DPS/NRBPSU/11/N1/2239 TENDER DOCUMENT NO BARC/NRB/FRWMD/FRFCF/46750/SP/007 SUPPLY OF PID CONTROLLERS CONTENTS OF THE TENDER DOCUMENT SECTION - A SECTION - B SECTION - C TECHNICAL SPECIFICATIONS SCHEDULE OF QUANTITIES PRICE SCHEDULE SECTION-A TECHNICAL SPECIFICATIONS I) DETAILED SPECIFICATIONS : 1) End Use & Requirement : These PID Controllers shall be used in ACVE system of WMP,FRFCF. These items are to be delivered at FRFCF stores, IGCAR, Kalpakkam. 2) PID CONTROLLER : i) Make : CHINO ( M-System ) (SC110-10-M2/E , SC 210 -11-M2 /300/M2/E/1MV) / YOKOGAWA(US1000-00/A10)/Honeywell(DC1040-CL-302-000-E) /Equivalent ii) It shall be electronic microprocessor based / digital indicating type PID controller. It shall function as a single loop controller, receiving an input from a measured variable and giving an output of desired characteristics as per setting and the following specifications. The indication of measured variable ( MV) , set point ( SP) and output to the final control element shall be by LED or bar graphs. The MV, SP and output bar graphs shall be of different colour for easy distinguishability or shall be 3& ½ digits LED. It shall be flush panel mounted with dimension of 98 x 98 x 100 mm or as mentioned in make specified above. Enclosure protection shall be IP 65. iii) Indications : MV and SP : 200 segments bar graphs / 3&1/2 digits LED Output segment : 50 segments bar graphs / 3&1/2 digits LED Power supply & Fault indication : LED lamps. Deviation alarms : Flashing position of indication above. iv) Function Details : Operating Mode : Both Automatic and Manual Transfer from automation to manual & vice versa : bumpless smooth transfer. Control Action : P+I+D Set point : Externally Adjustable. Input : 4 to 20 mA DC linear Output : 4 to 20 mA DC linear Proportional Band : Adjustable from 1 to 500 % Integral Action : 0.03 to 60 min Derivative Action : 1 to 15 min. Controller should have auto tuned facility. Manual operating Range : Internal drive – 5 secs full scale for fast and 40 secs. Full Full scale for slow operation. Set Point : Externally continuously adjustable. Power Supply : 230 V AC , 50 Hz. v) Performance Characteristics : MV & SP accuracy of indication : +/- 0.5% FS Output indication accuracy : +/- 2 % FS Control Accuracy : +/ - 0.2 % FS Influence of common mode or normal mode & RF: Nil Drift on manual output SP vi) Inspection & Tests required : No drift. : a. Physical & Functional tests for 100% qty. b. Calibration test for 100% qty. c. Dimensional Check etc for 100% qty etc. vii) REQUIREMENT: 15 nos. 3) IDENTIFICATION: Each instrument shall be identified with the following information: The Manufacturer shall inscribe the Manufacturer’s serial no. on the instrument. The identification serial no. shall appear on the test data sheets. a) Manufacturer’s name or identity. b) Manufacturer’s model and/or serial number. In addition, each instrument shall be identified by aluminium tag of suitable dimensions, affixed to it firmly in a prominent position by means of a corrosion resistant wire, and bearing the following information in a permanent (preferably engraved) form: a) Purchase order No. b) Tag No. as indicated in the individual specification sheet. 4) PACKING: All openings shall be protected by suitable plastic caps/plugs. Individual item shall be packed with adequate sealing to prevent ingress of moisture /dust and with adequate cushioning material to prevent damage during shipment, delivery and storage at site. The method of packing is subjected to approval of purchaser/ indenter. All the packages shall be clearly marked in a suitable permanent manner with the following information: a) Purchase Order No. b) Brief description of the item c) Quantity I) QUOTATION : Quotations shall be submitted in duplicate along with company’ s profile, manufacturing techniques, sources of raw materials, manufacturing and testing facilities available as well as quality assurance program supported by detailed technical literature. All the specifications shall be answered and any deviation in the quoted item from above specifications shall be clearly brought out. Reputed manufacturer / supplier with QA & testing facilities for instrumentation items shall only be considered. Any previous supply of instrumentation items to any DAE units and / or reputed companies shall be mentioned with purchase order details. II) FACTORY EVALUATION, INSPECTION , TESTING & DOCUMENTATION Purchaser reserves the right to evaluate supplier’s works himself or by his representative. Successful bidder shall have to present the item to the purchaser for his inspection and shall also carry in his presence necessary tests as mentioned in QAP to demonstrate performance of the item as per ordered specifications. IV ) DELIVERY PERIOD : 12 months from the date of PO placed. V) WARRANTY PERIOD : 24 months from the date of delivery. VI) VALIDITY : Quotation shall be valid for 120 days . ***** SECTION-B SCHEDULE OF QUANTITIES s.n. Description of Items to be supplied Unit 1 PID Controllers Nos. Total Qty 15 SECTION – C PRICE SCHEDULE S.N. 1 a) b) c) d) e) f) g) h) i) Description of Items to be supplied Qty. PID Controllers Unit Rate (Rs.) Total in Rupees Total Price of Essential Spares if any (Rs.)__________________________________ Total Price of Recommended Spares if any (Rs.)_____________________________ Discount if any (Rs.)____________________________________________________ Excise Duty (%)/ Nil against Govt. Certificate:_______________________________ VAT/CST (%)________________________________________________________ Packing/ Forwarding (Rs.)_______________________________________________ Freight (Rs.)__________________________________________________________ GRAND TOTAL (Rs.) (Both in Figure & Word)_____________________________ Validity of the offer____________________________________________________ Signature Designation Company Date Seal of Company