PowerPlus™ Panelboards

advertisement
Cooper Crouse-Hinds ®
PowerPlus™ Panelboards
L i g h t i n g a n d H e a t Tr a c i n g
E P L S e r i e s ( D i v. 1 )
D 2 L S e r i e s ( D i v. 2 )
EPLCN
D2LBS
(INVERTED)
PowerPlus D2L/EPL series panelboards provide
distributors, engineers, contractors, and end-users
with the ideal solution for the protection of lighting
and heat tracing circuits. Tailored toward simplicity
of installation, ease of maintenance, nearly infinite
configurations for numerous applications, and reliable
peace-of-mind performance, this offering is designed
and manufactured as the industry's safest and most
dependable panelboard for hazardous area locations.
EPLCA
PowerPlus™ Panelboards
This corrosion-resistant Type 4X
breather and drain comes standard
with all D2L/EPL panelboards. This
permits all models to maintain their
Type 4 (Type 4X with suffix S752)
rating while utilizing a breather/
drain solution to drain internal condensation while protecting against
ingress of rain and hose water.
D2L/EPL panels come
standard with a high-quality
silver-plated copper buss
system. This provides highefficiency current flow
between the main feed
and branch breakers.
D2L/EPL panels are
available with GFI and/or
EPD breakers. This 21position electrical test
circuit allows for testing of
GFI, EPD, or a combination
of both in one panel.
Each branch and main
breaker handle is provided
with lockout/tagout capability,
which provides safety and
complies with OSHA lockout/
tagout requirements. This
allows for locking in the ON
or OFF position for standard
maintenance checks.
Spring-loaded, quick-release, captive stainlesssteel cover bolts come standard. This design
prevents damage to the flat joint flame path
when opening and closing the cover while providing visual identification of bolt engagement.
D2L/EPL panels are available
with an optional hinged stainlesssteel ice shield. This ice shield
solution prevents ice and snow
build-up on breaker handles to
allow for proper handle function
in cold/wet climate applications.
(cut away photo)
Stainless-steel hinges are engineered to
provide maximum stability and allow the
cover to swing fully open. This avoids
misalignment of cover to the body of the
enclosure and prevents the cover from
obstructing interior access.
2
EPLCN
Integrated steel lifting eye is mounted
on the top side of each D2L/EPL panel.
This provides a stable lifting position
to ensure ease of mounting during the
installation process.
D2L/EPL cast enclosures are manufactured
with an external flange design. This design
allows for a wide unobstructed cover opening
and provides a completely accessible interior
for ease of maintenance and wiring.
Superior self-aligning breaker operators
are designed for both field and factory
installation. This patent-pending design
guarantees proper handle alignment when
closing the cover.
All panels with terminal housings
are factory sealed* and fully wired
for maximum available circuits.
This allows D2L/EPL models the
ability to have additional breakers
field installed while maintaining
their factory seal.
All terminal blocks
come fully wired with
each contact numbered
for easy connecting of
branch entries.
Heavy-guage 316L stainlesssteel terminal housings (D2LBS
and D2LCS series) are supplied
with three removable gland
plates to be used with Myers®
hubs. This design allows for
the flexibility of factory- or fielddrilled openings for hubs.
D2LBS (INVERTED)
D2L series lighting and heat
tracing panelboards offer an
industrial-grade 316L stainlesssteel terminal housing as standard.
This design offers an increased
internal volume with a removable
front cover for easy access during
field installation and maintenance.
A cast aluminum terminal housing
is standard on EPL panels and
available on D2L panels.
Stainless-steel terminal housings
offer a high-integrity gasket,
providing a watertight seal to meet
enclosure Type 4/CSA ENC. 4/
IP65 requirements. This provides
superior protection of enclosed
wiring against water and corrosion.
Cast aluminum enclosures are
also gasketed providing a NEMA 4
watertight seal.
*Conduit entries 2" or larger in
Class I, Div. 1 Group B must be
sealed within 18" of enclosure.
3
PowerPlus™ Panelboards
PowerPlus factory-sealed panelboards provide flexibility and labor savings when installed, and for future changes in the
field. Panels are prewired to maximum circuit capacity and ratings with field-replaceable factory-sealed components.
APPLICATIONS:
ELECTRICAL RATINGS:
EPL/D2L PowerPlus Panelboards are used:
• in areas subject to weather, dampness, and corrosion
Branch Breakers (120/240VAC Quicklag® Bolt-on) Trip Ratings:
1, 2 & 3-pole
10, 15, 20, 25, 30, 35, 40, 45, 50 amp (available in all breaker
spaces in panel) 55, 60, 70, 80, 90, 100 amp (only 3 breaker
spaces available for 55 to 100 amp branch breakers)
• for branch power distribution and circuit protection to motors,
valves, pumps, lighting, heat tracing, receptacles, etc.
• GFI type, 1 & 2-pole (5mA sensitivity) 15, 20, 25, 30, 40
(50 amp – available 2-pole only)
• for indoor and outdoor applications in petroleum refineries,
chemical and petrochemical plants, and other process industry
facilities where similar hazards exist
• EPD type, 1 & 2-pole (30mA sensitivity) 15, 20, 25, 30, 40
(50 amp – available 2-pole only)
• in areas made hazardous by the continuous or abnormal
presence of flammable gases, vapors, and combustible dusts
• to accommodate up to 100 amp branch loads (only 3 circuits),
balance is up to 50 amps
• HID Type, 1 & 2-pole, 15, 20, 25, 30, 35, 40, 50, 60
• Available with GFI, EPD, or a combination of both in one panel
with a 21 position electrical test circuit
Main Breaker Trip Ratings:
CERTIFICATIONS
AND
COMPLIANCES:
EPL Series (Division 1):
• NEC/CEC:
Class I, Division 1 & 2, Groups B†,C,D
Class I, Zone 1 & 2, IIB+ Hydrogen†
Class II, Division 1, Groups E,F,G
Class II, Division 2, Groups F,G
Class III
• 2- or 3-pole
• Size B: 10 to 100 amps
• Size C: 10 to 225 amps
Main Lugs:
• Size B and C: 225 amp
STANDARD MATERIALS
AND
FINISHES:
• NEMA/EEMAC: 3, 4, 4X*, 7B†CD, 9EFG, 12
• CSA Enc. 3, 4, 5
• Breaker enclosure body and cover – copper-free aluminum
• UL Standard: 67, 877
• Terminal housing – Type 316L stainless-steel (D2LBS and
D2LCS only), copper-free aluminum (EPL, D2LBA & D2LCA)
• cUL (to CSA Standard C22.2 Nos. 29 & 30)
4
• IP65
• Gasket – neoprene (cast aluminum enclosures), Foam-in-place
(stainless-steel enclosure)
D2L Series (Division 2):
• Operating handles – die-cast aluminum (copper-free)
• NEC/CEC:
Class I, Division 2, Groups B†,C,D
Class I, Zone 2, IIB+ Hydrogen†
Class II, Division 2, Groups F,G
Class III
• Operating shafts and bushings, cover bolts, washers, and
retractile springs – stainless-steel
• NEMA/EEMAC: 3, 4, 4X*, 7B†CD, 12
• Hinges – Type 316 stainless-steel
• CSA ENC. 3, 4, 5
• Chassis – silver-plated copper
• UL Standard: 67, 877
• Breather and drain – Type 316 stainless-steel
• cUL (to CSA Standard C22.2 Nos. 29 & 30)
• Breather cap – Delrin® non-metallic material
• IP65
• Neutral and ground bar – tin-plated aluminum
† Group B and IIB + Hydrogen is standard on all EPL and D2L panels, but requires
special brackets to be installed on breakers. To order with brackets installed at
factory, add suffix -GB. For field installable kit order EPL-GB-KIT separately.
* NEMA 4X rating is available when ordered with suffix S752 or S753.
Delrin® is a registered trademark of DuPont
• Circuit breaker operators – non-metallic
• Lifting bracket – electrogalvanized cold rolled steel
OPTIONS:
ACCESSORIES:
To add the following features to the panelboard, add a dash and
then the suffix to the catalog number. Multiple suffixes should be
added in alpha-numeric order.
Field-installable gland plates with factory-provided
aluminum Myers Hubs for the D2L stainless-steel terminal
housing (one 3-inch hub and 12 branch entry hubs – size
dependent upon suffix, each kit includes 3 gland plates,
one for the top or bottom and 1 for each side):
Space heater (120/240V) . . . . . . . . . . . . . . . . . . . . . . . . R22
Square-head plugs on all conduit openings . . . . . . . . . . . . . SP
Epoxy powder coat finish, external . . . . . . . . . . . . . . . . . S752
Epoxy powder coat finish, internal and external . . . . . . . . S753
Recess-head plugs on all conduit openings . . . . . . . . . . . . . RP
Stainless-steel breaker operator cover (ice shield) . . . . . . . .HG
Group B Kit factory installed . . . . . . . . . . . . . . . . . . . . . . . GB
GFI breakers (see ordering example) . . . . . . . . . . . . . . . . . . G
EPD breakers (see ordering example) . . . . . . . . . . . . . . . . . . E
HID breakers (see ordering example) . . . . . . . . . . . . . . . . . . H
Ambient compensated breakers (50°C) . . . . . . . . . . . . . . . . V
(i.e. D2LCS324V)
A standard panelboard has conduit openings for power
and branch circuits on top.
• To order a panelboard with main power feed from the
bottom of breaker housing, and branch entries on top,
(Alternate) add . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -A
• To order an inverted panelboard with conduit openings for
power and branch circuits on the bottom, (Inverted) add . . . -I
• To order an inverted panelboard with main power feed on
top and branch entries on the bottom, (Alternate inverted)
combine the above options . . . . . . . . . . . . . . . . . . . . . . -A-I
¾" branch entry hub. . . . . . . . . . . . . . . . . . . .D2L-HUB2-KIT
1" branch entry hub . . . . . . . . . . . . . . . . . . . .D2L-HUB3-KIT
1½" branch entry hub. . . . . . . . . . . . . . . . . . .D2L-HUB5-KIT
Replacement gland plate (no hubs) . . . . . . . . . .D2L-HUB0-KIT
• Extra circuit-breaker operator assemblies for 1-pole or 3-pole
breakers (Qty. 1): EPL-HDL13 (handle kits include operating
handle, shaft, bearing, pin, and non-metallic slider)
• Extra circuit-breaker operator assemblies for 2-pole breakers
(Qty. 1): EPL-HDL2 (handle kits include operating handle,
shaft, bearing, pin, and non-metallic slider)
• Replacement cover plugs for unused circuit breaker positions
(Qty. 5): EPL-OP-PLG
• Kit for Group B, standard panels less GB suffix are good for
Group B, but it is required to install brackets on breakers.
To order brackets factory installed add suffix -GB. For field
installable kit order: EPL-GB-KIT
• Stainless-steel breaker operator cover to protect operators
from ice build-up:
– Kit for Size B panel: EPL-HG24-KIT
– Kit for Size C with no main breaker or main breaker 100
amps or less: EPL-HG42-KIT
– Kit for Size C with 110 amp to 225 amp main breaker:
EPL-HG36-KIT
• Space Heater Kit: EPL-R22-KIT
• Mounting plate kit for cast-aluminum terminal housing to adapt
depth of terminal housing to same depth as breaker enclosure:
EPLA-MTG-KIT*
• Mounting plate kit for stainless-steel terminal housing to adapt
depth of terminal housing to same depth as breaker enclosure:
D2LS-MTG-KIT*
*note that the weight of the panel is sufficiently supported by mounting of the
breaker enclosure
D2L Panelboard with
inverted option (-I)
5
PowerPlus™ Panelboards
ORDERING INFORMATION:
Figure 1: Base Panelboard Catalog Numbers
1. Select the base panelboard catalog number from Figure 1.
EPL and D2L Factory Sealed 120/240
Lighting Panelboards
• Determine phase (available with single-phase or threephase wiring)
• Determine a total even number of breaker spaces needed to
complete your desired lighting panelboard
NOTE:
Three-pole breaker
Two-pole breaker
Two-pole GFI
(or EPD) breaker
Single-pole breaker
Single-pole GFI
(or EPD) breaker
= 3 breaker spaces
}
}
= 2 breaker spaces
= 1 breaker space
• Review Table A on page 7 to determine panel size
• If GFI or EPD breakers are to be included insert ‘‘G’’ and/or
‘‘E’’ after base catalog number and review Table B (e.g.,
D2LBS318G)
• If ambient compensated breakers are to be supplied insert ‘‘V’’
after base catalog number (e.g., D2LBS318V). All breakers will
be supplied ambient compensated
• If HID breakers are to be included insert ‘‘H’’ after base catalog
number (e.g., D2LBS318H)
DIVISION 1‡
(w/cast aluminum
terminal box)
DIVISION 2‡
(w/sheet 316L Stainlesssteel terminal box)
1 Phase
3 Wire
3 Phase
4 Wire
1 Phase
3 Wire
3 Phase
4 Wire
2
EPLBA102
EPLBA302
D2LBS102
D2LBS302
4
EPLBA104
EPLBA304
D2LBS104
D2LBS304
6
EPLBA106
EPLBA306
D2LBS106
D2LBS306
8
EPLBA108
EPLBA308
D2LBS108
D2LBS308
10
EPLBA110
EPLBA310
D2LBS110
D2LBS310
12
EPLBA112
EPLBA312
D2LBS112
D2LBS312
14
EPLBA114
EPLBA314
D2LBS114
D2LBS314
16
EPLBA116
EPLBA316
D2LBS116
D2LBS316
18
EPLBA118
EPLBA318
D2LBS118
D2LBS318
20
EPLBA120
EPLBA320
D2LBS120
D2LBS320
20
EPLCA120
EPLCA320
D2LCS120
D2LCS320
22
EPLBA122
EPLBA322
D2LBS122
D2LBS322
22
EPLCA122
EPLCA322
D2LCS122
D2LCS322
24*
EPLBA124
EPLBA324
D2LBS124
D2LBS324
24
EPLCA124
EPLCA324
D2LCS124
D2LCS324
2. Using three-pole breakers first, designate circuit breakers for
your lighting panelboard application:
26
EPLCA126
EPLCA326
D2LCS126
D2LCS326
28
EPLCA128
EPLCA328
D2LCS128
D2LCS328
• Place an asterisk (*) before each quantity of circuit breakers
30
EPLCA130
EPLCA330
D2LCS130
D2LCS330
• First # is number of breakers needed (less than 10 insert 0
before quantity. e.g., 09)
32
EPLCA132
EPLCA332
D2LCS132
D2LCS332
34
EPLCA134
EPLCA334
D2LCS134
D2LCS334
36
EPLCA136
EPLCA336
D2LCS136
D2LCS336
38
EPLCA138
EPLCA338
D2LCS138
D2LCS338
40
EPLCA140
EPLCA340
D2LCS140
D2LCS340
• If multiple breaker options are required please insert in alpha
numeric order (e.g. D2LBS318EGHV)
• Second # is number of poles (start with three-pole breakers)
NOTE: Single-phase panelboards can have single- or two-pole
breakers. Three-phase panelboards can have single-, two- or
three-pole breakers.
• Third # is the ampere rating needed (start with highest
ampere rating)
• Insert ‘‘G’’ for GFI, ‘‘E’’ for EPD or ‘‘H’’ for HID type breakers,
if desired
3. For additional circuit breakers repeat step 2. If there are more
three-pole breakers with different amp ratings, continue with
three-pole designations. Otherwise continue with two-pole circuit
breakers, and then single-pole breakers.
4. To add a main breaker, insert a dash (-), the number of poles
(2 or 3), an ‘‘M’’ to indicate main breaker, then indicate the amp
rating. (See ‘‘electrical ratings’’ for trip ratings available.) Threephase panelboards can only have a three-pole main breaker. If no
main breaker is specified, the panelboard will have main lugs. No
suffix needed in catalog number for main lug only.
Lighting panelboards are available with three 100 amp
branch spaces maximum with balance up to 50 amps. For
future spaces, to provide for operating mechanism without
breaker write 00 (Example: One 3-pole mechanism
without breaker: 01300).
Unused breaker positions without designations will be
blank and plugged, complete panel will be prewired for
future breaker installations.
6
Breaker
Spaces
Needed
42*
EPLCA142
EPLCA342
D2LCS142
D2LCS342
(Empty°)
EPLBA100
EPLBA300
D2LBS100
D2LBS300
(Empty°)
EPLCA100
EPLCA300
D2LCS100
D2LCS300
‡ EPL Panels are provided as standard with a cast aluminum terminal housing,
to order less terminal housing change the ‘‘A’’ in base part number to ‘‘N’’
(i.e. EPLCA342 becomes EPLCN342). D2L Panels are provided as standard
with a sheet stainless-steel terminal housing, to order with a cast aluminum
terminal housing change the ‘‘S’’ in base part number to ‘‘A’’ (i.e. D2LCS342
becomes D2LCA342).
* Items not available with a main circuit breaker.
° Empty enclosures provided with a main lug only, accommodations for a main
breaker may be provided but must be specified (add suffix -2M00 or -3M00).
Empty enclosures are not available with GFI or EPD breakers. Panels to
accommodate GFI or EPD breakers must be ordered with at least one such
breaker installed.
Table A – Panel Capacity
Maximum Number of Breaker Spaces:
Max. No. of Breaker Spaces
Panel
Size
B
C#
Available
w/GFI, EPD
Branch Protection
Yes
Yes
Yes
Available
Main Breaker
Ampacity
Up to 100
Up to 100
110 to 225
w/Main Breaker
two-pole
three-pole
22
21
40
39
36
36
w/Main
Lug Only
24
42
# Size C panels with main breaker rated up to 100 amps uses a back-fed branch breaker. Size C panels with main breaker rated from 110 amps to 225 amps has a dedicated location for main breaker.
Size C ordered with suffix 2M00 or 3M00 are provided with 36 branch circuits for maximum breaker ampacity.
Table B – To Size Panels with GFI or EPD Branch Breakers
Maximum number of GFI or EPD breakers
Panel Size
SinglePole
TwoPole
with Main Lug
or Main Breaker
B
21
12
(10 with 3 pole MCB,
11 with 2P MCB)
C
21
14
Each factory-sealed panel is equipped with 42 load wires for GFI/
EPD breakers and any combination with standard branch breakers.
Determine the total number of load wires required to complete your
panel. You may not exceed 42 load wires.
Single-pole breaker
Single-pole GFI (or EPD) breaker
Two-pole breaker
Two-pole GFI (or EPD) breaker
Three-pole breaker
=
=
=
=
=
Load Wires Required
1
2
2
3
3
Maximum total: 42 load wires
Lighting Panelboard Catalog Number Example
Lighting panelboards can be furnished with
an assortment of breaker ratings and pole
configurations. Assortments may be ordered
by adding the number of poles and amp
rating designations to the catalog number.
Example would be ordered as:
Example:
A three phase, Class I, Division 2, Groups B, C, D lighting panelboard with:
(1) three-pole breaker with 100 amp rating.
(2) two-pole breakers–both with 30 amp GFI personnel protection.
(20) one-pole breakers–with 20 amp rating.
Three-pole main breaker–with 225 amp rating.
D2L CS 3 28 G * 01 3 100 *02230G *20120 –3M225 –GB
1. Select Division 2 Lighting
panelboard – D2L
a. CS – size C enclosure with stainless
steel terminal housing to handle
27 circuits with main circuit
breaker and GFI protection
b. 3 phase
c. (1) three-pole
= 3 breaker spaces
+ (2) two-pole (GFI) = 4 breaker spaces
+ (20) single-pole
= 20 breaker spaces
27 breaker spaces
If odd # round up to even #:
28 breaker spaces
d. GFI breakers included (Use ‘‘E’’ for EPD)
Verify load wires required w/panel size (Table B)
(1) three-pole
= 3 load wires (3 wires each)
(2) two-pole (GFI)
= 6 load wires (3 wires each)
(20) single-pole
= 20 load wires (1 wire each)
29 load wires
(42 load wires available)
2. Choose branch circuit breakers
(three-pole first)
(1) three-pole with ampere rating
a. Insert Asterisk *
b. Quantity is 1: 01
(if less than 10 insert 0 before quantity)
c. Three-pole: 3
d. Ampere Rating is 100: 100
5. Group B kit factory
installed –
4. Main Breaker –3M225
(3-pole, Main breaker, 225 Amp)
3. Additional breakers (three-pole first)
(2) two-pole w/30 ampere rating (GFI) . . . . . . . . . *02230G
(20) single-pole w/20 ampere
rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . *20120
(For operating mechanisms with no breaker supplied, add
‘‘00’’ for amperage)
For D2LBS/D2LCS Series with stainless-steel terminal
housing, removeable gland plates must be field drilled to
¡
separately:
Trade
Size
1⁄2˝
3⁄4˝
1˝
11⁄4˝
11⁄2˝
2˝
21⁄2˝
3˝
31⁄2˝
4˝
Zinc
ST 1
ST 2
ST 3
ST 4
ST 5
ST 6
ST 7
ST 8
ST 9
ST 10
Aluminum
STA 1
STA 2
STA 3
STA 4
STA 5
STA 6
STA 7
STA 8
STA 9
STA 10
Type 316
Stainless
SSTG 1
SSTG 2
SSTG 3
SSTG 4
SSTG 5
SSTG 6
SSTG 7
SSTG 8
SSTG 9
SSTG 10
7
PowerPlus™ Panelboards
DIMENSIONS:
6.50 (165.1)
4.66 (118.4)
2.81 (71.4)
6.50
(165.1)
1-1/2" NPT
12 PLACES
4.66
(118.4)
2.81
(71.4)
3 1/2" NPT
5.10
3.51
(129.5) (89.2)
TYP.
TYP.
.92 (23.4)
1/2" BOLT (M12)
1.31 (33.3)TYP.
1.83 (46.5)
.50 (12.7)
20.12
(511.0)
5.50 (139.7)
12.93 (328.4)
APPROXIMATE
CL
3/8"
BOLT (M9)
11.16 (283.5)
4.00 (101.6)
61.75
(1568.5)
11.52 (292.6)
APPROXIMATE
29.50 (749.3)
3 1/2" NPT
ALTERNATE FEED OPTION
(SUFFIX 'A') ONLY
48.63
(1235.2)
17.50 (444.5)
6.00 (152.4)
5.75 (146.0)
14.88 (377.8)
TYP.
14.88 (377.8) TYP.
Size C Panel
(with cast terminal housing)
Size B Panel
(with stainless-steel terminal housing)
For more information:
Contact an authorized Cooper Crouse-Hinds Distributor,
Sales Office or Customer Service Department:
Distributed by:
In the U.S.:
In Canada:
Cooper Crouse-Hinds
P.O. Box 4999
Syracuse, NY 13221
Toll Free: 866-764-5454
(315) 477-5531
FAX: (315) 477-5179
crouse.customerctr@crouse-hinds.com
Cooper Crouse-Hinds Canada
Toll Free: 800-265-0502
(905) 507-4187
FAX: (905) 568-7048
For office locations outside of North America
or for additional product information, visit our
website at: www.crouse-hinds.com
Mexico • Latin America/Caribbean • Germany • Australia • Asia • Dubai • India
Solutions.Worldwide.
TM
4886-1206
Crouse-Hinds is a registered trademark of Cooper Industries, Inc.
© 2006 Cooper Industries, Inc.
Printed in U.S.A
Download