Miltonvale Wellfield Development Phase 1C Wellfield Controls and Systems Charlottetown Water & Sewer Utility Section 00 01 01 July 28, 2016 Page 1 Addendum #2 ADDENDUM #2 All clauses set forth in the Bidding Documents, Contract Documents and General Requirements of the original Contract Documents shall apply to and govern this work. The addendum refers to changes and additions to the original Contract Documents and is to be read in conjunction with the same. All other parts of the original Contract Documents are to be considered as applying to the work of this Contract with the exceptions and changes as noted below. SPECIFICATIONS 1. Reference Section 00 41 13 - Bid Form .1 Reference Appendix 'E' - Cost Breakdown .1 Delete Appendix 'E' (Page 7 & 8) of the Bid Form and replace with revised Appendix 'E' (Page 7 & 8), issued with and forming part of this Addendum. 2. Reference Section 22 42 01 - Plumbing Specialties and Accessories .1 Reference Paragraph 2.5 - Back Flow Preventers .1 Reference Paragraph 2.5.1.1.1: Add Approved Equal Wilkins .2 Reference Paragraph 2.5.2.1: Add Approved Equal Wilkins .2 Reference Paragraph 2.7 - Pressure Regulators Add new Paragraph 2.7.5: .1 ".5 Approved Equal Wilkins" .3 Reference Paragraph 2.13 - Strainers Add new Paragraph 2.13.4: .1 ".4 Approved Equal SXL" 3. Reference Section 33 32 69 - Water Fluoridation Systems .1 Reference Paragraph 2.2 - Equipment and Materials .1 Reference Paragraph 2.2.2.1: 35 US Gallon solution tank will be acceptable. .2 Reference Paragraph 2.2.2.2: Float type level control shall be connected to Milltronics ultrasonic system and used as backup. 4. Reference Section 33 32 76 - Water Disinfection Systems .1 Reference Paragraph 1.4 - Scope of Work .1 Reference Paragraph 1.4.1.5: Delete as written and replace with revised Paragraph to read: ".5 Water Services: This shall include the supply and transportation of all labour, material, and connection of the existing water service inside the Building to the chlorine residual analyzer system, tube mixer, etc., all as specified or as shown or as directed by the Engineer." .2 Reference Paragraph 2.2 - Equipment and Materials Add new Paragraph 2.2.5.4: .1 ".4 Booster pump shall be sized for flow and pressure differential equivalent with 20 ft of piping including elbows, tees, ejector and check valve shown on Drawing M102 for fully functional system." Coles Associates Ltd. Miltonvale Wellfield Development Phase 1C Wellfield Controls and Systems Charlottetown Water & Sewer Utility Addendum #2 Section 00 01 01 July 28, 2016 Page 2 DRAWINGS 1. Reference Drawing C202 - Wellhead Details Control Building Schematic Layout Sections & Details .1 Reference Submersible Pump Data Table: Add the following information to the table: .1 2. Reference Drawing M101 - Control Building Mechanical Floor Plan and Details .1 Reference Plumbing Fixture Schedule: Add note: "Zurn, Stern Williams, AMI will be accepted as an approved .1 equal for all items." 3. Reference Drawing M102 - Control Building Floor Plan Fluoride and Chlorine Schematic Details .1 Reference Detail 2: Add manual isolation ball valves at vacuum regulators and automatic switch over module in the gas and vent lines. .2 Reference Detail 4: Add manual isolation ball valves at vacuum regulators and automatic switch over module in the gas and vent lines. 4. Reference Drawing E102 - Wellfield Site Plan Electrical Trench Details .1 Modify trench details C, E, F, H, and O as indicated in attached Sketches SK-02 and SK-03. 5. Reference Drawing E101 - Wellfield Site Plan Electrical .1 Reference Detail 1/E101/E101: .1 Padmounted service transformer and associated concrete transformer pad and bollards which are located at the north end of the wellfield is to be replaced by a 200A, 600V, three phase pole mounted transformer bank. Coordinate exact location of transformer bank utility pole with Maritime Electric and fit-up pole in accordance with Maritime Electric Construction Drawing Standard UG-08-01. Install a new CSA 4x rated 200A fused disconnect switch c/w neutral kit located on the back side of the field mounted distribution panel support structure and extend the underground service from the utility pole, up through the concrete pad to the new service rated disconnect switch in accordance with trench detail H. Wire 4#3/0 ,1#4 bond in 53mmC from new service rated disconnect through a new utility meter cabinet to the field distribution panel. Delete the main breaker and neutral kit from the field distribution panel so that the panelboard is main lugs only. Provide sufficient space on the field distribution panel support structure to mount the utility meter cabinet. The ground rods which are indicated in Note #1 are to be connected to the neutral kit of the new service rated disconnect switch, not the field distribution panelboard. Coles Associates Ltd. Miltonvale Wellfield Development Phase 1C Wellfield Controls and Systems Charlottetown Water & Sewer Utility Addendum #2 Section 00 01 01 July 28, 2016 Page 3 6. Reference Drawing E103 - Water Treatment Building and Well Chamber Electrical Floor Plans .1 Reference Detail 1/E103/E103: .1 In Control Room 004 route a new 103mmC from the bottom of panelboard 'A', into the ground alongside the existing underground 103mmC and stub the conduit just outside the exterior wall adjacent to the intersection of gridlines 2 & C. Open trench and core through the concrete foundation wall as required to install new conduit beside the existing Well #2 conduit run. New 103mmC is to be installed for the parallel run of 3c#500MCM teck cable to Well #2. Coordinate open trenching in Control Room 004 with the General Contractor so that all work is completed prior to pouring of the concrete floor. Coordinate open trenching in the Control Building parking area with the General Contractor so that all work is completed prior to paving. Once conduit and cabling are installed, reinstate 100mm Class "A" gravel surface with a 600mm compacted sandstone base to match site existing conditions. 7. Reference Drawing E105 - SCADA System Schematic .1 Reference UPS System Specification Section: .1 For clarification only, well chamber control panels do not require UPS, only UPS is needed at the main control building PLC cabinet. Add "Liebert" as an acceptable manufacturer. .2 .2 Reference Variable Frequency Drive Specification Section: Add "Vacon" as an acceptable manufacturer. .1 .3 Reference VFD Enclosure Specification Section: .1 For clarification only, the exact size of the VFD enclosure is to be coordinated with the VFD manufacturer to ensure proper clearances and ventilation is maintain for all the different sizes of VFD's. Final sizing of the enclosures shall be coordinated on site with the Contractor for mounting fasteners and supports. End of Section Coles Associates Ltd. Miltonvale Wellfield Development Phase 1C Wellfield Controls and Systems Charlottetown Water & Sewer Utility 1.7 Section 00 41 13 Bid Form (Issued via Addendum #2) Page 7 APPENDIX 'E' .1 COST BREAKDOWN We submit herewith our cost breakdown for the work to be performed on this Project and in accordance with the requirements of the appropriate specifications herein. Class of Labour, Materials Plant and/or Equipment: Total Cost ------------------------------------------------------------------------------------------------------------------General Requirements: (incl. insurance, permits, O/H, Profit, etc.) $___________________ Mobilization & Demobilization: $___________________ Site Work: $___________________ Asphalt Paving: $___________________ Concrete Work: $___________________ Landscaping: $___________________ Piping, Pumps and Valving: $___________________ Mechanical - Control Building: $___________________ Electrical Wiring & Equipment: $___________________ Communications: $___________________ Controls & System Programming: $___________________ Chlorination System: $___________________ Fluoridation System: $___________________ Commissioning: $___________________ Others (Specify): $___________________ Others (Specify): $___________________ Others (Specify): $___________________ Cash Allowance - SCADA Programming: $40,000 Cash Allowance - Maritime Electric: $20,000 Cash Allowance - Radio Communications Equipment: $10,000 Coles Associates Ltd. Miltonvale Wellfield Development Phase 1C Wellfield Controls and Systems Charlottetown Water & Sewer Utility Section 00 41 13 Bid Form (Issued via Addendum #2) Page 8 Cash Allowance - As-Built documents and O&M Manuals: $20,000 Cash Allowance - CW&SU unspecified additional work: $100,000 SUBTOTAL $___________________ TAXES $___________________ TOTAL $___________________ COMPANY: ____________________________________________________________ AUTHORIZED SIGNATURE: ______________________________________________ End of Section Coles Associates Ltd.