Addendum No. Addendum No. 4 Issued: Issued: 7/18

advertisement
Addendum No. 4
Issued: 7/ 18/12
/12
Addendum No. Four
for
Wahlquist Jr High School
Weber School District
MHTN Project No. 20115
2011553
1553.00
53.00
All Contractors submitting proposals on the above captioned project shall be governed by the
following addendum, changes and explanations to the bidding documents dated June 28, 2012
shall submit their bids in accordance therewith:
Changes to the Project Manual:
A4.01 TABLE OF CONTENTS DELETE 072713 MODIFIED POLYOLEFIN SHEET AIR
BARRIER
A4.02 ADVERTISEMENT FOR PROPOSAL Date for Proposal Receipt is revised to July 26,
2012.
A4.03 PROPOSAL FORM, showing revisions to Unit Price Schedule is revised and reissued as
an attachment to this Addendum
A4.04 SUPPLEMENTARY CONDITIONS Article 9.3.1.3 Revise Progress Payments to 95
percent with 5% retainage.
A4.05 SECTION 012100 – ALLOWANCES
Thousand dollars, $500,000.00
REVISE ALLOWANCE No. 1 to be Five Hundred
A4.06 SECTION 012200 – UNIT PRICES Article 3.1 revise to read as follows:
3.1
LIST OF UNIT PRICES
1.
Imported Engineered Structural Fill Per Cubic Yard
________
2.
Mass Excavation
Per Cubic Yard
_________
3.
Hand Excavation
Per Cubic Yard
_________
4.
Haul Excavated Material
Per Cubic Yard
_________
5.
Backfill
Per Cubic Yard
_________
$
$
$
$
$
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 - 2:38 PM
J:\K-12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 2 of 15
6.
Road Base
Per
_________
7.
3” Asphalt Paving
Per
8.
Pedestrian Walkway
Per
_________
9
8” Sanitary Sewer
Per
10.
24” Storm Drain Piping
_________
11.
15” Storm Drain Piping
_________
12.
10” Water Lines
_________
13.
Trenching/Backfilling (0’-0” to 5’-0”)
$ _________
14.
Trenching/Backfilling (5’-0” to 10’-0”)
$ _________
Cubic Yard
$
Square Foot
Square foot
$ _________
$
Lin. Ft.
Per Lin. Ft.
$ _________
$
Per Lin. Ft.
$
Per Lin. Ft
$
Per Cubic Yard
Per Cubic Yard
A4.07 SECTION 015000 – TEMPORARY FACILITIES AND CONTROLS, delete Paragraph
3.4.A in its entirety.
A4.08 SECTION 017419 – CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL delete
Paragraph 1.4.A in its entirety.
A4.09 SECTION 075419 – PVC MEMBRANE ROOFING, Paragraph 2.1.A Manufacturers,
revise to read as follows:
Manufacturers:
Carlisle 60 mil SureFlex KEE
GAF EverGuard elvaloy PVC
Johns Manville SP6RM
Sarnafil, Inc S-327 PVC
Versico Versiflex PVC KEE
A4.10 SECTION 077200 – ROOF ACCESSORIES , Paragraph 2.1.A, add the following:
“f.
Precision”
A4.11
SECTION 083113 – ACCESS DOORS, Paragraph 2.1.A, add the following: “7. Elmdoor.”
A4.12 SECTION 083323 – OVERHEAD COILING DOORS, Paragraph 2.1.A, add the following:
“7. Wayne Dalton
8. Cookson
9. Cornell “
A4.13 SECTION 084113 – ALUMINUM ENTRANCES AND STOREFRONT Paragraph 2.1.A, add
the following:
PART 1 “6.
EFCO
7.
Architectural Facades, Inc.”
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 3 of 15
A4.14 SECTION 088000 – GLASS AND GLAZING Revise as follows:
A.
B.
Paragraph 1.2.B add the following: “5. Metal Insulated spandrels”
Add Article 2.9 as follows::
“2.9 METAL INSULATED SPANDREL PANELS
A.
Laminated-Insulation-Core Metal Wall Panels: Formed with flush exterior
panel facing and integral, extruded edge members; designed for
independent installation by mechanically attaching panels to supports
through edge framing using concealed fasteners;
1. Available Products:
a. Alply, Inc.; Alply Architectural Metal Wall Panels.
b. Architectural Specialty Products, Inc.; Series MLW.
c. Citadel Architectural Products, Inc.
2.
Exterior Facing:
a. Material: Aluminum sheet, 0.032 inch (0.8
(0. 8 mm)
a. Surface: Smooth, flat.
flat
a. Finish: Fluoropolymer.
Fluoropolymer
1) Color:
noted.
2.
Matching
storefront members unless otherwise
Interior Facing:
a. Material: Aluminum sheet, 0.032 inch (0.8 mm)
b. Finish: Manufacturer's standard primer or white polyester.
3.
Core Material: ExpandedExpanded-polystyrene or polyisocvyasnurate
board insulation.
a. Backing Panel: 0.1250.125-inchinch- (3(3-mmmm-) thick hardboard behind
exterior facing for increased impact resistance.
4.
Edge Members: Extruded aluminum, not less than 0.063-inch- (1.6mm-) thick, nominal wall thickness.
5.
Gaskets: Extruded, dry seal silicone.
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 4 of 15
6.
Panel Thickness: 1.0 inch (25 mm)
A4.15 SECTION 096566 – RESILIENT ATHLETIC FLOORING Paragraph 2.1.A add the
following:
“2.
Tarkett DropDeck”
A4.16 SECTION 102226 – OPERABLE PANEL PARTITIONS, Article 2.2 Add Paragraphs H as
follows:
H.
Storage Pocket Doors: Full height at end of partition runs to conceal stacked
partition; of same materials, finish, construction, thickness, and acoustical qualities as
panels; complete with operating Hardware. Hinge finish to match other exposed
hardware.”
A4. 17 SECTION 105113 – METAL LOCKERS Article 2.4 ATHLETIC LOCKERS, Paragraph
2.4.A.1 delete solid backs , backs sides and intermediate partitions will be expanded
metal. End panels solid.
A4.18 SECTION 113100 – RESIDENTIAL APPLIANCES add 3.4.I as follows:
“I.
Free-standing Icemakers for Training rooms:
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 5 of 15
Manufacturer: Manitowoc
Model #:
#QD-0132A
80 LB Storage capacity, 135 lbs production at 70deg air 50 deg
water
Dimensions: 26”W x 26.5”D x 32.5”H
Utilities:
A)
3/8” cold water.
B)
1/2” indirect drain to floor sink.
C.)
208-230/60/1, 15 amp. .42hp Compressor
Accessories:
A)
Stainless steel finish.
B)
incoming water.
C)
Installation Notes:
B)
Provide filter for
Self contained, air-cooled.
A)
Water pressure to be 20-80 PSIG.
Set and level as per plan.
A4.19 SECTION 115213 - AUDIO VISUAL EQUIPMENT is revised and reissued as an
attachment to this Addendum.
A4.20 SECTION 116623 – GYMNASIUM EQUIPMENT, Paragraph 2.1.A.1 add the following:
“d.
Performance Sports Systems, Inc.”
A4.21 SECTION 116801 – EXTERIOR SPORTS EQUIPMENT Add Paragraph 2.6.E as follows:
“E. Dugout Benches: Aluminum bench, 10 inch plank on galvanized uprights
1.
Seat Planks, extruded aluminum alloy, 6063-T6 , Clear anodized 204R1, AAM10C22A31, Class II finish
a.
Channel End Caps: Aluminum alloy 6063-T6, clear anodized 204R1,
AA-M10C22A31, Class II.
2. Fixed Pedestals: Manufacturer's standard supports, spaced a maximum of 6’ o.c.
with predrilled fastener holes for attaching bench top and anchoring to slab or
footing, complete with fasteners and anchors, and as follows
a.
Tubular Steel: 1-1/4-inch- (32-mm-) diameter steel tubing, with 0.1265inch- (3.2-mm-) thick steel flanges welded at top and base; with bakedbaked-enamel
finish; anchored with exposed fasteners.”
A4.22 SECTION 12660 - TELESCOPING STANDS Paragraph 2.3.N, ACCESSORIES delete
Item 9. End Panels, and Item 12. Seat numbers at each seat
A4.23 SECTION 133416 – ANGLE FRAME BLEACHERS, Article 2.01 add the following”
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 6 of 15
“D.
DGJD Bleachers.”
A4.24
A4. 24 SECTION 329300 LANDSCAPE PLANTING is revised and reissued as an attachment
to this Addendum.
4.25
Section 230000230000-14.1.6.Q:
1.
4.26
See prior approvals, this addendum, for additional chiller manufacturers. Chiller
manufacturers
listed in addendum are approved by name only. Chiller
manufacturer, representative, and
contractor are responsible to insure that
equipment is similar in type, meets or exceeds performance, quality, and warranty
requirements specified and meets dimensions listed.
Section 230100230100-7.1.16: Add the following:
1.
J. Ductwork coordination drawings will be mandatory and shall be submitted for
approval prior to any fabrication.
4.27
Section 233000233000-10.2.39 – Rooftop Air Conditioning Units:
1.
Approved manufacturers for packaged rooftop units shall be York, Carrier, McQuay, and
Lennox. (No substitutions)
4.28
Section 233000233000-9.2.37 – Sawdust Collector:
2.37.A: Replace section with the following:
SAWDUST COLLECTOR:
Furnish and install complete the high efficiency, cartridge filter type sawdust collector shown and
specified on the drawings. Unit will have self-cleaning backward incline fan. Filter media shall
deliver a minimum of 99.9% separation efficiency down to 0.5 microns by weight.
Unit module shall be constructed of 7-gauge steel with door, hopper, inlet, and panels of 10-gauge
steel. Entire housing shall have baked on powder coated paint finish for weather/corrosion
resistance. Support legs for unit shall be designed for seismic zone 3.
Filter cartridges shall have open pleat design for high dust capture efficiency and better cleaning
ability. Media shall be flame retardant. Overbags shall be provided to act as a pre-filter for the filter
cartridge to protect the pleats from clogging.
Unit shall be furnished with pulse type compressed air automatic filter cleaning system complete
with solenoid valve in NEMA 4 enclosure.
Factory-mounted sawdust level indicators in each hopper shall be provided to detect sawdust
accumulation.
Unit shall be equipped with a dust collector controller. The controller shall control the automatic
pulsing of the filters based on differential pressure of the filters, so the cleaning cycle only pulses
when the filters are dirty. The mechanical contractor shall provide field wiring between the
controller, differential pressure sensors, sawdust level indicator, and the solenoid valve.
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 7 of 15
Domed rupture disks manufactured from 304 stainless steel suitable for class ST1 dust with Kst
value below 200bar*m/sec shall be provided and shall meet NFPA Explosion venting guidelines.
Unit shall be complete with factory-mounted starter, discharge silence, and manually operated fan
outlet damper.
Factory certified technician shall provide 4 hours of training for shop instructor and maintenance
personnel.
Sawdust collector shall be Farr, Torit or United Air Specialists, Inc.
4.29
Section 251000251000-18.3.11: Add the following:
1.
Q. Minimum heating water return temperature shall be 140 deg. F.
4.30
Section 251000251000-21.3.22.A: Add the following:
1.
ATC contractor shall control motorized damper in MUA supply duct. Damper shall be
normally
closed and damper shall open when unit is energized.
4.31
Section 251000251000-23.3.34.A: Add the following:
1.
Manual shower control shall be switch or 0-15 minute spring controller as required by Weber
School District.
4.32
Section 251000251000-25: Add the following:
1.
3.50 Training Room Ventilation
A. VAV box to cool spaces in occupied mode. Exhaust fan and dampers to ventilate
spac in un-occupied mode.
4.33
APPROVED MANUFACTURERS' PRODUCTS:
The following manufacturers, tradenames, and products are approved with the provision that they
shall completely satisfy all and every requirement of the Drawings, Specifications, and all Addenda,
and shall conform to the design, quality, and standards specified, established, and required for the
complete and satisfactory installation and performance of the building and all its respective parts.
PRODUCT
MANUFACTURER
Chiller
Boilers
Custom Rooftops
Cabinet Unit Heaters
McQuay, York
Bryan
Temtrol
Beacon Morris, Williams, Sterling
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 8 of 15
Unit Heaters
Fan Coils
Baseboard Radiation
Radiant Heating Panels
CW/HW Coils
Flow Venturis
Multi-Purpose Valves
Circuit Setters
Strainers
HW/CW Expansion Tanks
Check Valves
Air Separators
Flex Connectors
Temperature Gauges
Pressure Gauges
Boiler Stacks
VAV Re-Heat Boxes
Fire/Smoke Dampers
Fire Dampers
Paint Spray Booth
Sawdust Collector
Sound Traps
Make-Up Air Units
Flex Duct
Louvers
Custom Grille G-5
Filter Banks
Pressure Reducing Valves
RPBP
Domestic Check Valve
Gas Regulators
Water Heaters
Domestic HW Tank
Domestic Expansion Tank
Domestic Circ. Pumps
Faucets
Sinks
Mixing Valves
PRODUCT
Beacon Morris, Sterling
McQuay
Beacon Morris, Vulcan
Sterling
Temtrol
Flow Design, Preso
Taco
Flow Design, Nexus
Titan, Conbraco, Metraflex
Taco
Conbraco, Metraflex
Taco
Twin City Hose
Miljoco
Miljoco
Van Packer, Schebler
Tuttle & Bailey
Air Balance, Safe Air, Greenheck
Safe Air, Greenheck
AFC
Torit-Donaldson
Price, Aerosonics
Econ Aire
Quietflex
Greenheck
Reliable
Koch
Conbraco
Conbraco
Nibco
Governor
Raypack, Lockinvar
Raypack, Ace, Lockinvar
Flexcom, Elbi
Grundfos
American Standard, Elkay, T&S Brass, Chicago
Elkay
Bradley, Acorn, Symmons
MANUFACTURER
Emergency Fixtures
Service Sinks
Acid Neutralization Tank
Acid Sinks
Traps, Stops & Supplies
Water Hammer Arrestors
Cleanouts
ADA Insulation Kits
Showers
Drinking Fountains
Hose Bibbs
Floor Drains
Trench Drains
Floor Sinks
Hopper Drain
Roof Drains
Bradley, Econ, Speakman, Acorn
Speakman
Town & Country, Park USA
Orion
Watts, Zurn, Proflo
Zurn
Zurn
Proflo
Acorn
Acorn
JR Smith, Josam
JR Smith, Josam
JR Smith, Josam
JR Smith, Josam
Josam
Josam
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 9 of 15
Downspouts
Water Softener
Fixture Carriers
Solids Interceptor
Toilet Seats
Josam
Pacific
Josam
Josam
American Standard
4.34
Section 26 09 25 – Occupancy Sensed Lighting Control
1.
Change: Change section 2.4(A) to allow microphonics as an acceptable source.
2. Change: Change section 2.3(J) to be compatible with LED lighting.
4.35
Section 26 36 23 – Automatic Transfer Switch
3. Delete: Delete section 26 36 23-2.4 BYPASS ISOLATION SWITCH.
4.36
Section 28 10 00 – Security Intrusion Detection System
4. Change: Change section 1.3(A) to be model DSC PC 4020.
4.37
Section 27 51 23 – AMX School View System
5. Add: In section 3.15(F), add or Equivalent to the equipment.
4.38
Section 28 23 00 – Closed Circuit Television
6. Change: Change specification to the correct version. See attached section.
4.39
PRIOR APPROVAL TO BID
The following manufacturers are prior approved to bid the project. All manufacturers must bid an
equal to that specified, as determined by the Engineer. Products approved, but later proving not to be
equal, may be disqualified at a later date, and the contractor shall then supply the original specified
products. Products not listed did not meet the prior approval deadline, or are not considered equal to
those specified.
4.40
SECTION 26 09 13 – ELECTRIC POWER MONITORING
7. Add: Add Square D Power Link & Emon Dmon to section 2.1A – Acceptable Manufacturers
4.41
SECTION 26 22 00 – TRANSFORMERS
8. Add: Add Synergy Energy Inc. to section 2.1A – Acceptable Manufacturers
4.42
SECTION 26 24 13 – SWITCHBOARDS 600 VOLT & BELOW
9. Add: Add Siemens to section 2.1A – Acceptable Manufacturers
4.43
SECTION 26 24 16 – PANELBOARDS
10. Add: Add Siemens to section 2.1A – Acceptable Manufacturers
4.44
SECTION 26 43 00 – SURGE PROTECTIVE DEVICES
11. Add: SquareD to section 2.1A – Acceptable Manufacturers
12. Add: APT (Advanced Protection Technologies) to section 2.1A - Acceptable Manufacturers
4.45
SECTION 27 05 00 – VOICE AND DATA WIRING
13. Add: Hubbell/Hitachi to section 1.4A and 2.2A – Acceptable Manufacturers
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 10 of 15
Changes to the Drawings:
Drawings:
A4.46 Sheet AS501 Detail C3 Revise the detail note to read “Complete black vinyl fence at irrigation
filter/pump station enclosure including gates and hardware”. Add detail callout. See
AD03-A01
Detail C2 Revise note which reads: “4’-0” W x 6” thick concrete mowstrip. Crown for
drainage” to read: 2’-9”w x 4” thick concrete mowstrip. Crown for drainage.”
Detail B1 Add detail callout B1 see AD03-A02
A 4.47 SHEET LI102
Revise the irrigation system on the east side of the building as per AD03- L02
A 4.48 SHEET LI103
Delete irrigation valve C-9 Along with all associated pipes, heads, and sleeves
A4.49 SHEET LP100
Revise the landscape turf area on the east side of the building as per AD03-L03.
Clarification: The keynotes on this sheet do not refer to civil construction items. The notes tell
the landscape contractor what site elements his work abuts to.
A 4.50 Sheet S1.0
Has been revised to show primary wall and column footing locations only. The nonbearing
wall footings have been removed to help clarify where the rammed aggregate piers are
required to go deeper as outlined in the geotechnical report. Note 2-D has also been revised
from 10’ to 5’ to be consistent with the specification.
A 4.51 All Sheets
Added the following keynotes (issued in previous Addenda)
105 (Locker Benches – Refer to Specifications)
106 (Ice Maker – Stand Alone) Refer to Specifications
107 (4” Vent Space – Refer to A5.40)
108 (RTU Refer to Mechanical)
109 (Roof Walk-Pads Refer to Specifications)
110 (Roof Hatch & Ladder – Refer to Specifications)
111 (Roof Drain)
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 11 of 15
112 (Concrete Benches)
113 (Deck Mounted Acoustic Panels)
Bullnose all interior corners
A 4.52 Sheet A1.1B, A1.1F
Keynote 23 Trophy Cases – Refer to A5.15 for typical detail – All cases to be similar
(field verify)
4.53
All plumbing drawings:
1.
All installation of underground waste, vent, and steam water piping installation shall be
carefully
coordinated with structure pier system
All mechanical ductwork plans:
1.
and
VAV boxes shall not be located in a position that light fixture cannot be serviced or VAV box
piping cannot be serviced.
4.54
Sheet P8.1 & P8.3:
1.
Automatic gas valve for main cook hood shall be located in kitchen area in lieu of boiler
room. Valve shall be located above ceiling near cook hood. Coordinate exact location in field with
owner and engineer.
4.55
Sheet P8.4:
1.
Training Room J126 & J127 – Provide and pipe ice bin drain and ice machine drain indirect to
floor sink.
4.56
Sheet M2.1A:
1.
Scullery A116 – Diffuser D-5 CFM shall be 450.
4.57
Sheet M2.1D:
1.
IDF D105 – Provide combination fire/smoke damper at 2-hour wall for 12” x 6” transfer air
duct. Reference with note 16.
4.58
Sheet M2.1F:
1.
Kitchenette F106 – Provide combination fire/smoke damper at 2-hour wall for 24” x 10”
transfer air duct. Reference with note 29.
Option/Resource F131 – Provide combination fire/smoke damper at 2-hour wall for (2) 36” x
16” transfer air ducts and 48” x 18” oval supply air duct. Reference with note 29.
2.
4.59
Sheet M2.1H:
M2.1H:
1.
Provide an additional (2) G-5 grilles at northwest and southwest corners of Gym H101.
Reference detail 9/M5.7.
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 12 of 15
4.60
Sheet M5.1:
1.
Mechanical Equipment Schedule:
a.
RTU-9 design CFM shall be 2100.
4.61
Sheet M8.2:
1.
All blast gates at equipment connections shall be located at 6’-8” A.F.F.
4.62
Sheet E0.2 – Electrical Site Plan
14. Add: Add utility vaults along 2700 North, identified by Keyed Note 5 & 6. See sheet AD4-E1
15. Add: Add ropes in empty conduits identified by Keyed Note 12. See sheet AD4-E1.
4.63
Sheet E1.1B – First Floor Lighting Plan Area B
16. Add: Add 4-way switching in room Art Classroom B120 by door into Art Classroom B117. See
sheet AD4-E2
17. Add: Add egress lighting circuit in Reception B127 and Conference B124. See sheet AD4-E3.
4.64
Sheet E1.1D – First Floor Lighting Plan Area D
18. Add: Add egress lighting circuit in Hall D131 and Attendance Office D19. See sheet AD4-E4.
4.65
Sheet E1.1F – First Floor Lighting Plan Area F
19. Add: Add egress lighting circuit in Band F118, Choral F123 and Drama F128. See sheets AD4E5 & AD4-E6.
4.66
Sheet E1.1H – First Floor Lighting Plan Area H
20. Add: Add egress lighting circuit in Foods H122, Instruction H119, Sewing H118. See sheets AD4E7 & AD4-E8.
4.67
Sheet E1.2–
E1.2– Luminaire Schedule
21. Update: Update Luminaire Schedule. See sheets AD4-E9 & AD4-E10.
4.68
Sheet E2.1B – First Floor Power Plan Area B
22. Add: Add control switch for the Platform motorized screen. See sheet AD4-E11
23. Change: Changed the circuits for the network racks to panel SE. See sheet AD4-E12.
24. Add: Add dome sensor to Art Classroom B117. See sheet AD4-E13.
25. Add: Add dome sensor to Art Classroom B120. See sheet AD4-E14.
4.69
Sheet E2.1C – First Floor Power Plan Area C
26. Add: Add dome sensor to Classroom C111. See sheet AD4-E15.
4.70
E2.1D
Sheet E2
.1D – First Floor Power Plan Area D
27. Add: Provide (1) dedicated rack for the CCTV equipment in Server D134. Modify Keyed Note
13. See sheet AD4-E16.
28. Change: Change the circuits for the network racks in Server D134 to Panel SD1. See sheet
AD4-E16.
29. Change: Change the circuits for the network racks in IDF D105 to Panel SA1. See sheet AD4E17.
30. Change: Change the circuits for the network racks in MDF D114 to Panel SD1. See sheet AD4E18.
4.71
Sheet E2.1F – First Floor Power Plan Area F
31. Change: Change the circuits for the network racks in IDF F110 to Panel SF1. See sheet AD4E19.
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 13 of 15
32. Note: The receptacles in the Staff Workroom Lounge kitchenette are to be above counter.
The fridge receptacle is at +48”, the range receptacle is at standard height. Microwave
receptacles heights are to be coordinated with the architectural interior elevations.
33. Add: Add dome sensor to Resource F131 and Cirr Lab F133. See sheet AD4-E20.
34. Add: Add dome sensor and dedicated circuit for AV Rack in Band F118. See sheet AD4-E21.
35. Add: Add dome sensor and dedicated circuit for AV Rack in Choral F123. See sheet AD4-E22.
36. Add: Add dome sensor and dedicated circuit for AV Rack in Drama F18. See sheet AD4-E22.
37. Move: Move the AV rack that is in the Weight Room into the AV Closet H105A. Change the
rack number to “4”.
38. Note: Keyed Note 8 is to be located by circuit PF1-11 in the Staff Lounge F105 kitchenette.
4.72
Sheet
39. Add: Add
40. Add: Add
41. Add: Add
42. Add: Add
43. Add: Add
44. Add: Add
45. Add: Add
46. Add: Add
E2.1G – First Floor Power Plan Area G
dome sensor to TLC Business G113 and Classroom G111. See sheet AD4-E23.
dome sensor to Classroom G107 and Classroom G105. See sheet AD4-E24.
dome sensor to Science G101 and Science G125. See sheet AD4-E25.
dome sensor to Curriculum G114. See sheet AD4-E26.
dome sensor to Classroom G112. See sheet AD4-E27.
dome sensor to Classroom G108 and Science G106. See sheet AD4-E28.
dome sensor to Science G102. See sheet AD4-E29.
dome sensor to Science G124. See sheet AD4-E30.
4.73
Sheet E2.1H – First Floor Power Plan Area H
47. Move: Move the AV rack that is in the Weight Room into the AV Closet H105A. Change the
rack number to “4”.
48. Add: Add dedicated circuit for AV Rack in AV H105A. See sheet AD4-E31.
49. Add: Add dome sensor to Foods H122. See sheet AD4-E32.
50. Add: Add dome sensor to Instruction H119. See sheet AD4-E32.
51. Change: Change Keyed Note 10 on EF-25 to be Keyed Note 7. See sheet AD4-E32.
52. Add: Add dome sensor to Sewing H118. See sheet AD4-E33.
4.74
Sheet E2.1J – First Floor Power Plan Area J
53. Add: Add dome sensor to Metals Class J102. See sheet AD4-E34.
54. Add: Add dome sensor to Computer Lab J103. See sheet AD4-E34.
55. Add: Add dome sensor to Woods Class J111. See sheet AD4-E35.
56. Change: Change circuit PJ1-8 to PJ1-36,38 in Training J127.
57. Change: Change circuit PJ1-7 to PJ1-35,37 in Training J126.
4.75
4. 75
Sheet E2.4A – Overall Cable Tray Plan
58. Add: Add (2) conduits across the upper area of the main corridor. Install conduits as high as
possible, and along structural lines. See sheet AD4-E17.
59. Clarify: All data in the Media Center D135, Computer Cirr D133, Attendance D120 and adjacent
areas are to be routed to Server D134. Do not cross the main corridor to MDF D114.
4.76
Sheet E3.1B – First Floor System Plan Area B
60. Add: Add clocks to rooms Art Class B117, Art Class B120, Reception B127.
61. Add: Add (2) clocks to Cafetorium B104.
4.77
Sheet E3.1D – First Floor System Plan Area D
62. Add: Add Keyed Note 5 to Server D134. Keyed Note 5 to read “LOCATE (2) CCTV NVR’S
IN CCTV RACK LOCATED IN SERVER ROOM D134. REFER TO ENLARGED PLAN
4/E2.1D FOR INFORMATION.
4.78
Sheet
Sheet E3.1J – First Floor System Plan Area J
63. Delete: Delete Keyed Note 5 from IDF J114. Keyed Note 5 in the notes list will be “NOT USED”.
4.79
Sheet E4.1D – First Floor Fire Alarm Plan Area D
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 14 of 15
64. Add: Add (1) fire smoke damper with required control module and relay to IDF D105. Connect
relay to 120V circuit in Classroom Storage D101.
4.80
Sheet E4.1F – First Floor Fire Alarm Plan Area F
65. Add: Add (3) fire smoke dampers with required control modules and relays to
Option/Resource F131. Connect relays to 120V circuit in Curriculum Lab F33.
66. Add: Add (4) fire smoke dampers with required control modules and relays to the kitchenette
in Workroom Lounge F105. Connect relays to 120V circuit in Electrical G117.
4.81
Sheet E4.2 – Electrical Details
67. Change: Change the title block sheet name to “FIRE ALARM RISER DIAGRAM”.
4.82
Sheet E7.1 – Electrical Details
68. Change: Change the CCTV Riser Diagram. See sheet AD4-E36.
4.83
Sheet E7.3 – Electrical Details
69. Change: Change the title block sheet name to “TELECOM RISER AND RACEWAY DIAGRAM”.
70. Clarify: All fiber optic cable between closets is to be 62.5 micron multimode fiber.
4.84
Sheet E6.1 – OneOne-Line Diagram
71. Change: Change ATS-S to a 4-pole transfer switch.
4.85
Sheet E6.2 – Panel Board Schedules
72. Change: Panel PA2, change circuit 27 to be a 20A/1P spare. Change circuit 26 to be spare.
73. Change: Panel PD1 Section1, change circuit 32 to be a 20A/1P spare.
74. Change: The second PD1 Section1 panel should be Section 2. See sheet AD4-E37.
75. Change: Panel PD4, change circuit 31 to be a 20A/1P spare. Change circuit 30 to be spare.
Change circuit 41 to be an AV Rack.
76. Change: Panel PF1, change circuit 34 to be a 20A/1P spare.
4.86
Sheet E6.3 – Panel Board Schedules
77. Add: Add the AIC ratings to the following panelboards: PF4=10K AIC, PF5=10K AIC,
PF6=10K AIC, PF7=10K AIC, PF8=10K AIC, PF9=10K AIC, PF0=10K AIC, PJ1=10K AIC,
MA1=65K AIC, MA2=65K AIC, MA3=65K AIC
78. Add: Panel PF4, add AV Rack to circuits 26, 28, 30, 32.
79. Change: Panel PJ1, change circuit 7 to a spare. Change circuit 8 to a spare. Change circuit 3537 to be a 20A/2P breaker for an Ice Machine. Change circuit 36-38 to be a 20A/2P
breaker for an Ice Machine.
4.87
Sheet E6.4 – Panel Board Schedules
80. Add: Add the AIC ratings to the following panelboards: MD1=22K AIC, MD2=42K AIC,
MF1=22K AIC, MF2=22K AIC, LA1=42K AIC, LD1=10K AIC, LD2=22K AIC, LF1=10K AIC,
LF2=22K AIC, SA1=K AIC, SD1=K AIC, SD1=K AIC
81. Change: Change panels LA1, LD1, LD2, LF1, LF2 to 100A Bus
82. Change: Add circuits to Panel SA1. See sheet AD4-38.
83. Change: Add circuits to Panel SD1. See sheet AD4-39.
84. Change: Add circuits to Panel SF1. See sheet AD4-40.
4.88
Sheet E6.5 – Panel Board Schedules
85. Add: Add the AIC ratings to the following panelboards: EA1=10K AIC, ED1=10K AIC, EF1=10K
AIC, KA1=22K AIC, KA2=42K AIC
86. Add: Panel EA1, add lighting to circuit 4.
87. Add: Panel EF1, add lighting to circuits 14 and 16.
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . Fax 801.595.6717 . www.mhtn.com
07/18/12 & 2:38 PM
J:\K&12\2011553 WSD Wahlquist Jr High School\6 BID\1 Addenda\addendum_04WJRHS.doc
Addendum Continued
Page 15 of 15
4.89
CS102 Updated Site Plan Key Notes. Added key not 34 Concrete Sidewalk.
Added information referencing other drawings and details. Mow strip and
concrete edge keynotes have been revised.
4.90
CS103 Updated Site Plan Key Notes. Added Key note 34 Concrete Sidewalk.
We added information referencing other drawings and details. Added a note
to remove existing fence along the east boundary line. Revised length of chain
link fencing along the southern boundary.
4.91
CU101 Updated Utility Plan Key Note. We added key note 40 pertaining to the
3” Culinary water meter. We changed the culinary service lateral to tie into an
existing stub near where the fire line ties in on 2700 North Street. We also
added callouts to the mechanical plan sheets which detail sampling manholes in
two locations.
4.92
CU102 Relocated an 8” Gate Valve on the Fire line.
4.93
CD101 Updated Details 1, 3, 6, 7.
4.94
CD103 Added Details 6 - Concrete Waterway and 7 – Concrete Driveway
Approach
Attachments:
Addendum No. 4, Addendum RFI 4, Revised Proposal form, Specification Section 115213,
Specification Section 329300, AD04-A01, AD04-A02, AD04-L01-AD04-L03, S1.0, AD4-E1-AD4E40
End of Addendum No. 4