PowerPact™ M-, P- and R-Frame, and Compact™ NS630b–NS3200 Circuit Breakers Section 2—Electronic Trip Systems exceeded, will trip the circuit breaker with no intentional delay. Instantaneous trip dial settings are 2–16 x In for 600 A circuit breakers and 1.5–12 x In for 800–1200 A circuit breakers. Micrologic™ Electronic Trip Systems The P-frame, R-frame and NS630b–NS3200 electronic trip circuit breakers can be equipped with the optional Micrologic trip systems listed below: Table 15: Micrologic Trip Systems (LSIG) Long-time + Short-time + Instantaneous Protection + Equipment Ground-fault Protection (UL LIsted, IEC Rated) Model (LS0) Long-time + Short-time + Zero delay (IEC Rated Only) (LI) Long-time + Instantaneous Protection (UL Listed, IEC Rated) (LSI) Long-time + Short-time + Instantaneous Protection (UL LIsted, IEC Rated) Micrologic Basic Trip Unit 2.0 3.0 5.0 — Micrologic A Trip Unit 2.0A 3.0A 5.0A 6.0A Micrologic P Trip Unit — — 5.0P 6.0P Micrologic H Trip Unit — — 5.0H 6.0H Trip units are designed to protect power circuits and loads. Micrologic trip systems use a set of current transformers (called CTs or sensors) to sense current, a trip unit to evaluate the current, and a tripping solenoid to trip the circuit breaker. Adjustable rotary switches on the trip unit allow the user to set the proper overcurrent or equipment ground-fault current protection required in the electrical system. If current exceeds a set value for longer than its set time delay, the trip system opens the circuit breaker. Alarms may be programmed for remote indications. Measurements of current, voltage, frequency, power, and power quality optimize continuity of service and energy management. Integration of protection functions in the Application Specific Integrated Circuit (ASIC) electronic component used in all Micrologic trip units guarantees a high degree of reliability and immunity to conducted or radiated disturbances. On Micrologic P and H trip units, advanced functions are managed by an independent microprocessor. Circuit breakers are shipped with the trip unit long-time pickup switch set at 1.0 and all other trip unit adjustments set at their lowest settings. Actual settings required for a specific application must be determined by a qualified consultant or plant engineer. A coordination study is recommended to provide coordination between all circuit breakers in the distribution system. Table 16: Micrologic™ Trip Unit Features Micrologic Trip Unit (X = Standard Feature O = Available Option) Feature Standard Field-Installable Harmonics 3.0 5.0 2.0A 3.0A 5.0A 6.0A 5.0P 6.0P 5.0H 6.0H X X X X X X X X X X X X LS0 Power 2.0 LI X X X LSI LSIG/Ground-Fault Ammeter X X Trip1 X X Ground-Fault Alarm/No Trip1, 2 X X X Ground-Fault Alarm and Trip1, 2 X X X X Adjustable Rating Plugs X X X X X X X X X X X True RMS Sensing X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X UL Listed Thermal Imaging X Phase-Loading Bar Graph 23 © 2001–2012 Schneider Electric All Rights Reserved ™ 10/2012 PowerPact™ M-, P- and R-Frame, and Compact™ NS630b–NS3200 Circuit Breakers Section 8—Accessories Micrologic™ Trip Unit Accessories Circuit breakers are shipped with trip unit installed, but can have the trip units replaced in the field. Actual trip units and settings required for specific applications must be determined by a qualified consultant or plant engineer. A coordination study is recommended to provide coordination between all circuit breakers in the distribution system. Table 70: Field-Installable Micrologic Trip Unit Model Protection Additional Features Field-Installable Cat. No.1 2.0 (IEC only) 3.0 (UL/ANSI only) 5.0 LSO LI LSI None S132R S131A S133A 2.0A (IEC only) 3.0A (UL/ANSI only) 5.0A 6.0A LSO LI LSI LSIG Ammeter S142R S141A S143A S144A 5.0P 6.0P LSI LSIG Metering, Advanced Protection S163A 2 S164A 2 5.0H 6.0H LSI LSIG Metering, Advanced Protection & Harmonic Analysis S173A 2 S174A 2 1 The standard rating plug supplied with a trip unit is the “A” rating plug. To specify an alternative adjustable rating plug, please add the letter designation to the end of the catalog number. Please refer to Digest for a complete listing of adjustable settings available with each plug. (Example: S143B would specify a “B” rating plug instead of the standard "A" plug.) Use suffix “N” if no rating plug is required. When replacing a Basic trip unit with Type A (Ammeter), P (Power metering) or H (Harmonic analysis) trip unit, order the 12pin connector kit S33101 for the PowerPact P-frame drawout circuit breakers or kit S33100 for PowerPact P-frame unit-mount and R-frame circuit breakers. 2 Requires Circuit Breaker Communications Module. Lead-Free Trip Unit Sealing Kit The MICROTUSEAL lead-free trip unit seal was designed as a RoHS-compliant replacement for lead seals. It may be used to seal Micrologic trip units and other devices. It is manufactured as a stainless steel cable and polycarbonate locking mechanism which shows evidence of tampering. The seal is individually numbered for control purposes. Order kit number MICROTUSEAL . Replacement Covers Table 71: Replacement Covers Device Cat. No. Micrologic A Trip Unit Cover, clear S33592 Micrologic P/H Trip Unit Cover, opaque gray S47067 74 10/2012 ™ © 2001–2012 Schneider Electric All Rights Reserved