Relays for use in hazardous locations Class I, Division 2 and ATEX Explosion protection in North America Hazardous (classified) locations, as defined in the National Electric Code (NEC), are locations where fire or explosion hazards may exist due to the presence of flammable gases, vapors, flammable liquids, combustible dusts, ignitable fibers or flying matter. Article 500 of the NEC divides all hazardous (classified) locations into Classes, Divisions and Groups. Phoenix Contact’s hazardous-location relays have been tested and approved for: Class I, Division 2; Groups A, B, C, D; and Class I, Zone 2 •Class I: Areas in which flammable gases or vapors are or may be present in the air in quantities sufficient to produce explosive or ignitable mixtures •Division 2: Environments that are not normally hazardous • Groups A, B, C, D: Gas mixtures have been grouped on the basis of their characteristics: - Group A – Atmospheres containing acetylene - Group B – Atmospheres containing acrolein, butadiene, ethylene oxide, propylene oxide, hydrogen and fuel and combustible process gases containing more than 30 percent hydrogen by volume - Group C – Atmospheres containing ethyl ether and ethylene - Group D – Atmospheres containing acetone, ammonia, benzene, butane, cyclopropane, ethanol, gasoline, hexane, methane, methanol, naphtha and propane • Class I, Zone 2 - Non-sparking – Equipment has no normally arcing parts or thermal effects capable of ignition - Sparking with protected contacts – Arcing contacts are in non-incendive circuits, or are inside a hermetically sealed container or sealed device PHOENIX CONTACT Explosion protection in Europe The countries that make up the European economic area adopt directives as their national laws. The ATEX directive is the law of every country in the European community, and part of that law states that all products for use in explosive atmospheres must meet the directive. This means that all manufacturers of mechanical and electrical equipment intended for use in potentially explosive atmospheres that wish to place these products on the market within the European Union need to comply with the ATEX directive. Phoenix Contact’s ATEX relays are dual rated for Class I, Division 2 and for ATEX. ATEX-approved parts are classified into Device Groups and Categories. Our ATEX relays are approved for Device Group II and Category 3G, for use in Zone 2 (gases). • II (Device Group II) – Areas with an explosive atmosphere, like chemical industries, mills (combustible gases and dusts) • 3 (Category 3) – Equipment that is intended for use in areas where an explosive atmosphere is unlikely to occur in normal operation and where operators must ensure a normal level of protection • G – Gas, suitable for atmospheres containing gas • Ex – Explosion-proof electrical equipment • II (Device Group) – Surface installations • C (Gas Group) – Hydrogen Hazardous location relays The industry has imposed stringent requirements on the reliability and safety of switching components in potentially explosive areas. In order to protect against explosion, all equipment that could be exposed to the flammable or combustible atmospheres in hazardous (classified) locations must be of a type suitable for installation in these areas. The classes and groups for which equipment has been certified are shown in the individual certifications under the respective categories and are marked on the equipment itself. Phoenix Contact’s hazardous-location relays – our slim PLC Relay series – have the required approvals for process control equipment. Our Class I, Division 2 (CID2) relays are UL/cUL listed for use in the Americas. Also available are dual-rated ATEX relays: rated for both CID2 and ATEX approvals. Therefore, these relays are certified through UL/DEMKO and comply with the ATEX directive required for the European market. PHOENIX CONTACT ATEX relays D W H D W H 2 PDT with power contact 1 PDT with power contact Notes: 21 Type of housing: Polyamide PA non-reinforced, color: green. 24 Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or FBST 500.... A2 11 A1 14 22 A2 11 A1 14 12 Technical data ② ② ③ Input data Switching level (with reference to UN) 12 Technical data 1 signal (“H”) 0 signal (“L”) Typ. input current at UN [mA] 18 9 3.5 Typ. response time/switch-on time at UN [ms] 8 5 6 Typ. release time/switch-off time at UN [ms] 10 8 15 Transmission frequency flimit [Hz] Input circuit DC Yellow LED, protection against polarity reversal, Yellow LED, protection against polarity reversal, surge protection free-wheeling diode Yellow LED, bridge rectifier Input circuit AC/DC Output data Contact material AgNi AgSnO Max. switching voltage 250 V AC/DC 250 V AC/DC Min. switching voltage 5 V AC/DC (at 10 mA) 5 V (at 100 mA) Limiting continuous current 6A 6A Max. inrush current 15 A (300 ms) on request Min. switching current 10 mA (at 5 V) 10 mA (at 12 V) Test voltage input/output 4 kV (50 Hz, 1 min.) 4 kV AC (50 Hz, 1 min.) Ambient temperature (operation) -40°C to +70°C -40°C to +60°C Mechanical service life 3 x 107 cycles 2 x 107 cycles Standards/regulations IEC 60664, EN 50178, IEC 62103, EN 60079-0, EN 60079-15 IEC 60664, EN 50178, IEC 62103, EN 60079-0, EN 60079-15 Pollution degree/surge voltage category 2/III 3/III Connection data solid/stranded/AWG 0.14 to 2.5 mm²/0.14 to 2.5 mm²/26 to 14 0.14 to 2.5 mm²/0.14 to 2.5 mm²/26 to 14 14 mm/80 mm/94 mm 6.2 mm/80 mm/94 mm Conformance CE-compliant CE-compliant ATEX DEMKO 03 ATEX 0326050U; II 3G Ex nA nC IIC Gc DEMKO 11 ATEX 1111531U; II 3G Ex nA nC IIC Gc UL, USA Class I, Zone 2, AEx nA nC IIC T6 Class I, Zone 2, AEx nA nC IIC T6 UL, USA / Canada Class I, Division 2, Groups A, B, C, D Class I, Division 2, Groups A, B, C, D UL, Canada Class I, Zone 2, Ex nA nC IIC Gc T6 X Class I, Zone 2, Ex nA nC IIC Gc T6 X Output protection Voltage drop at max. limiting continuous current General data Dimensions W/H/D EMC note Conformance/approvals Ordering data Description Input voltage UN PLC INTERFACE, with screw connection ① 12 V DC ② 24 V DC ③ 120 V AC (110 V DC) ④ 230 V AC PLC INTERFACE, with spring-cage connection ① ② ③ 12 V DC 24 V DC 120 V AC (110 V DC) Ordering data Type Order number Replacement relay order number Type Order number Replacement relay order number PLC-RSC-24DC/21-21ATEX 2980461 2906213 PLC-RSC-24DC/21 ATEX PLC-RSC-120UC/21 ATEX 2902955 2902956 2961105 2961118 Class I, Division 2 (CID2) relays D W H D W H 1 PDT with power contact D W H Max. DC voltage output of 3 A Max. DC voltage output of 100 mA A2 11 A2 13+ A2 13+ A1 14 A1 14 A1 14 12 Technical data ① ② Technical data ③ ④ Technical data ② ③ ② ③ ≥ 0.8 ≥ 0.8 ≥ 0.8 ≥ 0.9 ≤ 0.4 ≤ 0.3 ≤ 0.4 ≤ 0.3 15.3 9 3.5 3.2 8.5 3.5 8.5 3.5 5 5 6 7 0.02 3.5 0.02 3 8 8 15 15 0.3 7 0.3 4 300 10 300 10 Yellow LED, protection against polarity reversal, Yellow LED, protection against polarity reversal, free-wheeling diode free-wheeling diode Yellow LED, bridge rectifier Yellow LED, bridge rectifier 250 V AC/DC 33 V DC 48 V DC 12 V AC/DC 3 V DC 3 V DC 6A 3A 100 mA Yellow LED, protection against polarity reversal, Yellow LED, bridge rectifier AgSnO 15 mA (10 ms) 10 mA Protection against polarity reversal, surge protection Protection against polarity reversal, surge protection ≤ 200 mV ≤1V 4 kV AC (50 Hz, 1 min.) 2.5 kV (50 Hz, 1 min.) 2.5 kV (50 Hz, 1 min.) -20°C to +60°C -20°C to +60°C -20°C to +60°C 2 x 107 cycles - - IEC 60664, EN 50178, IEC 62103 IEC 60664, EN 50178, IEC 62103 IEC 60664, EN 50178, IEC 62103 3/III 2/III 2/III 0.14 to 2.5 mm²/0.14 to 2.5 mm²/26 to 14 0.14 to 2.5 mm²/0.14 to 2.5 mm²/26 to 14 0.14 to 2.5 mm²/0.14 to 2.5 mm²/26 to 14 6.2 mm/80 mm/94 mm 6.2 mm/80 mm/94 mm 6.2 mm/80 mm/94 mm Class A product Class A product Class A product CE-compliant CE-compliant CE-compliant - - - Class I, Zone 2, AEx nA nC IIC T6 Class I, Zone 2, AEx nA nC IIC T6 Class I, Zone 2, AEx nA nC IIC T6 Class I, Division 2, Groups A, B, C, D Class I, Division 2, Groups A, B, C, D Class I, Division 2, Groups A, B, C, D Class I, Zone 2, Ex nA nC IIC Gc T6 X Class I, Zone 2, Ex nA nC IIC Gc T6 X Class I, Zone 2, Ex nA nC IIC Gc T6 X Ordering data Ordering data Type Order number Replacement relay order number PLC-RSC-12DC/21/C1D2 PLC-RSC-24DC/21/C1D2 PLC-RSC-120UC/21/C1D2 PLC-RSC-230UC/21/C1D2 5606331 5603154 5603157 5607072 2961150 2961105 2961118 2961118 PLC-RSP-12DC/21/C1D2 PLC-RSP-24DC/21/C1D2 PLC-RSP-120UC/21/C1D2 5606332 5603684 5603683 2961150 2961105 2961118 Ordering data Type Order number Replacement relay order number Type Order number Replacement relay order number PLC-OSC-24DC/ 24DC/ 2/C1D2 PLC-OSC-120UC/ 24DC/ 2/C1D2 5603260 5603262 2966595 2966605 PLC-OSC-24DC/ 48DC/100/C1D2 PLC-OSC-120UC/ 48DC/100/C1D2 5603261 5603263 2966618 2966621 Always up-to-date, always available. Everything you’ll need to know about our products, our solutions and our service is right here: www.phoenixcontact.com Product range • Cables and connectors • Connectors • Controllers and PLCs • Electronic reversing contactors and motor controls • Electronics housing • Ethernet networks • Fieldbus components and systems • Functional safety • HMIs and industrial PCs USA PHOENIX CONTACT P.O. Box 4100 Harrisburg, PA 17111-0100 Phone:800-888-7388 717-944-1300 Technical Service: 800-322-3225 Fax:717-944-1625 E-mail:info@phoenixcon.com Website:www.phoenixcontact.com • I/O systems • Industrial communication technology • Industrial lighting • Installation and mounting material • Marking and labeling • Measurement and control technology • Modular terminal blocks • Monitoring • PCB terminal blocks and PCB connectors • Power-supply units and UPS • Protective devices • Relay modules • Sensor cables and connectors • Software • Surge protection devices • System cabling for DCS and PLC • Tools • Wireless data communication Canada PHOENIX CONTACT Ltd. 8240 Parkhill Drive Milton, Ontario L9T 5V7 Toll Free: 800-890-2820 Phone: 905-864-8700 Fax: 905-864-7900 E-mail: cdinfo@phoenixcontact.ca L003468A:07.15 © 2015 PHOENIX CONTACT