> Reference number: 035< 1 Synchronous Voltage Reversal control of TCSC – impact on SSR conditions Hailian Xie Lennart Ängquist Master student Researcher Royal Institute of Technology, Stockholm Abstract—The paper describes the laboratory setup of a TCSC model. A new control scheme named SVR (Synchronous Voltage Reversal) control is employed instead of the traditional firing angle control scheme. The impact of the SVR controlled TCSC on SSR is investigated in this real-time simulator by analysing the system damping. Some results are presented graphically together with conclusions. Index Terms— Series compensation, SSR, TCSC, Boost control. Fig. 1. TCSC main circuit I. INTRODUCTION S eries compensation is an effective mean to increase the electrical power transfer capability of high-voltage transmission lines. Insertion of a capacitive reactance in series with the line’s inherent inductive reactance lowers the total, effective impedance of the line and thus virtually reduces its length. As a result both angular and voltage stability in the power system gets improved. A side effect of the inserting a series capacitor in series with the transmission line is that an electrical resonance will be introduced. In the 70’ies it was experienced that this electrical resonance may be harmful if a series compensated transmission line is connected electrically close to a thermal power station. The reason is that the shaft system joining the electrical generator with the various turbine stages exhibits mechanical torsional resonance at various “subsynchronous” frequencies, i.e. frequencies below the nominal 50 or 60 Hz frequency of the network. At certain unfavourable relations between the electrical and mechanical resonance frequencies oscillations with exponentially increasing amplitude can be excited spontaneously. This condition is being referred to as a Torsional Interaction SubSynchronous Resonance “TI-SSR”. This condition potentially may cause damage to the generator with severe consequences for the power supply and causing harsh economical loss. During the 90’ies the Thyristor Controlled Series Capacitor (TCSC) was being introduced. In this apparatus a thyristor controlled, inductive branch has been connected as an add-on in parallel with the series capacitor bank (Fig. 1.). When a forward-biased thyristor is fired the capacitor will be partially discharged through the LC circuit constituted by the thyristor controlled inductive branch and the capacitor bank. The circulating current pulse passes through the capacitor in phase with the line current. It creates an additional voltage across the capacitor in excess of the voltage, which is caused by the line current. The increased voltage at a given line current amplitude is perceived by the transmission system as if the inserted capacitive reactance had been increased or “boosted” by the action of the thyristor valves. The generic waveform of the TCSC is shown in Fig. 2. 2 0 -2 5 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 -5 50 0 -50 0 -20 -40 Fig. 2. Generic waveforms for the TCSC. From top to bottom: line current, valve current, capacitor voltage, apparent reactance It was recognized early that the characteristics of the TCSC with respect to SSR differed completely from that of a passive, fixed series capacitor. The latter reveals a capacitive > Reference number: 035< 2 reactance, which is inversely proportional to the frequency. Accordingly it tends towards infinity at zero frequency (DC). The apparent reactance of the TCSC, in contrast, decreases with frequency and gets zero at zero frequency (DC). The reason for this dissimilarity is that the TCSC reacts on an injected subsynchronous line current component by modulating the thyristor current in the inductive branch. This influences the subsynchronous current passing through the capacitor, which determines the subsynchronous voltage across the TCSC. The algorithm that has been selected for the thyristor triggering control plays the main role in forming the characteristics of the TCSC with respect to SSR behaviour. However, also the regulators executing synchronization and boost control do have an impact on the TCSC’s SSR properties. II. TCSC WITH SYNCHRONOUS VOLTAGE REVERSAL CONTROL Figure 3 depicts a control system named Synchronous Voltage Reversal (SVR) scheme, in which the boost regulator provides the time reference for the capacitor voltage zero-crossing instants rather than, as in conventional approaches, the thyristor firing instants. A supplementary device then determines the firing instant taking into account actual line current and capacitor voltage values. IL-meas phase comp PLL SVR that can be utilized by eliminating the risk of SSR. A simple explanation is as follows: an SSR condition can only arise through interaction between a mechanical and an electrical resonance at complementary frequencies. The effect of using TCSC instead of fixed series capacitors is that the electrical resonance frequency is pushed towards a lower frequency, as if a lower degree of compensation had been used. A. SVR control scheme Traditional boost control method controls the firing angle β = π − α of the thyristor. A rather non-linear relation exists between the boost factor k B and the steady state conduction angle σ = 2β making k B very sensitive to the instant of triggering when the TCSC runs at a high boost factor. Further, at transients, a complicated dynamic characteristic governs the relation between the firing angle and the conduction angle. Instead of controlling the thyristor firing angle, another control scheme, named ‘Synchronous Voltage Reversal’, is being used. It aims for controlling the instant when the capacitor voltage crosses zero [1]. Analysis of the TCSC circuit during the conduction interval shows that the capacitor voltages at the start and end instants of the conduction have the same magnitude but with opposite sign. Therefore, the effect of the conduction of the thyristor controlled inductance branch can be represented by an equivalent, instantaneous voltage reversal. In steady state when there is no change in the boost factor, the zero-crossing point of the capacitor voltage will coincide with the peak point of the line current, called equilibrium point of the synchronous voltage reversal. However, if the zero-crossing occurs at a point other than the equilibrium point, e.g. with an angular displacement of ∆ϕc as shown in Figure 4, the boost factor will change according to (1). uc iL UC Phasor eval IL UC-meas Boost meas Boost ref α − iv π 2 β Boost contr t Fig. 3. Outline of TCSC boost control system (inner layer marked SVR) It is shown in [1] that this approach ideally provides an apparent inductive reactance of the TCSC for subsynchronous frequencies, independent of the boost level. As a general rule the risk for SSR problems increases with increasing degree of compensation of the transmission line. Experience shows that normally 30 % of the line reactance can be compensated by series capacitors without any risk of SSR. However, from a power transmission point of view, often more compensation is desired in order to improve stability in the system, specifically during contingencies. The use of TCSC can enhance the degree of compensation ∆ϕc Fig. 4. Illustration of SVR control scheme 16 f N ∆ϕc π s where s is the Laplace operator. ∆k B = (1) > Reference number: 035< 3 In order to control the boost factor, it is advantageous to immediately control the angular displacement ∆ϕc of the synchronous voltage reversals from their equilibrium points. It should be noticed that any change of the phase of the line current would have the same impact on the boost factor as the change of ∆ϕ c has. To eliminate this impact a Phase-LockedLoop (PLL) is introduced. The PLL works on the line current and gives out the PLL angle θ PLL , which is used in the coordinate transformation from the fixed coordinate system to the rotating coordinate system and in the calculation of the firing time. Analysis of the circuit equation during the conduction interval yields another expression for ucz [1]. Namely, B. Synchronous voltage Reversal (SVR) equation The output of the boost controller is the angular displacement of the equivalent voltage reversals from their equilibrium point ∆ϕ c . This angle displacement determines the instant when the voltage zero-crossing should occur. The voltage zero-crossing instant, together with ω PLL and the tF = tZ − known circuit parameters such as X0 and λ (see table 1), in turn determines the firing time of the related thyristor. Methods for calculating the firing time have been described in [1]. The method used in the implementation is based on the simple assumption that the line current is constant and equals to the measured value during the interval between the measurement and the firing time. Below a brief review of this calculation procedure is presented. First the notations are defined according to Fig. 5. t M : the instant at which line currents and capacitor voltages are sampled; t F : thyristor firing instant. t Z : the desired instant when the capacitor voltage zerocrossing occurs; The PLL angles corresponding to these three instants are: θ PLL _ M , θ PLL _ F , and θ PLL _ Z . θ PLL_Z θ PLL_F β π 2π iL ∆ϕ c 0 u c ----without boosted tF tZ = uCM + X 0 i LM λω PLL (t Z − t M ) (2) = uCM + X 0 i LM λ (θ PLL _ Z − θ PLL _ M ) uCZ = X 0iLM [λβ − tan(λβ )] (3) where β = ω PLL (t Z − t F ) is the angle difference between firing time and voltage zero-crossing time. By solving the nonlinear equation, which is obtained by combining (2) and (3), β can be acquired. The firing time is then obtained from (4): β ω PLL (4) C. Boost control system The overview of the boost control system is shown in Fig. 3. The line current and capacitor voltage are measured and the components of fundamental frequency are extracted through phasor estimation [3]. The complex quotient between these two phasors gives the apparent impedance of the TCSC capacitor bank. Normalizing the imaginary part of the apparent impedance with the physical reactance of the capacitor bank yields the measured boost factor, which will be taken as a feedback signal and compared with the reference boost factor. The error of the boost factor is delivered to the boost controller, whose output can be visualized as a series of time reference pulses that defines the instants when the capacitor voltage should cross zero. The block named ‘SVR’ will determine the thyristor firing time taking into account the measured line current and capacitor voltage and then trigger the corresponding thyristor at desired instant. In the KTH laboratory for electrical machine and power electronics, a real-time power system simulator is being implemented. The simulator contains a general-purpose control system of type ABB Mach 2, which is adapted to control power electronic apparatus for high-power applications e.g. the TCSC. θ PLL_M tM 1 i LM ∆t CTCSC III. LABORATORY SET UP PLL angle PLL angle uCZ = uCM + ∆uC = u CM + tim e Fig. 5. Illustration of SVR equation As the first step, (2) gives an estimation of the capacitor voltage at t Z based on the measured value of the line current iLM and the assumption mentioned above. A. Simulation system overview Fig. 6 shows the TCSC simulation system, which is the model of a simple transmission system. The system consists of two voltage sources (an infinite bus and a source with source impedance) and a transmission line compensated by a TCSC in series with a fixed capacitor bank. > Reference number: 035< 4 Thyristor Valve TCSC inductance Source 1 line fixed Impedance impedance capacitor TCSC capacitor infinite bus Fig. 6. TCSC simulation system diagram The part within the dashed-line frame forms the TCSC. The thyristor valve module is designed with compensation for the thyristor forward voltage drop during conduction and for the resistive voltage drop in the TCSC inductor. With such a design, the thyristor controlled inductance branch will appear as an ideal thyristor valve in series with a pure inductance. The transmission lines in the power system are represented by inductors and resistors. The specifications of the simulation system are given in Table 1. simulate a voltage produced by a synchronous machine, for which the shaft speed contains a small sinusoidal variation. The generic voltage generated is derived assuming that the rotor flux is constant in the rotor coordinate system [1]. For oscillation frequencies in question with respect to Subsynchronous Resonance, i.e. 15-45 Hz mechanical frequencies, this approximation seems to be adequate. At these rotor frequencies, the resistance in the damper windings has little impact and thus these windings serve as a magnetic screen, which captures the rotor flux and prevents it from being varied. The leakage between the stator winding and the damper windings is represented by the subtransient reactance and the rotor flux behind that reactance can be considered to be constant in the rotor-fixed coordinate system. This means that the sub-transient reactance of the machine should be incorporated with the transmission system when the analysis is being performed. Similarly the stator resistance can be incorporated with the transmission system impedance. The machine model is shown in Fig. 7 within the dashed frame. us = dψ r Rsource XL_source dt Rline XL_line Infinite bus Table 1 specification of the simulation system Parameter Notation Value Source resistance [Ω] Rsource 0.98 Fig. 7. The generator model Source reactance at fN [Ω] XL_source 9.5 Source inductance [mH] Lsource 30.3 2) Formulas for generated voltage Assume that rotor flux is constant in the rotor reference frame and is given by Figure 2.2. Generator model Line resistance [Ω] Rline 1.86 Line reactance at fN [Ω] XL_line 23.6 Line inductance [mH] Lline 75.1 Fixed capacitor bank [µF] Cfixed 550 Fixed capacitor reactance at fN [Ω] Xc_fixed 5.79 TCSC capacitor bank CTCSC 650 TCSC capacitor reactance at fN [Ω] Xc_TCSC 4.90 TCSC inductance LTCSC 2.45 [µF] [ mH ] λ(ratio between the TCSC resonance frequency and fN) TCSC resonance frequency [ Hz ] f0 126 TCSC capacitor reactance at f0 X0 1.94 [Ω] ψ RR (t ) ≡ ψˆ R (5) The mechanical angle of the shaft is θ sh (t ) with respect to a certain reference angle in the stator. Generally, the stator flux in the rotor coordinate system is given by: ψ sR = L's' ⋅ isR + ψ RR (6) 2.52 Since the transient reactance of the generator has be incorporated into the transmission system, the flux then becomes: ψ sR = ψ RR = ψˆ R B. Voltage sources The source voltages are generated by electronic power amplifiers controlled by a DSP. The selected power scale utilizes 10 3 V rms as the nominal line-line voltage (might correspond to 500 kV) and 8VA as a nominal power (might correspond to 1000 MVA). 1) Generator model In order to investigate the impact of the TCSC on SubSynchronous Resonance, one of the voltage sources should (7) Accordingly, in the stator coordinate system, the stator flux becomes ψ SS (t ) = ψˆ R e jθ sh (t ) (8) Assume that the nominal angular frequency is ω N . Then the induced stator voltage is given by > Reference number: 035< u SS (t ) = 5 θ& 1 dψ SS = jψˆ R sh e jθ sh (t ) ω N dt ωN (9) Let the normalized shaft speed be defined by nsh (t ) = θ&sh (t ) ωN u t ( ) a 1 1 ub (t ) = − u (t ) 2 c 1 − 2 0 3 uα (t ) 2 u β (t ) 3 − 2 (16) (10) With all the above equations implemented in the DSP and the scaling adjusted, two source voltages are obtained with one per unit voltage corresponding to 10V rms phase voltage. Then (9) yields u SS (t ) = jψˆ R nsh (t )e jθ sh (t ) (11) IV. SSR a) Voltage generated in the infinite bus For the infinite bus, the generator shaft angle is given by (12): θ sh (t ) = ω N t + ϕ (12) where ω N is the nominal angular frequency and ϕ is the phase angle. Inserting (12) to (11) yields the generated voltage vector. b) Voltage generated with Shaft torsional oscillation Assume that the generator is running with nominal average speed but with a small super-imposed sinusoidal phase angle variation with amplitude ∆θˆ and frequency Ω ; and assume the phase is ϕ . { } θ sh (t ) = ω N t + Re ∆θˆ e jΩt + ϕ (13) The corresponding normalized speed variation can be obtained from (10), which yields { nsh (t ) = 1 + Re ∆nˆ e jΩt ∆nˆ = j Ω ωN (14) Insertion of (13) and (14) in (11) defines the voltage generated in the stator. This voltage contains both the nominal fundamental frequency and side-bands at frequencies that deviate from the fundamental frequency by the mechanical oscillation frequency. However, in the DSP program the general formula without linearization is utilized. Equation (11) gives out the voltage space vector in the stator coordinate system, i.e., u SS (t ) = uα (t ) + ju β (t ) A. Analysing method 1) Electrical torque The source voltage generated by the DSP as stated in Chapter 2 is a simulation of a turbine-generator, whose shaft angle is modulated with a frequency of Ω and amplitude ∆θˆ , i.e., with an angular deviation from its steady state: ) ) ∆θ = Re(∆θ e jΩt ) = ∆θ cos Ωt (15) The three phase quantities of the generated voltage can be obtained by the following transformation [2]: (17) Correspondingly, the speed variation is: ∆n = − Ω ωN ∆θˆ sin Ωt (18) With the generated source voltages connected to the simulation system, the line currents that occur are measured and returned into the DSP. The electro-dynamical torque now can be calculated from the generated voltage and the measured current according to (19) { } ∆θˆ With the TCSC simulation system runs with a shaft angle modulated voltage source, the damping performance of the system with respect to SSR has been investigated. Tel (t ) = Im iSS (t )e − jθ sh (t )ψˆ R } (19) The electrical torque contains two components, the steady state one Tel _ av and the variation one ∆Tel as shown in (20). Tel (t ) = Tel _ av + ∆Tel (20) The variation component ∆Tel is caused by the angle modulation of the generator shaft and thus has the same frequency Ω as the shaft oscillation. Therefore, ∆Tel can be expressed as (21). { } ∆Tel = Re ∆Tˆel e jΩt = Re Re(∆Tˆel ) + j Im(∆Tˆel ) e jΩt = Re(∆Tˆ ) cos Ωt − Im(∆Tˆ ) sin Ωt {[ el ] } el (21) > Reference number: 035< 6 ~ Ω ∆Tel = − K el ∆θˆ cos Ωt − Del (− ∆θˆ sin Ωt ) (22) ωN Here K el and Del can be identified as the ‘electrical spring constant’ and ‘electrical damping factor’ respectively. Comparing (21) and (22) yields: ~ − Re(∆Tˆel ) K el = ∆θˆ ~ − Im(∆Tˆel )ω N Del = ∆θˆ Ω (23) Equation (23) gives the spring constant and damping factor of the system with a certain shaft modulation frequency. In order to measure the damping coefficient in the subsynchronous frequency range, a MATLAB program is applied to interface the DSP, which controls the generated voltage. The MATLAB program will automatically perform the investigation by commanding various oscillation frequencies and recording the measured results. Every time MATLAB commands a new frequency to the DSP, a new source voltage with that new modulation frequency will be generated. With the measured line current sent back to DSP, the DSP could calculate the electrical torque, extract the component with the modulation frequency and split it into real part and imaginary part. The MATLAB program reads these two parts of the torque phasor from the DSP and calculates the spring constant and the damping coefficient. Finally, the program generates the curve showing the damping coefficient and the spring constant as functions of mechanical modulation frequency. B. SSR behaviour of the TCSC The simulation results for several cases will be presented in this part. As a first example, the simulated transmission line is compensated by a fixed capacitor bank of 224 µF which gives a compensation of Xc = 14.2 Ω In this case, the electrical resonance frequency of the transmission system will be: 1 2π ( Lsource+ Lline ) C fixed 1 2π (75.12 + 30.25) * 224*10−9 (24) = 32.8 Hz Theoretically, this is the complementary frequency of the critical undamping mechanical frequency, which will be testified by the actual damping curve plotted in Fig. 8. Del & Kel with fixed series compensation 5 Del [pu trq/pu spd] ~ pass filters these two parts, Re(∆Tˆel ) and Im(∆Tˆel ) , can be extracted. 2) Damping curve Generally, the torque variation can be resolved into two parts, proportional to the angular variation and the speed variation respectively, i.e., = 0 -5 -10 -15 10 15 20 10 15 20 25 30 35 40 45 25 30 mech freq [Hz] 35 40 45 3 Kel [pu trq/rad] It can be observed that the variation component can be split into two parts, in phase with the speed variation and the angular variation respectively. By utilizing three 1st-order low fo _ line = 2 1 0 -1 -2 Fig.8. Electrical damping (Del) and spring constant (Kel) for system with fixed series compensation The figure shows that with a torsional shaft vibration frequency of about 17 Hz, the fixed series compensated system has a large negative damping, which means high danger to the generator shaft. Then the 224 µF fixed capacitor bank will be replaced by a combination of a 550 µF fixed bank in series with the TCSC. When the TCSC operates at a boost factor of 1.72, the total compensation becomes: Xc = Xc _ fix + k B ⋅ X c _ TCSC = 5.787 + 1.72 ⋅ 4.897 = 14.2Ω (25) This gives the same compensation degree at network frequency as the 224 µF capacitor bank. Let the gain of PLL and boost controller both be very low (0.015) and the integrating part be very slow so that the damping characteristic is determined almost completely by the SVR control scheme. Fig. 9 presents resulted damping curve for boost factor 1.2 and 1.72. > Reference number: 035< 7 while as increases the undamping peak values. S V R c ontrol, no P LL, no boos t c ontrol 2 SVR, KB=1.72, medium boost control with different PLL speed 0 4 Del [pu trq/pu spd] Del [pu trq/pu spd] 4 -2 -4 -6 10 15 20 25 30 35 40 45 2 1 -6 10 15 20 25 30 35 -1 10 15 20 25 30 m ec h freq [Hz ] 35 40 45 When compared with figure 8 it can be seen that the critical undamping frequency is pushed rightward, from about 17 Hz to 31 Hz. The use of the TCSC with SVR control scheme makes it possible to utilize high compensation even in a system fed by a generator having a torsional resonance frequency about 10 Hz higher than if only fixed series compensation is used. It should also be noted that the discrepancy between different boost factors is quite small. This implies that the TCSC using SVR control can mitigate SSR problems even when operating at low boost factor. Direct control of the thyristor fire angle does not provide similar performance. Fig. 10 gives a comparison between these two control methods both with a boost factor of 1.2. It shows that SVR can provide much better damping for frequencies lower than 25 Hz. • • • [1] -2 [2] -4 20 25 30 35 40 45 3 SVR control beta control 2 1 0 -1 10 15 20 25 30 mech freq [Hz] 35 15 20 25 30 mech freq [Hz] 35 40 45 V. CONCLUSION 0 15 10 At low boost factor, SVR controlled TCSC can provide much better damping than conventional control scheme that controls the firing angle directly. The damping characteristic of SVR controlled TCSC with respect to SSR is almost independent of the boost factor. The tuning of the boost controller and PLL makes no critical difference on the TCSC SSR behaviour. REFERENCES 2 10 0 Fig.11. SVR control; medium boost control; Boost factor 1.72; slow PLL (thick line); medium PLL (dashed line); fast PLL (thin line) KB=1.2, no PLL, no boost control -2 45 slow medium fast 2 -2 4 -6 40 4 Fig.9. SVR control; no PLL, no boost control; Boost factor 1.2 (thick line); boost factor 1.72 (thin line) Del [pu trq/pu spd] -4 0 -2 Kel [pu trq/rad] 0 -2 -8 K B = 1.2 K B = 1.72 Kel [pu trq/rad] Kel [pu trq/rad] 3 2 40 45 Fig. 10. No PLL, no boost control; boost factor 1.2; β control (thin line); SVR control (thick line) Finally, the system is assumed have a medium boost controller gain but with different synchronizing speed. It can be seen from Fig. 11 that for frequencies lower than 11 Hz, a fast PLL reduces the damping. Moreover, a fast PLL speed pushes the critical undamping frequency rightward slightly as [3] Lennart Ängquist, “Synchronous Voltage Reversal Control of Thyristor Controlled Series Capacitor”, Royal Institute of Technology, TRITAETS-2002-07, ISSN 1650-674X Lennart Harnefors, Hans-Peter Nee, “Control of Variable-Speed AC Drives”, Royal Institute of Technology, 1998 Lennart Ängquist, “RLS-based Phasor Estimator for POD”, ABB Utilities AB (SE), 1JNR100001-406