23rdInternational Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0302 COMPARING THE LVRT CAPABILITY OF GRID CONNECTED WIND ENERGY CONVERSION SYSTEM WITH DIFFERENT FACT DEVICES Mona N. Eskander Maged N. F. Nashed Electronics Research Institute, Cairo, Egypt E-mail: eskander@eri.sci.eg ABSTRACT This paper compares the effectiveness of installing two types of FACTS devices, namely the Static Synchronous Compensator "STATCOM", and the Unified Power Quality Controller "UPQC" to enhance the low voltage ride through "LVRT" capability of a grid-connected wind energy conversion systems (WECS) employing a doubly fed induction generator (DFIG). These devices are applied to protect the system from ground faults, allow fast recovery, improve the system power factor, and prevent the system from rotor over-current and dc-link overvoltage. Comparing the responses of the stator and rotor currents, electric torque, rotor speed, active power, and reactive power of the two investigated systems during grid faults is presented. Results revealed the better performance of the WECS with UPQC. Faster recovery, smoother speed and electric torque variations, smoother current profiles, and electric generator protection are proven when employing the UPQC. The advantages of STATCOM are confined to lower cost and less complexity of control systems due to the usage of one converter only. These instructions give the author basic guidelines to prepare the final version of the paper to be included in the Conference USB. You are kindly asked to read and follow them carefully as the reproduction of your paper will be made directly from the document sent by the authors. I. INTRODUCTION Wind power generation has been growing rapidly around the world over the past decade and has become one of the most mature renewable generation technologies. This rapid growth has motivated the establishment of grid codes for the interconnection of wind power plants. The performance of the doubly fed induction generator (DFIG) during grid faults is attracting much interest due to the proliferation of wind turbines that employ this technology. International grid codes specify that the generator must exhibit a fault-ride-through (FRT) capability by remaining connected and contributing to network stability during a fault [1]. In wind energy systems employing double fed induction generators (DFIGs), the system is sensitive to grid disturbances. Therefore, proper protection schemes and FRT techniques are necessary in order to withstand grid faults. Active crowbars are commonly utilized to protect the rotor-side converters (RSCs) against voltage and current transients, which are caused by voltage dips in the stator side [2-3]. During faults, when crowbar is engaged, the CIRED2015 DFIG behaves like an induction machine since the rotor winding is short circuited by shunt resistors and the RSC is disabled. The main drawback of crowbar protection is that the DFIG consumes reactive power when it is activated and this aggravates the grid voltage dip during a fault. In [4], series dynamic resistors are utilized to restrain significant rotor currents so that the RSC and rotor circuits can be effectively protected by way of coordination control of the chopper resistor and the crowbar. However, if the wind farm is connected to a weak power network, the employment of such technique makes the DFIG unable to supply substantial amounts of reactive power, and thus increases the chance of system instability. Therefore, static synchronous compensators (STATCOMs) have been proposed to supply additional reactive power and compensate the DFIG consumption [5]. Nevertheless, a STATCOM is inadequate to prevent the system from either rotor over-current or dc-link overvoltage. To achieve full system protection, this scheme is usually combined with other protective elements, such as stator braking resistors and Crowbar, which increase system complexity [5-6]. To achieve full system protection a unified power quality controller UPQC is proposed to protect the system from ground faults, allows fast recovery, improve power factor, and prevent the system from rotor over-current and dc-link overvoltage. Comparing the responses of the stator and rotor voltages, stator and rotor currents, dc link voltage, electric torque, rotor speed, active power, and reactive power of the system employing the STATCOM and the system employing the UPQC during grid faults is presented PI controllers are tuned to allow maximum power tracking and control the FACTS devices. Results revealed the better performance of the WECS with UPQC. II. SYSTEM DESCRIPTION The DFIG system is presented in Fig. 1. The system consists of a wound rotor induction generator with slip rings and a back-to-back converter connected between the rotor slip rings and the grid. The stator is directly connected to the grid through a three-winding transformer. The rotor side converter (RSC) is utilized to control the electromagnetic torque and the excitation of the generator, while the generator side converter (GSC) controls the dc-link voltage. Since only the slip power is handled by the converter, the power rating of the converter can be only a fraction of the rated power of the wind turbine, typically in the range of 10% as proved in [7]. 1/5 23rdInternational Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0302 Figure 1, Schematic diagram of the DFIG-based wind energy generation system Where: ω is the synchronous angular speed of the fundamental system voltage. Neglecting the voltage harmonics produced by the inverter, and according to the PWM technique, the voltage at the inverter output terminals and the DC-side can be written as: v d1 = Kmv dc sin α (3) v q1 = Kmv dc cos α III. STATCOM MODELLING The STATCOM connection with the WECS employing the DFIG consists of a two level VSC, a DC energy source, a passive filter, and a coupling transformer connecting the VSC in shunt to the distribution network. In general, a coupling transformer is installed between the distribution system and the STATCOM for isolating the low voltage STATCOM from the high-voltage distribution system. The passive filter is installed at the point of common connection to reduce harmonics and allow better power quality. The VSC converts the DC voltage across the storage device (a 250 V battery) into a set of 3-phase AC output voltages. Suitable adjustment of the phase and magnitude of the STATCOM output voltages allows effective control of active and reactive power exchanges between the STATCOM and the AC system. The control scheme consists of phase locked loop to track the magnitude and phase angle of the supply voltage during normal operation to detect the occurrence of voltage sag. A 250 V battery is applied to DC input of VSC. The VSC switching strategy is based on a sinusoidal PWM technique, which offers simplicity and good response. The switching frequency is set at 2000 Hz. The controller input is an error signal obtained from the reference voltage and the value rms of the terminal voltage measured. Such error is processed by a PI controller whose output is provided to the PWM signal generator to drive the error to zero, i.e., the load rms voltage is brought back to the reference voltage. Fig. 2 shows the STATCOM connected to the PCC in three phase form, the differential equations for Fig. 2 in threephase form can be written as: di a = − Ri dt di b L = − Ri dt di c L = − Ri dt L a + ( v a − v a1 ) b + ( v b − v b1 ) c + ( v c − v c1 ) (1) where ia, ib, and ic are the AC line currents of the STATCOM; va, vb, and vc are the PCC voltages; va1, vb1, and vc1,and are the inverter terminal voltages; R and L represent the equivalent conduction losses and the inductance for the transformer and the filter. The threephase voltages and currents in a synchronously rotating d-q frame: di d = − Ri d + ω Li q + ( v d − v d 1 ) dt di q L = − Ri q − ω Li d + ( v q − v q 1 ) dt L CIRED2015 (2) Figure 2, STATCOM equivalent circuit The instantaneous active and reactive power at the PCC is given as: 3 (v d i d + v q i q ) 2 3 Q = (v d i q − v q i d ) 2 P= (4) While the instantaneous power at the dc side is: dv (5) P = v dc c dc dt From eqs. 4&5, the DC capacitor equation as function of STATCOM current is: dv dc 3 (6) = (v d i d + v q i q ) dt 2c Assuming d-axis coincides with always coincident with the instantaneous voltage vector Vq, and neglecting R, a simplified model for the STATCOM is: di L d = ωLi q + ( v d − Kmv dc sin α) dt (7) di q L = −ωLi d + Kmv dc cos α dt dv dc 3 (8) = vdid dt 2 The reactive power is given by 3 (9) Q = vdiq 2 Therefore, the DC-voltage vdc can be regulated by controlling iq, and id which is sufficient to control the reactive power and hence the PCC voltage can be regulated. IV. SYSTEM WITH UPQC The conventional UPFC, shown in Fig.(3), is the combination of two voltage source converters (VSC); one converter connected to the power system through a shunt transformer, while the second converter is inserted into the transmission line via a series transformer. The 2/5 23rdInternational Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0302 converters are connected by a common DC link. The main objective of the series converter is to produce an ac voltage of controllable magnitude and phase angle, and inject this voltage at fundamental frequency into the transmission line, exchanging real and reactive power at its ac terminals through the series connected transformer. The shunt converter provides the required real power at the dc terminals. The two converters and associated transformers are simulated with Matlab/Simulink. PI controllers are designed for each converter, and the proposed system is tested under 3 phase ground fault. Similarly, the real and reactive powers received at the receiving bus are: Po = −PR = −VR2 G + VS VR G cos(δS − δ R ) − VS VR Bsin(δS − δ R ) Qo = −QR = VR2 B − VS VR G sin(δS − δR ) − VS VR Bcos(δS − δ R ) For typical transmission line X>>R. Therefore, the conductance G is usually neglected and suseptance B is replaced by B=-1/X. Using these approximations, the expression for real power transmitted over the line form the sending to the receiving bus becomes: PS = − PR = − VS VR B sin(δS − δ R ) = − = VS VR B sin(δS − δ R ) X VS VR B sin δ = Po (δ) X The angle δ =δS −δR is called the power angle. The reactive power sent to the line from the sending bus and received from the line at the receiving bus are: Figure 3, UPQC Schematic. The objective of UPQC controlled by PI controllers is to enhance system stability by fast recovery from symmetrical ground faults and fast damping of low frequency oscillations. The UPQC is placed between two busses, as shown in Fig. (4), referred to as the sending bus and the receiving bus. The RMS voltages of the sending and receiving buses are: Figure 4, Equivalent Power System. Vs = VS ∠δ s (10) VR = VR ∠δ R (11) I*line is phasor current on the line, R and X are resistance and reactance of the line respectively δs and δr are the phase angles of sending and receiving ends respectively. The complex power injected into the sending bus: (12) SS = PS + jQ S = VS I *line Where PS and QS are the real and reactive powers injected into the sending bus, * denotes conjugate complex value. The line current can be written as: VS2 − VSVR cos(δS − δR ) X 2 − V + V R SVR cos(δS − δR ) − QR = −VR2 B − VSVR Bcos(δS − δR ) = = Qo (δ) X QS = −VS2B + VSVR Bsin(δS − δR ) = V. SIMULATION RESULTS AND DISCUSSION FOR 3-PHASE GROUND FAULTS The performance of the considered power system is modeled and its performance evaluated for both FACTS devices, i.e. with STATCOM, and with UPQC, using the Matlab software. A 3- phase voltage to ground fault is assumed 0.15 sec duration. The simulation results are given in Figs. 5 to Fig.9. Always Figure (a) show the system performance with STATCOM, while Figure (b) show the system performance with UPQC. From these figures, the active and reactive power profiles during and after fault recovery as shown in Figures 5a and 5b, shows that the stator power does not fall to zero during fault in the system employing the UPQC. This performance is due to the series-connected transformer coupling the series inverter of the UPQC, leading to protection of the generator. This is not the case for the system with the STATCOM. 4 3 x 10 2.5 2 I line = VS − VR = ( VS − VR )(G + jB) R − jX Where, G = R 2 R +X and 2 (13) B= X R + X2 2 Stator P&Q 1.5 1 0.5 0 -0.5 -1 Combining equations (10) to (13), the following expressions for the real and reactive powers injected into the sending bus are obtained: PS = VS2 G − VS VR G cos(δ S − δ R ) − VS VR B sin(δ S − δ R ) QS = −VS2 B − CIRED2015 VS VR G sin(δ S − δ R ) + VS VR B cos(δ S − δ R ) -1.5 -2 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 Time Figure 5a, Stator active and reactive power with STATCOM 3/5 23rdInternational Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0302 4 x 10 50 2 40 1.5 30 1 20 rotor current stator P&Q 2.5 0.5 0 10 0 -0.5 -10 -1 -20 -1.5 -30 -2 0 0.1 0.2 0.3 0.4 0.5 0.6 -40 0.7 0 0.1 0.2 0.3 time 0.4 0.5 0.6 0.7 time Figure 7b, Rotor current with UPQC. Figure 5b, Stator active and reactive power with UPQC 80 60 60 40 40 Torque stator current 20 20 0 -20 -20 -40 -60 0 -40 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 -60 time 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 time Figure 6a, Stator current with STATCOM. Figure 8a, Electric torque with STATCOM 50 60 40 30 50 20 0 Torque stator current 40 10 -10 30 20 -20 10 -30 -40 -50 0 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 -10 time 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 time Figure 6b, Stator current with UPQC. Figure 8b, Electric torque with UPQC. 60 200 180 40 160 140 rotor speed rotor current 20 0 -20 120 100 80 60 -40 40 20 -60 0 0.1 0.2 0.3 0.4 0.5 0.6 time Figure 7a, Rotor current with STATCOM. CIRED2015 0.7 0 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 time Figure 9a, Rotor speed with STATCOM. 4/5 23rdInternational Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0302 200 REFERENCES 180 160 rotor speed 140 120 100 80 60 40 20 0 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 time Figure 9b, Rotor speed with STATCOM. This effect is also obvious in Figures 6a and b where the fast recovery of the stator current to its rated value and its non-zero magnitude during fault is demonstrated. Figures 7 a and b reveals the smoother profile of the rotor current as well as the fast recovery for the system incorporating the UPQC. The electric torque, demonstrated in Figures 8a and b, for both systems shows a smoother profile for the system with the system incorporating the UPQC. The variation in the rotor speed during fault, shown in Figures 9a and b is comparable for both systems. However the recovery to its value before fault occurrence is faster with the UPQC. VI. CONCLUSION: In this paper investigation of the effectiveness of installing two types of FACTS devices, namely the Static Synchronous Compensator "STATCOM", and the Unified Power Quality Controller "UPQC" to enhance the low voltage ride through "LVRT" capability of a grid connected wind energy conversion systems (WECS) employing a doubly fed induction generator (DFIG) is presented. These devices are applied to protect the system from ground faults, allow fast recovery, improve the system power factor, and prevent the system from rotor over-current and dc-link overvoltage. Comparing the responses of the stator and rotor currents, dc link voltage, electric torque, rotor speed, active power, and reactive power of the two investigated systems during grid faults is presented. Results revealed the safer operation of the system using the UPQC, revealed from the non-zero stator current during fault and the slight increase in rotor speed. Faster recovery, and smoother profiles are proven when employing the UPQC. The advantages of STATCOM are confined to lower cost and less complexity of control systems due to the usage of one converter only. CIRED2015 [1] L.. Z. Xu, J. Ostergaard, Z. Y. Dong, and K. P. Wong, 2012 "Advanced Control Strategy of DFIG Wind Turbines for Power System Fault Ride Through" IEEE Transactions on Power Systems, Vol. 27, No. 2, May, pp: 713-723. [2] J. Liang, D. F. Howard, J. A. Restrepo, and R. G. Harley, 2013 "Feed forward Transient Compensation Control for DFIG Wind Turbines During Both Balanced and Unbalanced Grid Disturbances", IEEE Transactions on Industry Applications, Vol. 49, No. 3, May/June, 1452-1463. [3] J Vidal, G. Abad, J. Arza, and S. Aurtenechea, 2013 "Single-Phase DC Crowbar Topologies for Low Voltage Ride Through Fulfillment of High-Power Doubly Fed Induction Generator-Based Wind Turbines", IEEE Transactions on Energy Conversion, Vol. 28, No. 3, Sept., 768-781. [4] J. Yang, J. E. Fletcher, and J. O’Reilly, 2010, "A Series-Dynamic-Resistor-Based Converter Protection Scheme for Doubly-Fed Induction Generator During Various Fault Conditions" IEEE Transactions on Energy Conversion, Vol. 25, NO. 2, June, 422-432. [5] Y. Xu, and F. Li, 2014, "Adaptive PI Control of STATCOM for Voltage Regulation” IEEE Transactions on Power Delivery, Vol. 29, No. 3, June, 1002-1011. [6] M. M. Montazeri, D. Xu, 2012 "Coordination of DFIG and STATCOM in a Power System" IEEE International Symposium on Industrial Electronics (ISIE), May, 993-998. [7] V. Khadkikar, 2013," Fixed and variable power angle control methods for unified power quality conditioner: operation, control and impact assessment on shunt and series inverter kVA loadings", IET Power Electron., Vol. 6, Iss. 7, 1299–1307. [8] B. B. Ambati and V. Khadkikar," 2014, "Optimal Sizing of UPQC Considering VA Loading and Maximum Utilization of Power-Electronic Converters", IEEE Transactions on Power Delivery, Vol. 29, NO. 3, June, 1490-1498. [9] R. J. M. Santos, J. C. Cunha, and M. Mezaroba, 2014, "A Simplified Control Technique for a Dual Unified Power Quality Conditioner", IEEE Transactions on Industrial Electronics, Vol. 61, No. 11, Nov., 58515861. [10] M. A. H. Saleh, and M. N. Eskander, 2011, "Sizing of Converters Interfacing the Rotor of Wind Driven DFIG to the Power Grid" Smart Grid and Renewable Energy, Vol 2, 300-304. 5/5