Bulletin 1492 Circuit Protection 12 The Allen-Bradley Line of Circuit Protection Devices Allen-Bradley offers 3 different lines of Circuit Breakers (Supplementary Protectors) and a line of branch circuit rated Fuse Holders. Allen-Bradley Thermal Magnetic Circuit Breakers are ideal for protecting control circuitry components from damage due to overcurrents and short circuits. Circuit Breakers are UL Component Recognized and CSA Certified as Supplementary Protectors. • UL File Number E65138, Guide Number QVNU2 • CSA File Number LR37712. Class 9091-01 (1492-CB) • CSA File Numbers LR67768, LR16185. Class 9091-01 (1492-GH) • VDE 0641 Certified as Miniature Circuit Breakers (1492-CB Only) • Compliant with IEC 934 — Circuit Breakers for Equipment • CE Marked Potential applications include: • Solenoids • Relay/contactor coils • Transformers • PLCs • Computers • Medical equipment • Power supplies • PLC I/O points Three types of rail-mounted circuit breakers are available: • Energy Limiting style CB • High-density style GH — single-pole • High-density style GS — multi-pole 1492 Circuit Breaker (Supplementary Protectors) Selection Table Type Approvals UL CSA Standards IEC CE Marked Poles Volts AC Volts DC Current Range Optional Auxiliary Contacts 2 Trip Characteristics 1492-CB 1492-GH 1077 1077 1492-GS 1077 22.2-235 22.2-235 22.2-235 898 934 934 Yes Yes Yes 1, 2, 3 1 1, 2, 3 277/480 250 277/480 65 65 65 0.5…50 A 0.2…15 A 0.2…25 A Yes No Yes 3…5 x In, 6…10 x In, 12…20 x In 6…12 x In 6…12 x In Energy Limiting Yes No No Manual Operation Yes Yes Yes Poles/foot 17 24 24 Mounting DIN Rail DIN Rail, A-B Rail DIN Rail, A-B Rail Yes Yes Yes IEC 529 and 947 Finger Protection 1492-FB Fuse Holders 1492-FB Class CC Fuse Holders provide a DIN Rail-mounted package for use in Class CC fuse applications such as transformers and motors. Features include: • IEC 529 finger protection — dead front construction • Compact size requiring less panel space than open-style fuse holders • Optional blown fuse indicator • Branch circuit protection • UL listed • DIN #3 Rail mounted 12-90 Bulletin 1492 Circuit Protection Fuse Holders 1492-FB Description Features Approvals Bulletin 1492 Class CC Fuse Holders provide a safe and convenient means for the installation of Class CC fuses. The 1492-FB Fuse Holders are available in 1-, 2-, and 3-pole configurations and have an optional neon blown fuse indication light. The fuse holder is 30 A, rated at 600V and is UL listed. The FB Fuse Holder utilizes a self-lifting box lug on the line and load side of the block, each capable of accepting a #6…#14 AWG copper wire. • IEC 529 finger protection — dead front construction. • The patented handle design isolates the fuse from line power when the handle is opened for insertion or removal. • Compact size requiring less panel space than open style fuse holders. • Optional blown fuse indicators — allow for easy troubleshooting of electrical circuits. • 30 A frame size — accepts 0…30 A Class CC fuses from major fuse manufacturers. • 600V AC/DC. • 200 kA withstand rating. • Available in 1-, 2-, and 3-pole versions. • Mounts on standard 35 mm DIN Rail (Allen-Bradley Cat. No. 199-DR1). • Easy installation and removal of fuses (no special tools required). • Accepts copper wire sizes #6…#14 AWG. • Rejection features — rejects midget fuses and international 10 x 38 mm fuses, which do not have interrupt ratings as high as Class CC fuses. • • • • Applications • • • • • Protection of equipment. Control transformers. Solenoids. Lighting and heating loads. Branch circuits in electrical distribution systems. • Excellent for small motor loads (up to approximately 10 Hp). • Excellent for group protection of small motors (for example a grouping of 1 Hp motors). • Consult fuse manufacturers to select the best fuse for the application. UL 512 listed CSA C22.2 certified IEC 947-7-1 IEC 529 finger protection — dead front construction • CE marked 12-91 Bulletin 1492 Circuit Protection Fuse Holders, Continued 1492-FB, Continued 2.13" (54 mm) 0.69" (17.5 mm) 1-pole fuse block. Approvals UL CSA 600V AC/DC 600V AC/DC 600V AC/DC 30 A 30 A 30 A #14…#6 AWG #14… #6 AWG #14…#6 AWG #14… #6 AWG Voltage Rating Wire Range (Rated Cross Section) Wire Strip Length 1492-FB3C30(-L) 3.07" (78 mm) 2.13" (54 mm) 1.38" (35 mm) Specifications Maximum Current 2-pole fuse block. 2.13" (54 mm) 2.07" (52.5 mm) 3-pole fuse block. UL CSA UL CSA 600V AC/DC 600V AC/DC 600V AC/DC 30 A 30 A 30 A #14…#6 AWG #14… #6 AWG 0.5" (12.7 mm) 0.5" (12.7 mm) 0.5" (12.7 mm) Recommended Tightening Torque 15 lb-in. (1.7 Nm) 15 lb-in. (1.7 Nm) 15 lb-in. (1.7 Nm) Working Voltage (Indicating Circuit) 95…600V AC, 110…600V DC 95…600V AC, 110…600V DC 95…600V AC, 110…600V DC Leakage Current (Indicating Circuit) 0.8 mA max. @ 600V 0.8 mA max. @ 600V 0.8 mA max. @ 600V Use Class CC fuse only ➊ Use Class CC fuse only ➊ Use Class CC fuse only ➊ –40…+221°F (–40…+105°C) –40…+221°F (–40…+105°C) –40…+221°F (–40…+105°C) Fuse Type Insulation Temperature Range Fuse Holder Without Blown Fuse Indicator With Neon Blown Fuse Indicator Accessories (page 12-172) Mounting Rails 1 m Symmetrical DIN (Steel) 2 1492-FB2C30(-L) 3.07" (78 mm) Note: Height dimension is measured from top of rail to top of terminal block. 3.07" (78 mm) 1492-FB1C30(-L) Dimensions are not intended to be used for manufacturing purposes. Cat. No. Pcs./Pkg. Cat. No. Pcs./Pkg. Cat. No. 1492-FB1C30 6 1492-FB2C30 3 1492-FB3C30 Pcs./Pkg. 2 1492-FB1C30-L 6 1492-FB2C30-L 3 1492-FB3C30-L 2 Cat. No. Pcs./Pkg. Cat. No. Pcs./Pkg. Cat. No. Pcs./Pkg. 199-DR1 10 199-DR1 10 199-DR1 10 1 m Symmetrical DIN (Aluminum) 1492-DR5 10 1492-DR5 10 1492-DR5 10 1 m Hi-Rise Sym. DIN (Aluminum) 1492-DR6 2 1492-DR6 2 1492-DR6 2 1 m Angled Hi-Rise Sym. DIN (Steel) 1492-DR7 2 1492-DR7 2 1492-DR7 2 1492-EA35 50 1492-EA35 50 1492-EA35 50 1492-EAH35 10 1492-EAH35 10 1492-EAH35 10 End Anchors: DIN Rail — Normal Duty DIN Rail — Heavy Duty ➊ All major fuse brands and current ranges have been evaluated for use with this fuse holder. Due to the heat they generate, only the following fuses must be derated. Gould ATQR 1-1/4, I = 0.42 A max. Gould ATQR 1-2/5, I = 0.47 A max. 12-92 Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors) 1492-CB Trip Curves 1492-CB Trip Curves are available in publication 1492-2.5. The Benefits of Limiting Let-Through-Energy Bulletin 1492 Energy Limiting circuit breakers are thermal magnetic type supplementary overcurrent protective devices. Bulletin 1492-CB circuit breakers are available in 1-, 2-, and 3-pole units rated from 0.5…50 A. AC units are rated 65V DC as standard. 2- and 3- pole devices are connected internally and at the handle for simultaneous operation. Wire termination is achieved by a clamping style, self-lifting box lug on all Bulletin 1492-CB units. Both line and load side termination points will accept #16…6 AWG (1.5…16 mm2) copper wires. • A positively trip-free mechanism (breaker operation cannot be defeated by holding the handle in the ON position) • 3 trip curves: F, G, and H • Time delay (H characteristic) for high inrush currents during inductive start-ups such as transformers and power supplies • Superior shock and vibration resistance capabilities — helps to prevent nuisance tripping • Mounts on DIN Rail or optional through door brackets • On standard AC/DC versions (F, G, H) line and load connections may be reversed Features Short Circuit Interruption Diagrams Short Circuit Interruption 10 kA — 120 Volts AC Instant of initiation: 15° after voltage zero VOLTAGE ACROSS BREAKER CONVENTIONAL BREAKERS ALLEN-BRADLEY 1492-CB MAX ARC VOLTAGE RECOVERY VOLTAGE CURRENT • Energy Limiting Design — protects downstream components better than conventional breakers during short circuits • Field-mountable options for selective applications • True IP2X Finger-Safe design (top and sides) • International approvals — CE Marked, meets UL, CSA, and IEC (VDE) standards for worldwide acceptance • Ratings to 480V AC and 10,000 A Interrupt Capacity (refer to page 12-98) • AC and DC voltage ratings — in one convenient device TIME A B C A BC A = Instant when the short is initiated B = Instant when the contacts open and the arc is initiated C = Instant when the arc extinguishes and the current ceases to flow Let through I 2 t Description 1492-CB vs. Conventional Breakers The 1492-CB line features the unique ability to achieve short circuit interruptions far more effectively than conventional breakers. In conventional circuit breakers, short circuit interruption time required is approximately one or two half cycles of an AC sine wave. When the contacts open, the resulting arc continues to burn until the current level passes through zero. The arc may re-ignite because of the insufficient width of the contact gap. The current that flows until the arc is extinguished produces a heating effect proportional to the I2t value (let-through-energy) of the fault current. The 1492-CB Energy Limiting circuit breaker is designed to substantially reduce the amount of let-through-current and the resulting let-through-energy that can damage protected components. The 1492-CB has the ability to interrupt short circuit current within the first half cycle of the fault. 79,000 A2 s 3,500 A2s 12-93 Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors), Continued 2 1492-CB, Continued Accessories The Benefits of Limiting Let-Through-Energy (Continued) Accessory Notes Limiting let-through-energy will protect against the harmful effects of overcurrent and is focused primarily on avoiding the following: • Excessive Heat • Mechanical Damage Both of these factors are proportional to the square of the current. Thermal energy is proportional to the square of the RMS value and magnetic forces are proportional to the square of the peak value. The most effective way to provide protection is to substantially limit let-through-energy. This provides the following advantages: • Far less damage at the location of the short circuit. • Fast electric separation of a faulty unit from the system, especially power supplies connected in parallel that are switched off when the voltage of the power bus drops below a certain level. • Far less wear on the circuit breaker itself. This means more safe interruptions. • Better protection of all components in the short circuit path. • Far wider range of selective action when used with an upstream protective device. (No nuisance shut downs from feeder line interruptions, causing a blackout in all connected branches.) Applications Bulletin 1492-CB Energy Limiting circuit breakers have a wide range of trip characteristics for a wide range of applications. • F trip characteristic (3…5 x In) ➊ for low fault tolerant loads, such as PLC outputs, solid state control equipment, and also for selective action with an upstream fault device • G trip characteristic (6…10 x In) ➊ for standard duty loads, such as relay coils, control circuitry, and test equipment • H trip characteristic (12…20 x In) ➊ for high inrush loads, such as power supplies, heaters, and transformer primaries A type F has a fault level inrush current interruption approximately half that of type G. The type H has a fault level interruption approximately twice that of type G. 12-94 Relay Trip (Shunt-Trip) Note: Maximum of two accessories per device. Auxiliary Contacts Refer to Specifications on page 12-97 for ratings. Each auxiliary contact module contains one (1) contact, either Normally Open or Normally Closed. Actuation of the contact is determined by the handle position of the adjacent poles. Signal Contacts Refer to the table below for ratings. The Relay trip module can be used to trip the adjacent current carrying poles from a remote location by applying a voltage (pick-up voltage) to the Relay trip terminals. Contacts operate between 8 and 16 milliseconds after the pick-up voltage has been applied. Type Pick-Up Voltage Range Impedance A1 5…15 V AC/DC 1.1 Ω A2 10…24V AC/DC 4.7 Ω A3 20…48V AC/DC 16 Ω A4 40…110V AC/DC 63 Ω A5 90…240V AC/DC 395 Ω Switched Neutral Module (not field-mountable) Refer to Specifications on page 12-97 for ratings. Each contact module contains one contact that will be linked internally with the adjacent poles, but not through the handle. Contacts are actuated by a fault condition on the protected poles, not by the manual operation of them. Note: The difference between an auxiliary contact and a signal contact is the protected poles adjacent to the signal contact may be manually shut off without affecting the status of the signal contact, whereas the auxiliary contact is activated either by manual (possibly to service a panel) or automatic operation (fault) of the protected poles. Manual operation of the protected poles does not alter the contact state of the signal contact (which may be connected to an alarm circuit for fault indication only). ➊ In = rated current. The time/current trip characteristic k1…k2 x In is defined such that inrush current k1 x In has a time delay that exceeds 10 ms, and k2 x In has a time delay that is less than 10 ms. Refer to Specifications on page 12-97 for ratings. This module is used to open the neutral line of the circuit as a result of the condition of the protected poles. It is used as a safety measure (required by some standards) for the protection of networks with a grounded neutral system. The switched neutral pole opens after and closes before the adjacent protected pole (i.e., early make, late break). Automatic actuation is a result of the adjacent pole trip mechanism and manual actuation is by the linked handles. Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors), Continued 1492-CB, Continued • Will the system require additional shaping options (e.g., auxiliary contacts, signal contacts)? After defining these few parameters, the selection can be done by following the chart below. All options are field-mountable except the neutral switch, which comes installed from the factory. How to Order 1492-CB The following information must be known to select the proper circuit breaker: • What is the full load amperage that will be available in the system? • Is it a 1-, 2-, or 3-phase system? • What are the start-up or inrush properties of the load? 1492 – CB 3 G 200 – N Selection Information You can order a basic 1-, 2-, or 3-pole circuit breaker from the following tables and add an accessory module to meet your specific application requirements. ➊➍ Bulletin Number Switched Neutral Module Energy Limiting Circuit Breaker CB N➌ 277V 65 A Screw Terminal Number of Poles Rated Voltage ➋ By Trip Characteristic F, G, H DF, DG, DH 1 1 pole 277V AC 65V DC 120V DC 2 2 poles 480V AC 65V DC 240V DC 3 3 poles 480V AC 65V DC 360V DC Trip Characteristic Code Magnetic Trip Range F 3…5 x In G 6…10 x In H 12…20 x In DF ➌➍ 4.2…7 x In DG ➌➍ 8.5…14 x In DH ➌➍ 17…28 x In In = Rated Current Trip Char. ➊ ➋ ➌ ➍ Current Rating Code (Standard Trip Characteristic is Type G) 150 ➌ 160 ➌ 200 ➌ 250 ➌ 300 ➌ 320 ➌ 400 ➌ 500 ➌ F 005 010 015 020 030 040 050 060 070 100 120 G 005 010 015 020 030 040 050 060 070 100 120 150 160 200 250 300 320 400 500 H 005 010 015 020 030 040 050 060 070 100 120 150 160 200 250 300 320 400 500 DF ➌➍ 005 010 015 020 030 040 050 060 070 100 120 150 160 200 250 300 320 400 — DG ➌➍ 005 010 015 020 030 040 050 060 070 100 120 150 160 200 250 300 320 400 — DH ➌➍ — — — — — — — 060 070 100 120 150 160 200 250 300 320 400 — Amp Rating 0.5 1 1.5 2 3 4 5 6 7 10 12 15 16 20 25 30 32 40 50 This alphanumeric character is for the optional neutral module. Rated volts are UL Recognized. Minimum order of 10 breakers required. Attention: Do not use these DC versions in AC networks. Polarity markings must be observed with the DC versions. 12-95 Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors), Continued 1492-CB, Continued Accessories Used with All 1492-CB Circuit Breakers Accessory (page 12-172) Mounting Rails 1 m Symmetrical DIN Cat. No. Pcs./Pkg. 199-DR1 10 1 m Hi-Rise Symmetrical DIN 1492-DR6 2 1 m Angled Hi-Rise Symmetrical DIN 1492-DR7 2 1492-EAH35 50 End Anchor 1492-GM35 10 1492-SMN83 5 Cat. No. Pcs./Pkg. 1492-ACBH1 1 1492-ACBH2 1 1492-ACBS1 1 1492-ACBS2 1 Relay Trip Module: 5…12V AC/DC 1492-ACBA1 1 10…24V AC/DC 1492-ACBA2 1 20…48V AC/DC 1492-ACBA3 1 40…110V AC/DC 1492-ACBA4 1 90…240V AC/DC 1492-ACBA5 1 Connecting Clip 1492-ACBCC1 8 Opening Seal ➌ 1492-ACBHS1 10 Commoning Links 1 m — 1-Pole (56 devices/m) 30 A 1492-ACBCL1 1 1 m — 2-Pole (29 devices/m) 30 A 1492-ACBCL2 1 1 m — 3-Pole (19 devices/m) 40 A 1492-ACBCL3 1 1492-ACBEC1 10 Group Marking Marking Systems Field Mounted Accessories Used with 1492-CB Circuit Breakers Accessory (page 12-172) Auxiliary Contacts: Normally Open ➊ Normally Closed ➋ Signal Contacts: Normally Open ➊ Normally Closed ➋ Bus Bar End Cap for 2- or 3-Pole Devices 2 Front Panel Mounting Brackets: 1-Pole 1492-N711 5 2-Pole 1492-N712 5 3-Pole 1492-N713 5 4-Pole 1492-N714 5 5-Pole 1492-N715 5 ➊ Normally Open — Contact assumes the same position as the protected poles. When breaker is off, contact is open. ➋ Normally Closed — Contact assumes the opposite position of the protected poles. When breaker is off, contact is closed. ➌ Used to close openings made on the side of breakers when installing and then removing auxiliaries. 12-96 Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors), Continued 1492-CB, Continued Specifications ➊ Cat. No. 1492-CB1 1492-CB2 1492-CB3 1-Pole 2-Pole 3-Pole Description Approvals ➋ , CSA, VDE , CSA, VDE , CSA, VDE 480V AC, 65 Volts DC Max. DC Version up to 120V per Pole. A 3-Pole Breaker will operate to 360V DC. Maximum Voltage Ratings Dielectric Strength 1960V AC Shock 25 G Half Sine Wave for 11 ms (Three Axes) 10…500 Hz for 1 Hour Amplitude: 10…57 Hz; 0.030 inches peak to peak 57…500 Hz; 5G peak Vibration Operating Temperature Range –4…+140°F (–20…+60°C) Shipment and Short Term Temperature Limits –40…+185°F (–40…+85°C) Housing Material Melamine — Phenolic #16…#6 AWG (1.5…16 mm2) Wire Size Recommended Wire Strip Length 0.51" (13 mm) Up to 6 A 7…16 A 20…32 A 40…50 A Electromechanical Life 50,000 Cycles 30,000 Cycles 20,000 Cycles 12,000 Cycles Auxiliary Contact Ratings 277V AC, 6 A 125V DC, 1 A 50V DC, 6 A Signal Contact Ratings 277V AC, 6 A 125V DC, 1 A 50V DC, 6 A Switched Neutral Rating 277V AC, 65 A ➊ Performance Data — See Page Important-2. ➋ Circuit breakers also meet the requirements of AS, BS and SEV. Impedance Table Amp Rating (A) 0.5 1 1.5 2 3 4 5 6 7 10 12 Impedance (Ω) G Characteristic 15 16 20 25 30 32 40 50 4.4 1.27 0.67 0.37 0.14 0.08 0.06 0.04 0.04 0.02 0.01 0.008 0.008 0.005 0.005 0.003 0.003 0.003 0.002 Impedance (Ω) H Characteristic 4.0 1.15 0.60 0.33 0.13 0.08 0.06 0.04 0.04 0.02 0.01 0.008 0.008 0.005 0.004 0.003 0.003 0.003 0.002 Approximate Dimensions Dimensions shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. Width 1.77 (45) No. of Poles 1.77 (45) CL of Rail Width (millimeters) 17.5 1 2 3 4 5 0.7 1.4 2.1 2.8 3.5 +0.05 –0 35 +1 –0 52.5 +1.5 –0 70 +2 –0 87.5 +2.5 –0 0.89 (22.6) 3.53 (89.7) 60˚ Width (inches) 1.76 (44.7) 2.44 (62) 2.72 (69) 12-97 Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors), Continued 1492-CB, Continued Approvals • UL 1077 • CSA 22.2 NO. 235 • VDE 0641 (IEC 60898) In North America, the Cat. No. 1492-CB circuit breaker is rated as a Supplementary Protector with a short-circuit current rating. Internationally, it is rated by IEC as a Miniature Circuit Breaker with an interrupt rating Electrical Characteristics Voltage Rating Short-Circuit Current Rating ➊ Interrupt Rating Icn (IEC only) Poles Tripping Characteristics 1 F, G, H 0.5…50 125 — 10 kA, U2 1 F, G, H 0.5…50 277 — 3 kA, U2 2, 3 F, G, H 0.5…50 240 — 5 kA, U2 2, 3 F, G, H 0.5…50 480 — 3 kA, U2 1, 2 F, G, H 0.5…50 — 65 2 kA, U1 DF, DG 0.5…40 — 120 10 kA, U1 DH 6…40 — 120 5 kA, U1 DF, DG 0.5…40 — 240 10 kA, U1 DH 6…40 — 240 5 kA, U1 DF, DG 0.5…40 — 360 10 kA, U1 6…40 — 360 5 kA, U1 Rated Current (A) AC DC UL 1077 Supplementary Protector Rating 1 2 wired in series 3 wired in series DH CSA 22.2 #235 Supplementary Protector Ratings 1 F, G, H 0.5…50 277 — 5 kA, U1 2 F, G, H 0.5…50 480 — 5 kA, U1 3 F, G, H 0.5…50 480 — 5 kA, U1 1 F, G, H 0.5…50 — 65 2 kA, U1 DF, DG 0.5…40 — 120 10 kA, U1 DH 6…40 — 120 5 kA, U1 DF, DG 0.5…40 — 240 10 kA, U1 DH 6…40 — 240 5 kA, U1 DF, DG 0.5…40 — 360 10 kA, U1 6…40 — 360 5 kA, U1 1 2 wired in series 3 wired in series DH 2 VDE 0641 (IEC 60898) Miniature Circuit Breaker Ratings 1 F, G 0.5…25 240/420 — 10 kA 1 F, G 30…40 240/420 — 6 kA 1 H 0.5…40 240/420 — 6 kA 2 F, G 0.5…25 420 — 10 kA 2 F, G 30…40 420 — 6 kA 2 H 0.5…40 420 — 6 kA 3 F, G 0.5…25 420 — 10 kA 3 F, G 30…40 420 — 6 kA 3 H 0.5…40 420 — 6 kA ➊ The short-circuit current rating is followed by a letter and number designating the test conditions and any calibrations and dielectric tests following the short-circuit test. These designations are defined as follows (see ➋ also): C — Indicates that the short-circuit test was conducted with series overcurrent protection U — Indicates that the short-circuit test was conducted without series overcurrent protection 1 — Indicates that a recalibration and dielectric test was not conducted as part of the short-circuit test 2 — Indicates that a recalibration and dielectric test was conducted as part of the short-circuit test ➋ These alphanumeric designations were established by UL. CSA has not yet adopted them; however, the test conditions are equivalent to UL and the coding is appropriate. 12-98 Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors), Continued 1492-GH High Density Circuit Breakers 1492-GH… Description 2.89" (73.4 mm) Bulletin 1492 High Density circuit breakers are thermal magnetic type supplementary overcurrent protective devices. Bulletin 1492-GH circuit breakers are available in one pole units. The 1492-GH is rated at 250V AC, and has a 65V DC rating as standard. Wire termination is achieved by a clamping style, self-lifting box lug. 3.15" (80.0 mm) 0.49" (12.4 mm) High-density 1-pole circuit breaker, thermal magnetic, mounts on A-B rail and DIN Rails. Specifications Approvals /CSA/VDE Maximum Voltage Rating 250V AC, 65V DC Maximum Interrupting Capacity (that allows continued use) 200 A (not to exceed 100 times rated current) #22…#10 AWG (0.5…6 mm2) Wire Range (Rated Cross Section) Wire Strip Length 0.44" (11.2 mm) Recommended Screw Tightening Torque 10…12 lb-in. (1.13…1.4 Nm) Insulation Temperature Range –40…+221°F (–40…+105°C) Cat. No. Pcs./ Pkg. 0.2 A 1492-GH002 1 0.5 A 1492-GH005 1 0.8 A 1492-GH008 1 1.0 A 1492-GH010 1 1.2 A 1492-GH012 1 1.5 A 1492-GH015 1 2.0 A 1492-GH020 1 2.5 A 1492-GH025 1 3.0 A 1492-GH030 1 4.0 A 1492-GH040 1 5.0 A 1492-GH050 1 7.0 A 1492-GH070 1 10.0 A 1492-GH100 1 15.0 A 1492-GH150 1 Cat. No. Pcs./ Pkg. Terminal Blocks Amperage Rating: Accessories (page 12-172) Mounting Rails: 1 m Symmetrical DIN 199-DR1 10 1 m Hi-Rise Symmetrical DIN 1492-DR6 2 1 m Angled Hi-Rise Sym. DIN 1492-DR7 2 3' Scored Channel 1492-N1 20 3' Rigid Channel 1492-N22 20 3' Hi-Rise Channel 1492-N44 2 1492-N25 ➊ 2 1492-N23 10 1492-N47 50 Standoff Brackets End Anchors: A-B Rail — Heavy Duty A-B Rail — Snap On DIN Rails — Normal Duty 1492-EA35 50 DIN Rails — Heavy Duty 1492-EAH35 50 Marking Systems Group Marker (DIN Rail only) 1492-SMN83 5 1492-GM35 10 Features • High density design allows 24 one-pole breakers per foot • Wide range of currents for precise circuit requirements • International approvals — meets UL, CSA, and IEC standards for worldwide acceptance • CE Marked • Ratings to 250V AC • AC and DC voltage ratings — in one convenient device • A positively trip free mechanism (breaker operation cannot be defeated by holding the handle in the ON position) • Superior shock and vibration resistance capabilities — helps prevent nuisance tripping • Universal mounting foot for a variety of mounting channels One Pole Style 1492-GH Single-pole, high-density circuit breaker that incorporates a thermal portion and a magnetic trip function for the combined advantages of two sensing systems. The 1492-GH style of breakers uses a pushto-set mechanism for circuit actuation and comes with a manual trip button for manually opening the circuit. Applications Included but not limited to the protection of test equipment, control instrumentation, solenoids and power supplies. The wide range of current values and the use of a thermal magnetic trip system allows for a variety of applications where a very accurate and compact breaker is required. ➊ Use every 12" with 1492-N22 rail. 12-99 Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors), Continued 1492-GH, Continued UL, CSA, and IEC Rated Selection Guide — To select a circuit breaker use the following procedure: • Determine the inrush correction factor from Table 1. • Determine the temperature correction factor from Table 2. • Determine the sealed current of the load being protected. • Multiply the sealed current by the two correction factors and select the closest higher ampere rating. Example — What size circuit breaker should be selected for a solenoid with sealed current of 0.5 A, an inrush ratio of 1:8, and an ambient temperature of +110°F (43.7°C)? 0.5 x 1.7 x 1.15 = 0.9775 Select the 1.0 A circuit breaker. Table 1. Inrush Ratio Correction Table Inrush Ratio 1:1 to 1:4 1:5 1:6 1:7 1:8 1.3 1.4 1.5 1.6 1.7 Factor Note: For resistive loads, use inrush correction factor of 1.0. Table 2. Ambient Temperature Correction Table Ambient Temperature 70°F (21.1°C) 100°F (37.8°C) 120°F (48.9°C) 140°F (60°C) 160°F (71.1°C) 180°F (82.2°C) 200°F (93.3°C) 1.0 1.1 1.2 1.3 1.4 1.5 1.6 Factor Tripping time of the circuit breaker is determined from Table 3 below. Divide the circuit breaker value by the temperature correction factor from Table 2 above to determine the actual rated current referenced in Table 3. Table 3. Tripping Time Tripping Times in Seconds at 70°F (21.1°C) Percent Rated Current 100% 200% 300% 400% 500% 600% 1000% 2000% Greater No Trip 10…40 3…18 1.5…9 0.8…6 0.003…4 0.003…2 Maximum 0.02 Tripping Times (Seconds) Note: When several breakers are rail mounted adjacent to each other, the no-trip current will be 80% of rated current at 70°F (21.1°C). Trip Current 10000 8000 6000 4000 3000 2000 Trip current is 140% of rated current. Protector will hold 100% of rated current indefinitely. Will trip within one hour at 140% of rated current. 1000 800 600 400 300 200 100 80 60 40 30 20 0.05 to 7.5 amp 10 8 6 4 3 2 1 .800 .600 .400 .300 .200 8 to 15 amp .100 .080 .060 .040 .030 .020 .010 .008 .006 .004 .003 .002 PERCENT RATED CURRENT 12-100 80 70 60 50 100 150 200 300 800 700 600 500 400 1000 1500 2000 3000 4000 6000 5000 8000 10000 .001 SECONDS TRIPPING TIME AT 70 F 2 ° Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors), Continued 1492-GH, Continued Specifications ➊ Cat. No. 1492-GH Series B Description 1-pole with universal mounting foot for Allen-Bradley and DIN Rail mounting 250V AC 50/60 Hz 65V DC Maximum Voltage Ratings Standard Current Ratings Internal Resistance per Pole A Ω 0.2 44 0.5 6.6 0.8 2.55 1.0 1.97 1.2 1.22 1.5 0.86 2.0 0.49 Dielectric Strength 2.5 3.0 4.0 5.0 7.0 10.0 15.0 0.313 0.205 0.104 0.082 0.034 <0.20 <0.20 1500V AC Shock: 25 G, 11 ms duration Vibration: 5 G (10…500 Hz) Shock and Vibration Specifications Insulation Resistance 100 MΩ @ 500V DC 6000 cycles @ rated current (UL 1077) 4000 cycles @ 200% rated current Operating Life Temperature Range –40…+149°F (–40…+65°C) Housing Material Glass-filled Polyamide 6.6 #22…#10 AWG (0.5…6 mm2) Wire Size Recommended Wire Strip Length 0.44" (11.2 mm) Terminals Tubular screw with self-lifting box lug Recommended Tightening Torque 10…12 lb-in. (1.13…1.4 Nm) ➊ Performance Data — See Page Important-2. Approvals • UL 1077 • CSA 22.2 NO. 235 • VDE 0631 (IEC 60934) In North America, the Cat. No. 1492-GH circuit breaker is rated as a Supplementary Protector with a short-circuit current rating. Internationally, it is rated by IEC as a Circuit Breaker for Equipment with an interrupt rating. Electrical Characteristics Voltage Rating Short-Circuit Current Rating ➊ Interrupt Rating Icn (IEC only) Poles Rated Current (A) 1 0.2…15 250 — 1 kA, U1 1 0.2…15 — 80 1 kA, U1 1 9…14 250 — 2 kA, C1 AC DC UL 1077/CSA 22.2 #235 Supplementary Protector Rating VDE 0631 (IEC 60934) Circuit Breaker for Equipment Ratings 1 0.2…15 250 65 0.2 kA, but not to exceed 100 x In ➊ The short-circuit current rating is followed by a letter and number designating the test conditions and any calibrations and dielectric tests following the short-circuit test. These designations are defined as follows (see ➋ also): C — Indicates that the short-circuit test was conducted with series overcurrent protection U — Indicates that the short-circuit test was conducted without series overcurrent protection 1 — Indicates that a recalibration and dielectric test was not conducted as part of the short-circuit test 2 — Indicates that a recalibration and dielectric test was conducted as part of the short-circuit test ➋ These alphanumeric designations were established by UL. CSA has not yet adopted them; however, the test conditions are equivalent to UL and the coding is appropriate. 12-101 Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors), Continued 1492-GS High-Density Circuit Breakers Description Features Bulletin 1492 High Density circuit breakers are thermal magnetic type supplementary overcurrent protective devices. Bulletin 1492-GS circuit breakers are available in 1-, 2-, and 3-pole devices, and all are available with an internally mounted auxiliary contact. The 1492-GS is rated 0.2…25 A at 277V/480V AC. The 1492-GS also has a DC voltage rating of 65V DC. • High Density Design — allows 24 1-pole breakers per foot. • Optional Auxiliary Contacts are built-in, no additional modules to attach. Auxiliary Contacts do not increase size of the device. • Universal mounting foot for DIN Rails and A-B Rails. • International approvals — meets UL, CSA, and IEC standards for worldwide acceptance • Toggle style handle for ease of operation. • Ratings to 480V/277V AC for 2- and 3-pole devices, and 277V AC for single-pole devices. • A positively trip-free mechanism (breaker operation cannot be defeated by holding the handle in the ON position) Approvals • • • • UL 1077 CSA 22.2 NO. 235 IEC 934 CE Marked VAC, 73F/23C 10 000 2 x In 1 1.05 1.4 6.0 12.0 1000 5 lb-in (0.6 Nm) 3.15 in (80 mm) 0 1 .49 in (12.5 mm) .98 in (25 mm) 100 Si 2 3.28 in (83.5 mm) .51 in (13 mm) #18-10 AWG (0.75-6 mm2) 8-25A 0.1-7.5A 10 t (S) #18-16 AWG (0.75-1.5 mm2) .41 in (10.5 mm) 3.48 in (88.5 mm) Aux. Si Main 1 t ∞ > 1 hr < 1 hr > 0.1s < 0.1s 1 0,1 0,01 1.47 in (37.5 mm) 0,001 12-102 1 2 3 4 6 810 20 30 50 70 100 x ln (rated current) Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors), Continued 1492-GS, Continued • Will the system require additional shaping options: auxiliary contacts, signal contacts, etc.? After defining these few parameters, the selection can be done by following the chart below. How to Order The following information must be known to select the proper circuit breaker: • What is the full load amperage that will be available in the system? • Is it a 1-, 2-, or 3-phase system? • What are the startup or inrush properties of the load? 1492 – GS 2 G Selection Information You can order a basic 1-, 2-, or 3-pole circuit breaker from the following tables and add an auxiliary contact to meet your specific application requirements. 008 – H1 Bulletin Number Optional Auxiliary Contacts Circuit Breaker GS Screw Terminal Number of Poles H1 Normally Open ➊ H2 Normally Closed ➋ Note: 1 contact max. for 1-pole circuit breaker. 2 contacts max. for 2- and 3-pole circuit breakers. Rated Voltage By Trip Characteristic G 1 One Pole 277V AC 65V DC 2 Two Pole 277/480V AC 65V DC 3 Three Pole 277/480V AC 65V DC Trip Characteristic Code Magnetic Trip Range G 6…10 x In In = Rated Current Current Rating Code (Standard Trip Characteristic is Type G) Code 002 005 008 010 015 020 025 030 040 050 060 070 080 100 120 150 160 200 250 Amp Rating 0.2 0.5 0.8 1 1.5 2 2.5 3 4 5 6 7 8 10 12 15 16 20 25 Accessories Used with All 1492-GS Circuit Breakers Accessory (page 12-172) Mounting Rails: 1 m Symmetrical DIN Cat. No. Pcs./Pkg. 199-DR1 10 1 m Hi-Rise Symmetrical DIN 1492-DR6 2 1 m Angled Hi-Rise Symmetrical DIN 1492-DR7 2 3' Scored A-B Rail 1492-N1 10 3' Rigid A-B Rail 1492-N22 2 3' High Rise A-B Rail 1492-N44 2 End Anchor: DIN Rail A-B Rail (Heavy Duty) Group Marking (DIN Rail) Marking Systems 1492-EAH35 50 1492-N23 10 1492-GM35 10 1492-SMN83 5 ➊ Normally Open — Contact assumes the same position as the protected poles. When breaker is off, contact is open. ➋ Normally Closed — Contact assumes the opposite position of the protected poles. When breaker is off, contact is closed. 12-103 Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors), Continued 1492-GS, Continued Specifications ➊ Cat. No. 1492-GS Description High-density circuit breaker (supplementary protector) with universal mounting foot for Allen-Bradley and DIN rail mounting 277/480V AC 50/60 Hz 65V DC Maximum Voltage Ratings Standard Current Ratings Internal Resistance per Pole A Ω 0.2 0.5 0.8 26 4.2 1.6 Dielectric Strength Shock and Vibration Specifications Insulation Resistance Current Capacity of Auxiliary Contacts (N.O., N.C.) Voltage Rating of Auxiliary Contacts Operating Life Temperature Range Wire Size Recommended Wire Strip Length Recommended Tightening Torque ➊ Performance Data — See page Important-2. 2 12-104 1.0 1.1 1.5 0.47 2.0 0.25 2.5 0.20 3.0 0.13 4.0 0.08 5.0 0.06 6.0 0.05 8.0 10.0 12.0 15.0 16.0 20.0 25.0 0.01 0.01 0.01 0.01 0.01 0.005 0.004 1960V AC Shock: 25 G, 11 ms duration Vibration: 5 G (10…500 Hz) Greater than 100 MΩ @ 500V DC 1.0 A AC or DC (resistive load) 277V AC 65V DC 6000 cycles @ rated current (UL 1077) –40…+149°F (–40…+65°C) #22…#10 AWG (0.5…6 mm 2) 0.51" (13.0 mm) for Mail Terminals 0.41" (10.4 mm) for Auxiliary Terminals 5 lb-in. (0.565 Nm) Bulletin 1492 Circuit Protection Circuit Breakers (Supplementary Protectors), Continued 1492-GS, Continued Approvals • UL 1077 • CSA 22.2 NO. 235 • VDE 0631 (IEC 60934) In North America, the Cat. No. 1492-GS circuit breaker is rated as a Supplementary Protector with a short-circuit current rating. Internationally, it is rated by IEC as a Circuit Breaker for Equipment with an interrupt rating Electrical Characteristics Voltage Rating Short-Circuit Current Rating ➊ Interrupt Rating Icn (IEC only) Poles Rated Current (A) 1 0.2…5 277 — 0.4 kA, U2 1 6…25 277 — 0.7 kA, U2 2, 3 0.2…5 277/480 — 0.4 kA, U2 2, 3 6…25 277/480 — 0.5 kA, U2 1, 2, 3 0.2…5 — 65 0.4 kA, U2 0.8 kA, U2 AC DC UL 1077 Supplementary Protector Rating 1, 2, 3 6…25 — 65 1 0.2…16 277 — 5 kA, C1 1 18…25 277 — 2 kA, C1 2, 3 0.2…16 277/480 — 5 kA, C1 2, 3 18…25 277/480 — 2 kA, C1 1 0.2…25 — 65 2 kA, C1 CSA 22.2 #235 Supplementary Protector Ratings 1 0.2…16 277 — 5 kA, C1 1 18…25 277 — 2 kA, C1 2, 3 0.2…16 277/480 — 5 kA, C1 2, 3 18…25 277/480 — 2 kA, C1 1 0.2…25 — 65 2 kA, C1 IEC 60934 Circuit Breaker for Equipment Ratings 1 0.2…5 250 — 0.4 kA 1 6…25 250 — 0.8 kA 2, 3 0.2…5 240/415 — 0.4 kA 2, 3 6…25 240/415 — 0.8 kA 1 0.2…5 — 65 0.4 kA 1 6…25 — 65 0.8 kA ➊ The short-circuit current rating is followed by a letter and number designating the test conditions and any calibrations and dielectric tests following the short-circuit test. These designations are defined as follows (see ➋ also): C — Indicates that the short-circuit test was conducted with series overcurrent protection U — Indicates that the short-circuit test was conducted without series overcurrent protection 1 — Indicates that a recalibration and dielectric test was not conducted as part of the short-circuit test 2 — Indicates that a recalibration and dielectric test was conducted as part of the short-circuit test ➋ These alphanumeric designations were established by UL. CSA has not yet adopted them; however, the test conditions are equivalent to UL and the coding is appropriate. 12-105