LV Condensing Section 8 733 922 118 (2015/01) Installation, Operation and Maintenance Manual 2 | Condensing Section/Air Handler Pairing LV Condensing Section CONTENTS Condensing Section/Air Handler Pairing ............................. 2 CONDENSING SECTION/AIR HANDLER PAIRING UNIT MODEL Key to Symbols.................................................................. 3 Safety Warnings................................................................ 3 General Description........................................................... 4 Moving and Storage........................................................... 4 Initial Inspection ............................................................... 4 Location............................................................................ 4 Condensing Section ..................................................... 4 Air Handler ................................................................. 5 Water Quality .................................................................... 5 INSTALLATION .................................................................. 7 Condensing Section ..................................................... 7 Water Piping ..................................................................... 7 Electrical .......................................................................... 7 - High Voltage.............................................................. 8 - Low Voltage .............................................................. 8 Cooling and Heating Modes ........................................... 9 Unit Protection Module Safety Features .......................... 9 Options........................................................................... 14 Unit Mounted Non-Fused Disconnect Switch.................. 14 Internal 2-Way Water Valve ......................................... 14 Automatic Flow Control Valve ...................................... 14 LED Annunciator........................................................ 14 Flow Proving Switch................................................... 14 Application Considerations .............................................. 14 Well Water Systems ................................................... 14 Cooling Tower/Boiler Systems ..................................... 15 Geothermal Systems .................................................. 17 LV018-1CSC LV018-2CSC LV024-1CSC LV024-2CSC LV024-3CSC LV024-4CSC LV030-1CSC LV030-2CSC LV030-3CSC LV030-4CSC LV036-1CSC LV036-2CSC LV036-3CSC LV036-4CSC LV042-1CSC LV042-3CSC LV042-4CSC LV048-1CSC LV048-3CSC LV048-4CSC LV060-1CSC LV060-3CSC LV060-4CSC LV070-1CSC LV070-3CSC LV070-4CSC Paired Air Handler Unit 1 Unit 2 LV018-1AVX LV018-1AHX LV018-2AVX LV018-2AHX LV024-1AVX LV024-1AHX LV024-2AVX LV024-2AHX LV024-1AVX LV024-1AHX LV024-4AVX LV024-4AHX LV030-1AVX LV030-1AHX LV030-2AVX LV030-2AHX LV030-1AVX LV030-1AHX LV030-4AVX LV030-4AHX LV036-1AVX LV036-1AHX LV036-2AVX LV036-2AHX LV036-1AVX LV036-1AHX LV036-4AVX LV036-4AHX LV042-1AVX LV042-1AHX LV042-1AVX LV042-1AHX LV042-4AVX LV042-4AHX LV048-1AVX LV048-1AHX LV048-1AVX LV048-1AHX LV048-4AVX LV048-4AHX LV060-1AVX LV060-1AHX LV060-1AVX LV060-1AHX LV060-4AVX LV060-4AHX LV070-1AVX LV070-1AHX LV070-1AVX LV070-1AHX LV070-4AVX LV070-4AHX System Checkout ............................................................ 18 Unit Start-up ................................................................... 18 Maintenance ................................................................... 18 Unit Check-Out Sheet ...................................................... 20 Customer Data .......................................................... 20 Unit Nameplate Data .................................................. 20 Operating Conditions ................................................. 20 Auxiliary Heat............................................................ 21 Troubleshooting .............................................................. 22 Operating Temperatures and Pressures ............................ 27 Compressor Characteristics............................................. 31 Wiring Diagrams.............................................................. 32 Dimensional Drawings ..................................................... 34 Notes.............................................................................. 35 8 733 922 118 (2015/01) Subject to change without prior notice LV Condensing Section LV Condensing Section Key to Symbols | 3 LV CS MODEL NOMENCLATURE LV 024 - 1 CS C - F WATER CONNECTIONS LV F - Front SIZE COAX OPTIONS 018 024 030 036 042 048 060 070 C - Copper N - Cupro-Nickel CABINET CONFIGURATION CS - Condensing Section VOLTAGE DESIGNATIONS - 208/1/60 & 230/1/60 - 277/1/60 - 208/3/60 & 230/3/60 - 460/3/60 1 2 3 4 Revision level 032014 KEY TO SYMBOLS Warnings Warnings in this document are identified by a warning triangle printed against a grey background. Keywords at the start of the warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken. The following keywords are defined and can be used in this document: • NOTE indicates a situation that could result in damage to property or equipment. • CAUTION indicates a situation that could result in minor to medium injury. • WARNING indicates a situation that could result in severe injury or death. • DANGER indicates a situation that will result in severe injury or death. Important Information This symbol indicates important information where there is no risk to property or people. SAFETY WARNINGS Installation and servicing of this equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service the equipment. Revised 01-15 Before performing service or maintenance operations on the system, turn off main power to the unit. Electrical shock could cause personal injury or death. When working on equipment, always observe precautions described in the literature, tags, and labels attached to the unit. Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing, and place a fire extinguisher close to the work area. To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by technicians who meet local, state, and federal proficiency requirements. All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants. If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed. 8 733 922 118 (2015/01) 4 | General Description LV Condensing Section R410A is flammable when exposed to open flame. Recover all refrigerant prior to brazing. GENERAL DESCRIPTION The LV Split water-to-air heat pump provides an unmatched combination of performance, features and flexibility for both high performance new construction applications and replacement of existing water-to-air heat pumps. All units are certified by the Air conditioning, Heating and Refrigeration Institute (AHRI) to AHRI/ANSI/ ASHRAE/ISO standard 13256-1 for water-to-air and brine-to-air heat pumps at both Water Loop Heat Pump and Ground Loop Heat Pump application points. These units are safety listed with Intertek Test Labs (ETL) to cUL standard 1995 and certified to CAN/CSA C22.1 No 236. These units meet all current applicable requirements of ASHRAE 90.1. Split system heat pumps consist of two independently installed sections allowing for centralized air distribution while remotely locating the section containing the compressor and waterto-refrigerant heat exchanger. In the cooling mode, the air coil in the air handler section serves as an evaporator and the water-torefrigerant heat exchanger serves as a condenser. In the heating mode, their roles are reversed. In cooling mode, the refrigerant lines connecting the two sections consist of one line carrying liquid refrigerant and another carrying refrigerant vapor. The liquid carrying line will be referred to as the liquid line while the vapor carrying line will be referred to as the suction line. These units are designed and rated for indoor installation only. LV cabinets are constructed of heavy gauge G-90 galvanized steel and will resist most common types of corrosion for the life of the equipment. The Water-to-Air Heat Pumps are designed to operate with entering fluid temperature between 20°F to 80°F in the heating mode and between 50°F to 110°F in the cooling mode. For well water applications, a 50°F Minimum Entering Water Temperature (EWT) is recommended with sufficient water flow to prevent the water coil from freezing. Antifreeze solution is required for all closed loop applications. 8 733 922 118 (2015/01) Cooling Tower/Boiler and Geothermal applications without antifreeze must have means to protect against extreme conditions and equipment failure. Frozen water coils are not covered under warranty. Other equivalent methods of temperature control are acceptable. Several factory installed options are available: Flow Proving Switch, Auxiliary Pump Relay, Zone Valve, Measure Flow, Compressor Monitor Relay, Phase Monitor, Boilerless Control, Disconnect Switch and Status LED. See Options section for more detail. Safety devices are built into each unit to provide the maximum system protection possible when properly installed and maintained. MOVING AND STORAGE If the equipment is not needed for immediate installation upon its arrival at the job site, it should be left in its packaging and stored in a clean, dry area. Units must only be stored or moved in the normal upright position. INITIAL INSPECTION Be certain to inspect all packaging for each unit as received at the job site before signing the freight bill. Verify that all items have been received and that there are no visible damages; note any shortages or damages on all copies of the freight bill. In the event of damage or shortage, remember that the purchaser is responsible for filing the necessary claims with the carrier. Concealed damages not discovered until after removing the units from the packaging must be reported to the carrier within 24 hours of receipt. LOCATION To maximize system performance, efficiency and reliability, and to minimize installation costs, it is always best to keep the refrigerant lines as short as possible. Every effort should be made to locate the air handler and the condensing section as close as possible to each other. Condensing Section The condensing section is designed for indoor use. Locate the condensing section in an area that provides sufficient room to make water and electrical connections, and allows easy removal of the access panels, for service personnel to perform maintenance or repair. Subject to change without prior notice LV Condensing Section LV Condensing Section Air Handler Locate the air handler unit in an indoor area that allows easy removal of the filter and access panels, and has enough room for service personnel to perform maintenance or repair. Provide sufficient room to make electrical and duct connections. If the unit is located in a confined space such as a closet, provisions must be made for return air to freely enter that space. Reference the Factory Manual for your Air Handler, or the BOSCH Air Handler section of this manual for detailed installation and operation. WATER QUALITY Failure to insure proper water quality and flow rates can shorten the life of the heat pump and potentially void the unit warranty. Water Quality | 5 To limit scaling, water flow rates should be kept at 3 gallons/minute per nominal cooling ton (a 10°F temperature rise in cooling) and care should be taken to avoid air in the water lines from suction side leaks. Cupro-nickel coils are generally recommended. In installations with high hydrogen sulfide, chlorine or ammonia, corrosion is a potential problem. In these installations a cupro-nickel heat exchanger is recommended along with maintaining proper flow and keeping air out of the system. If water quality is outside of the values in Table #1, then a closed loop is recommended. Fouling due to iron bacteria can also pose problems in some open loop installations. Iron bacteria fouling can quickly degrade system performance and plug heat exchangers. Air in the water system will greatly accelerate the fouling or corrosion process. Maintaining proper water quality is important for insuring a long and trouble free service life for a heat pump. For closed loop and boiler/tower systems water chemistry can be checked and easily maintained to insure that corrosive elements, dissolved oxygen and pH levels are kept in check. It is important to insure that any additive, antifreeze or corrosion inhibitor that is added to the water loop is compliant with all applicable laws and regulations and is compatible with copper, brass and bronze alloys. Insure that all recommended safety precautions are followed when handling or adding chemicals to the water loop. For open loop systems, water quality is very important. Table #1 shows acceptable ranges for a variety of water quality factors. The three main concerns in open loop installations are scaling, corrosion and fouling. In installations with hard water, scaling due to a buildup of carbonates on the heat exchanger wall can gradually degrade the heat pump performance over time. Heat pumps that are affected by scaling may exhibit low suction pressures in heating and high head pressures in cooling with a gradual loss of capacity and efficiency. Scaled heat exchangers can be cleaned by a qualified technician but care should be taken to avoid scaling in the first place. Revised 01-15 8 733 922 118 (2015/01) 6 | Water Quality LV Condensing Section Table 1: Water Quality POTENTIAL PROBLEM SCALING CORROSION IRON FOULING Acceptable Value Water Characteristic Copper Cupro-Nickel pH (Acidity/Alkalinity) 7-9 7-9 Hardness (CaCO3, MgCO3) < 350 ppm < 350 ppm Ryznar Stability Index 6.0 - 7.5 6.0 - 7.5 Langelier Saturation Index -0.5 - +0.5 -0.5 - +0.5 Hydrogen Sulfide (H2S) < 0.5 ppm * 10-50 ppm Sulfates < 125 ppm < 125 ppm Chlorine < 0.5 ppm < 0.5 ppm Chlorides < 20 ppm < 150 ppm Carbon Dioxide < 50 ppm < 50 ppm Ammonia < 2 ppm < 2 ppm Ammonia Chloride < 0.5 ppm < 0.5 ppm Ammonia Nitrate < 0.5 ppm < 0.5 ppm Ammonia Hydroxide < 0.5 ppm < 0.5 ppm Ammonia Sulfate < 0.5 ppm < 0.5 ppm Dissolved Solids < 1,000 ppm < 1,500 ppm Iron (Fe2+ Iron Bacteria Potential) < 0.2 ppm < 0.2 ppm Iron Oxide < 1 ppm < 1 ppm Suspended Solids < 10 ppm, < 600 μm size ** < 10 ppm, < 600 μm size ** Maximum Water Velocity 6 ft/sec 6 ft/sec EROSION * No "rotten egg" smell present at < 0.5 ppm H2S. ** Equivalent to 30 mesh strainer 8 733 922 118 (2015/01) Subject to change without prior notice LV Condensing Section LV Condensing Section INSTALLATION | 7 INSTALLATION Loosen compressor mounting bolts. NOTE: The installer should comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedent over any recommendations contained in these instructions. In light of local codes, the equipment should be installed in accordance with the recommendations made by the National Electric Code, and in accordance with the recommendations made by the National Board of Fire Underwriters. Condensing Section The condensing section should be mounted on a vibration absorption pad on a cement slab or similar support to provide a good base and some degree of levelness. The cement pad should not come in contact with the foundation or side of the dwelling because sound may be transmitted into the residence. See Figure #1 below. DO NOT remove the protective caps or plugs from the service valves until the refrigerant lines are run and ready for final connections. Vibration Pad is recommended LV units are supplied with either a copper or optional cupro-nickel condenser. Copper is adequate for ground water that is not high in mineral content. Proper testing is recommended to assure the well water quality is suitable for use with water source equipment. In conditions anticipating moderate scale formation or in brackish water a cupro-nickel heat exchanger is recommended. Use cupro-nickel condenser in ground water applications due to possibility of high mineral content and corrosive properties. Both the supply and discharge water lines will sweat if subjected to low water temperature. These lines should be insulated to prevent damage from condensation. All manual flow valves used in the system must be ball valves. Globe and gate valves must not be used due to high pressure drop and poor throttling characteristics. Never exceed the recommended water flow rates as serious damage or erosion of the water-to-refrigerant heat exchanger could occur. Teflon tape sealer should be used when connecting water piping connections to the units to protect against leaks and possible heat exchanger fouling. Flexible hoses should be used between the unit and the rigid system to avoid possible vibration. Ball valves should be installed in the supply and return lines for unit isolation and unit water flow balancing. Refer to Options section for factory supplied flow control options. ELECTRICAL Figure # 1 WATER PIPING Always disconnect power to the unit before servicing to prevent injury or death due to electrical shock or contact with moving parts. Supply and return piping must be as large as the unit connections on the heat pump (or larger on long runs in order to reduce pressure drop losses). Never use flexible hoses of a smaller inside diameter than that of the fluid connections on the unit. Revised 01-15 8 733 922 118 (2015/01) 8 | Electrical LV Condensing Section - High Voltage Transformer Settings for 208/230 V Units All field installed wiring must comply with the National Electric Code as well as all applicable local codes. Refer to the unit electrical data on the unit name plate for wire and branch circuit protection sizing. Supply power voltage and phasing should match the required voltage and phasing shown on the unit name plate. Operating the unit below the minimum voltage, above the maximum voltage or with incorrect phasing can result in poor system performance or damage to the heat pump. All field wiring should be installed by qualified and trained personnel. Refer to the unit wiring diagram for field connection requirements. As factory built, all 208/230 V units are wired for 230 V operation unless the wire for 208 V option is ordered. For jobsites with a 208 V power supply, the primary leads on the unit transformer will need to be changed from 240 V to 208 V. Refer to the unit wiring diagram for details. All power connections must be properly torque to avoid the risk of overheating. Power wiring to the heat pump should be enclosed in flexible conduit to minimize the transmission of vibration from the unit cabinet to the building. For heat pumps with unit mounted disconnect switches, field power should be connected to the marked terminals on the disconnect switch. For heat pumps without unit mounted disconnect switches (except for 460 volt units noted below), power leads are connected to the line (L) side of the compressor contactor. Always be sure to connect the ground lead to the ground lug. 460V Wiring Considerations when Pairing Condensing & Air Handler Optional Constant Air Flow Motor A 460V air handler with the Constant Air Flow Motor option requires a properly sized neutral wire in addition to the three high voltage wires and the ground wire. These units employ a 265 V motor that requires power from one phase of the 460 V supply and the neutral wire. Standard Constant Torque Motor A 460V air handler with the standard Constant Torque Motor employs a 460 V motor, so in this case the additional neutral wire is not needed. Be sure to plan for the inclusion of a neutral wire if selecting the upgraded constant air flow motor option on a 460V job. All blower motors are single phase. Compressor motors may be either single or three phase. The power supply ground wire should never be used as a neutral wire. 8 733 922 118 (2015/01) - Low Voltage For heat pumps with constant torque fan motors, all thermostat wiring is connected to a terminal block located in the unit electrical box. For heat pumps with a constant air flow fan motor, thermostat wiring is connected to a removable terminal strip located on the ECM motor control board located in the electrical box. Refer to the unit wiring diagram for connection details. The thermostat should be connected to the air handlers and then from the air handler to the condensing section (so they are in series with the thermostat). Note, the low voltage power supply is located in the air handler. Never route control wiring through the same conduit as power supply wiring. The heat pump can be controlled by most commonly available single-stage heat pump thermostats. Note that the reversing valve on the unit is energized when the unit is in the cooling mode. Thermostats should be located on an interior wall away from supply ducts. Avoid locations subject to direct sunlight, drafts, or external walls. Thermostat wiring should be 18 AWG. Refer to the installation instructions for the thermostat for further details. Exceptionally long runs of thermostat wire should be avoided to prevent voltage drops in the control circuit. The Air Handlers are supplied with a 50 VA control transformer as standard – this transformer supplies the low voltage for both the air handler and condensing section. The VA capacity of the transformer should be considered when connecting low voltage accessories to the heat pump such as thermostats or solenoid valves. Table #2 shows the VA draw of factory mounted components in the heat pump. The total VA draw of the heat pump internal components plus any attached accessories must be lower than the VA capacity of the unit control transformer. Subject to change without prior notice LV Condensing Section LV Condensing Section Electrical | 9 Unit Protection Module Safety Features Exceeding the transformer capacity can result in low control voltage, erratic unit operation or damage to the heat pump. 13 Table 2: Low Voltage VA Draw - Condensing Section Standard Construction Optional Components Component Component VA VA Reversing Valve Solenoid Compressor Contactor UPM board Total VA draw 8-9 Internal 2 Way Motorized Valve 7 6-8 LED Annunciator 1 2 Pump/Valve Relay 11 12 1 2 3 6-7 4 5 16-19 UNITS CONTROLS - UPM These heat pumps are designed to be controlled by a standard 1 heat / 1 cool heat pump thermostat. The heat pump control circuit operates on 24 VAC control voltage regardless of the unit supply voltage. Compressor operation is controlled by the “Y” terminal on the heat pump thermostat terminal block. When “Y” is energized, a signal to start the compressor is sent to the Unit Protection Module (UPM). The UPM checks a number of safety features before then starting the compressor. If any of the safety features connected to the UPM is in a fault condition, the UPM will not start the compressor and will flash a fault code on the red status LED indicating the nature of the fault. Additionally the UPM will delay compressor operation randomly on initial start up (random start delay) and will prevent the compressor from restarting with less than 5 minutes of off time (anti short cycle delay). Once all faults are cleared and the time delays are satisfied, the UPM will energize the compressor. The compressor will operate as long as the thermostat calls for “Y” and there are no faults. Refer to the troubleshooting chart for fault diagnostics. Cooling and Heating Modes The unit operates in cooling with the reversing valve energized. When the “O” terminal is energized, the heat pump will be in the cooling mode, however, will not be actively cooling until the “Y” and “G” terminals are also energized. If the “Y” and “G” terminals are energized without the “O” terminal, then the heat pump will operate in the heating mode. Revised 01-15 6 7 8 9 10 Figure # 2 [1] Board Power Indicator [2] UPM Status LED Indicator [3] Water Coil Freeze Protection Temperature Selection [4] Air Coil Freeze Protection Temperature Selection [5] UPM Board Settings [6] Water Coil Freeze Connection [7] Air Coil Freeze Connection [8] LED Unit Display Connection [9] 24VAC Power Input [10] Compressor Contact Output [11] High Pressure Switch Connection [12] Call for Compressor Y1 [13] Low Pressure Switch Connection [14] 24VAC Power Common [15] Condensate Overflow Sensor [16]Dry Contact [17]UPM Ground Standoff If the unit is being connected to a thermostat with a malfunction light, this connection is made at the unit malfunction output or relay. 8 733 922 118 (2015/01) 10 | Electrical LV Condensing Section If the thermostat is provided with a malfunction light powered off of the common (C) side of the transformer, a jumper between “R” and “COM” terminal of “ALR” contacts must be made. If the thermostat is provided with a malfunction light powered off of the hot (R) side of the transformer, then the thermostat malfunction light connection should be connected directly to the (ALR) contact on the unit’s UPM board. Safety controls include the following: • High pressure switch located in the refrigerant discharge line and wired across the HPC terminals on the UPM • Low pressure switch located in the unit refrigerant suction line and wired across terminals LPC1 and LPC2 on the UPM. UPM Board Dry Contacts are Normally Open (NO) • Water side freeze protection sensor, mounted close to condensing water coil, monitors refrigerant temperature between condensing water coil and expansion valve or capillary tube. If temperature drops below or remains at freeze limit trip for 30 seconds, the controller will shut down the compressor and enter into a soft lockout condition. The default freeze limit trip is 26°F, however this can be changed to 15°F by cutting the R30 or Freeze1 resistor located on top of DIP switch SW1. Figure # 3 • UPM DIP SWITCH DEFAULT POSITION lockout 4 2 reset R Y alarm Cont pulse test yes no UPM Board Factory Default Settings TEMP 26°F LOCKOUT 2 RESET Y ALARM PULSE TEST NO Table 3: UPM Fault Blink Codes LED Blinks Fault Fault Criteria None None All fault conditions nominal High Pressure Refrigerant discharge pressure has exceeded 600 PSIG Low Pressure Refrigerant suction pressure has fallen below 40 PSIG 3 Water Coil Freeze Condition Refrigerant temperature to the water coil has fallen below 26°F for 30 seconds 4 Condensate Overflow 5 Air Coil Freeze Condition 6 Brown Out 1 2 Not Applicable Freeze sensor contact jumper not installed Control voltage has fallen below 18 VAC Air Coil freeze protection sensor is not factory mounted for split systems, the supplied jumper must be connected across the terminals if no freeze sensor is to be installed in the field. Unit will not operate without a field-installed freeze sensor or jumper. 8 733 922 118 (2015/01) Subject to change without prior notice LV Condensing Section LV Condensing Section The UPM Board includes the following features: • ANTI-SHORT CYCLE TIMER: 5 minute delay on Electrical | 11 • provides a quick visual indication of whether or not a heat pump is energized or if it has locked out on a fault. The LED kit is mounted to the electrical corner post of the heat pump and employs high intensity LEDs for better visibility. The LED kit will exactly mirror the blink codes on the UPM board (refer to the blink code table in the UPM sequence of operation). break timer to prevent compressor short cycling. • RANDOM START: Each controller has an unique random start delay ranging from 270 to 300 seconds on initial power up to reduce the chance of multiple unit simultaneously starting at the same time after power up or after a power interruption, thus avoiding creating large electrical spike. • LOW PRESSURE BYPASS TIMER: If the compressor is running and the low pressure switch opens, the controller will keep the compressor ON for 120 seconds. After 2 minutes if the low pressure switch remains open, the controllers will shut down the compressor and enter a soft lockout. The compressor will not be energized until the low pressure switch closes and the anti-short cycle time delay expires. If the low pressure switch opens 2-4 times in 1 hour, the unit will enter a hard lockout. In order to exit hard lockout power to the unit would need to be reset. • • Operation of unit in test mode can lead to accelerated wear and premature failure of components. The "TEST" switch must be set back to "NO" after troubleshooting/ servicing. • BROWNOUT/SURGE/POWER INTERRUPTION PROTECTION: The brownout MALFUNCTION OUTPUT: Alarm output is Normally Open (NO) dry contact. If pulse is selected the alarm output will be pulsed. The fault output will depend on the dip switch setting for "ALARM". If it is set to "CONST", a constant signal will be produced to indicate a fault has occurred and the unit requires inspection to determine the type of fault. If it is set to "PULSE", a pulse signal is produced and a fault code is detected by a remote device indicating the fault. See L.E.D Fault Indication below for blink code explanation. The remote device must have a malfunction detection capability when the UPM board is set to "PULSE". TEST DIP SWITCH: A test dip switch is provided to reduce all time delays settings to 10 seconds during troubleshooting or verification of unit operation. protection in the UPM board will shut does the compressor if the incoming power falls below 18 VAC. The compressor will remain OFF until the voltage is above 18 VAC and ANTI-SHORT CYCLE TIMER (300 seconds) times out. The unit will not go into a hard lockout. • LED ANNUNCIATOR: This optional LED kit FREEZE SENSOR: The default setting for the freeze limit trip is 26°F (sensor number 1); however this can be changed to 15°F by cutting the R30 resistor located on top of the DIP switch SW1. The UPM controller will constantly monitor the refrigerant temperature with the sensor mounted close to the condensing water coil between the thermal expansion valve and water coil. If temperature drops below or remains at the freeze limit trip for 30 seconds, the controller will shut the compressor down and enter into a soft lockout condition. Both the status LED and the Alarm contact will be active. The LED will flash (three (3) times) the code associated with this alarm condition. If this alarm occurs 2 times (or 4 if Dip switch is set to 4) within an hour the UPM controller will enter into a hard lockout condition. It is recommended to have a flow switch to prevent the unit from running if water flow is lost. • INTELLIGENT RESET: If a fault condition is initiated, the 5 minute delay on break time period is initiated and the unit will restart after these delays expire. During this period the fault LED will indicate the cause of the fault. If the fault condition still exists or occurs 2 or 4 times (depending on 2 or 4 setting for Lockout dip switch) before 60 minutes, the unit will go into a hard lockout and requires a manual lockout reset. If 24 VAC output is needed R must be wired to ALR-COM terminal; 24 VAC will be available o the ALR-OUT terminal when the unit is in the alarm condition. • LOCKOUT RESET: A hard lockout can be reset by turning the unit thermostat off and then back on when the “RESET” dip switch is set to “Y” or by shutting off unit power at the circuit breaker when the “RESET” dip switch is set to “R”. Revised 01-15 8 733 922 118 (2015/01) 12 | Electrical LV Condensing Section Table 4: Refrigerant Charge, Line Sizing and Capacity Multiplier1 SYSTEM MODEL Factory R410A Charge (Oz)2 Refrigerant Line O.D. Size (Based on Equivalent Line Length)3 35 FT. 25 FT.2 50 FT. Suct. Line 75 FT Riser Max.4 LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC. LV018 40 3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4 5/8 LV024 44 3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8 5/8 LV030 52 3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8 3/4 LV036 61 3/8 3/4 3/8 3/4 3/8 7/8 3/8 7/8 3/4 LV042 58 3/8 3/4 3/8 3/4 3/8 7/8 1/2 7/8 7/8 LV048 59 3/8 3/4 3/8 7/8 3/8 7/8 1/2 1-1/8 7/8 LV060 93 3/8 7/8 1/2 7/8 1/2 1-1/8 1/2 1-1/8 7/8 LV070 90 3/8 7/8 1/2 1-1/8 1/2 1-1/8 1/2 1-1/8 7/8 CAPACITY MULTIPLIER 1.00 .995 0.990 0.980 Example 1: Model LV018 with 50ft of equivalent length of 3/8” O.D Liquid Line and factory supplied filter drier. Total system charge = Factory charge +/adjustment for larger liquid line diameter and additional liquid line length + filter drier adjustment. Total System Charge = 40 oz - (25ft x .6 oz/ft) + (50ft x .60 oz/ft) + 6 oz = 61 oz. Add 21 oz of R410A refrigerant. After adding estimated additional charge, adjust final charge according to subcooling and superheat measurements. See section on charging according to subcooling and superheat. Example 2: Model LV036 with 45ft of equivalent length of 3/8” O.D Liquid Line and factory supplied filter drier. Estimated Total System Charge = Factory charge +/- liquid line length adjustment + filter drier adjustment. Estimated Total System Charge = 61 oz + ([45ft - 25ft] x .60 oz/ft) + 6 oz = 79 oz. Estimate an additional 18 oz of R410A refrigerant is required. After adding estimated additional charge, adjust final charge according to subcooling and superheat measurements. See section on charging according to subcooling and superheat. Example 3: Model LV060 with 35ft of equivalent length of 1/2” O.D Liquid Line and factory supplied filter drier. Total system charge = Factory charge - (25ft x 0.6 oz/ft) + (35ft x 1.15 oz/ft) + filter drier adjustment. Total System Charge = 93 oz - 15 + 40 + 9 oz = 127 oz. Add 34 oz of R410A refrigerant. After adding estimated additional charge, adjust final charge according to subcooling and superheat measurements. See section on charging according to subcooling and superheat. Notes: 1. Liquid and suction line sizes should be sized according to table, not according to king valve connection size. 2. Factory Charge is based on 25 ft of lineset with lineset diameter according to table. Charge adjustments will need to be made for linesets of differing length and/or diameters. Additional charge must also be added for factory supplied filter drier. All charge rates MUST ALWAYS to be confirmed and adjusted if necessary by subcooling and superheat measurements (even with a 25 ft lineset and default factory charge). See section on charging according to subcooling and superheat. 3. Next diameter size up should be used if equivalent length is longer than shown (75 ft is max) 4. Suction line max riser diameter is typically sized to meet minimum of 1,250 FPM refrigerant velocity for proper oil return. 5. With 1/2” liquid lines it is recommended to place units as close as practical (minimizing the increased refrigerant volume imposed by the larger line) for maximum compressor life. Table 5: Liquid Line Charge Per Linear Foot Liquid line Size, O.D. R410A oz per foot 8 733 922 118 (2015/01) 1/4 5/16 3/8 1/2 5/8 .25 .44 .60 1.15 1.95 Subject to change without prior notice LV Condensing Section LV Condensing Section Electrical | 13 Table 6: Additional Charge for factory supplied Filter Drier Filter Drier Description Charge – Filter Drier oz LV018 Filter Drier, BiFlow, R410A, 8 cu in, 3/8 ODF 6 LV024 Filter Drier, BiFlow, R410A, 8 cu in, 3/8 ODF 6 LV030 Filter Drier, BiFlow, R410A, 8 cu in, 3/8 ODF 6 LV036 Filter Drier, BiFlow, R410A, 8 cu in, 3/8 ODF 6 LV042 Filter Drier, BiFlow, R410A, 8 cu in, 3/8 ODF 6 LV048 Filter Drier, BiFlow, R410A, 16 cu in, 5/8 ODF 9 LV060 Filter Drier, BiFlow, R410A, 16 cu in, 5/8 ODF 9 LV070 Filter Drier, BiFlow, R410A, 16 cu in, 5/8 ODF 9 MODEL Notes: 1. All units re quire a bi-flow filter drier. Filter drier must be UL listed for R410A with a maximum working pressure of 680 psi. Substitute driers are permissible assuming drier meets these specifications. 2. Final Charge must be adjusted for filter drier - refer to table for charge adjustment. Table 7: Service Valve Connection Service Valve Connection Sizes SYSTEM LIQ. SUC. MODEL LV018 LV024 LV030 LV036 LV042 LV048 LV060 LV070 Revised 01-15 3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8 3/8 7/8 8 733 922 118 (2015/01) 14 | Options LV Condensing Section OPTIONS Automatic Flow Control Valve A number of factory installed options are available on Condensing Sections. The following details the purpose, function and components of each option. This factory installed option provides controlled flow over a wide range of working pressures and temperatures - limiting the water/fluid flow to the recommended rate (roughly 3 gpm / ton) for optimum system efficiency. The valve prevents excessive flow - protecting the heat exchanger surface from erosion and also minimizing the number of valves needed for unit and building / system balancing. The valve is designed to resist clogging and have a long life without maintenance; however, if maintenance is needed, the valve cartridge can easily be unscrewed and replaced. Unit Mounted Non-Fused Disconnect Switch The heat pumps can be supplied with an optional unit mounted disconnect switch mounted to the electrical corner post of the unit. Field electrical wiring is connected to the switch and the switch then routes power to the heat pump electrical box. When the switch is in the “OFF” position, the heat pump electrical box is completely de-energized. Internal 2-Way Water Valve In many applications, including variable pumping and well water installations, a motorized water valve is required on the heat pump water circuit. This water valve can be factory mounted and wired internally to the unit. The internal water valve option features a 24VAC motorized water valve rated to 450 psig working pressure. This valve is wired to open on a thermostat call for compressor operation (heating or cooling) and will remain open as long as the thermostat calls. The valve can remain seated with up to 20 psi of back pressure on all sizes. The valve consists of two main parts: the valve body and the actuator. The valve body is brazed into the leaving water line of the heat pump and is a permanent part of the unit. The valve actuator can be easily removed from the valve body for service. Refer to the water side pressure drop table in the operating temperatures and pressures section of this manual to determine the appropriate pressure drop across the heat pump with and without the water valve option. Note that the 2-Way Water Valve option will add additional pressure drop between the water in and water out connections of the heat pump. Note that this water valve cannot be used as an isolation valve. 8 733 922 118 (2015/01) LED Annunciator This heat pump can be equipped with an optional LED annunciator kit. This LED kit can provide a quick visual indication of whether or not a heat pump is energized and if it has locked out on a fault. The LED kit is mounted to the electrical corner post of the heat pump and employs high intensity LED’s for better visibility. The LED kit will exactly mirror the LED blink codes on the UPM board (refer to the blink code table in the UPM sequence of operation). Flow Proving Switch This heat pump can be equipped with an optional flow proving switch. This device senses a pressure drop across the water side of the condenser coil indicating water flow. When the pressure drop rises to five feet of head, the flow proving switch will enable the compressor. If the pressure drop across the condenser does not reach the required value, then the unit compressor is disabled. APPLICATION CONSIDERATIONS Well Water Systems Copper is adequate for ground water that is not high in mineral content. Should your well driller express concern regarding the quality of the well water available or should any known hazards exist in your area, we recommend proper testing to assure the well water quality is suitable for use with water source equipment. In conditions anticipating moderate scale formation or in brackish water a cupro-nickel heat exchanger is recommended. In well water applications water pressure must always be maintained in the heat exchanger. This can be accomplished with either a control valve or a bladder type expansion tank. Subject to change without prior notice LV Condensing Section LV Condensing Section Application Considerations | 15 When using a single water well to supply both domestic water and the heat pump, care must be taken to ensure that the well can provide sufficient flow for both. In well water applications a slow closing solenoid valve must be used to prevent water hammer. Solenoid valves should be connected across Y1 and C1 on the interface board for all. Make sure that the VA draw of the valve does not exceed the contact rating of the thermostat. Supply Air Refrigerant Lines Return Air Elec tric Pane al l Air Han dler Stan d Condensate Line Figure # 4 Example System Set-up Cooling Tower/Boiler Systems The cooling tower and boiler water loop temperature should be maintained between 50° F to 110 ° F to assure adequate cooling and heating performance. Revised 01-15 In the cooling mode, heat is rejected from the unit into the water loop. A cooling tower provides evaporative cooling to the loop water thus maintaining a constant supply temperature to the unit. When utilizing open cooling towers, chemical water treatment is mandatory to ensure the water is free from corrosive elements. A secondary heat exchanger (plate frame) between the unit and the open cooling tower may also be used. 8 733 922 118 (2015/01) 16 | Application Considerations LV Condensing Section It is imperative that all air be eliminated from the closed loop side of the heat exchanger to protect against fouling. In the heating mode, heat is absorbed from the water loop. A boiler can be utilized to maintain the loop at the desired temperature. Pressure/temperature ports are recommended in both supply and return lines for system flow balancing. Water flow can be accurately set by measuring the water-to-refrigerant heat exchanger’s water side pressure drop. See operating temperatures and pressures for water flow vs. pressure drop information. Water in piping exposed to extreme low ambient temperatures is subject to freezing. No unit should be connected to the supply or return piping until the water system has been completely cleaned and flushed to remove any dirt, piping chips or other foreign material. Supply and return hoses should be connected together during this process to ensure the entire system is properly flushed. Consult the specification sheets for piping sizes. Teflon tape sealer should be used when connecting to the unit to protect against leaks and possible heat exchanger fouling. Do not overtighten the connections. Flexible hoses should be used between the unit and the rigid system to avoid damage from vibration. Ball valves should be installed in the supply and return lines for unit isolation and unit water flow balancing. After the cleaning and flushing has taken place the unit may be connected to the water loop and should have all valves wide open. (Figure #5) Note: Diagram shows typical installation and is for illustration purposes only. Ensure access to Heat Pump is not restricted. Figure # 5 [1] [2] [3] [4] [5] [6] Line voltage disconnect (unit) Low voltage control connection P/T ports (optional) Hose kits (optional) Ball valves Supply and return line of central system 8 733 922 118 (2015/01) [7] Flex duct connection [8] Hanging bracket assembly [9] Threaded rod [10] Hanging bracket assembly Subject to change without prior notice LV Condensing Section LV Condensing Section Application Considerations | 17 Geothermal Systems Each condensing section comes with an insulated water-to-refrigerant heat exchanger making it suitable for geothermal applications. Closed loop and pond applications require specialized design knowledge. No attempt at these installations should be made unless the dealer has received specialized training. Utilizing the Ground Loop Pumping Package (GLP), makes the installation easy. Anti-freeze solutions are utilized when low evaporating conditions are expected to occur. Refer to the GLP installation manuals for more specific instructions. (Figure #6) Note: Diagram shows typical installation and is for illustration purposes only. Ensure access to Heat Pump is not restricted. Figure # 6 [1] Line voltage disconnect (unit) [2] Flex duct Connection [3] Low voltage control connection [4] Line voltage connection (unit) [5] P/T ports [6] Vibration pad [7] Condensate drain connection [8] Ground loop connection kit [9] Ground loop pumping package [10] Polyethylene with insulation [11] Line voltage disconnect (electric heater) Revised 01-15 8 733 922 118 (2015/01) 18 | System Checkout LV Condensing Section SYSTEM CHECKOUT UNIT START-UP After completing the installation, and before energizing the unit, the following system checks should be made: • Verify that the supply voltage to the heat pump is in accordance with the nameplate ratings. • Make sure that all electrical connections are tight and secure. • Check the electrical fusing and wiring for the correct size. 1. Put the UPM board in “test” mode. 2. Set the thermostat to the highest setting. 3. Set the thermostat system switch to “COOL”, and the fan switch to the “AUTO” position. The reversing valve solenoid should energize. The compressor and fan should not run. 4. Reduce the thermostat setting approximately 5 degrees below the room temperature. 5. Verify the heat pump is operating in the cooling mode. 6. Turn the thermostat system switch to the “OFF” position. The unit should stop running and the reversing valve should de energize. 7. Leave the unit off for approximately (5) minutes to allow for system equalization. 8. Turn the thermostat to the lowest setting. 9. Set the thermostat switch to “HEAT”. 10. Increase the thermostat setting approximately 5 degrees above the room temperature. 11. Verify the heat pump is operating in the heating mode. 12. Set the thermostat to maintain the desired space temperature. 13. Check for vibrations, leaks, etc. Ensure cabinet and Electrical Box are properly grounded. • • • • • • Verify that the low voltage wiring between the thermostat and the unit is correct. Verify that the water piping is complete and correct. Check that the water flow is correct, and adjust if necessary. Check the blower for free rotation, and that it is secured to the shaft. Verify that vibration isolation has been provided. Unit is serviceable. Be certain that all access panels are secured in place. Considerations: 1. Always check incoming line voltage power supply and secondary control voltage for adequacy. Transformer primaries are dual tapped for 208 and 230 volts. Connect the appropriate tap to ensure a minimum of 18 volts secondary control voltage. 24 volts is ideal for best operation. 2. Long length thermostat and control wiring leads may create voltage drop. Increased wire gauge or up-sized transformers may be required to ensure minimum secondary voltage supply. 3. The guidelines for wiring between a thermostat and the unit are: 18 GA up to 60 foot, 16 GA up to 100 ft and 14 GA up to 140 ft. 4. Do not apply additional controlled devices to the control circuit power supply without consulting the factory. Doing so may void equipment warranties. 5. Check with all code authorities on requirements involving condensate disposal/ over flow protection criteria. 8 733 922 118 (2015/01) MAINTENANCE 1. Filter changes or cleanings are required at regular intervals. The time period between filter changes will depend upon type of environment the equipment is used in. In a single family home, that is not under construction, changing or cleaning the filter every 60 days is sufficient. In other applications such as motels, where daily vacuuming produces a large amount of lint, filter changes may need to be as frequent as biweekly. Equipment should never be used during construction due to likelihood of wall board dust accumulation in the air coil of the equipment which permanently affects the performance and may shorten the life of the equipment. Subject to change without prior notice LV Condensing Section LV Condensing Section 2. An annual “checkup” is recommended by a licensed refrigeration mechanic. Recording the performance measurements of volts, amps, and water temperature differences (both heating and cooling) is recommended. This data should be compared to the information on the unit’s data plate and the data taken at the original startup of the equipment. 3. Lubrication of the blower motor is not required, however may be performed on some motors to extend motor life. Use SAE-20 nondetergent electric motor oil. 4. The condensate drain should be checked annually by cleaning and flushing to ensure proper drainage. 5. Periodic lockouts almost always are caused by air or water flow problems. The lockout (shutdown) of the unit is a normal protective measure in the design of the equipment. If continual lockouts occur call a mechanic immediately and have them check for: water flow problems, water temperature problems, air flow problems or air temperature problems. Use of the pressure and temperature charts for the unit may be required to properly determine the cause. Maintenance | 19 Table 8: Water Side Pressure Drop MODEL LV018 LV024 LV030 LV036 LV042 LV048 LV060 LV070 Water Flow Rate (GPM) Water Side Pressure Drop with out Internal Valve (PSI) Water Side Pressure Drop with Internal Valve (PSI) 2.5 4 5 3 4 6 4 6 8 4.5 6 9 5 8 11 6 8 12 7.5 10 15 9 12 18 1.1 2.7 4.0 1.7 2.8 5.8 2.0 4.2 7.0 1.6 2.6 5.4 2.0 4.6 8.2 0.8 1.4 2.8 1.4 2.3 4.8 2.0 3.4 7.0 2.1 5.2 8.0 2.0 3.4 7.2 2.6 5.6 9.6 2.4 4.0 8.6 3.0 7.2 13.0 1.4 2.5 5.4 2.4 4.1 8.8 3.4 5.9 12.7 All values based upon pure water at 70° F. Revised 01-15 8 733 922 118 (2015/01) 20 | Unit Check-Out Sheet LV Condensing Section UNIT CHECK-OUT SHEET Customer Data Customer Name _____________________________________________ Address ______________________________________________________ _______________________________________________________________ Phone _______________________________________________________ Date ___________________________________ Unit Number ___________________________ Unit Nameplate Data Unit Make _________________________________________ Model Number ____________________________________ Serial Number ____________________________________ Refrigerant Charge (oz) __________________________ Compressor: RLA ____________________ LRA ___________________________ Blower Motor: FLA (or NPA) ___________ HP ____________________________ Maximum Fuse Size (Amps) ____________ Maximum Circuit Ampacity _____________ Operating Conditions Entering / Leaving Air Temp Cooling Mode _______________ / _____________ Heating Mode _______________ / _____________ Entering Air Measured at: ______________________________ ______________________________ Leaving Air Measured at: ______________________________ ______________________________ Entering / Leaving Fluid Temp _______________ / _____________ _______________ / _____________ Fluid Flow (gpm) ______________________________ ______________________________ Compressor Volts / Amps _______________ / _____________ _______________ / _____________ Blower Motor Volts / Amps _______________ / _____________ _______________ / _____________ Source Fluid Type ______________________________ ______________________________ Fluid Flow (gpm)* ______________________________ ______________________________ Fluid Side Pressure Drop* ______________________________ ______________________________ Suction / Discharge Pressure (psig)* Suction / Discharge Temp* Suction Superheat* _______________ / _____________ _______________ / _____________ _______________ / _____________ ______________________________ _______________ / _____________ ______________________________ 8 733 922 118 (2015/01) Subject to change without prior notice LV Condensing Section LV Condensing Section Unit Check-Out Sheet | 21 Customer Data Entering TXV / Cap Tube Temp* Liquid Subcooling* ______________________________ ______________________________ ______________________________ ______________________________ * Required for Troubleshooting ONLY Auxiliary Heat Unit Make __________________________________ Model Number: ______________________________ Max Fuse Size (Amps) _______________________ Serial Number _____________________________ Volts / Amps _______________________________ Entering Air Temperature _____________________ Bosch Group Leaving Air Temperature ______________________ 601 NW 65th Court Scan the QR code and attach picture of this form with the information requested. Revised 01-15 Fort Lauderdale, FL 33309 Phone: (866) 642-3198 8 733 922 118 (2015/01) 22 | Troubleshooting LV Condensing Section TROUBLESHOOTING Table 9: UNIT TROUBLESHOOTING Problem Mode Cooling Check Possible Cause Action High Pressure fault - no or low water flow Check water valves and/or pumps for proper operation. Check for water coil blockage. High Pressure fault - high water temperature Check water temperature - is it in range? High Pressure fault fouled or scaled water coil Check for proper flow rate and water temperature, but low water side temp rise in cooling Heating X Is fault LED Blinking 1 time? Check fan motor for proper operation. High Pressure fault - no or low air flow X Check air filter Inspect air coil for dirt/debris Check duct work - are dampers closed or blocked? Check fan motor for proper operation. Low Pressure fault - no or low air flow X Inspect air coil for dirt/debris Check duct work - are dampers closed or blocked? No compressor operation but fan runs Is fault LED Blinking 2 times? X X 8 733 922 118 (2015/01) Check air filter Is fault LED Blinking 3 times? Low Pressure fault - low refrigerant Check refrigerant pressure with gauge set Low Pressure fault - no or low water flow Check water valves and/or pumps for proper operation. Check for water coil blockage. 75Unit Check for proper flow rate and water temperature, but low water side temp drop in heating. Low Pressure fault - low refrigerant Check refrigerant pressure with gauge set Freeze fault, water coil no or low water flow Check water valves and/or pumps for proper operation. Check for water coil blockage. Freeze fault - low water temperature Check water temperature - is it below 40° entering? If heat pump is connected to a closed loop with antifreeze check that the "FREEZE 1" resistor on the UPM board has been cut to set the unit to antifreeze mode (see UPM features on pages 15-17). Freeze fault - low refrigerant Check refrigerant pressure with gauge set Subject to change without prior notice LV Condensing Section LV Condensing Section Troubleshooting | 23 Table 9: UNIT TROUBLESHOOTING Problem Mode Check Action Condensate fault - poor drainage Check condensate pan for high water level. Check drain line for blockages, double trapping or inadequate trapping. Condensate fault blocked return air Check condensate pan for high water level. Check air filter and return air duct work for blockage. Check that there is adequate space between the return air opening and walls or other obstructions on free return applications. Brown out fault - low supply voltage Check primary voltage - insure it is within the limits listed on the unit data plate. Brown out fault overloaded control circuit Check control voltage - if it is below 18 V check accessories connected to the unit and insure that they do not exceed the VA draw shown on page 11. Brown out fault - bad thermostat connection Check that thermostat wiring is proper gauge and length, that it is not damaged and that all connections at the thermostat and heat pump are secure. Is fault LED Blinking 4 times? X X Possible Cause X Is fault LED Blinking 5 times? Check fan motor for proper operation. No compressor operation but fan runs Freeze fault, air coil - no or low air flow X Revised 01-15 X No fault LED contactor not energized Inspect air coil for dirt/debris Check duct work - are dampers closed or blocked? Is fault LED Blinking 6 times? X Check air filter Freeze fault, air coil blocked return air Check that there is adequate space between the return air opening and walls or other obstructions on free return applications. Freeze fault, air coil - low refrigerant Check refrigerant pressure with gauge set. Thermostat not calling for compressor operation Ensure that the thermostat is on and calling for "Y" Bad thermostat connection Check "Y" connection from thermostat. Insure that there is 24 VAC between "Y" and "C". Loose wire to contactor coil Check wiring - insure that there is 24 VAC across the contactor coil. Burned out contactor coil Test contactor with 24VAC (between "R" and "C"). Ohm contactor coil - an open circuit indicates a burned coil. 8 733 922 118 (2015/01) 24 | Troubleshooting LV Condensing Section Table 9: UNIT TROUBLESHOOTING Problem No compressor operation but fan runs Mode X Check X X Action Open compressor overload Check for supply voltage at the load side of the contactor. For 3 phase models check phase rotation and voltage at all 3 phases. Poor wiring connections Look for signs of heat on the wiring insulation. Check that all wiring connections are secure and properly torqued. Burned out compressor Does compressor hum when power is applied? If not check the resistance of the compressor windings using the values shown in the compressor characteristics chart. Note that the compressor must be cool (70° F) when checking the windings. Bad thermostat connection / faulty thermostat Check thermostat and wiring. Check unit terminal block for 24 VAC between "Y" and "C" and "G" and "C". Low or no supply power Insure that the supply voltage to the unit is with in the range shown on the unit data plate. Faulty control transformer Check for 24 VAC between "R" and "C" on the unit terminal block. For 75 and 100 VA transformers, check that the transformer circuit breaker has not tripped. Check low voltage circuit for overload conditons or short circuits before replacing the transformer. Faulty motor check supply voltage from the fan relay to the motor. Check that all motor wires are secure. With power off spin the motor shaft noise, resistance or uneven motion can be signs of motor failure. No fan operation signal Check for 24 VAC across the fan relay coil. Check all wiring connections. Bad fan relay If the relay coil is energized but the relay does not pull in, check the resistance across the relay coil - an open circuit is an indicator of a faulty relay. No fan operation signal Check for 24 VAC between "G" and "C". Check all wiring connections. Loose wiring Check all wiring connections at motor and control box. Faulty motor Check supply voltage to the motor. Check that all motor wires are secure. With power off spin the motor shaft - noise, resistance or uneven motion can be signs of motor failure. No fault LED contactor energized Power LED on No compressor or fan operation Possible Cause X Power LED off Fan relay energized No fan operation PSC motor X X Fan relay not energized No fan operation constant torque motor 8 733 922 118 (2015/01) X X Subject to change without prior notice LV Condensing Section LV Condensing Section Troubleshooting | 25 Table 9: UNIT TROUBLESHOOTING Problem No fan operation constant airflow motor Mode X Check Possible Cause Action No fan operation signal Check for 24 VAC between "G" and "C". Check all wiring connections. Make sure that the thermostat connection plug is securely connected. Loose wiring Check all wiring connections at motor and control box. Check that power and control harnesses are securely connected. Interface board problems Make sure that the interface board is not damged and that all DIP switches are in the proper configuration (refer to the blower performance tables). Faulty motor Check supply voltage to the motor. Check that all motor wires are secure. Move the "TEST" DIP switch to "ON" and the other switches to "OFF" on the "ADJUST" switch block on the interface board - the motor should run at 70% torque whrn "G" is called. With power off spin the motor shaft - noise, resistance or uneven motion can be signs of motor failure. Faulty solenoid Check that the reversing valve solenoid is receiving 24 VAC. If so, check the resistance of the solenoid - an open circuit may indicate a burned out solenoid. Miswired/faulty thermostat Check that the reversing valve theromstat wire is connected to the "O" terminal of the thermostat. Check for a contact closure between "O" and "R". Loose wire on "O" terminal Check that the wires from the thermostat to the unit are securely connected and that the wires from the electrical box to the reversing valve are connected. Dirty Filter Replace filter. Fan speed too low Consult blower performance table and increase fan speed if possible. Excessive duct pressure drop Consult blower performance table and increase fan speed if possible. Air flow too high Fan speed setting too high Consult blower performance table and reduce fan speed if possible. High or low water temperature Inlet water temperature out of range Check unit capacity vs. water temperature. Air leakage Leaky duct work Inspect duct work. Loss of refrigeration capacity Low refrigerant Check refrigerant pressures with gauge set. X Reversing valve solenoid energized Unit not shifting into cooling X Reversing valve solenoid not energized Excessively cold supply air temperature in cooling or excessively hot supply air temperature in heating Excessively warm supply air temperature in cooling and/or excessively cool air in heating Revised 01-15 X X X Reduced air flow X 8 733 922 118 (2015/01) 26 | Troubleshooting LV Condensing Section Table 9: UNIT TROUBLESHOOTING Problem High humidity Mode Check Possible Cause Action Air flow too high Fan speed setting too high Consult blower performance table and reduce fan speed if possible. Loss of refrigeration capacity Low refrigerant Check refrigerant pressures with gauge set. Unit oversized Check unit performance against building load calculations. Poor thermostat location Make sure that thermostat is not located by a supply air duct . Poor duct work/grille design Insure duct work and grilles are properly sized for unit air flow. Fan speed setting too high Consult blower performance table and reduce fan speed if possible. Unit not mounted on full vibration pad Mount unit on a vibration pad (see page 7). Unit not connected with flexible conduit, water lines and/or duct work Install unit in accordance with instructions on pages 6-8. Unit cabinet touching wall or other building component Adjust unit location to avoid unit touching structure. High water temperature or low water flow rate elevating head pressure Increase water flow rate and/or reduce water temperature if possible. Scaled or fouled water coil elevating heat pressure Clean/descale water coil. X Short cycling Air noise X X Structure bourne noise Objectionable noise levels X Compressor noise Low air flow elevating head pressure X X 8 733 922 118 (2015/01) X Water hammer Fast closing valves installed Subject to change without prior notice Check filter. Increase fan speed. change valves to slow-close type. LV Condensing Section LV Condensing Section Operating Temperatures and Pressures | 27 OPERATING TEMPERATURES AND PRESSURES OPERATING DATA MODEL ENTERING WATER WATER FLOW GPM TEMP, ˚F 30˚ 40˚ 50˚ LV018 60˚ 70˚ 80˚ 90˚ 100˚ COOLING HEATING WATER SUCTION DISCHARGE SUCTION PRESSURE PRESSURE TEMP RISE, AIR TEMP PRESSURE ˚F DROP, ˚F PSIG PSIG PSIG 3 65-80 282-344 6-7 14-17 5 73-89 294-359 3-4 15-18 3 121-148 184-225 17-21 18-22 80-98 299-365 7-9 16-20 5 117-143 167-204 10-13 19-23 89-108 311-380 4-5 17-21 3 123-151 222-271 17-20 17-21 95-116 315-385 9-11 19-23 5 119-145 202-247 10-12 18-23 105-128 329-402 5-7 20-24 3 125-153 260-318 16-19 17-21 109-133 332-406 11-13 21-26 5 120-147 237-289 10-12 18-22 121-148 346-423 6-8 22-27 3 127-155 298-365 15-19 17-20 124-151 349-427 12-15 23-28 5 122-149 271-331 9-11 18-21 138-168 364-444 7-9 25-30 3 129-158 336-411 14-18 16-20 138-169 366-447 14-17 26-31 5 124-152 306-374 9-11 17-21 154-188 381-466 8-10 27-33 3 131-160 374-458 14-17 16-19 153-187 383-468 16-16 28-34 5 126-154 340-416 8-10 17-20 170-208 399-487 9-12 29-36 3 133-162 413-504 13-16 15-19 5 128-156 375-458 8-10 16-20 72-87 296-361 5-6 21-25 5 30˚ 40˚ 50˚ LV024 60˚ 70˚ 80˚ 90˚ 100˚ DISCHARGE WATER PRESSURE TEMP AIR TEMP PSIG DROP, ˚F RISE, ˚F 7 75-92 301-368 3-4 22-26 5 114-139 155-190 14-17 22-27 88-107 314-384 6-7 24-29 7 108-132 147-180 10-12 23-28 92-112 321-392 4-5 25-30 5 116-142 192-234 13-16 21-26 104-127 333-407 7-9 27-33 7 111-135 182-222 9-12 22-27 109-133 340-415 5-6 28-34 5 119-146 228-279 13-16 21-26 120-146 352-430 8-10 30-37 7 113-138 217-265 9-11 22-27 125-153 359-439 6-7 32-39 5 122-149 264-323 13-15 20-25 136-166 371-453 9-12 33-41 7 116-142 251-307 9-11 21-26 142-174 378-462 7-8 35-43 5 125-152 301-368 12-15 20-24 152-185 389-476 11-13 36-44 7 118-145 286-349 9-11 21-26 159-194 397-485 8-9 38-47 5 127-156 337-412 12-15 19-24 168-205 408-499 12-15 39-48 7 121-148 320-392 9-10 20-25 176-215 416-509 8-10 41-51 5 130-159 374-457 12-14 19-23 7 124-151 355-434 8-10 20-24 This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development, specifications are subject to change without notice. Revised 01-15 8 733 922 118 (2015/01) 28 | Operating Temperatures and Pressures LV Condensing Section OPERATING DATA MODEL ENTERING WATER WATER FLOW GPM TEMP, ˚F 30˚ 40˚ 50˚ LV030 60˚ 70˚ 80˚ 90˚ 100˚ COOLING HEATING WATER SUCTION DISCHARGE SUCTION PRESSURE PRESSURE TEMP RISE, AIR TEMP PRESSURE ˚F DROP, ˚F PSIG PSIG PSIG 3.5 73-89 266-325 5-6 15-18 7.5 77-94 272-333 3-4 16-19 3.5 117-143 189-231 14-17 18-22 86-105 279-341 6-7 17-21 7.5 112-137 178-217 8-9 19-24 90-110 286-350 4-5 18-22 3.5 126-154 221-270 14-17 18-21 162-198 293-358 7-8 20-24 7.5 121-148 207-253 8-9 19-23 170-208 300-366 5-6 21-25 3.5 131-160 252-308 13-16 17-21 110-134 306-374 8-10 22-27 7.5 125-153 237-290 8-9 18-22 115-141 314-383 6-7 23-29 3.5 135-165 284-347 13-16 17-20 122-150 320-391 9-11 24-30 7.5 130-158 266-326 7-9 18-22 129-157 327-400 6-8 26-32 3.5 140-171 320-391 13-16 16-20 134-164 333-407 11-13 27-33 7.5 134-164 300-367 7-9 17-21 141-172 341-417 7-9 28-35 3.5 144-176 360-440 13-16 16-19 147-179 347-424 12-14 29-36 7.5 138-169 338-414 7-9 17-21 154-188 355-434 8-10 31-38 3.5 149-182 405-495 13-15 15-19 7.5 143-174 381-465 7-9 16-20 74-90 244-299 3-4 13-15 4.5 30˚ 40˚ 50˚ LV036 60˚ 70˚ 80˚ 90˚ 100˚ DISCHARGE WATER PRESSURE TEMP AIR TEMP PSIG DROP, ˚F RISE, ˚F 78-95 251-306 2-3 13-16 4.5 9 122-149 183-224 14-18 19-23 87-106 257-314 4-5 15-18 9 117-143 172-210 8-10 20-24 91-111 263-322 3-3 16-19 4.5 131-160 214-261 14-18 18-22 164-201 269-329 5-6 17-20 9 126-154 201-245 8-10 19-24 173-211 276-337 3-4 18-22 4.5 136-166 244-298 14-17 18-22 111-136 282-344 6-7 19-23 9 131-160 230-281 8-10 19-23 117-143 289-353 4-5 20-24 4.5 141-172 275-336 14-17 17-21 124-152 294-360 7-8 21-25 9 135-165 258-316 8-10 18-22 131-160 302-369 5-6 22-27 4.5 145-178 310-378 14-17 17-20 136-166 307-375 8-9 23-28 9 140-171 291-356 8-10 18-22 143-175 314-384 5-6 24-30 4.5 150-183 349-426 14-17 16-20 149-182 319-390 8-10 25-30 9 144-176 328-401 8-9 17-21 156-191 327-400 6-7 26-32 4.5 155-189 392-480 13-16 16-19 9 149-182 369-451 8-9 17-21 This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development, specifications are subject to change without notice. 8 733 922 118 (2015/01) Subject to change without prior notice LV Condensing Section LV Condensing Section Operating Temperatures and Pressures | 29 OPERATING DATA MODEL ENTERING WATER WATER FLOW GPM TEMP, ˚F 30˚ LV042 COOLING HEATING WATER SUCTION DISCHARGE SUCTION PRESSURE PRESSURE TEMP RISE, AIR TEMP PRESSURE ˚F DROP, ˚F PSIG PSIG PSIG 6 64-78 248-303 5-6 15-18 10 67-82 254-311 3-4 16-19 6 109-134 183-224 18-22 19-23 75-91 261-319 6-8 17-21 40˚ 10 105-128 172-210 10-12 20-25 79-96 267-327 4-5 18-23 6 118-144 214-261 18-22 19-23 142-173 273-334 8-10 20-24 50˚ 10 113-138 201-245 10-12 20-24 149-182 280-342 5-7 21-26 6 122-149 244-298 17-21 18-22 96-117 286-349 9-11 22-27 10 117-143 230-281 10-12 19-24 101-123 293-358 6-8 24-29 6 126-154 275-336 17-21 18-22 107-131 299-365 11-13 25-30 60˚ 70˚ 10 121-148 258-316 10-12 19-23 113-138 306-374 7-9 26-32 6 130-159 310-378 17-21 17-21 117-143 311-380 12-15 27-33 10 125-153 291-356 10-12 18-22 123-151 319-390 8-10 29-35 6 134-164 349-426 17-20 17-20 128-157 324-396 13-16 29-36 90˚ 10 129-158 328-401 9-12 18-22 135-165 332-406 9-11 31-38 6 139-170 392-480 16-20 16-20 100˚ 10 133-163 369-451 9-11 17-21 71-87 277-339 6-7 15-19 80˚ 6 30˚ 75-92 284-347 4-5 16-20 6 118-144 194-237 21-25 19-23 84-102 291-356 7-9 18-22 10 113-138 182-223 12-14 20-24 88-108 299-365 5-6 19-23 6 127-155 226-276 21-25 18-22 159-194 305-373 9-11 20-25 50˚ 10 122-149 213-260 12-14 19-24 167-204 313-383 6-7 21-26 6 131-160 259-316 21-25 18-22 108-132 320-391 10-13 23-28 60˚ 10 126-154 243-297 12-14 19-23 113-138 328-400 7-9 24-29 6 136-166 291-355 20-25 17-21 120-147 334-408 12-15 25-31 10 130-159 273-334 12-14 18-22 126-154 342-418 8-10 27-32 6 140-171 328-401 20-24 17-20 131-161 348-425 14-17 27-34 80˚ 10 135-165 308-377 11-14 18-22 138-169 356-436 9-11 29-36 6 145-177 369-451 20-24 16-20 144-176 362-442 15-18 30-37 90˚ 10 139-170 347-424 11-14 17-21 151-185 371-453 10-12 32-39 6 149-183 415-508 19-24 16-19 10 143-175 391-477 11-14 17-21 40˚ LV048 DISCHARGE WATER PRESSURE TEMP AIR TEMP PSIG DROP, ˚F RISE, ˚F 70˚ 100˚ 10 This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development, specifications are subject to change without notice. Revised 01-15 8 733 922 118 (2015/01) 30 | Operating Temperatures and Pressures LV Condensing Section OPERATING DATA MODEL ENTERING WATER WATER FLOW GPM TEMP, ˚F 30˚ LV060 COOLING HEATING WATER SUCTION DISCHARGE SUCTION PRESSURE PRESSURE TEMP RISE, AIR TEMP PRESSURE ˚F DROP, ˚F PSIG PSIG PSIG 8 68-84 256-313 5-7 19-23 12 73-89 261-319 4-5 20-25 8 113-138 173-212 18-22 19-23 81-99 277-339 7-8 22-26 40˚ 12 110-134 162-198 12-14 20-24 86-105 283-346 5-6 23-28 8 116-142 207-253 17-21 19-23 93-114 299-365 8-9 24-29 50˚ 12 112-137 193-236 12-14 19-24 99-121 305-373 6-7 25-31 8 118-145 240-293 17-21 18-23 106-129 321-392 9-11 26-32 12 115-140 224-274 11-14 19-23 113-138 327-400 7-8 28-34 8 121-148 273-334 17-21 18-22 118-145 342-418 10-12 29-35 12 117-143 255-312 11-14 19-23 126-154 349-427 8-9 30-37 8 123-151 307-375 16-20 18-22 131-160 364-444 11-14 31-38 12 120-146 287-350 11-13 19-23 139-170 371-454 8-10 33-40 8 126-154 340-416 16-20 18-22 143-175 385-471 12-15 33-41 90˚ 12 122-149 318-388 11-13 18-22 152-186 393-480 9-11 35-43 8 128-157 373-456 16-19 17-21 100˚ 12 125-152 349-426 11-13 18-22 68-84 256-313 5-7 19-23 60˚ 70˚ 80˚ 12 30˚ 40˚ 50˚ LV070 DISCHARGE WATER PRESSURE TEMP AIR TEMP PSIG DROP, ˚F RISE, ˚F 60˚ 70˚ 80˚ 90˚ 100˚ 16 73-89 261-319 4-5 20-25 12 117-143 182-222 15-19 21-26 81-99 277-339 7-8 22-26 16 114-139 170-208 11-14 22-27 86-105 283-346 5-6 23-28 12 120-147 215-263 15-18 20-25 93-114 299-365 8-9 24-29 16 117-143 201-246 11-14 21-26 99-121 305-373 6-7 25-31 12 123-150 248-304 14-17 20-24 106-129 321-392 9-11 26-32 16 119-146 232-284 11-13 21-25 113-138 327-400 7-8 28-34 12 126-154 282-344 14-17 19-24 118-145 342-418 10-12 29-35 16 122-149 263-322 10-13 20-25 126-154 349-427 8-9 30-37 12 129-157 315-385 13-16 19-23 131-160 364-444 11-14 31-38 16 125-153 294-360 10-12 19-24 139-170 371-454 8-10 33-40 12 132-161 348-426 13-16 18-22 143-175 385-471 12-15 33-41 16 128-156 326-398 10-12 19-23 152-186 393-480 9-11 35-43 12 134-164 382-466 12-15 17-21 16 131-160 357-436 9-11 18-22 This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development, specifications are subject to change without notice. 8 733 922 118 (2015/01) Subject to change without prior notice LV Condensing Section LV Condensing Section Compressor Characteristics | 31 COMPRESSOR CHARACTERISTICS Compressor Data Plate Model LV018 LV024 LV030 LV036 LV042 LV048 LV060 LV070 Revised 01-15 Cold Winding Resistance Values (+/10%) Three Phase Voltage Code Rated Voltage Phase RLA LRA R-C S-C Line-Line Run Capacitor (μF/V) 1 2 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 3 4 5 1 3 4 5 1 3 4 5 208-230/1/60 265/1/60 208-230/1/60 265/1/60 208-230/3/60 460/3/60 208-230/1/60 265/1/60 208-230/3/60 460/3/60 208-230/1/60 265/1/60 208-230/3/60 460/3/60 208-230/1/60 265/1/60 208-230/3/60 460/3/60 208-230/1/60 208-230/3/60 460/3/60 575/3/60 208-230/1/60 208-230/3/60 460/3/60 575/3/60 208-230/1/60 208-230/3/60 460/3/60 575/3/60 1 1 1 1 3 3 1 1 3 3 1 1 3 3 1 1 3 3 1 3 3 3 1 3 3 3 1 3 3 3 6.5 5.8 7.4 6.7 5.9 2.9 9.9 8.5 6.9 3.6 13.0 11.3 7.8 3.9 13.6 12.0 8.8 4.4 15.7 11.0 5.4 4.4 26.3 15.6 7.8 5.8 28.3 19.2 8.7 6.9 43 46 43 46 63 30 54 46 63 30 74 67 68 34 88 67 68 34 84 88 44 36 134 110 52 38.9 178 136 67.1 55.3 1.431 1.4 1.431 1.4 0.982 1.4 0.819 0.802 0.656 0.802 0.54 0.453 0.97 - 2.383 2.4 2.383 2.4 1.729 2.46 1.634 1.76 1.558 1.76 1.6 0.792 0.365 - 1.362 5.329 1.362 5.329 1.152 4.606 1.152 4.606 0.928 3.593 5.678 0.68 3.2 5.33 0.6 2.52 3.74 30/370 30/440 35/370 30/440 35/370 30/440 40/370 35/440 45/370 35/370 45/370 80/370 80/370 - Single Phase 8 733 922 118 (2015/01) 32 | Wiring Diagrams LV Condensing Section WIRING DIAGRAMS Figure # 7 8 733 922 118 (2015/01) Subject to change without prior notice LV Condensing Section LV Condensing Section Wiring Diagrams | 33 Figure # 8 Revised 01-15 8 733 922 118 (2015/01) 8 733 922 118 (2015/01) 24.0 26.0 LV048-CS LV060-CS LV070-CS 21.5 33.3 32.5 32.5 26.0 21.5 C 21.00 21.00 21.00 19.00 19.00 19.00 HEIGHT D 2.9 3.3 3.3 2.8 2.8 2.8 WATER IN E 13.4 13.2 13.2 10.8 9.8 8.5 WATER OUT All dimensions within ±0.125. All dimensions in inches. Specifications subject to change without notice 21.5 24.0 LV036, 042-CS 21.5 21.5 LV030-CS B DEPTH A WIDTH LV018, 024-CS Model F G H 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 1" 1" 3/4" 3/4" 3/4" 3/4" 3.6 3.6 3.6 3.6 3.6 3.6 LIQUID SUCTION ELECTRICAL CONNECTION CONNECTION KNOCKOUT 10.7 10.7 10.7 10.7 10.7 10.7 J 1" F.P.T. 1" F.P.T. 1" F.P.T. 3/4" F.P.T. 3/4" F.P.T. 3/4" F.P.T. WATER CONNECTIONS K 1.6 1.6 1.6 1.6 1.6 1.6 SERVICE VALVE GAS 8.4 5.2 5.2 7.0 5.7 5.7 L 3/8 OD 3/8 OD 3/8 OD 3/8 OD 3/8 OD 3/8 OD 1.9 1.9 1.9 1.9 1.9 1.9 SERVICE M VALVE GAS CONNECTION SERVICE VALVE LIQUID 10.2 7.1 7.1 8.8 7.5 7.5 N 7/8 ID 7/8 ID 3/4 ID 3/4 ID 3/4 ID 3/4 ID SERVICE VALVE LIQUID CONNECTION 34 | Dimensional Drawings LV Condensing Section DIMENSIONAL DRAWINGS Subject to change without prior notice LV Condensing Section LV Condensing Section Notes | 35 NOTES Revised 01-15 8 733 922 118 (2015/01) 601 N.W. 65th Court, Ft. Lauderdale, FL 33309 Phone: 866-642-3198 | Fax: 954-776-5529 www.boschtaxcredit.com | www.FHP-MFG.com Revised 01-15