8 GND. PROVIDE 60A DISCONNECT WITH 60A
FUSE.
CONNECTION TO ELEVATOR CAB LIGHTS. PROVIDE
30A DISCONNECT WITH 20A FUSE.
PROVIDE DEDICATE L5-20 DUPLEX RECEPTACLE FOR
TELECOM EQUIPMENT.
CRAC UNIT POWERED THROUGH CONDENSING UNIT
ON ROOF, SEE MECHANICAL SCHEDULE FOR FEEDER
INFORMATION.
PROVIDE UNISTRUT TO MOUNT PANELS.
CONNECT TO EXISTING UH CIRCUIT.
PROVIDE CONNECTION TO NEW DDC CONTROL
PANEL.
(E)4-C
(E)4-D
AB
F
4
G
F1
AA
(E)4-1
RBW- 9
(E)E
1
2
ERW- 11
MWA- 2,4,6
6
(E)D
(E)C.9
TO
(E)4-2
(E)C
(E)
(E)C.4
EP0.1
ERW- 6
ERW
(E)
ELW
SDP3
(E)
DP2
(E)
LW
(E)
Architecture Engineering Planning Interiors
(E)
(E)
(E)A
KEY PLAN
(E)
D
B
A
E
C
1
EP0.1
BENJAMIN TALPOS
9/11/2013 11:51:36 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
(E)4-3
RBW
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
(E)B
PUEBLO COUNTY SCHOOL DISTRICT 70
(E)G.5
NEW POWER PLAN, CRAWL SPACE - AREA A
MWA- 1,3,5
NEW CRAWL SPACE POWER
PLAN - AREA A
1/8" = 1'-0"
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
G
VFD
AG
Revisions
(E)G.7
37-13102-00
09.12.2013
AH
Pueblo West High School Additions + Renovations
(E)G.9
GENERAL NOTES:
1. ELECTRICAL CONTRACTOR SHALL COORDINATE
EXACT LOCATION OF ALL MECHANICAL AND PLUMBING
EQUIPMENT WITH MECHANICAL AND PLUMBING
CONTRACTORS. REFER TO MECHANICAL AND PLUMBING
EQUIPMENT SCHEDULES FOR ALL MECHANICAL AND
PLUMBING EQUIPMENT ELECTRICAL CONNECTIONS.
2. ALL EXPOSED CONDUIT SHALL BE ROUTED
PERPENDICULAR, PARALLEL, AND TIGHT TO COLUMNS
AND BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE
COORDINATED WITH ENGINEER AND ARCHITECT PRIOR
TO INSTALLATION. NO ADDITIONAL COST TO OWNER
WILL BE ALLOWED FOR RELOCATING CONDUIT DUE TO
THE LACK OF COORDINATION WITH ARCHITECT.
(E)6
(E)7
(E)8
(E)10
(E)9
(E)21 (E)11
(E)22
(E)23
(E)12
3. ALL BACK BOXES SHALL BE FLUSH MOUNTED UNLESS
NOTED OTHERWISE. ALL VERTICAL SECTIONS OF
CONDUIT SHALL BE CONCEALED. CONTRACTOR SHALL
COORDINATE INSTALLATION OF CONDUIT AND BACK
BOXES IN CONCRETE, MASONRY AND GYP. WALLS.
(E)24
(E)J
(E)G.9
(E)G.5
KEYNOTE LEGEND
(E)G
1
EMERGENCY POWER OFF (EPO) BUTTON FOR
EMERGENCY BOILER SHUTDOWN. PROVIDE
CONNECTION TO EACH NEW BOILER CONTROL
PANEL, BOILER SHUNT TRIP BREAKER, AND DDC
PANEL.
2
EMERGENCY POWER OFF (EPO) BUTTON FOR
EMERGENCY CHILLER SHUTDOWN. PROVIDE
CONNECTION TO NEW CHILLER CONTROL PANEL,
CHILLER SHUNT TRIP BREAKER, AND DDC PANEL.
PROVIDE CONNECTION TO NEW DDC CONTROL
PANEL.
CH
2
P
16
P
15
MSB
(E)
3
E- 7
E- 6
P
P
13
P
RWA
3
TRWA
VFD
VFD
B
E- 9
VFD
4
RWA- 1,3
E- 2
P
RWA- 4,6
(E)
DP1
E- 8
VFD
(E)F
(E)E.9
11
14
P
E- 4
4
E- 3
B
P
(E)
R8
(E)
EM1
(E)
RWA- 11
E- 1
3
E
E- 5
(E)
RWA- 7
12
5
D
TEM2
1
(E)
(E)E
1
3
2
(E)
SDP
TSDP
EM2
(E)
(E)D
(E)C.9
(E)C.4
NEW POWER PLAN, CRAWL SPACE - AREA B
(E)G.7
PUEBLO COUNTY SCHOOL DISTRICT 70
(E)K.9
Pueblo West High School Additions + Renovations
661 W Capistrano Ave
Pueblo West, CO 81007
4. PROVIDE A 120V CONNECTION TO EACH CLOCK USING
3/4"C, 2#12 & 1#12 GND. FIRST FLOOR CLOCKS SHALL BE
CIRCUITED TO 1RNA1-28, AND SECOND FLOOR CLOCKS
SHALL BE CIRCUITED TO 2RNA2-24. SEE TECHNOLOGY
DRAWINGS FOR QUANTITY AND LOCATIONS.
BC
EP0.2
NEW CRAWL SPACE POWER
PLAN - AREA B
1/8" = 1'-0"
D
B
A
E
BENJAMIN TALPOS
C
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
Architecture Engineering Planning Interiors
KEY PLAN
1
Revisions
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
BB
9/11/2013 11:51:41 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
(E)B
37-13102-00
09.12.2013
EP0.2
(E)C
GENERAL NOTES:
1. ELECTRICAL CONTRACTOR SHALL COORDINATE
EXACT LOCATION OF ALL MECHANICAL AND PLUMBING
EQUIPMENT WITH MECHANICAL AND PLUMBING
CONTRACTORS. REFER TO MECHANICAL AND PLUMBING
EQUIPMENT SCHEDULES FOR ALL MECHANICAL AND
PLUMBING EQUIPMENT ELECTRICAL CONNECTIONS.
(E)1
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10 A11
(E)2
(E)2.1
2. ALL EXPOSED CONDUIT SHALL BE ROUTED
PERPENDICULAR, PARALLEL, AND TIGHT TO COLUMNS
AND BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE
COORDINATED WITH ENGINEER AND ARCHITECT PRIOR
TO INSTALLATION. NO ADDITIONAL COST TO OWNER
WILL BE ALLOWED FOR RELOCATING CONDUIT DUE TO
THE LACK OF COORDINATION WITH ARCHITECT.
(E)2.6
3. ALL BACK BOXES SHALL BE FLUSH MOUNTED UNLESS
NOTED OTHERWISE. ALL VERTICAL SECTIONS OF
CONDUIT SHALL BE CONCEALED. CONTRACTOR SHALL
COORDINATE INSTALLATION OF CONDUIT AND BACK
BOXES IN CONCRETE, MASONRY AND GYP. WALLS.
A12
4. PROVIDE A 120V CONNECTION TO EACH CLOCK USING
3/4"C, 2#12 & 1#12 GND. FIRST FLOOR CLOCKS SHALL BE
CIRCUITED TO 1RNA1-28, AND SECOND FLOOR CLOCKS
SHALL BE CIRCUITED TO 2RNA2-24. SEE TECHNOLOGY
DRAWINGS FOR QUANTITY AND LOCATIONS.
661 W Capistrano Ave
Pueblo West, CO 81007
(E)K.9
AJ
AI
17
17
9
15
7
7
5
22
1RNA1- 18,20,22
TV
15
19
22
20
20
18
AC
4
5
9
CLASSROOM
A115
1RNA1- 10
13
SCIENCE
CLASSROOM
A108
1
19
11
3
CLASSROOM
A103
13
AC
1RNA1- 16
(E)J
18
1RNA2- 13,15,17
11
27
3
1RNA2- 7,9,11
1RNA2- 19,21,23
1RNA1- 24
23
1RNA2- 14
1
1
27
29
25
G
21
(E)G.7
27
G
4
TV
TV
G
G
AG
27
1
27
1RNA2- 16 CORRIDOR 1RNA1- 12
1RNA2- 1,3,5
2
29
A104
25
2
2
4
G
29
G
29
25
1RNA1- 2
5
25
29
G
1RNA2- 25,27,29
31
J
TELECOMM
A107
1RNA2
1RNA1- 6
1RNA2- 20
G
TV
STORAGE
A106
3
AC
3
AC
3
AD
4
1RNA2- 18
4
21
AC
21
AC
21
(E)G
1
21
AC
21
AC
REF. 19
+48"
2
GIRLS
A111
13
13
15
2
BOYS
A112
1RNA1- 14
15
1
11
11
(E)F
(E)E.9
2
CLASSROOM
A100
17
1RNA2- 8,10,12
12
G
3
AC
3
AC
5
9
CLASSROOM
A110
1RNA1- 13,15,17
(E)
9
(E)4-B
10
(E)4-C
MED
(E)E.5
(E)4-D4
12
8
8
10
7
7
TV
(E)4-1
1RNA1- 4
1
(E)E
1
1
1
CORRIDOR
A113
(E)D
(E)C.9
(E)4-2
(E)C.4
(E)C
1RN
EP1.1
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
(E)B
Architecture Engineering Planning Interiors
(E)A
KEY PLAN
D
B
A
E
C
1
EP1.1
BENJAMIN TALPOS
9/11/2013 11:51:47 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
(E)4-3
1ST FLOOR NEW POWER PLAN AREA A
1/8" = 1'-0"
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
(E)
Revisions
AA
(E)4-A
17
G
(E)4-AA
AB
6
DEDICATED RECEPTACLE FOR SMARTBOARD.
COORDINATE EXACT LOCATION AND MOUNTING
HEIGHT WITH EQUIPMENT PRIOR TO ROUGH-IN.
RECEPTACLES MOUNTED IN CASEWORK,
COORDINATE EXACT LOCATION AND MOUNTING
HEIGHT.
ELECTRICAL CONNECTION TO FUME HOOD.
OUTLET FOR TV, MOUNT 2'-0" BELOW CEILING.
PROVIDE CONNECTION TO MECHANICAL LOW
VOLTAGE POWER SUPPLY FOR THIS FLOOR.
COORDINATE EXACT LOCATION AND REQUIREMENTS
WITH MECHANICAL.
G
6
3
4
5
1RNA1- 7,9,11
1RNA2- 2,4,6
AC
KEYNOTE LEGEND
SCIENCE PREP
A108A
37-13102-00
09.12.2013
TV
1
4
CORRIDOR
A109
23
J
3
G
35
33
1RNA1- 8
21
AC
CORRIDOR
A101
23
3
23
5
35
4
23
23
G
1RNA1- 26
1RNA1
1
1RNA1- 25,27,29
1RNA1- 19,21,23
1RNA2- 31,33,35
33
25
2
G
JANITOR
A105
29
5
G
CLASSROOM
A114
5
G
AE
G
ELEC
A102
25
2
G
31
2
5
1RNA1- 1,3,5
G
AF
(E)G.5
G
G
NEW POWER PLAN, FIRST LEVEL - AREA A
1
PUEBLO COUNTY SCHOOL DISTRICT 70
23
21
AH
Pueblo West High School Additions + Renovations
(E)G.9
GENERAL NOTES:
1. ELECTRICAL CONTRACTOR SHALL COORDINATE
EXACT LOCATION OF ALL MECHANICAL AND PLUMBING
EQUIPMENT WITH MECHANICAL AND PLUMBING
CONTRACTORS. REFER TO MECHANICAL AND PLUMBING
EQUIPMENT SCHEDULES FOR ALL MECHANICAL AND
PLUMBING EQUIPMENT ELECTRICAL CONNECTIONS.
(E)1
A4
A5
A6
A7
A8
A9
A10 A11
3. ALL BACK BOXES SHALL BE FLUSH MOUNTED UNLESS
NOTED OTHERWISE. ALL VERTICAL SECTIONS OF
CONDUIT SHALL BE CONCEALED. CONTRACTOR SHALL
COORDINATE INSTALLATION OF CONDUIT AND BACK
BOXES IN CONCRETE, MASONRY AND GYP. WALLS.
A12
4. PROVIDE A 120V CONNECTION TO EACH CLOCK USING
3/4"C, 2#12 & 1#12 GND. FIRST FLOOR CLOCKS SHALL BE
CIRCUITED TO 1RNA1-28, AND SECOND FLOOR CLOCKS
SHALL BE CIRCUITED TO 2RNA2-24. SEE TECHNOLOGY
DRAWINGS FOR QUANTITY AND LOCATIONS.
661 W Capistrano Ave
Pueblo West, CO 81007
(E)K.9
AJ
AI
9
9
7
17
29
29
7
5
17
3
20
15
19
3
21
2RNA3- 7,9,11
13
CLASSROOM
A203
15
1
15
14
22
12
CLASSROOM
A209
22
TV STUDIO
A208
1
23
15
20
9
21
TV CLASSROOM
A207
14
3
3
1
3
16
3
16
12
10
24
2
AH
1
23
27
3
13
1
24
2RNA1- 20,22,24
7
2RNA3- 13,15,17
2
17
16
2RNA1- 2
TV
2RNA1- 35
2RNA2- 19,21,23
2RNA1- 8,10,12
1
17
(E)G.9
10
27
TV
2RNA3- 1,3,5
(E)J
25
2RNA2- 7,9,11
13
25
2RNA2- 1,3,5
(E)G.7
1
2
2RNA1- 4
8
8
TV
AG
23
23
21
21
CORRIDOR
A206
19
2RNA2- 6
25
25
27
27
2RNA2- 25,27,29
6
2RNA2- 13,15,17
2RNA1- 17,19,21
2RNA2- 8
21
(E)G.5
2RNA1- 33
4
19
25
6
6
19
2RNA2- 12
6
2RNA3- 19,21,23
2RNA3- 25,27,29
29
JANITOR
A204
2RNA1
2RNA2
AE
21
G
G
J
AF
19
TELECOMM
A210
ELEC
A202
2RNA3
29
CLASSROOM
A212
31
17
2RNA2- 2,4
25
31
17
2
27
2RNA3- 14
2RNA3- 18
TV
CORRIDOR
A201
G
29
27
4
STORAGE
A205
2
4
AC
4
AC
G
1
CORRIDOR
A211
2
(E)G
1
KEYNOTE LEGEND
1
2RNA1- 15,29,31
15
15
TV
AD
TV
TV
4
4
1
2
3
2
2RNA1- 7,9,11
2
GIRLS
A215
BOYS
A214
2RNA1- 6
2RNA1- 13
11
4
2
1
2RNA3- 2,4,6
(E)F
(E)E.9
11
AC
DEDICATED RECEPTACLE FOR SMARTBOARD.
COORDINATE EXACT LOCATION AND MOUNTING
HEIGHT WITH EQUIPMENT PRIOR TO ROUGH-IN.
OUTLET FOR TV, MOUNT 2'-0" BELOW CEILING.
RECTRACTABLE OUTLET CORD REEL, COORDINATE
EXACT LOCATION WITH OWNER PRIOR TO ROUGH-IN.
PROVIDE CONNECTION TO MECHANICAL LOW
VOLTAGE POWER SUPPLY FOR THIS FLOOR.
COORDINATE EXACT LOCATION AND REQUIREMENTS
WITH MECHANICAL.
2
2RNA3- 8,10,12
6
G
4
G
CLASSROOM
A200
4
AC
4
AC
6
(E)4-A
(E)4-B
8
AA
10
10
(E)E.5
7
(E)4-C
(E)4-D
7 2RNA1- 1,3,5
12
8
9
G
5
5
(E)4-1
2RNA2- 10
3
1
1
(E)E
2
2
3
2
2
CORRIDOR
A216
(E)D
(E)C.9
(E)4-2
(E)C.4
(E)C
2RN
EP1.5
(E)
(E)B
(E)
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
2RE
(E)
2RS
Architecture Engineering Planning Interiors
(E)A
KEY PLAN
D
B
A
E
C
1
EP1.5
BENJAMIN TALPOS
9/11/2013 11:51:54 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
(E)4-3
2ND FLOOR NEW POWER PLAN AREA A
1/8" = 1'-0"
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
(E)4-AA
AB
CLASSROOM
A213
9
12
NEW POWER PLAN,SECOND LEVEL - AREA A
23
23
2RNA1- 23,25,27
Revisions
13
16
2RNA1- 14,16,18
5
11
18
11
19
5
11
18
5
PUEBLO COUNTY SCHOOL DISTRICT 70
A3
(E)2.6
Pueblo West High School Additions + Renovations
A2
(E)2.1
37-13102-00
09.12.2013
A1
(E)2
2. ALL EXPOSED CONDUIT SHALL BE ROUTED
PERPENDICULAR, PARALLEL, AND TIGHT TO COLUMNS
AND BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE
COORDINATED WITH ENGINEER AND ARCHITECT PRIOR
TO INSTALLATION. NO ADDITIONAL COST TO OWNER
WILL BE ALLOWED FOR RELOCATING CONDUIT DUE TO
THE LACK OF COORDINATION WITH ARCHITECT.
GENERAL NOTES:
1. ELECTRICAL CONTRACTOR SHALL COORDINATE
EXACT LOCATION OF ALL MECHANICAL AND PLUMBING
EQUIPMENT WITH MECHANICAL AND PLUMBING
CONTRACTORS. REFER TO MECHANICAL AND PLUMBING
EQUIPMENT SCHEDULES FOR ALL MECHANICAL AND
PLUMBING EQUIPMENT ELECTRICAL CONNECTIONS.
(E)1
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10 A11
(E)2
(E)2.1
2. ALL EXPOSED CONDUIT SHALL BE ROUTED
PERPENDICULAR, PARALLEL, AND TIGHT TO COLUMNS
AND BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE
COORDINATED WITH ENGINEER AND ARCHITECT PRIOR
TO INSTALLATION. NO ADDITIONAL COST TO OWNER
WILL BE ALLOWED FOR RELOCATING CONDUIT DUE TO
THE LACK OF COORDINATION WITH ARCHITECT.
(E)2.6
3. ALL BACK BOXES SHALL BE FLUSH MOUNTED UNLESS
NOTED OTHERWISE. ALL VERTICAL SECTIONS OF
CONDUIT SHALL BE CONCEALED. CONTRACTOR SHALL
COORDINATE INSTALLATION OF CONDUIT AND BACK
BOXES IN CONCRETE, MASONRY AND GYP. WALLS.
A12
4. PROVIDE A 120V CONNECTION TO EACH CLOCK USING
3/4"C, 2#12 & 1#12 GND. FIRST FLOOR CLOCKS SHALL BE
CIRCUITED TO 1RNA1-28, AND SECOND FLOOR CLOCKS
SHALL BE CIRCUITED TO 2RNA2-24. SEE TECHNOLOGY
DRAWINGS FOR QUANTITY AND LOCATIONS.
661 W Capistrano Ave
Pueblo West, CO 81007
(E)K.9
AJ
AI
(E)J
(E)G.7
EF
23-4
(E)G.5
AF
2RNA1- 28
WP
1
TO
IF
AE
WP
MWA- 14,16,18
23-1
WP
WP
EF
MWA- 7,9,11
POWER NEW ROOF PLAN - AREA A
23-3
2
(E)G
KEYNOTE LEGEND
WP
TO
1
2RNA1- 26
2
AD
PROVIDE CONNECTION TO 120V MOTORIZED
DAMPER.
INTERLOCK EXFAUST FAN WITH FUME HOOD.
2RNA1- 34,36
(E)F
(E)E.9
2RNA1- 30,32
AC
WP
WP
CU
5-1
WP
EF
(E)4-AA
(E)4-A
(E)4-B
CU
MWA- 13,15,17
23-1
5-4
WP
(E)E.5
(E)4-C
(E)4-D
AB
AA
(E)4-1
(E)E
(E)D
(E)C.9
(E)4-2
(E)C.4
37-13102-00
09.12.2013
EP2.1
(E)C
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
(E)B
Architecture Engineering Planning Interiors
(E)A
KEY PLAN
D
B
A
E
C
1
EP2.1
BENJAMIN TALPOS
9/11/2013 11:51:58 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
(E)4-3
ROOF NEW POWER PLAN - AREA
A
1/8" = 1'-0"
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
AG
PUEBLO COUNTY SCHOOL DISTRICT 70
AH
Revisions
Pueblo West High School Additions + Renovations
(E)G.9
GENERAL NOTES:
1. REFER TO E6.2 FOR LIGHT FIXTURE SCHEDULE.
2. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS
FOR ALL FIXTURE LOCATIONS WITHIN A CEILING OR
CEILING GRID. FOR AREAS WITHOUT CEILINGS, FIXTURE
LOCATIONS ARE DIAGRAMMATIC. THE INTENT IS TO ALIGN,
CENTER, OR SPACE FIXTURES BETWEEN ARCHITECTURAL
AND STRUCTURAL ELEMENTS.
(E)1
A2
A3
A4
A5
A6
A7
A8
A9
A10 A11
(E)2.1
(E)2.6
A12
4. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXACT
FIXTURE LENGTHS FOR ALL CONTINUOUS LINEAR
FLUORESCENT FIXTURES. FOR COVES, PROVIDE
CONTINUOUS ILLUMINATION WITH 6" MAXIMUM DISTANCE
BETWEEN END OF FIXTURE AND WALL.
(E)K.9
5. ELECTRICAL CONTRACTOR TO COORDINATE WITH
MECHANICAL CONTRACTOR FOR PLACEMENT OF FIXTURES
WITHIN MECHANICAL ROOMS.
AJ
6. PROVIDE QUARTZ RE-STRIKE WITH TIME DELAY FOR
ALL METAL HALIDE FIXTURES ON EMERGENCY OR
STANDBY POWER.
AI
7. PROVIDE AN UN-SWITCHED, AND NOT RELAY
CONTROLLED, HOT CONDUCTOR TO EACH EXIT SIGN AND
EMERGENCY BATTERY PACK.
8. COORDINATE EXACT LOCATIONS AND QUANTITIES OF
OCCUPANCY SENSORS WITH MANUFACTURERS
RECOMMENDATIONS FOR COVERAGE AND REQUIRED
DISTANCES FROM HVAC DIFFUSERS.
661 W Capistrano Ave
Pueblo West, CO 81007
A1
(E)2
3. ALL SURFACE MOUNTED CONDUIT SHALL BE ROUTED
PERPENDICULAR AND PARALLEL TO BEAMS AND COLUMNS.
ALL CONDUIT ROUTING SHALL BE COORDINATED WITH THE
ARCHITECT PRIOR TO INSTALLATION AND INSTALLED IN A
NEAT AND CONSISTENT MANNER. ALL SURFACE MOUNTED
CONDUIT WHERE EXPOSED TO PUBLIC AREAS SHALL BE
PAINTED. PAINT COLOR TO BE DETERMINED BY THE
ARCHITECT.
(E)J
(E)G.7
F
(E)G.5
AF
AE
F
(E)G
KEYNOTE LEGEND
1
2
AD
F
F
F
CONNECT TO EXISTING LIGHTING CIRCUIT.
MATCH EXISTING LCP AND CONNECT BACK TO
EXISTING LIGHTING CONTROLS. SEE LIGHTING
CONTROL DIAGRAM ON SHEET E6.2 FOR ADDITIONAL
INFORMATION.
F
F
(E)F
(E)E.9
AC
F
F
IT ROOM
A002
(E)E.5
F
F
(E)4-B
(E)4-C
(E)4-D
AA
(E)4-1
(E)E
(E)
1
(E)D
(E)C.9
(E)
(E)4-2
ELW- 4
3
1
(E)C.4
LW- 1
(E)C
(E)
(E)
(E)
(E)
(E)
EL0.1
(E)
(E)
(E)
(E)B
2
(E)
(E)
(E)
(E)
(E)
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
(E)
LCPA1
(E)
(E)
3
(E)
(E)
(E)
(E)
(E)
(E)A
KEY PLAN
D
B
A
E
C
1
BENJAMIN TALPOS
EL0.1
NEW CRAWL SPACE LIGHTING
PLAN - AREA A
1/8" = 1'-0"
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
(E)
Architecture Engineering Planning Interiors
(E)
9/11/2013 11:52:02 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
(E)4-3
(E)
Revisions
(E)4-A
37-13102-00
09.12.2013
(E)4-AA
AB
NEW LIGHTING PLAN, CRAWL SPACE - AREA A
AG
PUEBLO COUNTY SCHOOL DISTRICT 70
AH
Pueblo West High School Additions + Renovations
(E)G.9
F
GENERAL NOTES:
1. REFER TO E6.2 FOR LIGHT FIXTURE SCHEDULE.
2. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS
FOR ALL FIXTURE LOCATIONS WITHIN A CEILING OR
CEILING GRID. FOR AREAS WITHOUT CEILINGS, FIXTURE
LOCATIONS ARE DIAGRAMMATIC. THE INTENT IS TO ALIGN,
CENTER, OR SPACE FIXTURES BETWEEN ARCHITECTURAL
AND STRUCTURAL ELEMENTS.
(E)1
A2
A3
A4
A5
A6
A7
A8
A9
A10 A11
(E)2.6
A12
4. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXACT
FIXTURE LENGTHS FOR ALL CONTINUOUS LINEAR
FLUORESCENT FIXTURES. FOR COVES, PROVIDE
CONTINUOUS ILLUMINATION WITH 6" MAXIMUM DISTANCE
BETWEEN END OF FIXTURE AND WALL.
(E)K.9
1
N
(E)2.1
5. ELECTRICAL CONTRACTOR TO COORDINATE WITH
MECHANICAL CONTRACTOR FOR PLACEMENT OF FIXTURES
WITHIN MECHANICAL ROOMS.
N
AJ
AI
6. PROVIDE QUARTZ RE-STRIKE WITH TIME DELAY FOR
ALL METAL HALIDE FIXTURES ON EMERGENCY OR
STANDBY POWER.
a,b,c
3
7. PROVIDE AN UN-SWITCHED, AND NOT RELAY
CONTROLLED, HOT CONDUCTOR TO EACH EXIT SIGN AND
EMERGENCY BATTERY PACK.
a,b
a,b
C
C
a,b
C
a,b
a,b
C
C
C
CLASSROOM
A115
a,b
8. COORDINATE EXACT LOCATIONS AND QUANTITIES OF
OCCUPANCY SENSORS WITH MANUFACTURERS
RECOMMENDATIONS FOR COVERAGE AND REQUIRED
DISTANCES FROM HVAC DIFFUSERS.
C
C
a,b
a,b
CLASSROOM
A103
a,b
C
a,b
C
a,b
C
a,b
C
SCIENCE
CLASSROOM
A108
a,c
C
661 W Capistrano Ave
Pueblo West, CO 81007
A1
(E)2
3. ALL SURFACE MOUNTED CONDUIT SHALL BE ROUTED
PERPENDICULAR AND PARALLEL TO BEAMS AND COLUMNS.
ALL CONDUIT ROUTING SHALL BE COORDINATED WITH THE
ARCHITECT PRIOR TO INSTALLATION AND INSTALLED IN A
NEAT AND CONSISTENT MANNER. ALL SURFACE MOUNTED
CONDUIT WHERE EXPOSED TO PUBLIC AREAS SHALL BE
PAINTED. PAINT COLOR TO BE DETERMINED BY THE
ARCHITECT.
(E)J
E
1
N
a,b,c
3
a,b,c
a,b,c
AG
a,b
C
a,b
a,b
a,b
C
C
C
a,b
a,b
N
A
A
a,b
(E)G.7
A
A
NL
NL
A
C
NL
CORRIDOR
A104
(E)G.5
AF
F
a,b
a,b
C
1
F
C
a,b
D
AE
ELEC
A102
A
JANITOR
A105
F
TELECOMM
A107
E
a,c
a,c
C
A
3
a,b,c
J
J
E
J
J
C
SCIENCE PREP
A108A
D1
D1
D1
E
1
J
A
a,b,c
D
AD
J
J
J
J
J
E
E
a,c
a,c
C
C
D
J
A
a,b
A
NL
STORAGE
A106
CLASSROOM
A110
E
J
(E)4-A
E
C
(E)4-B
a,b,c
ELW- 1
AB
TO RELOCATED
WALL PACK ABOVE
(E)4-1
(E)
(E)
(E)
E
a,b
(E)4-C
E
E
ELW- 3
1
C
a,b
C
(E)E.5
(E)4-D
E
E
E
a,b,c
NL
NL
E
LV
AA
LW- 13
NL
J
J
LV
(E)4-AA
a,b
C
C
(E)F
(E)E.9
1
a,b
a,b
C
J
E
J
LW- 11
REF.
PROVIDE WATTSTOPPER ELCU, OR APPROVED
EQUAL, FOR EACH SWITCH LEG.
NL
NL
AC
KEYNOTE LEGEND
1
A
E
N
(E)G
LW- 9
(E)
(E)
(E)
(E)
(E)E
(E)
(E)
(RE)
(E)
(E)
1
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)D
(E)C.9
LW- 15
(E)4-2
(E)C.4
EL1.1
(E)C
Architecture Engineering Planning Interiors
(E)A
(E)
KEY PLAN
D
B
A
E
C
1
EL1.1
BENJAMIN TALPOS
9/11/2013 11:52:08 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
(E)4-3
1ST FLOOR NEW LIGHTING PLAN
- AREA A
1/8" = 1'-0"
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
(E)B
PUEBLO COUNTY SCHOOL DISTRICT 70
C
C
NEW LIGHTING PLAN, FIRST LEVEL - AREA A
a,b
C
C
C
3
a,b
a,b
C
Revisions
C
a,c
37-13102-00
09.12.2013
C
a,b
AH
Pueblo West High School Additions + Renovations
(E)G.9
1
GENERAL NOTES:
1. REFER TO E6.2 FOR LIGHT FIXTURE SCHEDULE.
2. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS
FOR ALL FIXTURE LOCATIONS WITHIN A CEILING OR
CEILING GRID. FOR AREAS WITHOUT CEILINGS, FIXTURE
LOCATIONS ARE DIAGRAMMATIC. THE INTENT IS TO ALIGN,
CENTER, OR SPACE FIXTURES BETWEEN ARCHITECTURAL
AND STRUCTURAL ELEMENTS.
(E)1
A7
A8
A9
A10 A11
A12
4. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXACT
FIXTURE LENGTHS FOR ALL CONTINUOUS LINEAR
FLUORESCENT FIXTURES. FOR COVES, PROVIDE
CONTINUOUS ILLUMINATION WITH 6" MAXIMUM DISTANCE
BETWEEN END OF FIXTURE AND WALL.
(E)K.9
5. ELECTRICAL CONTRACTOR TO COORDINATE WITH
MECHANICAL CONTRACTOR FOR PLACEMENT OF FIXTURES
WITHIN MECHANICAL ROOMS.
AJ
AI
D1D
C
C
C
1
D1D
6. PROVIDE QUARTZ RE-STRIKE WITH TIME DELAY FOR
ALL METAL HALIDE FIXTURES ON EMERGENCY OR
STANDBY POWER.
D1D
7. PROVIDE AN UN-SWITCHED, AND NOT RELAY
CONTROLLED, HOT CONDUCTOR TO EACH EXIT SIGN AND
EMERGENCY BATTERY PACK.
C
C
J
J
C
C
C
8. COORDINATE EXACT LOCATIONS AND QUANTITIES OF
OCCUPANCY SENSORS WITH MANUFACTURERS
RECOMMENDATIONS FOR COVERAGE AND REQUIRED
DISTANCES FROM HVAC DIFFUSERS.
1
a,c
a,b
a,b
2RNA2- 18,20,22
a,b
J
a,b
TV CLASSROOM
A207
D1D
C1
C
C
C
2
C
a,b
a,c
2RNA2- 14,16
2
E
a,b,c
D1D
D1D
2
(E)G.9
C
C
C
a,b
a,c
a,b
1
LW- 16
a,b
(E)J
J
1
a,b
a,b
CLASSROOM
A209
TV STUDIO
A208
J
a,b
a,b
D1D
D1D
CLASSROOM
A203
AH
a,b
1
2
E
a,b,c
(E)G.7
a,b,c
A
A
A
a,b
a,b
C
A
A
NL
NL
a,b
C
NL
CORRIDOR
A206
a,b
C
(E)G.5
CLASSROOM
A212
JANITOR
A204
AF
F
a,b
a,b
C
F
F
a,b
C
D
AE
LW- 16
ELEC
A202
A
TELECOMM
A210
J
a,c
C
J
CORRIDOR
A201
2
E
J
J
a,c
D
J
C
J
D
(E)4-A
A
E
J
E
J
2
(E)4-C
E
E
E
a,b
E
E
(E)
(E)
(E)
C
a,b
ELW- 11
(E)
(E)E.5
LW- 18
(E)4-D C
a,b
C
E
NL
LV
TO EXTERIOR LTG
CIRCUIT BELOW
C
a,b
LV
(E)4-1
(E)F
(E)E.9
CLASSROOM
A213
J
NL
AA
C
a,c
NL
C
a,b,c
PROVIDE 30A, 120V CONNECTION TO OWNER
PROVIDED LIGHT USE 3/4"C, 2#10 & 1#10 GND.
COORDINATE EXACT REQUIREMENTS WITH OWNER
EQUIPMENT.
PROVIDE WATTSTOPPER ELCU, OR APPROVED
EQUAL, FOR EACH SWITCH LEG.
NL
E
(E)4-B
ELW- 5
C
a,c
NL
2
(E)4-AA
BOYS
A214
J
J
AB
KEYNOTE LEGEND
2
E
A
a,b
(E)G
a,b,c
E
GIRLS
NL A215
AC
C
C
J
STORAGE
A205
J
J
a,b
a,c
1
E
J
E
a,c
C
CORRIDOR
A211
A
A
C
C
2
a,b,c
AD
a,c
a,b
A
E
C
C
J
E
a,c
C
(E)
(E)
LW- 14
a,b,c
(E)
(E)
(E)
(E)E
(E)
(E)
CORRIDOR
A216
(RE)
(E)
2
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)D
(E)C.9
(E)4-2
(E)C.4
EL1.5
(E)C
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
(E)B
Architecture Engineering Planning Interiors
(E)A
KEY PLAN
D
B
A
E
C
1
BENJAMIN TALPOS
9/11/2013 11:52:15 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
(E)4-3
EL1.5
NEW LIGHTING PLAN, SECOND LEVEL - AREA A
AG
PUEBLO COUNTY SCHOOL DISTRICT 70
A6
2ND FLOOR NEW LIGHTING
PLAN - AREA A
1/8" = 1'-0"
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
A5
Pueblo West High School Additions + Renovations
A4
Revisions
A3
(E)2.6
37-13102-00
09.12.2013
A2
(E)2.1
661 W Capistrano Ave
Pueblo West, CO 81007
A1
(E)2
3. ALL SURFACE MOUNTED CONDUIT SHALL BE ROUTED
PERPENDICULAR AND PARALLEL TO BEAMS AND COLUMNS.
ALL CONDUIT ROUTING SHALL BE COORDINATED WITH THE
ARCHITECT PRIOR TO INSTALLATION AND INSTALLED IN A
NEAT AND CONSISTENT MANNER. ALL SURFACE MOUNTED
CONDUIT WHERE EXPOSED TO PUBLIC AREAS SHALL BE
PAINTED. PAINT COLOR TO BE DETERMINED BY THE
ARCHITECT.
GENERAL NOTES:
1. THE FIRE ALARM SYSTEM INDICATED ON THESE
DRAWINGS IS A DEFERRED APPROVAL ITEM, SHALL BE
USED FOR BIDDING PURPOSES ONLY, AND IS NOT FOR
CONSTRUCTION . THE CONTRACTOR SHALL SUBMIT FIRE
ALARM SYSTEM SHOP DRAWINGS, INDICATING ALL
DEVICES, CONDUITS AND CONDUCTORS TO THE FIRE
MARSHAL OR AHJ FOR APPROVAL PRIOR TO INSTALLATION.
SYSTEM SHALL MEET SPECIFICATION REQUIREMENTS.
(E)1
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10 A11
(E)2
(E)2.1
2. CONNECT ALL ELEVATOR LOBBY, ELEVATOR MACHINE
ROOM, TOP OF SHAFT AND ELEVATOR PIT SMOKE/HEAT
DETECTORS TO ELEVATOR CONTROLLER FOR ELEVATOR
RECALL. PROVIDE SHUNT TRIP DEVICE TO DISCONNECT
ALL ELEVATOR CONTROLLERS. VERIFY SHUNT TRIP
LOCATION REQUIREMENTS WITH AHJ. PROVIDE A HEAT
DETECTOR AT THE TOP OF ELEVATOR SHAFT AND WITHIN
TWO FEET OF EACH SPRINKLER HEAD IN ALL ELEVATOR
MACHINE ROOMS. ACTIVATION OF HEAT DETECTOR TO
INITIATE SHUNT-TRIP.
(E)2.6
A12
2
6. CONTRACTOR SHALL COORDINATE EXACT QUANTITY
AND LOCATIONS OF ALL FIRE SPRINKLER SYSTEM TAMPER
AND FLOW SWITCHES WITH CONSTRUCTION MANAGER
AND FIRE PROTECTION. CONNECT ALL TAMPER AND FLOW
SWITCHES TO FIRE ALARM SYSTEM.
2
1
7. CONTRACTOR SHALL COORDINATE EXACT LOCATION
AND QUANTITY OF ALL DUCT TYPE SMOKE DETECTORS
WITH MECHANICAL CONTRACTOR. ELECTRICAL
CONTRACTOR SHALL HARD WIRE TO RELAY STARTER.
(E)J
(E)G.9
8. PROVIDE (1) DUCT TYPE SMOKE DETECTORS FOR EACH
FAN COIL UNIT, AIR HANDLING UNIT, SUPPLY FAN, AND HEAT
PUMP OF 2,000 CFM AND GREATER. PROVIDE (2) DUCT
TYPE SMOKE DETECTORS FOR EACH FAN COIL UNIT, AIR
HANDLING UNIT, HEAT PUMP AND SUPPLY FAN OF 15,000
CFM AND GREATER.
AH
(E)G.7
9. PROVIDE CONNECTION OF FA SYSTEMS TO ALL
MAGNETIC DOOR HOLD-OPEN DEVICES TO
AUTOMATICALLY CLOSE DOORS (INCLUDING OVERHEAD
STORAGE DOORS) DURING ALARM CONDITIONS.
AG
10. DEVICES INDICATED ON FIRE ALARM ONE-LINE ARE
FOR REFERENCE ONLY. REFER TO PLAN DRAWINGS AND
SPECIFICATIONS FOR QUANTITIES. REFER TO
ARCHITECTURAL DOOR SCHEDULE FOR MAGNETIC DOOR
HOLDER AND BLOW OPEN DOOR REQUIREMENTS.
(E)G.5
AF
11. PROVIDE DUCT DETECTOR AND FIRE ALARM RELAY
MODULE FOR EVERY FIRE-SMOKE DAMPER. LOCATE DUCT
DETECTOR WITHIN FIVE FEET OF FIRE-SMOKE DAMPER.
PROVIDE FIRE ALARM RELAY MODULE AT EACH FIRESMOKE DAMPER FOR DAMPER POSITION INDICATION.
AE
12. ALL VISUAL DEVICES SHALL BE SYNCHRONIZED.
13. PROVIDE FIRE ALARM RELAY MODULE FOR ALL CARD
READERS.
15. COORDINATE ALL HEAT AND SMOKE DETECTORS, IN
AREAS WITH EXPOSED CEILINGS, WITH ALL BEAM
POCKETS. PROVIDE ADDITIONAL DEVICES AS REQUIRED.
(E)G
AD
(E)F
(E)E.9
AC
FACP
(E)E.5
(E)4-A
(E)4-B
(E)4-C
KEYNOTE LEGEND
(E)4-D
1
AB
2
AA
(E)4-1
PROVIDE CONNECTION TO MECHANICAL EQUIPMENT
SHUT-DOWN.
PROVIDE ZERO VELOCITY, IN-DUCT, DUCT DETECTOR
AND CONNECT TO FIRE/SMOKE DAMPER.
(E)E
(E)D
(E)C.9
(E)4-2
(E)C.4
EF0.1
(E)C
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
(E)B
Architecture Engineering Planning Interiors
(E)A
KEY PLAN
D
B
A
E
C
1
EF0.1
BENJAMIN TALPOS
9/11/2013 11:52:18 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
(E)4-3
NEW CRAWL SPACE FIRE
ALARM PLAN - AREA A
1/8" = 1'-0"
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
(E)4-AA
NEW FIRE ALARM PLAN, CRAWL SPACE - AREA A
2
PUEBLO COUNTY SCHOOL DISTRICT 70
5. ALL BACK BOXES SHALL BE FLUSH MOUNTED UNLESS
OTHERWISE NOTED. CONTRACTOR SHALL COORDINATE
INSTALLATION OF CONDUIT AND BACK BOXES IN POURED
CONCRETE, PRE-CAST CONCRETE, MASONRY AND GYP.
WALLS.
Pueblo West High School Additions + Renovations
AI
Revisions
AJ
37-13102-00
09.12.2013
4. ALL EXPOSED CONDUIT SHALL BE ROUTED
PERPENDICULAR AND PARALLEL TO COLUMNS AND
BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE
COORDINATED WITH THE ARCHITECT PRIOR TO
INSTALLATION. NO ADDITIONAL COST TO THE OWNER WILL
BE ALLOWED FOR RELOCATING CONDUIT DUE TO LACK OF
COORDINATION WITH THE ARCHITECT.
(E)K.9
661 W Capistrano Ave
Pueblo West, CO 81007
3. PROVIDE #18 AWG MINIMUM WIRING FOR ALL SIGNAL
AND INITIATION DEVICES.
GENERAL NOTES:
1. THE FIRE ALARM SYSTEM INDICATED ON THESE
DRAWINGS IS A DEFERRED APPROVAL ITEM, SHALL BE
USED FOR BIDDING PURPOSES ONLY, AND IS NOT FOR
CONSTRUCTION . THE CONTRACTOR SHALL SUBMIT FIRE
ALARM SYSTEM SHOP DRAWINGS, INDICATING ALL
DEVICES, CONDUITS AND CONDUCTORS TO THE FIRE
MARSHAL OR AHJ FOR APPROVAL PRIOR TO INSTALLATION.
SYSTEM SHALL MEET SPECIFICATION REQUIREMENTS.
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10 A11
2. CONNECT ALL ELEVATOR LOBBY, ELEVATOR MACHINE
ROOM, TOP OF SHAFT AND ELEVATOR PIT SMOKE/HEAT
DETECTORS TO ELEVATOR CONTROLLER FOR ELEVATOR
RECALL. PROVIDE SHUNT TRIP DEVICE TO DISCONNECT
ALL ELEVATOR CONTROLLERS. VERIFY SHUNT TRIP
LOCATION REQUIREMENTS WITH AHJ. PROVIDE A HEAT
DETECTOR AT THE TOP OF ELEVATOR SHAFT AND WITHIN
TWO FEET OF EACH SPRINKLER HEAD IN ALL ELEVATOR
MACHINE ROOMS. ACTIVATION OF HEAT DETECTOR TO
INITIATE SHUNT-TRIP.
A12
6. CONTRACTOR SHALL COORDINATE EXACT QUANTITY
AND LOCATIONS OF ALL FIRE SPRINKLER SYSTEM TAMPER
AND FLOW SWITCHES WITH CONSTRUCTION MANAGER
AND FIRE PROTECTION. CONNECT ALL TAMPER AND FLOW
SWITCHES TO FIRE ALARM SYSTEM.
7. CONTRACTOR SHALL COORDINATE EXACT LOCATION
AND QUANTITY OF ALL DUCT TYPE SMOKE DETECTORS
WITH MECHANICAL CONTRACTOR. ELECTRICAL
CONTRACTOR SHALL HARD WIRE TO RELAY STARTER.
(E)G.7
9. PROVIDE CONNECTION OF FA SYSTEMS TO ALL
MAGNETIC DOOR HOLD-OPEN DEVICES TO
AUTOMATICALLY CLOSE DOORS (INCLUDING OVERHEAD
STORAGE DOORS) DURING ALARM CONDITIONS.
AG
10. DEVICES INDICATED ON FIRE ALARM ONE-LINE ARE
FOR REFERENCE ONLY. REFER TO PLAN DRAWINGS AND
SPECIFICATIONS FOR QUANTITIES. REFER TO
ARCHITECTURAL DOOR SCHEDULE FOR MAGNETIC DOOR
HOLDER AND BLOW OPEN DOOR REQUIREMENTS.
AF
1
11. PROVIDE DUCT DETECTOR AND FIRE ALARM RELAY
MODULE FOR EVERY FIRE-SMOKE DAMPER. LOCATE DUCT
DETECTOR WITHIN FIVE FEET OF FIRE-SMOKE DAMPER.
PROVIDE FIRE ALARM RELAY MODULE AT EACH FIRESMOKE DAMPER FOR DAMPER POSITION INDICATION.
1
12. ALL VISUAL DEVICES SHALL BE SYNCHRONIZED.
1
1
AE
13. PROVIDE FIRE ALARM RELAY MODULE FOR ALL CARD
READERS.
15. COORDINATE ALL HEAT AND SMOKE DETECTORS, IN
AREAS WITH EXPOSED CEILINGS, WITH ALL BEAM
POCKETS. PROVIDE ADDITIONAL DEVICES AS REQUIRED.
REF.
AD
AC
KEYNOTE LEGEND
1
PROVIDE ZERO VELOCITY, IN-DUCT, DUCT DETECTOR
AND CONNECT TO FIRE/SMOKE DAMPER.
DH
DH
DH
DH
AB
AA
DH
(E)
(RE)
(E)
(E)
DH
(E)
DH
(E)
DH
(E)
D
B
A
E
C
1
BENJAMIN TALPOS
EF1.1
NEW 1ST FLOOR FIRE ALARM
PLAN - AREA A
1/8" = 1'-0"
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
Architecture Engineering Planning Interiors
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
KEY PLAN
9/11/2013 11:52:25 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
EF1.1
(E)
NEW FIRE ALARM PLAN, FIRST LEVEL - AREA A
8. PROVIDE (1) DUCT TYPE SMOKE DETECTORS FOR EACH
FAN COIL UNIT, AIR HANDLING UNIT, SUPPLY FAN, AND HEAT
PUMP OF 2,000 CFM AND GREATER. PROVIDE (2) DUCT
TYPE SMOKE DETECTORS FOR EACH FAN COIL UNIT, AIR
HANDLING UNIT, HEAT PUMP AND SUPPLY FAN OF 15,000
CFM AND GREATER.
AH
PUEBLO COUNTY SCHOOL DISTRICT 70
5. ALL BACK BOXES SHALL BE FLUSH MOUNTED UNLESS
OTHERWISE NOTED. CONTRACTOR SHALL COORDINATE
INSTALLATION OF CONDUIT AND BACK BOXES IN POURED
CONCRETE, PRE-CAST CONCRETE, MASONRY AND GYP.
WALLS.
Pueblo West High School Additions + Renovations
AI
Revisions
AJ
37-13102-00
09.12.2013
4. ALL EXPOSED CONDUIT SHALL BE ROUTED
PERPENDICULAR AND PARALLEL TO COLUMNS AND
BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE
COORDINATED WITH THE ARCHITECT PRIOR TO
INSTALLATION. NO ADDITIONAL COST TO THE OWNER WILL
BE ALLOWED FOR RELOCATING CONDUIT DUE TO LACK OF
COORDINATION WITH THE ARCHITECT.
661 W Capistrano Ave
Pueblo West, CO 81007
3. PROVIDE #18 AWG MINIMUM WIRING FOR ALL SIGNAL
AND INITIATION DEVICES.
GENERAL NOTES:
1. THE FIRE ALARM SYSTEM INDICATED ON THESE
DRAWINGS IS A DEFERRED APPROVAL ITEM, SHALL BE
USED FOR BIDDING PURPOSES ONLY, AND IS NOT FOR
CONSTRUCTION . THE CONTRACTOR SHALL SUBMIT FIRE
ALARM SYSTEM SHOP DRAWINGS, INDICATING ALL
DEVICES, CONDUITS AND CONDUCTORS TO THE FIRE
MARSHAL OR AHJ FOR APPROVAL PRIOR TO INSTALLATION.
SYSTEM SHALL MEET SPECIFICATION REQUIREMENTS.
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10 A11
2. CONNECT ALL ELEVATOR LOBBY, ELEVATOR MACHINE
ROOM, TOP OF SHAFT AND ELEVATOR PIT SMOKE/HEAT
DETECTORS TO ELEVATOR CONTROLLER FOR ELEVATOR
RECALL. PROVIDE SHUNT TRIP DEVICE TO DISCONNECT
ALL ELEVATOR CONTROLLERS. VERIFY SHUNT TRIP
LOCATION REQUIREMENTS WITH AHJ. PROVIDE A HEAT
DETECTOR AT THE TOP OF ELEVATOR SHAFT AND WITHIN
TWO FEET OF EACH SPRINKLER HEAD IN ALL ELEVATOR
MACHINE ROOMS. ACTIVATION OF HEAT DETECTOR TO
INITIATE SHUNT-TRIP.
A12
6. CONTRACTOR SHALL COORDINATE EXACT QUANTITY
AND LOCATIONS OF ALL FIRE SPRINKLER SYSTEM TAMPER
AND FLOW SWITCHES WITH CONSTRUCTION MANAGER
AND FIRE PROTECTION. CONNECT ALL TAMPER AND FLOW
SWITCHES TO FIRE ALARM SYSTEM.
7. CONTRACTOR SHALL COORDINATE EXACT LOCATION
AND QUANTITY OF ALL DUCT TYPE SMOKE DETECTORS
WITH MECHANICAL CONTRACTOR. ELECTRICAL
CONTRACTOR SHALL HARD WIRE TO RELAY STARTER.
(E)G.7
9. PROVIDE CONNECTION OF FA SYSTEMS TO ALL
MAGNETIC DOOR HOLD-OPEN DEVICES TO
AUTOMATICALLY CLOSE DOORS (INCLUDING OVERHEAD
STORAGE DOORS) DURING ALARM CONDITIONS.
AG
10. DEVICES INDICATED ON FIRE ALARM ONE-LINE ARE
FOR REFERENCE ONLY. REFER TO PLAN DRAWINGS AND
SPECIFICATIONS FOR QUANTITIES. REFER TO
ARCHITECTURAL DOOR SCHEDULE FOR MAGNETIC DOOR
HOLDER AND BLOW OPEN DOOR REQUIREMENTS.
AF
1
11. PROVIDE DUCT DETECTOR AND FIRE ALARM RELAY
MODULE FOR EVERY FIRE-SMOKE DAMPER. LOCATE DUCT
DETECTOR WITHIN FIVE FEET OF FIRE-SMOKE DAMPER.
PROVIDE FIRE ALARM RELAY MODULE AT EACH FIRESMOKE DAMPER FOR DAMPER POSITION INDICATION.
1
AE
1
12. ALL VISUAL DEVICES SHALL BE SYNCHRONIZED.
13. PROVIDE FIRE ALARM RELAY MODULE FOR ALL CARD
READERS.
15. COORDINATE ALL HEAT AND SMOKE DETECTORS, IN
AREAS WITH EXPOSED CEILINGS, WITH ALL BEAM
POCKETS. PROVIDE ADDITIONAL DEVICES AS REQUIRED.
AD
AC
KEYNOTE LEGEND
1
PROVIDE ZERO VELOCITY, IN-DUCT, DUCT DETECTOR
AND CONNECT TO FIRE/SMOKE DAMPER.
DH
DH
DH
DH
AB
AA
(RE)
(E)
(E)
D
B
A
E
C
1
BENJAMIN TALPOS
EF1.5
NEW 2ND FLOOR FIRE ALARM
PLAN - AREA A
1/8" = 1'-0"
NORTH
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
Architecture Engineering Planning Interiors
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
KEY PLAN
9/11/2013 11:52:30 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
EF1.5
(E)
NEW FIRE ALARM PLAN, SECOND LEVEL - AREA A
8. PROVIDE (1) DUCT TYPE SMOKE DETECTORS FOR EACH
FAN COIL UNIT, AIR HANDLING UNIT, SUPPLY FAN, AND HEAT
PUMP OF 2,000 CFM AND GREATER. PROVIDE (2) DUCT
TYPE SMOKE DETECTORS FOR EACH FAN COIL UNIT, AIR
HANDLING UNIT, HEAT PUMP AND SUPPLY FAN OF 15,000
CFM AND GREATER.
AH
PUEBLO COUNTY SCHOOL DISTRICT 70
5. ALL BACK BOXES SHALL BE FLUSH MOUNTED UNLESS
OTHERWISE NOTED. CONTRACTOR SHALL COORDINATE
INSTALLATION OF CONDUIT AND BACK BOXES IN POURED
CONCRETE, PRE-CAST CONCRETE, MASONRY AND GYP.
WALLS.
Pueblo West High School Additions + Renovations
AI
Revisions
AJ
37-13102-00
09.12.2013
4. ALL EXPOSED CONDUIT SHALL BE ROUTED
PERPENDICULAR AND PARALLEL TO COLUMNS AND
BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE
COORDINATED WITH THE ARCHITECT PRIOR TO
INSTALLATION. NO ADDITIONAL COST TO THE OWNER WILL
BE ALLOWED FOR RELOCATING CONDUIT DUE TO LACK OF
COORDINATION WITH THE ARCHITECT.
661 W Capistrano Ave
Pueblo West, CO 81007
3. PROVIDE #18 AWG MINIMUM WIRING FOR ALL SIGNAL
AND INITIATION DEVICES.
1RN
NEW
NEW
1RNA1
1RNA2
FA10
FA10
NEW
NEW
R13
15 AND LESS
30
45
75
112.5
150
225
300
500
R11
FA8
13
8
6
4
2
1/0
1/0
2/0
3/0
4/0
3 WIRE
FDR WIRE
REF AWG/
KCMIL
3/4
3/4
3/4
3/4
1
1
1
1-1/4
1-1/4
NEW
GENERAL NOTES:
A. REFER TO MECHANICAL SHEDULES
FOR FEEDER AND DISCONNECT SIZES
FOR MECHANICAL EQUIPMENT.
RBW
SPD
B. PROVIDE 100% RATED MAIN CIRCUIT
BREAKERS FOR ALL SWITCHBOARDS.
1
MAIN
90A
3P
2
100A
3P
200A
3P
3
4
150A
3P
5
150A
3P
6
NEW
FA8
FA8
150A
3P
FA10
NEW
125A
3P
7
8
FA8
NEW
200A
3P
FA8
FA8
150A
3P
1
3P
800A
TRANSFORMER
45KVA
480-208/120V, 3PH,
4W
DISTRIBUTION PANEL "SDP3"
800A BUS
208/120V, 3PH, 4W
2
150A
3P
3
90A
3P
4
100A
3P
5
6
8
7
3P
400A
MAIN
FA18
SPACE
FA8
FA8
SPACE
FA10
1-1/4"C, 5#4
1-1/4"C, 5#4
NEW
FA7
SPACE
RNG
SPACE
1-1/4"C, 4#3+1#8G
SPD
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
F11
F12
F13
F14
F15
F16
F17
F18
F19
F20
F21
F22
F23
F24
F25
F26
4 WIRE
CONDUIT
W/GRD
INCHES
GRD
WIRE
AWG/KCMIL
(3) 12
(3) 10
(3) 8
(3) 6
(3) 4
(3) 2
(3) 1
(3) 1/0
(3) 2/0
(3) 3/0
(3) 4/0
(3) 250
(3) 350
(3) 500
(6) 4/0
(6) 250
(6) 350
(6) 500
(9) 300
(9) 500
(12) 350
(12) 750
(18) 500
(18) 750
(24) 600
(30) 600
12
10
10
10
8
8
6
6
6
6
4
4
4
3
(2) 3
(2) 2
(2) 1
(2) 1/0
(3) 1/0
(3) 2/0
(4) 3/0
(4) 4/0
(6) 250
(6) 350
(8) 400
(10) 500
3/4
3/4
3/4
1-1/4
1-1/4
1-1/2
2
2
2
2-1/2
2-1/2
2-1/2
3
3-1/2
(2) 2-1/2
(2) 2-1/2
(2) 3
(2) 3-1/2
(3) 3
(3) 3-1/2
(4) 3
(4) 4
(6) 3-1/2
(6) 4
(8) 4
(10) 4
FDR
REF
WIRE
AWG/
KCMIL
FA1
FA2
FA3
FA4
FA5
FA6
FA7
FA8
FA9
FA10
FA11
FA12
FA13
FA14
FA15
FA16
FA17
FA18
FA19
FA20
FA21
FA22
FA23
FA24
FA25
FA26
(4) 12
(4) 10
(4) 8
(4) 6
(4) 4
(4) 2
(4) 1
(4) 1/0
(4) 2/0
(4) 3/0
(4) 4/0
(4) 250
(4) 350
(4) 500
(8) 4/0
(8) 250
(8) 350
(8) 500
(12) 300
(12) 500
(16) 350
(16) 750
(24) 500
(24) 750
(32) 600
(40) 600
CONDUIT
W/GRD
INCHES
GRD
WIRE
AWG/KCMIL
3/4
3/4
1
1-1/4
1-1/4
1-1/2
2
2
2-1/2
2-1/2
2-1/2
12
10
10
10
8
8
6
6
6
6
2
2
2
1/0
(2) 3
(2) 2
(2) 1
(2) 1/0
(3) 1/0
(3) 4/0
(4) 4/0
(4) 400
(6) 250
(6) 350
(8) 400
(10) 500
3
3
3-1/2
(2) 2-1/2
(2) 3
(2) 3
(2) 3-1/2
(3) 3
(3) 3-1/2
(4) 3
(4) 4-1/2
(6) 3-1/2
(6) 4-1/2
(8) 4
(10) 4
DISTRIBUTION PANEL "SDP2"
400A BUS
208/120V, 3PH, 4W
FA14
F4
R7
MNG
ART
S
R6
R5
AHU
2
AHU
1
LW
CU
1
CU
2
EF
2
CT
2
EF
1
AHU
13
IF
13
AHU
17
AHU
20
AHU
18
AHU
19
R8
FA10
FA10
R4R
R3
MED
FA10
FA10
R10
10
9
350A
3P
8
30A
3P
7
FA13
F3
F5
F1
F2
F1
F1
FA1
FA6
F9
F1
100A
3P
6
30A
3P
5
70A
3P
4
90A
3P
3
FA6
FA6
FA10
FA6
100A
3P
20A
3P
2
1
20A
3P
1
300A
3P
40A
3P
2
3
60A
3P
4
20A
3P
5
30A
3P
6
20A
3P
7
20A
3P
8
15A
3P
9
20A
3P
10
175
3P
1
11
100A
3P
2
100A
3P
3
100A
3P
4
100A
3P
5
MAIN
DISTRIBUTION PANEL "DP1"
600A BUS
480/277V, 3PH, 4W
DISTRIBUTION PANEL "DP2"
600A BUS
480/277V, 3PH, 4W
EM2
FA10
100A
3P
6
30A
3P
7
200A
3P
8
FA10
SPACE
F1
SPACE
F1
SPACE
F5
SPARE
F4
SPARE
SPACE
11
30A
3P
F2
SPACE
F2
F14
SPARE
F2
1-1/4"C, 4#3+1#8G
400AS
9
200A
3P
10
200A
3P
12
11
200A
3P
13
200A
3P
14
DISTRIBUTION PANEL "SDP"
800A BUS
208/120V, 3PH, 4W
FA18
ERW
C
12
FA7
FA4
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
P
16
P
15
P
14
P
13
P
12
P
11
P
4
P
3
CH
2
FA3
MWA
9
8
7
6
5
4
3
TRANSFORMER
15KVA
480-208/120V, 3PH,
4W
2
F2
NEW
F4
NEW
NEW
NEW
FA10
*
*
NEW
*
NEW
*
NEW
*
NEW
*
NEW
*
NEW
SPACE
SPACE
13
NEW
25A
3P
10
9
NEW
30A
3P
8
NEW
15A
3P
7
NEW
15A
3P
6
NEW
60A
3P
5
NEW
60A
3P
4
NEW
60A
3P
3
NEW
400A
3P
2
FA7
CH
1
400AF
400AS
A
MCC
1
TRANSFORMER
112.5KVA
480-208/120V, 3PH,
4W
1
NEW
FA17
FA10
FA18
FA17
F14
F14
D
(E) 40KW NAT. GAS
480/277V GENERATOR
FA6
BUSS
#
FA10
FA10
F14
FA6
3000A BUS
G
4
600AF
600AS
3P
3
350AF
400AS
3P
2
400AF
400AS
3P
1
100AF
100AS
3P
FA13
FA10
F14
2000A BUS
1000A
3P
1200A
3P
1200A BUS
600AF
600AS
3P
BUSS
#
VOLTAGE
L-L
1
49,033
9
5,248
2
39,844
10
3,987
3
14,397
11
7,386
4
15,393
12
1,788
5
17,826
13
4,487
6
18,931
14
5,599
7
1,829
8
2,028
NOTES:
NEW
600AF
600AS
3P
1
VOLTAGE
L-L
FA14
ELW
MAIN
G
1
200AF
200AS
3P
2
200AF
200AS
3P
3
200AF
200AS
3P
4
175AF
200AS
3P
5
100AF
100AS
3P
6
300AF
400AS
3P
7
200AF
200AS
3P
8
9
350AF
400AS
3P
MAIN
SECTION 1
UTILITY
TRANSFORMER
T
M
SECTION 2
MAIN DISTRIBUTION SWITCHBOARD "MSB"
480/277V, 3PH, 4W
7 SETS OF 3"C, 4#500KCMIL
SECTION 3
1
E6.1
BENJAMIN TALPOS
FAULT SCHEDULE
*
2
9/11/2013 11:52:32 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
VAV1
TRANSFORMER
225KVA
480-208/120V, 3PH,
4W
FA6
NEW DISTRIBUTION PANEL "E"
600A BUS
480/277V, 3PH, 4W
65,000 AIC
K1
NEW
*
NEW
60A
3P
K
F1
EM1
NEW
200A
3P
11
B
TRANSFORMER
15KVA
480-208/120V, 3PH,
4W
SPACE
10
11
NEW
50A
3P
12
VAV2
1-1/4"C, 4#3+1#8G
TRANSFORMER
30KVA
480-208/120V, 3PH,
4W
200A
3P
16
3P
800A
NEW
RWA
200A
3P
15
ELECTRICAL ONE-LINE DIAGRAM
DWH
1
R4L
E6.1
TRANSFORMER
225KVA
480-208/120V, 3PH,
4W
R2
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
BOILER CONTROLLER
TRANSFORMER
112.5KVA
480-208/120V, 3PH,
4W
PUEBLO COUNTY SCHOOL DISTRICT 70
14
R12
EXISTING ELECTRICAL ONE-LINE DIAGRAM
SCALE: NONE
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
2RNA3
Pueblo West High School Additions + Renovations
2RNA2
FEEDER TABLE - COPPER CONDUCTORS
(SEE SPECIFICATIONS FOR INSULATION TYPE)
Revisions
2RNA1
TRANSFORMER GROUND SIZING TABLE
208/120 VOLT SECONDARY
KVA
CONDUIT
AWG/KCMIL
SIZE
Architecture Engineering Planning Interiors
NEW
37-13102-00
09.12.2013
2RE
NEW
661 W Capistrano Ave
Pueblo West, CO 81007
2RN
2RS
NEW
LIGHTING FIXTURE SCHEDULE
5.
186
277
PENDANT
10'-0" AFF
- 8'-0" DIRECT/INDIRECT LINEAR FLUORESCENT PENDANT
- SATIN LENS
- 3-LAMP CROSSECTION CONFIGURATION
- <10% THD ELECTRONIC PROGRAM START DUAL-LEVEL.
BALLAST.
C1
-
T8
3500K
3
32
93
277
PENDANT
10'-0" AFF
- SAME AS TYPE "C" EXCEPT 4'-0".
D
H.E. WILLIAMS: 50 STATIC SERIES
LITHONIA: GT8 SERIES
LIGHTOLIER: XP SERIES
METALUX: 2GR8 SERIES
T8
3500K
2
32
62
120
RECESSED
- 2'X4' FLUORESCENT LENSED TROFFER
- PROGRAM START BALLAST W/ <10%THD.
- MIN. 0.125" LENS
- FULLY ENCLOSED, SPRING-LOADED CAM LATCHES
D1
-
T8
3500K
3
32
93
120
RECESSED
- SAME AS TYPE "D" EXCEPT WITH 3 LAMPS.
D1D
-
T8
3500K
3
32
93
120
RECESSED
- SAME AS TYPE "D1" EXCEPT WITH 0-10V DIMMING BALLAST.
E
PRESCOLITE: LF6CFH SERIES
LIGHTOLIER: 8021 SERIES
GOTHAM: AF SERIES
HALO COMM: PD6 SERIES
32W CFL
3500K
1
32
36
277
RECESSED
- 6" DIA. COMPACT FLUORESCENT DOWNLIGHT
- 22 GAUGE GALVANNEALED STEEL PLATFORM.
- HIGH PURITY ALUMINUM SEMI-DIFFUSE REFLECTORS.
- PAINTED WHITE SELF-TRIM.
F
H.E. WILLIAMS: 76 SERIES
LIGHTOLIER: SW SERIES
LITHONIA: EJ SERIES
METALUX: ICF SERIES
T8
3500K
2
32
62
277
SURFACE/
CHAIN HUNG
AT 9' AFF
F1
-
T8
3500K
2
32
62
120/277
WALL
J
H.E. WILLIAMS: WS SERIES
PRUDENTIAL: P59 SERIES
METALUX RWW SERIES
T8
3500K
1
32
32
277
WALL
FLUSH WITH
GYP. CEILING
7 MECHANICALLY INTERLOCKED
AUXILIARY CONTACTS ON
SWITCH FOR OUTPUT TO
BATTERY LOWERING
PERMISSIVE RELAY. (AS
REQUIRED)
N
McPHILBEN: 101 TRAPAZOID
150W
HPS
1
70
93
277
WALL
MATCH HEIGHT
OF EXISTING
FIXTURES
FUSES PER DRAWINGS AND
SCHEDULES.
X
SURELITES: CAX
LED
-
-
7
277
UNIVERSAL
7
BL
1
ISOLATION RELAY TO ISOLATE
3 THE FIRE ALARM CONTACTS
FROM THE LOAD OF THE
SHUNT TRIP.
THE SYSTEM SHALL REMAIN IN THE ALARM MODE UNTIL
THE INITIATING DEVICE IS RESET AND THE FIRE ALARM
CONTROL PANEL IS RESET AND RESTORED TO NORMAL.
- 2'X4' RECESSED DIRECT/INDIRECT FLUORESCENT.
- 20 GAUGE STEEL REFLECTOR AND HOUSING.
- .080" FROSTED WHITE ACRYLIC DIFFUSER.
- .125" THICK MINIATURE PRISM ACRYLIC LENS AND .120"
THICK LINEAR SPREAD LENS.
- WHITE PERFORATED ROUND SHIELD
- <10% THD ELECTRONIC PROGRAM START BALLAST.
32
2 SHUNT TRIP COIL TO ACTIVATE
SHUNT TRIP MECHANISM ON
MOLDED CASE SWITCH.
SHUT DOWN OF ALL AIR HANDLING UNITS.
GRID CEILING
6
1 MOLDED CASE SWITCH WITH
SHUNT TRIP PROVISION,
AMPERE RATING PER
DRAWINGS AND SCHEDULES.
RELEASE OF POWER TO ELECTRIC DOOR LOCKS
THAT ARE PART OF THE MEANS OF EGRESS.
277
M
8
NORMALLY OPEN 24V FIRE
4 ALARM CONTACTS IN FACP
SUPPLIED BY THE FIRE ALARM
CONTRACTOR TO TRIGGER
ELEVATOR POWER SHUNT
TRIP.
120V
5A
2
ST
3
VOLTAGE MONITORING RELAY
5 TO MONITOR SHUNT TRIP
CONTROL VOLTAGE.
6
FR
AHU/DAMPER
SHUTDOWN
EXISTING FA
CIRCUIT
ERW-3
.
FR
8
IR
TO F/A SYSTEM
4
TO F/A SYSTEM
6
5
DH
2
E6.2
- SAME AS TYPE "F" EXCEPT 120V AND WALL MOUNTED.
VM
FIRE ALARM INPUT TO
MONITOR SHUNT TRIP
VOLTAGE AND DISPLAY
TROUBLE WHEN NO VOLTAGE
IS PRESENT.
J
- 4' STANDARD STRIP LIGHT.
- 22 GAUGE COLD ROLLED STEEL HOUSING AND
REFLECTOR.
- 14-GUAGE WIREGUARD
- <10% THD ELECTRONIC PROGRAM START BALLAST.
ELEVATOR FIRE SHUNT TRIP DETAIL
- RECESSED PERIMETER WALL WASH COVE.
- 22 GUAGE COLD ROLLED STEEL HOUSING.
- SEMI-SPECULAR ALUMINUM REFLECTOR.
- <10% THD ELECTRONIC PROGRAM START BALLAST.
- FINISH: REFLECTIVE WHITE POLYESTER POWDER COAT.
- EXTERIOR SECURITY WALLPACK
- FULL CUT-OFF
- FLAT LENS OPTICS
- INTEGRAL PHOTOCELL
- FINISH: BRONZE
- HIGH ABUSE LED EXIT SIGN
- DIE-CAST ALUMINUM HOUSING
- GREEN LETTERING
- FACES AND CHEVRONS TO MATCH DRAWINGS
- AC ONLY
- FINISH: WHITE
SCALE: NONE
ELEV
EXISTING FACP
UPGRADE EXISTING
FACP AS REQUIRED.
FIRE ALARM RISER DIAGRAM
CONTROL WIRING PER MANUFACTURER RECOMMENDATION.
2
MINIMUM CONDUT SIZE BETWEEN POWER PANEL AND
LIGHTING CONTROL PANEL INDICATED. PROVIDE ADDITIONAL
CONDUITS AS REQUIRED FOR NUMBER OF CIRCUITS
CONTROLLED.
3
4
T.C.
LW-9
1ST FLR HALLS & RESTROOMS
2
NA1
T.C.
LW-11
1ST FLR WEST CLASSROOMS
3
NA1
T.C.
LW-13
1ST FLR EAST CLASSROOMS
4
T.C.
LW-14
2ND FLR HALLS & RESTROOMS
5
NA2
NA2
T.C.
LW-16
2ND FLR WEST CLASSROOMS
6
NA2
T.C.
LW-18
2ND FLR EAST CLASSROOMS
7
P.C/T.C.
LW-15
EXTERIOR LIGHTS
8
-
-
LABEL
LV
1
2
CONTROLLED
ZONE
NA1
NA2
FUNCTION
OVERRIDE
OVERRIDE
BUTTON LABEL
1ST FLOOR LIGHTING
2ND FLOOR LIGHTING
HOT
NEUTRAL
BLACK
BLACK
RED
BLACK
WHITE
NOTE: OVERRIDE DENOTES A 2-HOUR AFTER HOURS OVERIDE OF THE TIME CLOCK
ORANGE
BLUE
BLUE
SPARE
GREEN
T.C. = TIME CLOCK
P.C. = PHOTOCELL
GREEN
LOAD
LOAD2
WHITE
LOAD
BLACK
BLACK
NA1
BUTTON
NEUTRAL
1
SWITCH
BLACK
BLACK
LOW VOLTAGE 2-HOUR OVERRIDE SWITCH LOCATED AT THE
MAIN ENTRANCE, STAIRWELL ENTRANCES ON EACH FLOOR.
LOAD
RED
BLACK
WHITE
1
CIRCUIT
RED
BLACK
WHITE
LIGHTING CONTROL NOTES:
CONTROL
RELAY
SWITCH DESIGNATIONS
LIGHTING RELAY PANEL "LCPA1"
RELAY ZONE
UN-SWTICHED HOT
SCALE: NONE
FOR
DUAL-LEVEL
OR MULTIPLE
SWITCHING
NETWORK NEW LIGHTING CONTROL PANELS TO EXISTING
SYSTEM. UPGRADE EXISTING LIGHTING CONTROL SYSTEM AS
REQUIRED.
EXISTING
PANEL
EXISTING
PANEL
LW
ELW
SCALE: NONE
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
3
5
1E0.2
SCALE: NONE
WALL MOUNTED OCCUPANCY
SENSOR DIAGRAM
NEW
.
LW-12
4
(1) 1"C.
BLACK
BLACK
GREEN
BLACK
BLACK
BLUE
BLUE
GREEN
LOAD
LOAD1
LOAD2
EXISTING LIGHTING CONTROL SYSTEM
3
E6.2
LIGHTING CONTROL RISER DIAGRAM
SCALE: NONE
BENJAMIN TALPOS
6
1E0.2
WALL MOUNTED OCCUPANCY
SENSOR/SWITCH DIAGRAM
SCALE: NONE
7
1E0.2
WALL MOUNTED DUAL-LEVEL OCCUPANCY
SENSOR/SWITCH DIAGRAM
SCALE: NONE
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
2
Architecture Engineering Planning Interiors
LV 1
NEW LIGHTING CONTROL
PANEL BY TOUCHPLATE.
HOT
NEUTRAL
LCPA1
HOT
NEUTRAL
J
9/11/2013 11:52:34 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
(1) 2"C.
4
E6.2
CEILING MOUNTED OCCUPANCY
SENSOR DIAGRAM
E6.2
1
E6.2
ELECTRICAL SCHEDULES
ELEVATOR RECALL SYSTEM
CLASSROOM
ADDITION
FACP
PUEBLO COUNTY SCHOOL DISTRICT 70
4.
DESCRIPTION
T8
3500K
KEY NOTES
CONTINUOUS ACTIVATION OF ALL NOTIFICATION
APPLIANCES.
MOUNTING
Pueblo West High School Additions + Renovations
3.
VOLTAGE
H.E. WILLIAMS: SDI2 SERIES
CORELITE: NB SERIES
TRANSMISSION OF AN ALARM SIGNAL TO THE
CENTRAL STATION.
VISUAL INDICATION OF THE DEVICE OPERATED ON
THE FIRE ALARM CONTROL PANEL.
INPUT
WATTS
62
C
ACTIVATION OF ANY ALARM SYSTEM INITIATING DEVICE
SHALL CAUSE THE SYSTEM TO BE ACTIVATED INTO THE
ALARM MODE AND THE FOLLOWING FUNCTIONS:
2.
LAMP INFORMATION
#
WATTS
2
32
Revisions
H.E. WILLIAMS: DI 2X4 SERIES
LIGHTOLIER: HP90 SERIES
LITHONIA: AVANTE 2X4 SERIES
METALUX: 2RDI SERIES
FIRE ALARM/MASS
NOTIFICATION SEQUENCE
OF OPERATION
1.
TYPE
T8
3500K
37-13102-00
09.12.2013
MANUFACTURER: SERIES
661 W Capistrano Ave
Pueblo West, CO 81007
FIXTURE
TYPE
A
SWITCHBOARD
"E"
LOAD SCHEDULE
POWER PANELBOARD
"DP2"
LOAD SCHEDULE
POWER PANELBOARD
"SDP"
LOAD SCHEDULE
POWER PANELBOARD
"SDP3"
LOAD SCHEDULE
AMPS
CKT
AMPS
CKT
AMPS
CKT
AMPS
CKT
551.2
1
CH-2
198.0
1
EF-1
4.8
1
R8
92.3
1
TVSS
441.4
2
P-3
27.0
2
EF-2
3.4
2
R7
18.3
2
RBW
21.4
992.6
3
P-4
27.0
3
SPARE
-
3
R10
45.5
3
1RN
159.4
LCL x 25%
14.1
4
P-11
27.0
4
CU-2
55.0
4
S
83.8
4
2RS
123.7
LML x 25%
49.5
5
P-12
27.0
5
CU-1
65.0
5
SPARE
-
5
2RN
74.8
163.2
RECEPTACLE DIVERSITY
-55.9
6
P-13
4.8
6
AHU-1
14.0
6
SPARE
-
6
2RE
83.6
VAV1
238.5
KITCHEN DIVERSITY
7
P-14
4.8
7
LW
44.3
7
ART
117.5
7
1RNA1
125.1
8
CHILLER
198.0
TOTAL LOAD
8
P-15
14.0
8
AHU-2
11.0
8
B-4
11.0
8
2RNA1
9
SDP
450.6
9
P-16
11.0
9
SDP3
342.9
9
R5
112.9
SUB TOTAL
1,494.9
10
MWA
100.8
10
SPACE
-
10
B-5
11.0
LCL x 25%
LCL x 25%
72.9
11
SPARE
-
11
DWH-1
10.8
11
R6
110.2
LML x 25%
LML x 25%
49.5
12
SPARE
-
SUB TOTAL
551.2
12
R2
104.6
RECEPTACLE DIVERSITY
RECEPTACLE DIVERSITY
-90.0
LCL x 25%
14.1
13
R4L
178.8
KITCHEN DIVERSITY
LML x 25%
16.3
14
R3
76.3
TOTAL LOAD
RECEPTACLE DIVERSITY
-55.9
15
MED
77.6
16
SPACE
81.7
2
E
C
64.8
SUB TOTAL
4
K
145.1
5
D
75.3
6
VAV2
7
SUB TOTAL
1,000.3
LCL x 25%
1,527.4
TOTAL LOAD
MAXIMUM DEMAND LOAD OVER LAST 12 MONTHS:
MAXIMUM DEMAND AT 125% PER NEC 220.87:
441.4
SUB TOTAL
KITCHEN DIVERSITY
LOAD CALCULATION FOR MSB
3000A, 480Y/227V, 3 PHASE, 4 WIRE
DESCRIPTION
49.5
LML x 25%
RECEPTACLE DIVERSITY
KITCHEN DIVERSITY
KITCHEN DIVERSITY
TOTAL LOAD
+
MWA
2.8
LW
480Y/277V, 3PH-4W+GND
LOCATION:
480Y/277V, 3PH-4W+GND
MLO
MOUNTING: SURFACE
MLO
MOUNTING: SURFACE
MLO
225A BUS
RATING: 14K AIC
125A BUS
RATING: 14K AIC
RATING: 10K AIC
BRKR
90A/3P
-
-
-
-
-
-
EQ
15A/3P
-
-
3
5
7
IF-23-1
9
-
11 -
-
-
13 EF-23-1
M
15A/3P
15 -
-
-
17 -
-
-
PHASE C
PHASE B
PHASE A
13850
11080
11080
BRKR
TYPE
#
N
N
#
TYPE
BRKR
70A/3P
M
ELEVATOR
2
1
1
1
LTG - CRAWL SPACE
LT
20A/1P
-
-
-
4
3
LTG - 1ST TOILETS/CORRIDOR
LT
20A/1P
-
-
-
6
5
LTG - 1ST CLASS SW
LT
20A/1P
13850
11080
13850
ELEVATOR SHUNT TRIP
20A/1P
2105
20A/1P
2105
443
7
LTG - 1ST CLASS S+N
LT
20A/1P
10
2
9
N. ADD LTG - 1ST FLR HALL & RR
LT
20A/1P
8
12
2
11 N. ADD LTG - 1ST FLR W. CLASS
LT
20A/1P
M
EF-23-4
14
2
13 N. ADD LTG - 1ST FLR E. CLASS
LT
20A/1P
-
-
-
16
2
15 EXTERIOR LIGHTING
LT
20A/1P
-
-
-
18
17 SPARE
20A/1P
443
443
DESCRIPTION
15A/3P
20A/1P
2105
443
443
DESCRIPTION
443
PHASE C
PHASE B
PHASE A
1330
1544
2190
2320
3265
2990
1360
2725
1352
2260
2418
400
1338
3812
890
125A BUS
3518
3158
DESCRIPTION
#
N
BRKR
TYPE
N
#
TYPE
BRKR
20A/1P
LT
LTG - 2ND TOILETS/CORRIDOR
2
2
1
1ST FLR CLASSROOM EM LTG
LT
20A/1P
20A/1P
LT
LTG - 2ND CLASS SW
4
2
3
1ST FLR HALLWAY EM LTG
LT
20A/1P
20A/1P
LT
LTG - 2ND CLASS S+N
6
2
5
2ND FLR CLASSROOM EM LTG
LT
20A/1P
20A/1P
LT
LTG - 2ND CLASS S INDIRECT
8
7
SPACE
20A/1P
LT
LTG - 2ND CLASS SE
10
9
SPACE
20A/1P
LT
LCPA1
12
2
20A/1P
LT
N. ADD LTG - 2ND FLR HALL & RR
14
2
13 SPACE
20A/1P
LT
N. ADD LTG - 2ND FLR W. CLASS
16
2
20A/1P
LT
N. ADD LTG - 2ND FLR E. CLASS
18
2
3
DESCRIPTION
DESCRIPTION
TYPE
2
LTG - NIGHT/EM LIGHTS
4
P
ERW
6
-
-
-
8
-
-
-
10
SPACE
12
SPACE
14
15 SPACE
SPACE
16
17 SPACE
SPACE
18
474
20A/1P
1850
1396
1693
1630
1904
11 2ND FLR HALLWAY EM LTG
LT
20A/1P
474
20A/1P
20
19 SPARE
20A/1P
20A/1P
SPARE
20
19 SPACE
SPACE
20
21
20A/1P
20A/1P
22
21 SPARE
20A/1P
20A/1P
SPARE
22
21 SPACE
SPACE
22
23
20A/1P
20A/1P
24
23 SPARE
20A/1P
20A/1P
SPARE
24
23 SPACE
SPACE
24
25
20A/1P
20A/1P
26
25 SPARE
20A/1P
20A/1P
SPARE
26
25 SPACE
SPACE
26
27
20A/1P
20A/1P
28
27 SPARE
20A/1P
20A/1P
SPARE
28
27 SPACE
SPACE
28
29
20A/1P
20A/1P
30
29 SPARE
20A/1P
20A/1P
SPARE
30
29 SPACE
SPACE
30
31
20A/1P
20A/1P
32
31 SPARE
20A/1P
20A/1P
SPARE
32
33
20A/1P
20A/1P
34
33 SPARE
20A/1P
20A/1P
SPARE
34
35
20A/1P
20A/1P
36
35 SPARE
20A/1P
20A/1P
SPARE
36
37
20A/1P
20A/1P
38
37 SPARE
20A/1P
20A/1P
SPARE
38
39
20A/1P
20A/1P
40
39 SPARE
20A/1P
20A/1P
SPARE
40
20A/1P
42
41 SPARE
20A/1P
SPARE
42
20A/1P
27921
27921
27921
VA
100.8
100.8
100.8
AMPS
20A/1P
TOTAL CONNECTED PHASE LOAD
TOTAL CONNECTED LOAD
KVA
AMPS
83.76
100.8
LONG CONTINUOUS LOADS * 25%
NOTES:
12.5
10.39
LARGEST MOTOR LOAD * 25%
12109
12530
12231
43.7
45.2
44.2
TOTAL CONNECTED PHASE LOAD
KVA
AMPS
TOTAL CONNECTED LOAD
36.87
44.3
LONG CONTINUOUS LOADS * 25%
9.22
11.1
AMPS
113.2
94.15
VA
12.2
15.3
12.9
AMPS
AMPS
TOTAL CONNECTED LOAD
11.18
13.5
LONG CONTINUOUS LOADS * 25%
1.03
1.2
LARGEST MOTOR LOAD * 25%
0.28
0.3
* CIRCUITS ARE EXISTING TO REMAIN U.O.N.
NOTES:
1. REVISED EXISTING LOAD.
(RECEPTACLE LOADS - 10KVA) * 50%
2. NEW LOAD ON EXISITNG SPARE BREAKER.
KITCHEN LOADS * 0%
3. EXISTING SPR CB RELOCATED FROM CKT 7.
15.0
12.50
TOTAL LOAD
1. REVISED LOAD ON EXISTING CKT.
2. NEW LOAD ON EXSITING SPARE BREAKER.
55.4
46.09
TOTAL LOAD
1RNA1
3563
1RNA2
2RNA1
M-E ENGINEERS, INC.
M-E ENGINEERS, INC.
SD-70 Pueblo West HS Renovation & Addition
M-E ENGINEERS, INC.
SD-70 Pueblo West HS Renovation & Addition
LOCATION: 1ST FLR ELEC RM
208Y/120V, 3PH-4W+GND
LOCATION: 1ST FLR ELEC RM
208Y/120V, 3PH-4W+GND
LOCATION: 2ND FLR ELEC RM
208Y/120V, 3PH-4W+GND
MOUNTING: SURFACE
MLO
MOUNTING: SURFACE
MLO
MOUNTING: SURFACE
MLO
RATING: 10K AIC
225A BUS
RATING: 10K AIC
225A BUS
RATING: 10K AIC
SD-70 Pueblo West HS Renovation & Addition
VA
#
DESCRIPTION
TYPE
BRKR
1
CONV REC. CORRIDOR A113
R
20A/1P
3
CONV REC. CORRIDOR A109
R
20A/1P
5
CONV REC.STOR,JAN,ELEC
R
20A/1P
7
REC CLASSROOM A110 S. WALL
R
20A/1P
9
REC CLASSROOM A110 E. WALL
R
20A/1P
11 REC CLASSROOM A110 NE WALL
R
20A/1P
13 REC CLASSROOM A110 N. WALL
R
20A/1P
15 REC CLASSROOM A110 NW WALL
R
20A/1P
17 REC CLASSROOM A110 W. WALL
R
20A/1P
EQ
20A/1P
21 REC SCIENCE PREP A108A
R
20A/1P
23 REC SCIENCE A108 S. STATION
R
20A/1P
25 REC SCIENCE A108 E. STATION
R
20A/1P
27 REC SCIENCE A108 N. STATION
R
20A/1P
29 REC SCIENCE A108 W. STATION
R
20A/1P
31 REC CRAWLSPACE TELECOM RM
R
20A/1P
33 DATA RACK - CRAWLSPACE TELECOM
EQ
20A/1P
35 DATA RACK - CRAWLSPACE TELECOM
EQ
20A/1P
19 FRIDGE SCIENCE PREP A108A
PHASE C
740
1080
740
900
360
180
720
720
800
720
800
500
720
720
500
720
720
720
1200
1080
720
900
720
800
720
540
1200
720
900
1200
1200
#
N
BRKR
TYPE
TYPE
BRKR
20A/1P
EQ
EWC-1
2
1
REC CLASSROOM A103 S. WALL
R
20A/1P
20A/1P
EQ
EWC-1
4
3
REC CLASSROOM A103 E. WALL
R
20A/1P
20A/1P
R
REC TELECOMM A107
6
5
REC CLASSROOM A103 NE WALL
R
20A/1P
20A/1P
EQ
HOOD SCIENCE CLASSROOM A108
8
7
REC CLASSROOM A103 N. WALL
R
20A/1P
20A/1P
EQ
TV CLASSROOMS A110, A108
10
9
REC CLASSROOM A103 NW WALL
R
20A/1P
20A/1P
EQ
TV CLASSROOMS A103, A100
12
11 REC CLASSROOM A103 W. WALL
R
20A/1P
20A/1P
EQ
SMARTBOARD CLASSROOM A110
14
13 REC CLASSROOM A115 E. WALL
R
20A/1P
20A/1P
EQ
SMARTBOARD SCIENCE A108
16
15 REC CLASSROOM A115 NE WALL
R
20A/1P
20A/1P
R
REC SCIENCE A108 E. WALL
18
17 REC CLASSROOM A115 N. WALL
R
20A/1P
20A/1P
R
REC SCIENCE A108 NE WALL
20
19 REC CLASSROOM A115 W. WALL
R
20A/1P
20A/1P
R
REC SCIENCE A108 N. WALL
22
21 REC CLASSROOM A115 SW WALL
R
20A/1P
20A/1P
R
REC SCIENCE A108 W. WALL
24
23 REC CLASSROOM A115 SE WALL
R
20A/1P
20A/1P
EQ
MECH LV POWER SUPPLY
26
25 REC CLASSROOM A114 E. WALL
R
20A/1P
20A/1P
EQ
CLOCKS
28
27 REC CLASSROOM A114 N. WALL
R
20A/1P
20A/1P
SPARE
30
29 REC CLASSROOM A114 N. WALL
R
20A/1P
20A/1P
SPARE
32
31 REC CLASSROOM A114 W. WALL
R
20A/1P
20A/1P
SPARE
34
33 REC CLASSROOM A114 SW WALL
R
20A/1P
20A/1P
SPARE
36
35 REC CLASSROOM A114 SE WALL
R
20A/1P
DESCRIPTION
N
DESCRIPTION
#
PHASE B
PHASE A
720
PHASE C
720
720
720
720
720
720
720
720
720
720
720
720
500
720
500
720
720
1000
800
720
720
720
720
720
720
720
720
N
BRKR
TYPE
TYPE
BRKR
20A/1P
R
REC CLASSROOM A100 NE WALL
2
1
REC CLASSROOM A213 S.WALL
R
20A/1P
20A/1P
R
REC CLASSROOM A100 N. WALL
4
3
REC CLASSROOM A213 S. WALL
R
20A/1P
20A/1P
R
REC CLASSROOM A100 W. WALL
6
5
REC CLASSROOM A213 S. WALL
R
20A/1P
20A/1P
R
REC CLASSROOM A100 SW WALL
8
7
REC CLASSROOM A213 W. WALL
R
20A/1P
20A/1P
R
REC CLASSROOM A100 S. WALL
10
9
REC CLASSROOM A213 W. WALL
R
20A/1P
20A/1P
R
REC CLASSROOM A100 SE WALL
12
11 REC CLASSROOM A213 W. WALL
R
20A/1P
20A/1P
EQ
SMARTBOARD CLASSROOM A115
14
13 REC CLASSROOM A213 N. WALL
R
20A/1P
20A/1P
EQ
SMARTBOARD CLASSROOM A114
16
15 REC CLASSROOM A212 S. WALL
R
20A/1P
20A/1P
EQ
SMARTBOARD CLASSROOM A100
18
17 REC CLASSROOM A212 W. WALL
R
20A/1P
20A/1P
EQ
TVS CLASSROOMS A114, A100
20
19 REC CLASSROOM A212 W. WALL
R
20A/1P
20A/1P
SPARE
22
21 REC CLASSROOM A212 W. WALL
R
20A/1P
20A/1P
SPARE
24
23 REC CLASSROOM A212 N. WALL
R
20A/1P
20A/1P
SPARE
26
25 REC CLASSROOM A212 N. WALL
R
20A/1P
20A/1P
SPARE
28
27 REC CLASSROOM A212 N. WALL
R
20A/1P
20A/1P
SPARE
30
29 REC CLASSROOM A212 E. WALL
R
20A/1P
20A/1P
SPARE
32
31 REC CLASSROOM A212 E. WALL
R
20A/1P
20A/1P
SPARE
34
33 MECH LV POWER SUPPLY
EQ
20A/1P
20A/1P
SPARE
36
35 SMARTBOARD CLASSROOM A209
EQ
20A/1P
DESCRIPTION
#
N
DESCRIPTION
#
PHASE C
PHASE B
PHASE A
800
720
720
1200
720
1000
720
720
720
720
720
720
720
720
720
720
720
720
720
720
720
720
720
720
1176
720
720
640
720
1081
800
2080
500
#
TYPE
EQ
TV ROOMS A203, A207
2
20A/1P
EQ
TV CLASSROOMS A209, A212, A213
4
20A/1P
EQ
SMARTBOARD ROOMS A212, A213
6
20A/1P
R
REC CLASSROOM A209 S. WALL
8
20A/1P
R
REC CLASSROOM A209 E. WALL
10
20A/1P
R
REC CLASSROOM A209 E. WALL
12
20A/1P
R
REC CLASSROOM A209 E. WALL
14
20A/1P
R
REC CLASSROOM A209 N. WALL
16
20A/1P
R
REC CLASSROOM A209 N. WALL
18
20A/1P
R
REC CLASSROOM A209 W. WALL
20
20A/1P
R
REC CLASSROOM A209 W. WALL
22
20A/1P
R
REC CLASSROOM A209 W. WALL
24
20A/1P
M
EF-23-3
26
20A/1P
EQ
KM
28
20A/2P
EQ
CRAC-5-4, CU-5-4
30
-
-
-
32
15A/2P
EQ
CRAC-5-1, CU-5-1
34
-
-
-
36
1081
720
DESCRIPTION
BRKR
20A/1P
2080
37 SPARE
20A/1P
20A/1P
SPARE
38
37 SPARE
20A/1P
20A/1P
SPARE
38
37 SPARE
20A/1P
20A/1P
SPARE
38
39 SPARE
20A/1P
20A/1P
SPARE
40
39 SPARE
20A/1P
20A/1P
SPARE
40
39 SPARE
20A/1P
20A/1P
SPARE
40
41 SPARE
20A/1P
20A/1P
SPARE
42
41 SPARE
20A/1P
20A/1P
SPARE
42
41 SPARE
20A/1P
20A/1P
SPARE
42
7060
6260
6760
TOTAL CONNECTED PHASE LOAD
14980
15560
14520
VA
124.8
129.7
121.0
AMPS
TOTAL CONNECTED PHASE LOAD
VA
7060
6260
6760
VA
58.8
52.2
56.3
AMPS
TOTAL CONNECTED LOAD
KVA
AMPS
45.06
125.1
* FEED-THRU LUGS
TOTAL CONNECTED LOAD
LARGEST MOTOR LOAD * 25%
LARGEST MOTOR LOAD * 25%
(RECEPTACLE LOADS - 10KVA) * 50%
-11.20
-31.1
33.86
94.0
-3.64
2RNA2
SD-70 Pueblo West HS Renovation & Addition
LOCATION: 2ND FLR ELEC RM
208Y/120V, 3PH-4W+GND
MOUNTING: SURFACE
RATING: 10K AIC
TYPE
BRKR
REC TV STUDIO A208 SE WALL
R
20A/1P
3
REC TV STUDIO A208 E. WALL
R
20A/1P
5
REC TV STUDIO A208 N. WALL
R
20A/1P
7
CORD REEL TV STUDIO A208
R
20A/1P
9
CORD REEL TV STUDIO A208
R
20A/1P
11 CORD REEL TV STUDIO A208
R
20A/1P
13 REC TV STUDIO A208 SW WALL
R
20A/1P
15 REC TV STUDIO A208 W. WALL
R
20A/1P
17 REC TV CLASSROOM A207 N. WALL
R
20A/1P
19 REC TV CLASSROOM A207 E. WALL
R
20A/1P
21 REC TV CLASSROOM A207 E. WALL
R
20A/1P
23 REC TV CLASSROOM A207 E. WALL
R
20A/1P
25 REC TV CLASSROOM A207 S. WALL
R
20A/1P
27 REC TV CLASSROOM A207 SW WALL
R
20A/1P
29 REC TV CLASSROOM A207 NW WALL
R
20A/1P
DESCRIPTION
PHASE C
900
1080
720
720
720
740
180
740
180
360
180
2000
720
2000
720
2000
720
2000
720
2000
720
25400
23801
VA
200.6
211.7
198.3
AMPS
16.44
1200
720
720
720
720
VA
OPTIONS:
KVA
AMPS
TOTAL CONNECTED LOAD
73.28
203.4
LONG CONTINUOUS LOADS * 25%
2.50
6.9
LARGEST MOTOR LOAD * 25%
0.29
0.8
-17.68
-49.1
58.39
162.1
45.6
* FEED-THRU LUGS
KITCHEN LOADS * 0%
2RNA3
RWA
M-E ENGINEERS, INC.
SD-70 Pueblo West HS Renovation & Addition
LOCATION: 2ND FLR ELEC RM
208Y/120V, 3PH-4W+GND
LOCATION: CRAWLSPACE
208Y/120V, 3PH-4W+GND
MLO
MOUNTING: SURFACE
MLO
MOUNTING: SURFACE
MLO
225A BUS
RATING: 10K AIC
225A BUS
RATING: 10K AIC
DESCRIPTION
#
N
BRKR
TYPE
TYPE
BRKR
20A/1P
R
2ND FLOOR HALLWAY REC
2
1
REC CLASSROOM A203 E. WALL
R
20A/1P
20A/1P
R
CONV REC ROOMS A215, A214, A211
4
3
REC CLASSROOM A203 E. WALL
R
20A/1P
20A/1P
R
CONV REC ROOMS A205, A206, A204, A202
6
5
REC CLASSROOM A203 E. WALL
R
20A/1P
20A/1P
EQ
EWC-1
8
7
REC CLASSROOM A203 NE WALL
R
20A/1P
20A/1P
EQ
EWC-1
10
9
REC CLASSROOM A203 N. WALL
R
20A/1P
N
DESCRIPTION
#
20A/1P
R
REC TELECOMM A210
12
11 REC CLASSROOM A203 W. WALL
R
20A/1P
30A/1P
LT
LT TV STUDIO A208
14
13 REC CLASSROOM A203 W. WALL
R
20A/1P
30A/1P
LT
LT TV STUDIO A208
16
15 REC CLASSROOM A203 W. WALL
R
20A/1P
30A/1P
LT
LT TV STUDIO A208
18
17 REC CLASSROOM A203 S. WALL
R
20A/1P
30A/1P
LT
LT TV STUDIO A208
20
19 REC CLASSROOM A217 E. WALL
R
20A/1P
30A/1P
LT
LT TV STUDIO A208
22
21 REC CLASSROOM A217 N. WALL
R
20A/1P
30A/1P
EQ
2ND FLR CLOCKS
24
23 REC CLASSROOM A217 N. WALL
R
20A/1P
20A/1P
SPARE
26
25 REC CLASSROOM A217 W. WALL
R
20A/1P
20A/1P
SPARE
28
27 REC CLASSROOM A217 SW WALL
R
20A/1P
20A/1P
SPARE
30
29 REC CLASSROOM A217 SE WALL
R
20A/1P
PHASE C
PHASE B
PHASE A
720
720
720
720
720
720
720
720
720
720
720
720
800
720
1000
720
M-E ENGINEERS, INC.
100A BUS
VA
VA
PHASE B
PHASE A
720
24077
-10.1
VA
1
TOTAL CONNECTED PHASE LOAD
TOTAL LOAD
M-E ENGINEERS, INC.
#
13380
(RECEPTACLE LOADS - 10KVA) * 50%
TOTAL LOAD
SD-70 Pueblo West HS Renovation & Addition
55.7
14920
KITCHEN LOADS * 0%
KITCHEN LOADS * 0%
TOTAL LOAD
AMPS
14540
LONG CONTINUOUS LOADS * 25%
LONG CONTINUOUS LOADS * 25%
(RECEPTACLE LOADS - 10KVA) * 50%
KVA
20.08
FEED-THRU PANEL 2RNA2 PHASE LOAD
1000
720
720
720
720
720
720
720
DESCRIPTION
#
BRKR
TYPE
20A/1P
R
REC CLASSROOM A200 E. WALL
2
20A/1P
R
REC CLASSROOM A200 N. WALL
20A/1P
R
REC CLASSROOM A200 W. WALL
20A/1P
R
20A/1P
R
20A/1P
R
20A/1P
EQ
20A/1P
20A/1P
N
DESCRIPTION
TYPE
BRKR
EQ
20A/2P
N
#
1
1
B-4
4
3
-
6
5
SHUNT TRIP FOR CKT 1,3
REC CLASSROOM A200 SW WALL
8
7
MECHANICAL ROOM EPO
REC CLASSROOM A200 S. WALL
10
9
SPARE
REC CLASSROOM A200 E. WALL
12
11 DDC CONTROL PANELS
TVS CLASSROOMS A217, A200
14
13 SPARE
20A/1P
EQ
SMARTBOARD ROOMS A207, A203
16
15 SPARE
EQ
SMARTBOARDS ROOMS A217, A200
18
17 SPARE
20A/1P
SPARE
20
20A/1P
SPARE
20A/1P
-
PHASE C
PHASE B
PHASE A
BRKR
-
1185
1185
20A/1P
20A/2P
EQ
-
-
1185
DESCRIPTION
TYPE
20A/1P
1185
#
SHUNT TRIP FOR CKT 4,6
2
B-5
4
-
6
20A/1P
SPARE
8
20A/1P
SPARE
10
20A/1P
SPARE
12
20A/1P
SPARE
14
20A/1P
20A/1P
SPARE
16
20A/1P
20A/1P
SPARE
18
19 SPACE
SPACE
20
22
21 SPACE
SPACE
22
SPARE
24
23 SPACE
SPACE
24
20A/1P
SPARE
26
25 SPACE
SPACE
26
20A/1P
SPARE
28
27 SPACE
SPACE
28
20A/1P
SPARE
30
29 SPACE
SPACE
30
EQ
20A/1P
400
20A/1P
EQ
20A/1P
800
31 SPARE
20A/1P
20A/1P
SPARE
32
31 SPARE
20A/1P
20A/1P
SPARE
32
31 SPACE
SPACE
32
33 SPARE
20A/1P
20A/1P
SPARE
34
33 SPARE
20A/1P
20A/1P
SPARE
34
33 SPACE
SPACE
34
35 SPARE
20A/1P
20A/1P
SPARE
36
35 SPARE
20A/1P
20A/1P
SPARE
36
35 SPACE
SPACE
36
37 SPARE
20A/1P
20A/1P
SPARE
38
37 SPARE
20A/1P
20A/1P
SPARE
38
37 SPACE
SPACE
38
39 SPARE
20A/1P
20A/1P
SPARE
40
39 SPARE
20A/1P
20A/1P
SPARE
40
39 SPACE
SPACE
40
41 SPARE
20A/1P
20A/1P
SPARE
42
41 SPARE
20A/1P
20A/1P
SPARE
42
41 SPACE
SPACE
42
FEED-THRU PANEL 2RNA3 PHASE LOAD
5840
6040
6040
TOTAL CONNECTED PHASE LOAD
14540
14920
13380
VA
121.2
124.3
111.5
AMPS
TOTAL CONNECTED PHASE LOAD
VA
5840
6040
6040
VA
48.7
50.3
50.3
AMPS
OPTIONS:
KVA
AMPS
TOTAL CONNECTED LOAD
42.84
118.9
LONG CONTINUOUS LOADS * 25%
2.50
6.9
LARGEST MOTOR LOAD * 25%
(RECEPTACLE LOADS - 10KVA) * 50%
TOTAL CONNECTED LOAD
-8.68
-24.1
101.8
AMPS
49.7
1585
2370
1985
VA
13.2
19.8
16.5
AMPS
TOTAL CONNECTED LOAD
LONG CONTINUOUS LOADS * 25%
LARGEST MOTOR LOAD * 25%
LARGEST MOTOR LOAD * 25%
-2.56
-7.1
15.36
42.6
KITCHEN LOADS * 0%
TOTAL LOAD
36.66
KVA
17.92
TOTAL CONNECTED PHASE LOAD
LONG CONTINUOUS LOADS * 25%
(RECEPTACLE LOADS - 10KVA) * 50%
KITCHEN LOADS * 0%
TOTAL LOAD
* FEED-THRU LUGS
N
E6.3
FEED-THRU PANEL 1RNA2 PHASE LOAD
OPTIONS:
N
225A BUS
VA
VA
PHASE B
PHASE A
720
1
NOTES:
KITCHEN LOADS * 0%
TOTAL LOAD
4228
KVA
* CIRCUITS ARE EXISTING TO REMAIN U.O.N.
(RECEPTACLE LOADS - 10KVA) * 50%
KITCHEN LOADS * 0%
3393
N
OPTIONS:
VA
LARGEST MOTOR LOAD * 25%
1. CIRCUIT BREAKER HAS SHUNT TRIP.
(RECEPTACLE LOADS - 10KVA) * 50%
N
#
LTG - EXIT SIGNS
20A/3P
OPTIONS:
BENJAMIN TALPOS
BRKR
20A/1P
275
20A/1P
TOTAL CONNECTED PHASE LOAD
9/11/2013 11:52:37 AM
PHASE C
PHASE B
PHASE A
1488
19
41
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
M-E ENGINEERS, INC.
VA
VA
VA
EQ
ELW
LOCATION:
MOUNTING: SURFACE
TYPE
853.4
SD-70 Pueblo West HS Renovation & Addition
480Y/277V, 3PH-4W+GND
DESCRIPTION
670.1
M-E ENGINEERS, INC.
LOCATION: CRAWLSPACE
AHU-23
0.9
-129.0
-206.5
TOTAL LOAD
SD-70 Pueblo West HS Renovation & Addition
1
6.9
KITCHEN DIVERSITY
516.4 KVA
1416.4 KVA
1704.4 A, 480V-3PH
M-E ENGINEERS, INC.
#
791.3
17.2
LCL x 25%
LML x 25%
SD-70 Pueblo West HS Renovation & Addition
N
203.4
1,039.9
SUB TOTAL
RECEPTACLE DIVERSITY
NEW LOAD TO BE ADDED FROM NEW WORK:
TOTAL CALCULATED LOAD FOR MSB:
AMPS
DESCRIPTION
-
525.7
490.9
TOTAL LOAD
720.0 KVA
900.0 KVA
DESCRIPTION
PUEBLO COUNTY SCHOOL DISTRICT 70
B
3
DESCRIPTION
KVA
AMPS
5.94
16.5
NOTES:
1. CIRCUIT BREAKER HAS SHUNT TRIP.
(RECEPTACLE LOADS - 10KVA) * 50%
KITCHEN LOADS * 0%
TOTAL LOAD
5.94
16.5
N
1
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
2
DESCRIPTION
Pueblo West High School Additions + Renovations
DP2
Revisions
1
Architecture Engineering Planning Interiors
77.7
DESCRIPTION
37-13102-00
09.12.2013
CKT
A
661 W Capistrano Ave
Pueblo West, CO 81007
AMPS
1
CKT
ELECTRICAL PANEL SCHEDULES
SWITCHBOARD
"MSB3"
LOAD SCHEDULE
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
SWITCHBOARD
"MSB2"
LOAD SCHEDULE
RBW
ERW
M-E ENGINEERS, INC.
M-E ENGINEERS, INC.
SD-70 Pueblo West HS Renovation & Addition
LOCATION:
208Y/120V, 3PH-4W+GND
LOCATION:
208Y/120V, 3PH-4W+GND
MOUNTING: SURFACE
MLO
MOUNTING: SURFACE
50A MCB
RATING: 10K AIC
125A BUS
RATING: 10K AIC
125A BUS
VA
VA
20A/1P
PHASE B
DESCRIPTION
#
12
14
16
15 SPACE
SPACE
16
18
17 SPACE
SPACE
18
14
15 SPACE
SPACE
17 SPACE
SPACE
TOTAL CONNECTED PHASE LOAD
1020
1260
2320
2460
2942
VA
19.3
20.5
24.5
AMPS
ELEVATOR PIT AND MECH RM
SPACE
SPACE
20A/1P
9
13 SPACE
13 SPACE
20A/1P
M
11 ELEVATOR CAB LIGHTS
10
12
M
2
SPACE
10
SPARE
SP-5-1
11 SE-5-1
2
SPACE
SPARE
9
1
SPACE
8
20A/1P
1
720
400
7
6
20A/1P
20A/1P
20A/1P
SPARE
8
EQ
20A/1P
EQ
4
CMP - IT ROOM N WALL
DDC CONTROL PANEL
EQ
CMP - F/S DAMPERS
UNIT HEATER UH-02, UH-5-1
EQ
7
720
CMP - FIRE ALARM SYS
UNIT HEATER UH-01
20A/1P
1
962
5
M
6
720
3
M
4
CMP - IT ROOM E WALL N
720
1
#
PHASE A
PHASE C
1130
500
750
670
900
TOTAL CONNECTED LOAD
AMPS
7.72
21.4
EQ
20A/1P
LT
20A/1P
TOTAL CONNECTED PHASE LOAD
484
300
1630
1904
1693
VA
13.6
15.9
14.1
AMPS
LARGEST MOTOR LOAD * 25%
0.32
0.9
1. NEW LOAD ON EXISTING SPARE BREAKER.
(RECEPTACLE LOADS - 10KVA) * 50%
2. PROVIDE NEW CIRCUIT BREAKER.
KITCHEN LOADS * 0%
8.04
22.3
1
AMPS
TOTAL CONNECTED LOAD
5.23
14.5
LONG CONTINUOUS LOADS * 25%
0.08
0.2
LARGEST MOTOR LOAD * 25%
0.28
0.8
NOTES:
1. REVISED LOAD ON EXISTING CKT.
(RECEPTACLE LOADS - 10KVA) * 50%
2. PROVIDE NEW CIRCUIT BREAKER.
KITCHEN LOADS * 0%
TOTAL LOAD
* CIRCUITS ARE EXISTING TO REMAIN U.O.N.
5.58
15.5
© 2013 , DLR Group inc., a Colorado corporation, ALL RIGHTS RESERVED
Architecture Engineering Planning Interiors
M-E Engineers, Inc.
3425 austin bluffs pkwy, ste 201
colorado springs, co 80918
t. 719.536.0036/ f. 719.536.0037
www.me-engineers.com
BENJAMIN TALPOS
9/11/2013 11:52:39 AM
C:\Documents and Settings\eeifealdt\My Documents\temp\37-13102-00_Pueblo-West-HS-Addition_MEP_2013_eeifealdt.rvt
E6.4
ELECTRICAL PANEL SCHEDULES
TOTAL LOAD
NOTES:
N
OPTIONS:
KVA
* CIRCUITS ARE EXISTING TO REMAIN U.O.N.
LONG CONTINUOUS LOADS * 25%
493
20A/1P
OPTIONS:
KVA
#
20A/1P
CMP - IT ROOM E WALL S
EQ
20A/1P
DESCRIPTION
20A/1P
EQ
20A/1P
EQ
N
DESCRIPTION
PHASE B
2
20A/1P
R
GWH-1, RP-1
20A/1P
SUMP PUMP SP-01
20A/1P
REC - CRAWL SPACE S.
5
EQ
M
2
3
BRKR
CMP - AHU CTRL PANELS
TYPE
CMP - IT ROOM E WALL S
1
TYPE
1
BRKR
EQ
PHASE C
720
N
20A/1P
TYPE
PHASE A
480
PUEBLO COUNTY SCHOOL DISTRICT 70
BRKR
R
BRKR
REC - ELEC RM + CP 01
Pueblo West High School Additions + Renovations
TYPE
20A/1P
1
Revisions
DESCRIPTION
#
37-13102-00
09.12.2013
N
661 W Capistrano Ave
Pueblo West, CO 81007
SD-70 Pueblo West HS Renovation & Addition