Addendum#2 - RNF Ventures Ltd.

advertisement
Lloydminster & District Co-op Admin Building
ADDENDUM #2
Lloydminster, SK
SECTION 00 00 02
R.K.E. File 13-496
Page 1 of 2
General
This Addendum will be attached to and form part of the Contract Documents.
It is the responsibility of Contractors and bidders to ensure that their subcontractors are familiar with all items
included in this Addendum. This addendum contains a total of 3 pages, including sketches.
A2.1
Specifications
A2.1.1
.1
A2.2
Ref: Section 26 27 28: Electric Heat
Electrical contractor to provide and install all control wiring for 24 volt low voltage
relays and remote thermostats.
Co-op Drawings
A2.2.1
.1
.2
Ref: Drawing A8.0: Interior Elevations
Plan 1: 2nd Floor Plan: Clarification: Closet 220.1 is to come with closet rod and shelf.
Elevation 13: Clarification: Glass doors to be flush with cabinet doors below.
A2.2.2
.1
Ref: Drawing M8.3: Specifications
Lavatory L-1 shall be revised to read as follows:
“L-1 (Barrier Free): Equal to Crane model 1280V, self-rimming counter top vitreous
china lavatory to be complete with mounting hardware, off-set waste assembly and
insulated supply and waste assemblies with Handi-Lav-Guard by Truebro Inc.
Delta Commercial model 21C-133 trim.
Acceptable equivalents: American Standard, Briggs, Kohler.”
A2.2.3
.1
Ref: Drawing E1.1: Site Plan
See attached S(E1.1)R2 for revised circuit designation of vehicle pedestals (two
stalls per circuit) and revised cable quantities.
A2.2.4
.1
Ref: Drawing E2.1: Lighting Plan
Revise Type DD to read:
1220 TWO LAMP WALL MOUNTED FLUORESCENT C/W WHITE POWDER
COAT FINISH REFLECTOR, DIE-FORMED COLD ROLLED STEEL HOUSING,
WHITE OPAL LENS AND ELECTRONIC BALLAST.
CORELITE #AW-WO-2T8-1C-UNV OR APPROVED EQUIVALENT
C/W 2-F32T8/835 LAMPS
120V
.2
Revise Type 1 Luminaire to read:
LED EXTERIOR WALL MOUNT LUMINAIRE C/W MIN. 1600 DELIVERED
LUMENS, EPOXY-COATED DIE-CAST ALUMINUM HOUSING AND BACKPLATE,
UPLIGHT AND DOWNLIGHT, DIFFUSED TEMPERED GLASS OR ACRYLIC
LENS, BRUSHED ALUMINUM FINISH, 4000°K COLOUR TEMPERATURE.
LUMIERE “EON” #303-W2-LEDB2-4000-UNV-T2-BA
TMS LIGHTING #GE625-A-1-F18
120V.
A2.2.5
.1
Ref: Drawing E7.1: Single Line Diagram and Details
Delete 12-15A1P breakers from Panel A and replace with spares.
Subject to compliance with the requirements, the following items indicated as Approved may be incorporated
into the Work.
Approved Equivalents: Architectural
Specified
Approved Equivalent
Section 08 12 00 Automatic Door Opener
GyroTech Model GT 8500, Stanley Magic Force
Lloydminster & District Co-op Admin Building
Lloydminster, SK
R.K.E. File 13-496
ADDENDUM #2
SECTION 00 00 02
Page 2 of 2
Approved Equivalents: Mechanical, Drawing M8.2 & M8.3
Specified
Approved Equivalent
Crane, American Standard, Zurn, Kohler (Water Closets)
Contrac, Mansfield
Non-specified drainage and supplies
Delta Commercial
Crane, American Standard, Zurn, Kohler (Lavatories)
Contrac, Mansfield
Fiat (Mop Sinks)
Acorn, Zurn
Crane, American Standard, Zurn (Urinals)
Contrac, Mansfield, Kohler
Delta (S-1 & S-2 trim)
Zurn, Symmons, Kohler, Sloan
MiFab (Floor drains, trap primers, cleanouts)
Zurn, Watts
Conbraco (backflow preventors)
Zurn Wilkins, Watts
Watts (thermal expansion tank)
Zurn Wilkins
Price (Louvers)
Ventex, Westvent
Tamco (Control Dampers)
Alumavent
Price, Ruskin, Greenheck (Fire dampers)
Nailor
Lennox
York, Armstrong, Carrier
Aeromatic (HRV’s)
Lifebreath, Venmar
Price (Grilles, Diffusers, Registers)
Titus, Krueger
Cook
Broan Commercial, PennBarry
Barnes (Sump Pumps)
Bell & Gossett
Approved Equivalents: Electrical
Item
Type BB
Manufacturer
Focal Point, Pinnacle
Type CC
Visioneering, PMC Lighting
Type DD
HE Williams
Type A
Philips
Type B
Maxilite
Type C
Philips, Juno
Ceiling Occupancy Sensors
Greengate
Wall Occupancy Sensors
Greengate, Hubbell
Baseboard Heaters
Stelpro
Emergency Lighting
Beghelli
Exit Lighting
Beghelli
- End of Addendum #2 -