FAZ Series Thermal-magnetic Overcurrent Supplemental Protection

UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
Product Overview
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
PRODUCT OVERVIEW
Optimum and efficient protection
Features
•
Complete range of UL 1077 recognized DIN rail mounted
miniature circuit breakers up to 63A current rating
•
Standard ratings of 10 kAIC up to 277/480 Vac
•
Current limiting design provides fast short-circuit interruption
that reduces the let-through energy, which can damage
the circuit
•
Suitable for supplementary protection
•
Thermal-magnetic overcurrent protection
•
Optimum product quality, tested reliability and safety stand for
best protection of personnel, installations and plant. Eaton’s FAZ
DIN rail mountable circuit breaker is designed for use in control
panel applications.
Powerful offering for machine and system builders
The FAZ is available with B, C, D, K, S, and Z characteristics in
accordance with UL 1077, CSA C22.2 No.235 and IEC 60947-2.
These devices are CE marked.
Six levels of short-circuit protection,
categorized by B, C, D, K, S, and Z curves
•
Trip-free design—breaker can not be defeated by holding the
handle in the ON position
•
Captive screws cannot be lost
•
Fulfill UL 1077, CSA C22.2 No.235 and also IEC 60947-2
Standard
•
Field-installable shunt trip and auxiliary switch subsequent
mounting
•
Module width of only 17.7 mm (per pole)
•
Contact position indicator (red/green)
Typical applications
•
Easy installation on DIN rail
Supplementary protection
•
Possibility for sealing the toggle in ON or OFF position
•
Control circuits
•
Lighting
•
Business equipment
•
Appliances
FAZ complies with the latest national and
international standards
Standards—Supplementary Protection
UL 1077, CSA C22.2 No. 235
Apply to supplementary protectors intended for use
as overcurrent, or overvoltage or
undervoltage protection within an appliance or
other electrical equipment where branch circuit
protection is already provided, or is not required.
RoHS
These devices are RoHS compliant.
VDE
Devices with B, C, and D curves
are VDE compliant.
CCC
Devices with B, C, and D curves
are CCC compliant.
ABS
These devices are ABS compliant.
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
17
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
PRODUCT OVERVIEW
Six tripping curves to choose from
Trip-free design;
breaker cannot be
defeated by holding
the handle in the
ON position
Color-coded indicator
provides breaker
status for easy
troubleshooting
Breaker information
printed on the front
of the device for
quick identification
Even though not required by NEC or CEC for supplementary
protectors, Eaton’s FAZ devices are current limiting, which
means that they interrupt fault currents within one half cycle.
Current limiting devices offer superior protection by reducing
peak let-through current and energy.
1.30
Available in one-, two-,
three-, four-pole, 1+N
and 3+N models
1.05
Captive Posidrive
terminal screws
with finger and
back-of-hand
protection (IP20)
1.13
Breakers install on
standard DIN rail
Eaton FAZ supplementary protectors are available with six
different tripping characteristics, including Type B, C, D, K, S, and Z.
Definitions for each trip curve are contained on the ordering pages
and can be used to determine the optimal characteristic for your
application. For example, low-level short-circuit faults in control
wiring, such as PLCs, are best protected by devices with Type B
trip characteristics (3–5X continuous rating of the device (In).
1.45
Discover these advanced features
7200
3600
Time-current characteristic acc. to UL 1077
a Conventional
c 2.55 I :
N
non-tripping current
t = 1–60 s (IN < 32A)
t = 1–120 s (IN < 32A)
Int = 1.13 IN: t > 1 h
1200
600
300
b Conventional tripping
current
It = 1.45 IN: t < 1 h
120
60
30
e Type B: 5 I : t < 0.1 s
N
f Type C: 5 I : t > 0.1 s
N
g Type C: 10 I : t < 0.1 s
N
h Type D: 10 I : t > 0.1 s
N
i Type D: 20 I : t < 0.1 s
N
10
5
t (sec)
d Type B: 3 I : t > 0.1 s
N
2
1
0.5
D
0.2
0.1
0.05
Z
B
C
K
S
0.02
0.01
0.005
0.002
0.001
0.0005
1
2
3
4 5 6 7 8 9 10 15 20
30 40 50
I/In
Catalog Numbering System
FAZ - C 6 / 1 SP
Breaker Family
FAZ = Supplementary
protector
Single Package
Trip
Characteristic
B =3–5X In a
C =5–10X In a
D =10–20X In a
K =8–12X In a
S =13–17X In a
Z = 2–3X In a
Ampere Rating
0.5=0.5A
1 =1A
2 =2A
3 =3A
4 =4A
5 =5A
6 =6A
7 =7A
8 =8A
10 =10A
13=13A
15=15A
16=16A
20=20A
25=25A
30=30A
32=32A
40=40A
50=50A
63=63A
Number of Poles
1=Single-pole
2=Two-pole
3=Three-pole
a I = Rated current for instantaneous trip characteristics.
n
18
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
4 =Four-pole
1N = 1 + neutral
3N = 3 + neutral
SP =Single packaging of
single-pole curve B, C and
D for select amperes only
Blank=Standard packaging
Product Selection
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
1.13
FAZ product selection—B curve (3–5X In current rating)
•
Designed for resistive or slightly inductive loads
7200
•
Response time of instantaneous trip: 3–5X In current rating
3600
•
UL recognized and CSA Certified as supplementary protectors
1200
•
For international and domestic use (conform to IEC 60947-2)
•
UL file number 177451
1.45
PRODUCT SELECTION
Specified non-tripping
current
INT = 1.13 x IN for t > 1 h
Specified tripping current
IT = 1.45 x IN for t < 1 h
600
300
a 2.55 I :
N
t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)
b Type B: 3 x I : t > 0.1 s
N
c Type B: 5 x I : t < 0.1 s
N
120
1
60
30
10
t [sec]
Suitable for applications where protection against low-level shortcircuit faults in control wiring is desired. Instantaneous trip is
3–5X continuous rating of device (In). Applications include PLC
wiring, business equipment, lighting, appliances and some
motors. Low magnetic trip point.
5
2
1
1
0.5
0.2
3
0.1
2
0.05
B
0.02
0.01
0.005
0.002
0.001
0.0005
1
2
3
4
5
6 7 8 9 10
15
20
30
40
50
I / IN
B Curve (3–5X In Current Rating)—designed for resistive or slightly inductive loads a
Single-pole b
Catalog
Amperes Number
1
2
3
4
5
6
7
8
10
12
13
15
16
20
25
30
32
40
50
63
FAZ-B1/1-SP
FAZ-B2/1-SP
FAZ-B3/1-SP
FAZ-B4/1-SP
FAZ-B5/1-SP
FAZ-B6/1-SP
FAZ-B7/1-SP
FAZ-B8/1-SP
FAZ-B10/1-SP
FAZ-B12/1-SP
FAZ-B13/1-SP
FAZ-B15/1-SP
FAZ-B16/1-SP
FAZ-B20/1-SP
FAZ-B25/1-SP
FAZ-B30/1-SP
FAZ-B32/1-SP
FAZ-B40/1-SP
FAZ-B50/1-SP
FAZ-B63/1-SP
Two-pole
Three-pole
Four-pole
Single-pole + Neutral Three-pole + Neutral
Catalog
Number
Catalog
Number
Catalog
Number
Catalog
Number
Catalog
Number
FAZ-B1/2
FAZ-B2/2
FAZ-B3/2
FAZ-B4/2
FAZ-B5/2
FAZ-B6/2
FAZ-B7/2
FAZ-B8/2
FAZ-B10/2
FAZ-B12/2
FAZ-B13/2
FAZ-B15/2
FAZ-B16/2
FAZ-B20/2
FAZ-B25/2
FAZ-B30/2
FAZ-B32/2
FAZ-B40/2
FAZ-B50/2
FAZ-B63/2
FAZ-B1/3
FAZ-B2/3
FAZ-B3/3
FAZ-B4/3
FAZ-B5/3
FAZ-B6/3
FAZ-B7/3
FAZ-B8/3
FAZ-B10/3
FAZ-B12/3
FAZ-B13/3
FAZ-B15/3
FAZ-B16/3
FAZ-B20/3
FAZ-B25/3
FAZ-B30/3
FAZ-B32/3
FAZ-B40/3
FAZ-B50/3
FAZ-B63/3
FAZ-B1/4
FAZ-B2/4
FAZ-B3/4
FAZ-B4/4
FAZ-B5/4
FAZ-B6/4
FAZ-B7/4
FAZ-B8/4
FAZ-B10/4
FAZ-B12/4
FAZ-B13/4
FAZ-B15/4
FAZ-B16/4
FAZ-B20/4
FAZ-B25/4
FAZ-B30/4
FAZ-B32/4
FAZ-B40/4
FAZ-B50/4
FAZ-B63/4
FAZ-B1/1N
FAZ-B2/1N
FAZ-B3/1N
FAZ-B4/1N
FAZ-B5/1N
FAZ-B6/1N
FAZ-B7/1N
FAZ-B8/1N
FAZ-B10/1N
FAZ-B12/1N
FAZ-B13/1N
FAZ-B15/1N
FAZ-B16/1N
FAZ-B20/1N
FAZ-B25/1N
FAZ-B30/1N
FAZ-B32/1N
FAZ-B40/1N
FAZ-B50/1N
FAZ-B63/1N
FAZ-B1/3N
FAZ-B2/3N
FAZ-B3/3N
FAZ-B4/3N
FAZ-B5/3N
FAZ-B6/3N
FAZ-B7/3N
FAZ-B8/3N
FAZ-B10/3N
FAZ-B12/3N
FAZ-B13/3N
FAZ-B15/3N
FAZ-B16/3N
FAZ-B20/3N
FAZ-B25/3N
FAZ-B30/3N
FAZ-B32/3N
FAZ-B40/3N
FAZ-B50/3N
FAZ-B63/3N
a In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC
(Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent
protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
b Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering.
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
19
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
•
Designed for inductive loads
•
Response time of instantaneous trip: 5–10X In current rating
1.13
FAZ product selection—C curve (5–10X In current rating)
1.45
PRODUCT SELECTION
7200
•
UL recognized and CSA Certified as supplementary protectors
•
For international and domestic use (conform to IEC 60947-2)
•
UL file number 177451
Specified non-tripping
current
INT = 1.13 x IN for t > 1 h
3600
1200
a Type C: 5 x I : t > 0.1 s
N
b Type C: 10 x I : t < 0.1 s
N
Specified tripping current
IT = 1.45 x IN for t < 1 h
600
300
120
60
Suitable for applications where medium levels of inrush current
are expected. Instantaneous trip is 5–10X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits, and coils. Medium magnetic trip point.
30
t [sec]
10
5
2
1
0.5
0.2
2
0.1
1
0.05
C
0.02
0.01
0.005
0.002
0.001
0.0005
1
C Curve (5–10X In current rating)—designed for inductive loads
Amperes
0.5
1
1.6
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
40
50
63
2
3
4
5
6 7 8 9 10
15
20
30
40
50
I / IN
a
Single-pole b
Two-pole
Three-pole
Four-pole
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Single-pole + Neutral Three-pole + Neutral
Catalog Number
Catalog Number
FAZ-C0.5/1-SP
FAZ-C1/1-SP
FAZ-C1.6/1-SP
FAZ-C2/1-SP
FAZ-C3/1-SP
FAZ-C4/1-SP
FAZ-C5/1-SP
FAZ-C6/1-SP
FAZ-C7/1-SP
FAZ-C8/1-SP
FAZ-C10/1-SP
FAZ-C13/1-SP
FAZ-C15/1-SP
FAZ-C16/1-SP
FAZ-C20/1-SP
FAZ-C25/1-SP
FAZ-C30/1-SP
FAZ-C32/1-SP
FAZ-C40/1-SP
FAZ-C50/1-SP
FAZ-C63/1-SP
FAZ-C0.5/2
FAZ-C1/2
FAZ-C1.6/2
FAZ-C2/2
FAZ-C3/2
FAZ-C4/2
FAZ-C5/2
FAZ-C6/2
FAZ-C7/2
FAZ-C8/2
FAZ-C10/2
FAZ-C13/2
FAZ-C15/2
FAZ-C16/2
FAZ-C20/2
FAZ-C25/2
FAZ-C30/2
FAZ-C32/2
FAZ-C40/2
FAZ-C50/2
FAZ-C63/2
FAZ-C0.5/3
FAZ-C1/3
FAZ-C1.6/3
FAZ-C2/3
FAZ-C3/3
FAZ-C4/3
FAZ-C5/3
FAZ-C6/3
FAZ-C7/3
FAZ-C8/3
FAZ-C10/3
FAZ-C13/3
FAZ-C15/3
FAZ-C16/3
FAZ-C20/3
FAZ-C25/3
FAZ-C30/3
FAZ-C32/3
FAZ-C40/3
FAZ-C50/3
FAZ-C63/3
FAZ-C0.5/4
FAZ-C1/4
FAZ-C1.6/4
FAZ-C2/4
FAZ-C3/4
FAZ-C4/4
FAZ-C5/4
FAZ-C6/4
FAZ-C7/4
FAZ-C8/4
FAZ-C10/4
FAZ-C13/4
FAZ-C15/4
FAZ-C16/4
FAZ-C20/4
FAZ-C25/4
FAZ-C30/4
FAZ-C32/4
FAZ-C40/4
FAZ-C50/4
FAZ-C63/4
FAZ-C0.5/1N
FAZ-C1/1N
FAZ-C1.6/1N
FAZ-C2/1N
FAZ-C3/1N
FAZ-C4/1N
FAZ-C5/1N
FAZ-C6/1N
FAZ-C7/1N
FAZ-C8/1N
FAZ-C10/1N
FAZ-C13/1N
FAZ-C15/1N
FAZ-C16/1N
FAZ-C20/1N
FAZ-C25/1N
FAZ-C30/1N
FAZ-C32/1N
FAZ-C40/1N
FAZ-C50/1N
FAZ-C63/1N
FAZ-C0.5/3N
FAZ-C1/3N
FAZ-C1.6/3N
FAZ-C2/3N
FAZ-C3/3N
FAZ-C4/3N
FAZ-C5/3N
FAZ-C6/3N
FAZ-C7/3N
FAZ-C8/3N
FAZ-C10/3N
FAZ-C13/3N
FAZ-C15/3N
FAZ-C16/3N
FAZ-C20/3N
FAZ-C25/3N
FAZ-C30/3N
FAZ-C32/3N
FAZ-C40/3N
FAZ-C50/3N
FAZ-C63/3N
a In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical
Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other
electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
b Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering.
20
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
1.13
FAZ product selection—D curve (10–20X In current rating)
•
Designed for highly inductive loads
7200
•
Response time of instantaneous trip: 10–20X In current rating
3600
•
UL recognized and CSA Certified as supplementary protectors
1200
•
For international and domestic use (conform to IEC 60947-2)
•
UL file number 177451
1.45
PRODUCT SELECTION
Specified non-tripping
current
INT = 1.13 x IN for t > 1 h
Specified tripping current
IT = 1.45 x IN for t < 1 h
600
300
a 2.55 I :
N
t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)
b Type D: 10 x I : t > 0.1 s
N
c Type D: 20 x I : t < 0.1 s
N
120
1
60
Suitable for applications where high levels of inrush current are
expected. Instantaneous trip is 10–20X rating of device (In).
The high magnetic trip point prevents nuisance tripping in high
inductive applications such as motors, transformers and
power supplies.
30
t [sec]
10
5
2
1
1
0.5
0.2
3
0.1
2
0.05
D
0.02
0.01
0.005
0.002
0.001
0.0005
1
D Curve (10–20X In current rating)—designed for inductive loads
Single-pole b
Amperes Catalog Number
0.5
1
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
40
50 c
63 c
FAZ-D0.5/1-SP
FAZ-D1/1-SP
FAZ-D2/1-SP
FAZ-D3/1-SP
FAZ-D4/1-SP
FAZ-D5/1-SP
FAZ-D6/1-SP
FAZ-D7/1-SP
FAZ-D8/1-SP
FAZ-D10/1-SP
FAZ-D13/1-SP
FAZ-D15/1-SP
FAZ-D16/1-SP
FAZ-D20/1-SP
FAZ-D25/1-SP
FAZ-D30/1-SP
FAZ-D32/1-SP
FAZ-D40/1-SP
FAZ-D50/1-SP
FAZ-D63/1-SP
2
3
4
5
6 7 8 9 10
15
20
30
40
50
I / IN
a
Two-pole
Three-pole
Four-pole
Single-pole + Neutral Three-pole + Neutral
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
FAZ-D0.5/2
FAZ-D1/2
FAZ-D2/2
FAZ-D3/2
FAZ-D4/2
FAZ-D5/2
FAZ-D6/2
FAZ-D7/2
FAZ-D8/2
FAZ-D10/2
FAZ-D13/2
FAZ-D15/2
FAZ-D16/2
FAZ-D20/2
FAZ-D25/2
FAZ-D30/2
FAZ-D32/2
FAZ-D40/2
FAZ-D50/2
FAZ-D63/2
FAZ-D0.5/3
FAZ-D1/3
FAZ-D2/3
FAZ-D3/3
FAZ-D4/3
FAZ-D5/3
FAZ-D6/3
FAZ-D7/3
FAZ-D8/3
FAZ-D10/3
FAZ-D13/3
FAZ-D15/3
FAZ-D16/3
FAZ-D20/3
FAZ-D25/3
FAZ-D30/3
FAZ-D32/3
FAZ-D40/3
FAZ-D50/3
FAZ-D63/3
FAZ-D0.5/4
FAZ-D1/4
FAZ-D2/4
FAZ-D3/4
FAZ-D4/4
FAZ-D5/4
FAZ-D6/4
FAZ-D7/4
FAZ-D8/4
FAZ-D10/4
FAZ-D13/4
FAZ-D15/4
FAZ-D16/4
FAZ-D20/4
FAZ-D25/4
FAZ-D30/4
FAZ-D32/4
FAZ-D40/4
FAZ-D50/4
FAZ-D63/4
FAZ-D0.5/1N
FAZ-D1/1N
FAZ-D2/1N
FAZ-D3/1N
FAZ-D4/1N
FAZ-D5/1N
FAZ-D6/1N
FAZ-D7/1N
FAZ-D8/1N
FAZ-D10/1N
FAZ-D13/1N
FAZ-D15/1N
FAZ-D16/1N
FAZ-D20/1N
FAZ-D25/1N
FAZ-D30/1N
FAZ-D32/1N
FAZ-D40/1N
FAZ-D50/1N
FAZ-D63/1N
FAZ-D0.5/3N
FAZ-D1/3N
FAZ-D2/3N
FAZ-D3/3N
FAZ-D4/3N
FAZ-D5/3N
FAZ-D6/3N
FAZ-D7/3N
FAZ-D8/3N
FAZ-D10/3N
FAZ-D13/3N
FAZ-D15/3N
FAZ-D16/3N
FAZ-D20/3N
FAZ-D25/3N
FAZ-D30/3N
FAZ-D32/3N
FAZ-D40/3N
FAZ-D50/3N
FAZ-D63/3N
a In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical
Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other
electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
b Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering.
c IEC 60947-2 only.
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
21
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
PRODUCT SELECTION
•
Designed for motors, transformers, and upstream electronics
•
Response time of instantaneous trip: 8–12X In current rating
•
UL recognized and CSA Certified as supplementary protectors
•
For international and domestic use (conform to IEC 60947-2)
•
UL file number 177451
1.13
1.45
FAZ product selection—K curve (8–12X In current rating)
7200
3600
Specified
non-tripping current
Int = 1.05 u In
for t > 1 h
Specified
tripping current
It = 1.30 u In
for t < 1 h
1200
600
300
120
60
30
Suitable for applications where medium levels of inrush current
are expected. Instantaneous trip is 8–12X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits, and coils. Medium magnetic trip point.
t (sec)
10
5
2
1
0.5
K
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.0005
1
Single-pole c
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
FAZ-K0.5/1
FAZ-K1/1
FAZ-K1.6/1
FAZ-K2/1
FAZ-K3/1
FAZ-K4/1
FAZ-K6/1
FAZ-K8/1
FAZ-K10/1
FAZ-K13/1
FAZ-K16/1
FAZ-K20/1
FAZ-K25/1
FAZ-K32/1
FAZ-K40/1
FAZ-K50/1
FAZ-K63/1
3
4 5 6 7 8 9 10 15 20
30 40 50
U-rated Current
K Curve (8–12X In current rating)—
designed for inductive loads ab
Amperes Catalog Number
2
Two-pole
Three-pole
Four-pole
Single-pole + Neutral Three-pole + Neutral
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
FAZ-K0.5/2
FAZ-K1/2
FAZ-K1.6/2
FAZ-K2/2
FAZ-K3/2
FAZ-K4/2
FAZ-K6/2
FAZ-K8/2
FAZ-K10/2
FAZ-K13/2
FAZ-K16/2
FAZ-K20/2
FAZ-K25/2
FAZ-K32/2
FAZ-K40/2
FAZ-K50/2
FAZ-K63/2
FAZ-K0.5/3
FAZ-K1/3
FAZ-K1.6/3
FAZ-K2/3
FAZ-K3/3
FAZ-K4/3
FAZ-K6/3
FAZ-K8/3
FAZ-K10/3
FAZ-K13/3
FAZ-K16/3
FAZ-K20/3
FAZ-K25/3
FAZ-K32/3
FAZ-K40/3
FAZ-K50/3
FAZ-K63/3
FAZ-K0.5/4
FAZ-K1/4
FAZ-K1.6/4
FAZ-K2/4
FAZ-K3/4
FAZ-K4/4
FAZ-K6/4
FAZ-K8/4
FAZ-K10/4
FAZ-K13/4
FAZ-K16/4
FAZ-K20/4
FAZ-K25/4
FAZ-K32/4
FAZ-K40/4
FAZ-K50/4
FAZ-K63/4
FAZ-K0.5/1N
FAZ-K1/1N
FAZ-K1.6/1N
FAZ-K2/1N
FAZ-K3/1N
FAZ-K4/1N
FAZ-K6/1N
FAZ-K8/1N
FAZ-K10/1N
FAZ-K13/1N
FAZ-K16/1N
FAZ-K20/1N
FAZ-K25/1N
FAZ-K32/1N
FAZ-K40/1N
FAZ-K50/1N
FAZ-K63/1N
FAZ-K0.5/3N
FAZ-K1/3N
FAZ-K1.6/3N
FAZ-K2/3N
FAZ-K3/3N
FAZ-K4/3N
FAZ-K6/3N
FAZ-K8/3N
FAZ-K10/3N
FAZ-K13/3N
FAZ-K16/3N
FAZ-K20/3N
FAZ-K25/3N
FAZ-K32/3N
FAZ-K40/3N
FAZ-K50/3N
FAZ-K63/3N
a In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical
Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other
electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
b These breakers are available by special order and may result in additional delivery time.
c Two-piece box order, quantities of 2.
22
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
PRODUCT SELECTION
1.05
1.30
FAZ product selection—S curve (13–17X In current rating)
Designed for control circuits with high inrush
•
Response time of instantaneous trip: 13–17X In current rating
•
UL recognized and CSA Certified as supplementary protectors
•
For international and domestic use (conform to IEC 60947-2)
•
UL file number 177451
Suitable for applications where high levels of inrush current are
expected. Instantaneous trip is 13–17X rating of device (In).
The high magnetic trip point prevents nuisance tripping in high
inductive applications such as motors, transformers and
power supplies.
S Curve (13–17X In current rating)—
designed for inductive loads ab
7200
3600
Specified
non-tripping current
Int = 1.05 u In
for t > 1 h
Specified
tripping current
It = 1.30 u In
for t < 1 h
1200
600
300
120
60
30
10
5
t (sec)
•
2
1
0.5
S
0.2
0.1
0.05
0.02
0.01
0.005
Amperes
1
2
3
4
6
10
16
20
25
32
40
Single-pole c
Two-pole
Catalog Number
Catalog Number
FAZ-S1/1
FAZ-S2/1
FAZ-S3/1
FAZ-S4/1
FAZ-S6/1
FAZ-S10/1
FAZ-S16/1
FAZ-S20/1
FAZ-S25/1
FAZ-S32/1
FAZ-S40/1
FAZ-S1/2
FAZ-S2/2
FAZ-S3/2
FAZ-S4/2
FAZ-S6/2
FAZ-S10/2
FAZ-S16/2
FAZ-S20/2
FAZ-S25/2
FAZ-S32/2
FAZ-S40/2
0.002
0.001
0.0005
1
2
3
4 5 6 7 8 9 10 15 20
30 40 50
U-rated Current
a In North America, these switches are UL recognized and CSA Certified as supplementary
protection devices. Per the intent of NEC (National Electrical Code), Article 240, and
CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as
a substitute for the branch circuit protective device. They can be used to provide overcurrent
protection within an appliance or other electrical equipment where branch circuit
overcurrent protection is already provided, or is not required.
b These breakers are available by special order and may result in additional delivery time.
c Two-piece box order, quantities of 2.
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
23
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
PRODUCT SELECTION
1.05
1.30
FAZ product selection—Z curve (2–3X In current rating)
•
Designed for protection of electronic devices
•
Response time of instantaneous trip: 2–3X In current rating
•
UL recognized and CSA Certified as supplementary protectors
•
For international and domestic use (conform to IEC 60947-2)
1200
600
300
Suitable for applications where low levels of inrush current
are expected. Instantaneous trip is 2–3X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits, and coils. Medium magnetic trip point.
120
60
30
7200
3600
Specified
non-tripping current
Int = 1.05 u In
for t > 1 h
Specified
tripping current
It = 1.30 u In
for t < 1 h
t (sec)
10
5
2
1
0.5
Z
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.0005
1
2
3
4 5 6 7 8 9 10 15 20
30 40 50
U-rated Current
Z Curve (2–3X In current rating)—
designed for inductive loads ab
Single-pole c
Amperes Catalog Number
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
FAZ-Z0.5/1
FAZ-Z1/1
FAZ-Z1.6/1
FAZ-Z2/1
FAZ-Z3/1
FAZ-Z4/1
FAZ-Z6/1
FAZ-Z8/1
FAZ-Z10/1
FAZ-Z13/1
FAZ-Z16/1
FAZ-Z20/1
FAZ-Z25/1
FAZ-Z32/1
FAZ-Z40/1
FAZ-Z50/1
FAZ-Z63/1
Two-pole
Three-pole
Four-pole
Catalog Number
Catalog Number
Catalog Number
FAZ-Z0.5/2
FAZ-Z1/2
FAZ-Z1.6/2
FAZ-Z2/2
FAZ-Z3/2
FAZ-Z4/2
FAZ-Z6/2
FAZ-Z8/2
FAZ-Z10/2
FAZ-Z13/2
FAZ-Z16/2
FAZ-Z20/2
FAZ-Z25/2
FAZ-Z32/2
FAZ-Z40/2
FAZ-Z50/2
FAZ-Z63/2
FAZ-Z0.5/3
FAZ-Z1/3
FAZ-Z1.6/3
FAZ-Z2/3
FAZ-Z3/3
FAZ-Z4/3
FAZ-Z6/3
FAZ-Z8/3
FAZ-Z10/3
FAZ-Z13/3
FAZ-Z16/3
FAZ-Z20/3
FAZ-Z25/3
FAZ-Z32/3
FAZ-Z40/3
FAZ-Z50/3
FAZ-Z63/3
FAZ-Z0.5/4
FAZ-Z1/4
FAZ-Z1.6/4
FAZ-Z2/4
FAZ-Z3/4
FAZ-Z4/4
FAZ-Z6/4
FAZ-Z8/4
FAZ-Z10/4
FAZ-Z13/4
FAZ-Z16/4
FAZ-Z20/4
FAZ-Z25/4
FAZ-Z32/4
FAZ-Z40/4
FAZ-Z50/4
FAZ-Z63/4
a In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical
Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other
electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
b These breakers are available by special order and may result in additional delivery time.
c Two-piece box order, quantities of 2.
24
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
Accessories
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
ACCESSORIES
Auxiliary Contacts and Voltage Trips
Circuit
Diagram
Module
Rated Operational
Voltage
Catalog
Number
• 1NO/1NC
• Installs on left side of FAZ or shunt trip
• Max. one per FAZ (1077) device
• Switches when FAZ is tripped
electrically or manually
230 Vac
FAZ-XHIN11
• 1 changeover contact
• Installs on left side of FAZ or shunt trip
• Max. one per FAZ (1077) device
• Switches when FAZ is tripped
electrically or manually
230 Vac
FAZ-XHINW1
• Small selector screw changes mode
• Two Form C (changeover) contacts
• Installs on left side of FAZ or
shunt trip
• Auxiliary contacts switch when FAZ is
tripped electrically or manually
• Trip indicating contact switches only
when FAZ is tripped electrically
230 Vac
FAZ-XAM002
• Prevents FAZ from operating unless
voltage is present
• Installs on left side of FAZ
• Includes test button
115 Vac
FAZ-XUA(115VAC)
230 Vac
FAZ-XUA(230VAC)
400 Vac
FAZ-XUA(400VAC)
12–110 Vac
12–60 Vdc
FAZ-XAA-C-12-110VAC
110–415 Vac
110–230 Vdc
FAZ-XAA-C-110-415VAC
Description
Standard Auxiliary Contacts
14
12
11
Auxiliary/Trip Indicating Contact
Two-pole auxiliary mode
Trip indicating mode
Undervoltage Trip
D1
U
D2
Shunt Trip
• Allows remote trip of FAZ
• Installs on left side of FAZ
C1
C2
Allowable Combinations of Accessories
AUX
AUX
TRIP
FAZ
or
AUX
FAZ
AUX
TRIP
FAZ
or
Circuit
Breaker
Shunt
Trip
Circuit
Breaker
UnderV
Trip
Circuit
Breaker
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
25
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
ACCESSORIES
Busbar System
Description
Without Auxiliary Contacts
For connecting FAZ supplementary
protectors without auxiliary contacts.
May be fed from line or load side.
FAZ
FAZ
Rated Operational
Current
Number of Poles
per Device
Number of
Terminals
Catalog
Number a
80A
1
57
BB-UL-18/1P-1M/57
2
56
BB-UL-18/2P-2M/56
3
57
BB-UL-18/3P-3M/57
1
57
BB-UL-25/1P-1M/57
2
56
BB-UL-25/2P-2M/56
3
57
BB-UL-25/3P-3M/57
1
37
BB-UL-18/1P-1,5M/37
2
46
BB-UL-18/2P+AS-2,5M/46
3
48
BB-UL-18/3P+AS-3,5M/48
1
37
BB-UL-25/1P-1,5M/37
2
46
BB-UL-25/2P+AS-2,5M/46
3
48
BB-UL-25/3P+AS-3,5M/48
FAZ
100A
Auxiliary/Trip Indicating Contact
For connecting FAZ supplementary
protectors with auxiliary contacts.
May be fed from line or load side.
FAZ
FAZ
80A
100A
a Bus may be center fed for high current capacity.
26
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
Accessories
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
ACCESSORIES
Pin Type Incoming Supply Terminals
Accessories
Description
Installation
Bus Incoming Supply Terminals
Catalog
Number
Accessories
Incoming Terminal
Description
Installation
Catalog
Number
Incoming Terminal
• Accommodates
conductors from
6–35 mm2/
#10–2 AWG
• 4–5.5 Nm/
35–50 lb-in
• Two- and
three-pole
• 50 mm2
• #14–1 AWG
• 75 Deg wire
• 115 A/Y, 480V UL
• 160 A/Y 690V IEC
BB-UL-TEP/35
BB-UL-TE/50
Busbar End Cap
Accessories
Description
Poles
Catalog
Number
• Install after
cutting busbar
• Protects end
of busbar
2 and 3
BB-UL-EC/3
1
BB-UL-EC/1
Fork Connector
Pin Type Incoming Supply Terminals—Single-Phase Only
Accessories
Description
Poles
• Accommodates
conductors from
6–35 mm2/
#10–1/10 AWG
• 4–5.5 Nm/
35–50 Ib-in
Catalog
Number
BB-UL-TEPA/35
Protective Accessories
Accessories
Description
Catalog
Number
Busbar Terminal Cover
For covering
unused terminals
BB-IP/5
• Prevents reactivation
of the device during
maintenance
• Holds one padlock
IS/SPE-1TE
Padlock Hasp
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
27
Technical Data
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
TECHNICAL DATA
Technical Data
Description
Electrical
Approvals
Standards
Short-circuit trip response
Supplementary Protectors—UL/CSA
Current range
Maximum voltage ratings—UL/CSA
Single-pole, single-pole + neutral
Two-, three-pole, four-pole and
three-pole + neutral
Two poles in series
Thermal tripping characteristics
Single-pole
Multi-pole
Short-circuit ratings (at max. voltage)
Single-pole
Two-, three-pole
Single-pole
Two poles in series
Miniature Circuit Breaker—IEC
Current range
Maximum voltage ratings—IEC 68898-1
Single-pole
Two-, three-pole
Maximum voltage ratings—IEC 60947-2
Single-pole
Two-, three-pole
Two poles in series
Thermal tripping characteristics
Single-pole
Multi-pole
Interrupt ratings (at max. voltage)
IEC 60947-2
IEC 60898
Operational switching capacity
Max. backup fuse [gL/gG]
Rated impulse withstand—Uimp
Rated insulation voltage—Ui
Environmental/General
Selectivity class
Lifespan (operations)
Shock (IEC 68-2-22)
Operating temperature range
Shipment and short-term storage
Housing material
Mechanical
Standard front dimension
Device height
Terminal protection
Mounting width per pole
C Curve
D Curve
UR (UL 1077), CSA (CSA 22.2 No. 235), CE
IEC/EN 60947-2
3–5 In
5–10 In
10–20 In
1–63A
0.5–63A
0.5–40A
277 Vac
48 Vdc
277 Vac
48 Vdc
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
480Y/277 Vac
96 Vdc
480Y/277 Vac
96 Vdc
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA @ 48 Vdc
10 kA @ 96 Vdc
10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA @ 48 Vdc
10 kA @ 96 Vdc
5 kA
5 kA
10 kA @ 48 Vdc
10 kA @ 96 Vdc
1–63A
0.5–63A
0.5–63A
230 Vac
230/400 Vac
230 Vac
230/400 Vac
230 Vac
230/400 Vac
240 Vac
48 Vdc
240/415 Vac
96 Vdc
240 Vac
48 Vdc
240/415 Vac
96 Vdc
240 Vac
48 Vdc
240/415 Vac
96 Vdc
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
15 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac
15 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac
15 kA (10 kA for 50 and 63A)
10 kA (50 and 63A not available)
7.5 kA
125A
4000 Vac
440 Vac
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm
Mounting
Degree of protection
Terminals top and bottom
Supply connection
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
Terminal capacity [mm2]
Torque
Imperial torque
1 x 25 (AWG 4–18)/2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
1 x 25 (AWG 4–18)/2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
1 x 25 (AWG 4–18)/2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
Thickness of busbar material
Mounting position
28
B Curve
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
TECHNICAL DATA
Technical Data (continued)
Description
Electrical
Approvals
Standards
Short-circuit trip response
Supplementary Protectors—UL/CSA
Current range
Maximum voltage ratings—UL/CSA
Single-pole, single-pole + neutral
Two-, three-, four-pole and
three-pole + neutral
Two poles in series
Thermal tripping characteristics
Single-pole
Multi-pole
Short-circuit ratings (at max. voltage)
Single-pole
Single-pole + neutral
Two-, three-, four-pole
Two poles in series
Miniature Circuit Breaker—IEC
Current range
Maximum voltage ratings—IEC 60947-2
Single-pole, single-pole + neutral
Two-, three-, four-pole,
three-pole + neutral
Thermal tripping characteristics
Single-pole
Multi-pole
Interrupt ratings (at max. voltage)
IEC 60947-2
Operational switching capacity
Max. backup fuse [gL/gG]
Rated impulse withstand—Uimp
Rated insulation voltage—Ui
Environmental/General
Selectivity class
Lifespan (operations)
Shock (IEC 68-2-22)
Operating temperature range
Shipment and short-term storage
Housing material
Mechanical
Standard front dimension
Device height
Terminal protection
Mounting width per pole
K Curve
S Curve
Z Curve
UR (UL 1077), CSA (CSA 22.2 No. 235), CE
IEC/EN 60947-2, E177451, 204453
8–12 In
13–17 In
2–3 In
0.5–63A
0.5–40A
1–63A
277 Vac
48 Vdc
277 Vac
48 Vdc
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
480Y/277 Vac
96 Vdc
480Y/277 Vac
96 Vdc
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
—
5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
—
5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
—
0.5–63A
0.5–40A
1–63A
240 Vac
240 Vac
240 Vac
240/415 Vac
240/415 Vac
240/415 Vac
> 1 Hour @ 1.05 x In
< 1 Hour @ 1.3 x In
> 1 Hour @ 1.05 x In
< 1 Hour @ 1.3 x In
> 1 Hour @ 1.05 x In
< 1 Hour @ 1.3 x In
15 kA
7.5 kA
125A
4000 Vac
440 Vac
10 kA
7.5 kA
125A
4000 Vac
440 Vac
10 kA
7.5 kA
125A
4000 Vac
440 Vac
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
80 mm
Finger and back-of-hand proof to IEC 536
17.7 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.7 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.7 mm
Mounting
Degree of protection
Terminals top and bottom
Supply connection
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
Terminal capacity [mm2]
Torque
Imperial torque
1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
Thickness of busbar material
Mounting position
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
29
Technical Data
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
TECHNICAL DATA
Let-through energy I2t
Characteristic B and C
Let-through current ID
Characteristic B and C
∫i2dt 105
[A2s] 8
lD 104
9
[A] 8
63 A
50 A
40 A
32 A
25 A
20 A
16 A
13 A
10 A
6
4
63 A
50 A
40 A
32 A
25 A
16 A20 A
13 A
10 A
7
6
5
4
6A
4A
3A
2
1.5
6A
4A
104
3A
3
2
8
2A
6
1.5
2A
4
103
2
1A
1.5
0.5 A
1 A
103
0.5 A
8
5
6
4
3
0.5
1
1.5
2
3
4
5 6 7 8 910
2
15
0.5
1
1.5
2
3
4
5 6 7 8 910
15
Icc rms [kA]
Icc rms [kA]
Characteristic D
Characteristic D
∫i2dt 10
[A2s] 8
5
lD 104
9
[A] 8
40 A
32 A
25 A
20 A
16 A
13 A
6
4
40 A
32 A
25 A
20 A
16 A
13 A
10 A
6A
7
6
10 A
5
6A
4
2
3
1.5
10
4
8
2
6
1.5
4
103
2
1.5
103
5
8
6
4
0.5
1
1.5
2
3
4
5 6 7 8 910
2
15
30
0.5
1
1.5
2
3
4
5 6 7 8 910
15
Icc rms [kA]
Icc rms [kA]
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
TECHNICAL DATA
Let-through energy I2t
Characteristic K
lD
[A]
Characteristic S
lD
[A]
104
8
104
8
63 A
50 A
40 A
32 A 25 A
20 A
13 A 16 A
6
4
10 A
6A
4A
3A
3
4
6A
4A
3A
2A
3
2A
2
40 A
32 A
25 A
20 A
16 A
10 A
6
1.6 A
1.5
2
1A
1A
103
1.5
103
5
0.5 A
5
0.5
1
1.5
2
3
4
5
6
7 8 9 10
0.5
1
1.5
2
3
4
5
6
7 8 9 10
Icc rms [kA]
Icc rms [kA]
Characteristic Z
lD
[A]
104
8
6
63 A
50 A
40 A
32 A 25 A
20 A
16 A
4
10 A
8A
3
6A
2
4A
3A
1.5
2A
103
5
1.6 A
1A
0.5 A
0.5
1
1.5
2
3
4
5
6
7 8 9 10
Icc rms [kA]
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
31
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
TECHNICAL DATA
Influence of the Ambient Temperature on the Thermal Tripping Behavior
Corrected values of the rated current dependent on the ambient temperature
Ambient Temperature T
In (A)
0.16
0.25
0.50
0.75
1.00
1.50
1.60
2.00
2.50
3.00
3.50
4.00
5.00
6.00
7.00
8.00
10.00
12.00
13.00
15.00
16.00
20.00
25.00
32.00
35.00
40.00
50.00
63.00
–40°C
–30°C
–20°C
–10°C
0°C
10°C
20°C
30°C
35°C
40°C
45°C
50°C
55°C
60°C
65°C
70°C
75°C
0.20
0.32
0.64
0.96
1.30
1.90
2.00
2.60
3.20
3.80
4.50
5.10
6.40
7.70
9.00
10.20
13.00
15.00
17.00
19.00
20.00
26.00
32.00
41.00
45.00
51.00
64.00
81.00
0.20
0.31
0.62
0.93
1.20
1.90
2.00
2.50
3.10
3.70
4.40
5.00
6.20
7.50
8.70
9.90
12.00
15.00
16.00
19.00
20.00
25.00
31.00
40.00
43.00
50.00
62.00
78.00
0.19
0.30
0.60
0.90
1.20
1.80
1.90
2.40
3.00
3.60
4.20
4.80
6.00
7.20
8.40
9.60
12.00
14.00
16.00
18.00
19.00
24.00
30.00
38.00
41.00
48.00
60.00
76.00
0.19
0.29
0.58
0.87
1.20
1.70
1.90
2.30
2.90
3.50
4.10
4.70
5.80
7.00
8.20
9.30
12.00
14.00
15.00
17.00
19.00
23.00
29.00
37.00
41.00
47.00
58.00
73.00
0.18
0.28
0.56
0.84
1.10
1.70
1.80
2.20
2.80
3.40
3.90
4.50
5.60
6.70
7.80
9.00
11.00
13.00
15.00
17.00
18.00
22.00
28.00
36.00
38.00
45.00
56.00
71.00
0.17
0.27
0.54
0.81
1.10
1.60
1.70
2.20
2.70
3.30
3.80
4.30
5.40
6.50
7.60
8.70
11.00
13.00
14.00
16.00
17.00
22.00
27.00
35.00
38.00
43.00
54.00
68.00
0.17
0.26
0.52
0.78
1.00
1.60
1.70
2.10
2.60
3.10
3.70
4.20
5.20
6.30
7.40
8.40
10.00
13.00
14.00
16.00
17.00
21.00
26.00
33.00
36.00
42.00
52.00
66.00
0.16
0.25
0.50
0.75
1.00
1.50
1.60
2.00
2.50
3.00
3.50
4.00
5.00
6.00
7.00
8.00
10.00
12.00
13.00
15.00
16.00
20.00
25.00
32.00
35.00
40.00
50.00
63.00
0.16
0.25
0.49
0.74
0.99
1.50
1.60
2.00
2.50
3.00
3.40
3.90
4.90
5.90
6.90
7.90
9.90
12.00
13.00
15.00
16.00
20.00
25.00
32.00
35.00
39.00
49.00
62.00
0.15
0.24
0.48
0.73
0.97
1.50
1.50
1.90
2.40
2.90
3.40
3.90
4.80
5.80
6.80
7.70
9.70
12.00
13.00
15.00
15.00
19.00
24.00
31.00
34.00
39.00
48.00
61.00
0.15
0.24
0.47
0.71
0.95
1.40
1.50
1.90
2.40
2.80
3.30
3.80
4.70
5.70
6.70
7.60
9.50
11.00
12.00
14.00
15.00
19.00
24.00
30.00
33.00
38.00
47.00
60.00
0.15
0.23
0.46
0.69
0.93
1.40
1.50
1.90
2.30
2.80
3.20
3.70
4.60
5.60
6.50
7.40
9.30
11.00
12.00
14.00
15.00
19.00
23.00
30.00
32.00
37.00
46.00
58.00
0.14
0.23
0.45
0.68
0.90
1.40
1.40
1.80
2.30
2.70
3.20
3.60
4.50
5.40
6.30
7.20
9.00
11.00
12.00
14.00
14.00
18.00
23.00
29.00
32.00
36.00
45.00
57.00
0.14
0.22
0.44
0.66
0.89
1.30
1.40
1.80
2.20
2.70
3.10
3.50
4.40
5.30
6.20
7.10
8.90
11.00
12.00
13.00
14.00
18.00
22.00
28.00
32.00
35.00
44.00
56.00
0.14
0.22
0.43
0.65
0.87
1.30
1.40
1.70
2.20
2.60
3.00
3.50
4.30
5.20
6.10
6.90
8.70
10.00
11.00
13.00
14.00
17.00
22.00
28.00
30.00
35.00
43.00
55.00
0.14
0.21
0.42
0.64
0.85
1.30
1.40
1.70
2.10
2.50
3.00
3.40
4.20
5.10
6.00
6.80
8.50
10.00
11.00
13.00
14.00
17.00
21.00
27.00
29.00
34.00
42.00
53.00
0.13
0.21
0.41
0.62
0.83
1.20
1.30
1.70
2.10
2.50
2.90
3.30
4.10
5.00
5.80
6.60
8.30
10.00
11.00
12.00
13.00
17.00
21.00
26.00
29.00
33.00
41.00
52.00
Influence of the Mains Frequency
Influence of the mains frequency on the tripping behavior IMA
of the instantaneous release
Mains Frequency f [Hz]
IMA(f)IMA (50 Hz) [%]
16 2/3 50
60
100
200
300
400
91
101
106
115
134
141
100
Load Carrying Capacity of Adjoining Miniature Circuit Breakers
Rated Diversity Factor
1.00
0.90
0.80
0.70
1
2
3
4
5
6
7
8
Number of Circuit Breakers
32
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
Accessory Technical Data
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
ACCESSORY TECHNICAL DATA
Technical Data
FAZ-XHIN
FAZ-XAM002
FAZ-XAA-C
FAZ-XUA
Electrical
Contact function
Rated operational voltage Un
1A + 1B
2 C/O
250 Vac
—
—
—
Voltage range
—
Voltage range
—
Closing threshold [x Un]
Tripping threshold [x Un]
Rated frequency ƒ
General use (UL/CSA)
AC—230/240 Vac
DC—110/120 Vdc
Pilot duty
Conventional free air thermal current Ith
Rated operational current
AC-13 Ie
AC-15 Ie
DC-13 Ie
Rated insulation voltage Ui
Minimum operating voltage per contract Umin
Rated impulse withstand voltage (1.2/50μ) Uimp
Rated conditional short-circuit current with 6A backup fuse ISC
Max. admissible backup fuse
Mechanical
Standard front dimension
Device height
Mounting width
Mounting
Degree of protection
enclosed
Terminal protection
—
—
50/60 Hz
12–110 Vac
12–60 Vdc
110–415 Vac
110–230 Vdc
—
—
50/60 Hz
—
—
115 Vac
230 Vac
400 Vac
—
2/2A
0.5/0.5A
A600/Q600
4A
—
—
—
—
—
—
—
—
3A (250 Vac)
2A (250 Vac)
0.5A (110 Vdc)
250 Vac
5 Vdc
2.5 kV
1 kA
4A gL
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
45 mm
80 mm
8.8 mm
On MCB
45 mm
80 mm
17.6 mm
IEC/EN 60715 top-hat rail
45 mm
80 mm
17.8 mm
IEC/EN 60715 top-hat rail
IP40
Protection against
electric shock to IEC 536
Lift terminals
IP40
Protection against
electric shock to IEC 536
Twin-purpose terminals
IP40
Protection against
electric shock to IEC 536
Twin-purpose terminals
0.5–2.5 mm2
0.5–2.5 mm2
0.8–1.0 Nm (7–9 lb-in)
1–2.5 mm2
1–2.5 mm2
2.4 Nm (21 lb-in)
2 x (1–2.5) mm2
2 x (1–2.5) mm2
0.8 Nm (7 lb-in)
Description
Terminals
Terminal capacity
Solid
Flexible
Tightening torque of terminal screws
—
0.8
0.5
50/60 Hz
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
33
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
ACCESSORY TECHNICAL DATA
Dimensions are in millimeters, and not intended for manufacturing purposes.
Miniature circuit breakers
FAZ
80
45
9.4
17.7
35.4
53.1
5.5
70.8
44
60
Auxiliary Contacts
8.8
5.5
44
8.8
45
45
80
FAZ-XAM002
80
FAZ-XHI11 and FAZ-XH1NW1
5.5
FAZ-XAA
FAZ-XUA
26.2
30.5
10
44
17.8
5.5
44
60
60
34
80
45
5.5
45
Undervoltage Releases
80
Shunt Releases
17.6
44
60
60
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
UL 1077 DIN rail supplementary protectors
FAZ circuit breakers
ACCESSORY TECHNICAL DATA
Busbar and Accessory Weights and Dimensions
Catalog Number
BB-UL-18/1P-1M/57
BB-UL-18/2P-2M/56
BB-UL-18/3P-3M/57
BB-UL-18/1P-1.5M/37
BB-UL-18/2P+AS-2.5M/46
BB-UL-18/3P+AS-3.5M/48
BB-UL-25/1P-1M/57
BB-UL-25/2P-2M/56
BB-UL-25/3P-3M/57
BB-UL-25/1P-1.5M/37
BB-UL-25/2P+AS-2.5M/46
BB-UL-25/3P+AS-3.5M/48
BB-UL-TEP/35
BB-UL-TEPA/35
BB-UL-TE/50
BB-IP/5
BB-UL-EC/3
BB-UL-EC/1
Unit
Weight
(kg)
Length
(mm)
Width
(mm)
Height
(mm)
0.29
0.64
0.83
0.26
0.63
0.79
0.36
0.79
1.04
0.31
0.73
0.97
0.03
0.03
0.03
0.003
0.001
0.001
1009
991
1009
985
1009
982
1009
991
1009
985
1009
982
60
36
40
85
14
24
15
22
22
15
22
22
15
22
22
15
22
22
17
17
18
12
5
22
15
37
37
15
37
37
15
37
37
15
37
37
29
29
30
24
10
10
L
W
H
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
35
UL 1077 DIN rail supplementary protectors
Application guidelines for UL 489
circuit breakers and UL 1077
supplementary protectors
UL 489
Breaker
UL 489
Branch
UL 1077
Internal Receptacle
External
Receptacle
Electronics
UL 489
Branch
UL 1077
Other
Sensitive
Devices
External
Motor
M
UL 489
Branch
External
Motor
UL 489
Branch
M
UL 1077
HACR
Motor
Controller
Example of UL 489 and UL 1077 Application
UL 489 circuit breakers
Used for branch circuit protection, internal/external receptacles, external motors and HACR equipment
(heating, air conditioning and refrigeration).
UL 1077 supplementary protectors
Used for overcurrent protection within appliances or electrical equipment, where branch circuit protection
is already provided or not required.
NNote: UL 489 devices can be used in place of UL 1077; UL 1077 devices cannot be used in place of UL 489.
36
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
Miniature circuit breaker application
FAZ circuit breakers
Product Overview
Miniature circuit breaker application
FAZ circuit breakers
PRODUCT OVERVIEW
Applying branch circuit breakers and supplementary
protectors in North America
Characteristics of IEC-style miniature circuit breakers
Because FAZ miniature circuit breakers are IEC-style devices,
it is important to understand their inherent characteristics before
examining them in the context of UL/CSA requirements.
The Eaton series offer two types of miniature circuit breakers
for use in North America. The first version, FAZ-NA(RT), fully
complies with the molded-case circuit breaker standard UL 489
and the Canadian equivalent CSA 22.2 No. 5-09, which states that
devices within that range can be applied legitimately as feeder
and branch circuit protective devices per the U.S. and Canadian
electrical codes.
A second version, FAZ, is recognized per UL 1077 and certified
per CSA C22.2 No. 235 as a supplementary protector and can
be fully used per the NEC and CEC Codes in that capacity.
For international purposes, the entire FAZ family is CE marked
and in full conformity with the applicable IEC standards for
miniature circuit breakers, EN/IEC 60898 and EN/IEC 60947-2.
•
IEC-style miniature circuit breakers are thermal-magnetic,
inverse time protective devices, with both a fixed thermal
and a fixed magnetic trip setting
•
They are toggle operated, and like all modern circuit
breakers, feature a “trip-free” mechanism; this means
that the tripping action works independently of the handle
position for safety purposes
•
They all mount on a standard 35 mm DIN rail and share
a common single pole width of 17.5 mm
•
Most comply with EN/IEC 60898 and EN/IEC 60947-2,
which are the relevant international performance and testing
standards for low voltage (<1000V) circuit breakers in Europe
and the rest of the IEC world
•
Outside North America, they can be used in both residential
and industrial applications as feeder and branch circuit
protective devices
•
In North America, most European miniature circuit breakers
are only UL recognized and CSA certified as “supplementary
protectors,” meaning that they cannot be utilized as feeder
or branch circuit protective devices per the local electrical
codes. This commonly restricts their use to applications where
“closer” protection is desired than that offered by a branch
circuit protection device
•
Some variations, like the FAZ-NA(RT) line have been specially
designed to meet UL and CSA requirements for molded-case
circuit breakers and are marked accordingly. This makes them
suitable for feeder and branch circuit protection applications
in North America
Both FAZ and FAZ-NA(RT) are offered in various ampere ranges
and tripping characteristics. This paper will focus on the main
technical aspects of the entire line and should assist in the
proper selection and application of all versions.
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
37
Miniature circuit breaker application
FAZ circuit breakers
Miniature circuit breaker application
FAZ circuit breakers
PRODUCT OVERVIEW
Supplementary protectors
As mentioned, the standard FAZ line fulfills all of the criteria
per code of “supplementary overcurrent protective devices,”
or “supplementary protectors,” as they are better known.
What is the definition of a supplementary protector
per North American standards?
Typically, the branch circuit overcurrent protective device
(BOPD) will be either a listed molded-case circuit breaker
or a fuse. Supplementary protectors, such as FAZ devices
from the Eaton series, can therefore be added to any of
these branch circuits to “supplement” the branch circuit
protection. Examples of applications ideally suited for these
devices can include:
A supplementary protector is a manual reset device designed
to open the circuit automatically on a predetermined value
of time versus current or voltage within an appliance or other
electrical equipment. It may also be provided with manual
means for opening or closing the circuit. (Source: UL 1077)
•
Any type of OEM electrical equipment that is fed from
a service panel board and that often requires additional
protection for sensitive internal circuitry and components
(test and medical equipment, copiers and printers, computers
and power supplies, etc.)
In the United States (and similarly in Canada) the NEC 2005
further defines supplementary protectors as devices intended
to provide limited overcurrent protection for specific applications,
such as lighting fixtures and appliances. This limited protection
is in addition to the protection provided in the required branch
circuit by the branch circuit overcurrent protective device.
•
The need for manual reset devices with optional accessories
such as auxiliary contacts and voltage trips to accomplish
fuseless protective circuit designs and enhance operational
diagnostics
•
Isolation and protection of control cable, coils, contacts, and
circuit elements of motor control circuits tapped from the load
side of the branch circuit protective device (per NEC 430.72)
•
Protection of control circuit transformers, especially in the
secondary where the manual reset protector can be used
to isolate, as well as protect, secondary circuit conductors
and loads
Clearly, the underlying message in those definitions is that
supplementary protectors are not branch circuit overcurrent
protective devices per code, and neither are they tested that
way per UL and CSA standards. They cannot replace the primary
protective role performed by listed and certified molded case
circuit breakers and fuses.
That explains, in part, their status by UL as “recognized only”
devices. Supplementary protectors will never bear a UL listing
mark, simply because their suitability as protective devices is
dependent on a number of acceptability conditions that can
vary from make to make and ultimately define the manner in
which they can be properly applied per code. The manufacturer
should be consulted in all cases when evaluating the suitability
of “recognized only” components such as UL 1077
supplementary protectors.
FAZ protectors are not subject to any specific restrictions in this
respect, other than, like all supplementary protectors, they must
never be used as a substitute for true listed and certified primary
overcurrent protective devices.
Where can supplementary protectors be used effectively
per code standards?
Eaton series FAZ supplementary protectors can be used
in a number of significant areas. To more clearly illustrate
potential applications, however, let’s first present the NEC’s
definition of a branch circuit:
IEC-based miniature circuit breakers, such as the entire FAZ line,
are much more than just conventional supplementary protectors
from an internal design point of view and can provide an ideal
means to enhance the protective capabilities of any circuit.
•
As mentioned, they are in full compliance with the pertinent
EN/IEC standards (EN/IEC 60898, EN/IEC 60947-2) for miniature
circuit breakers and can thus be applied, outside of North
America, as full-fledged stand-alone overcurrent protective
devices in both residential and industrial applications
•
As this typical let-through current curve shows, they are highly
current limiting devices that appreciably limit the amount of
let-through current and destructive energy within their ratings
to minimize damage levels to downstream loads and circuits
Circuit breakers that are classified as “current limiting” have
the ability to clear damaging short-circuit currents within the
first half-cycle of the fault, resulting in better overall protection
for all circuit components.
•
They come in a variety of tripping characteristics, which
is ideal when customizing protection to match specific load
requirements. FAZ supplementary protectors offer a total
of six different protection characteristics for this purpose:
B, C, D, K, S, and Z tripping characteristics
•
They feature a number of electrical accessories to enhance
the performance and diagnostic capabilities of control panels,
as well as a means to facilitate panel mounting and wiring
The circuit conductors between the final overcurrent device
protecting the circuit and the outlets. (Source: NEC)
A branch circuit is that portion of the electrical distribution
system that extends beyond the final branch circuit overcurrent protective device and is intended to serve lighting,
appliance, motors, and/or other individual loads.
38
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
Miniature circuit breaker application
FAZ circuit breakers
PRODUCT OVERVIEW
Typical let-through curve profile of a current-limiting device
•
The X axis shows the prospective short-circuit current levels
•
The Y axis indicates the actual let-through values (let-through
current in the example shown) at those prospective fault
ratings for each FAZ device plotted
The following magnetic response times apply to each of the characteristic letters referenced in Eaton series FAZ part numbers:
•
B: Instantaneous response of 3–5x In (In = fixed current
rating of each unit)—ideally suited for resistive loads,
such as conductors or heaters
•
C: Instantaneous response of 5–10x In—ideally suited
for inductive loads, such as motors and solenoids
•
By design, all Eaton series FAZ supplementary protectors
and miniature molded-case circuit breakers are current-limiting
protective devices.
D: Instantaneous response of 10–20x In—ideally suited
for highly inductive loads, such as lighting and higher
efficiency motors
•
K: Instantaneous response of 8–12x In—ideally suited for
highly inductive loads, similar to D but with a narrower range
Characteristic B and C
•
S: Instantaneous response of 13–17x In—ideally suited
for highly inductive loads, especially in control circuits
with coils and light filaments
63 A
50 A
40 A
32 A
25 A
20 A
16 A
13 A
10 A
•
Z: Instantaneous response of 2–3x In—very low instantaneous
setting to provide tighter protection for loads that are more
sensitive to the effects of overcurrents
6A
4A
3A
Typical “inverse time” tripping characteristic
of a miniature circuit breaker
As can be interpreted from the bend in the plotted curves, each
device acts to limit the damaging let-through energy (and current)
at those values of short-circuit current.
lD
[A]
104
8
6
4
3
•
“Inverse time” refers to the device’s tripping characteristic;
as the curve shows, the higher the current, the lower the
tripping time
•
The trip response on the thermal portion is uniform
throughout the line
•
The instantaneous response differs, depending on the
characteristic selected. (i.e., B, C, or D)
•
Tripping is very quick (less than a half-cycle) in the upper range
of overcurrents (bottom right) due to the current-limiting design
of the Eaton series miniature circuit breakers
2
2A
1.5
103
1A
0.5 A
5
2
0.5
1
1.5
2
3
4
5
6 7 8 9 10
15
Icc rms [kA]
Tripping characteristics
Miniature circuit breakers are thermal-magnetic, inverse-time
tripping devices. From a thermal point of view, all FAZ protectors
are calibrated to trip at the same level, which is 135% of the
device’s fixed current rating for single-pole and 145% for
multi-pole at an ambient reference temperature of 40°C.
NNote: Higher ambient temperatures, as well as density of mounting
groups, can all be accommodated but may be subject to de-rating
factors. Please consult technical data for further information and
appropriate curves.
It is the response time of the magnetic trip that differentiates
each characteristic and for which an identifying letter is assigned.
The IEC 898 standard only specifically covers the B, C, and D
characteristics. The rest can vary from brand to brand, but
essentially follow a uniform convention.
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
39
Miniature circuit breaker application
FAZ circuit breakers
PRODUCT OVERVIEW
1.13
1.45
Typical FAZ miniature circuit breaker characteristic
7200
3600
Specified non-tripping current
Int = 1.13 X In for t > 1 h
Specified tripping current
1200
600
300
It = 1.45 X In for t < 1 h
➀ 2.55 X In : t = 1 – 60 s (In < 32 A)
t = 1 – 120 s (In > 32 A)
➁ Type B: 3 X In : t > 0.1 s
120
60
30
➂ Type B: 5 X In : t < 0.1 s
➀
➃ Type C: 5 X In : t > 0.1 s
➄ Type C: 10 X In : t < 0.1 s
➅ Type D: 10 X In : t > 0.1 s
t (sec)
10
5
➆ Type D: 20 X In : t < 0.1 s
2
1
0.5
➀
0.2
0.1
0.05
➄
➂
➁
B➃
C ➅
1
2
3
D
4 5 6 7 8 9 10 15 20
As previously mentioned, we have expanded our FAZ line
of miniature circuit breakers to include a version that is listed
and certified as a molded-case circuit breaker (UL 489 and
CSA No. 5).
This line is rated up to 40A and comes in single-, two-, and
three-pole versions with instantaneous trip characteristics B,
C and D. Of course, the line is also in conformity with the
IEC standard for molded-case circuit breakers, IEC 60947-2,
and can therefore be universally applied.
The NEC defines a circuit breaker as follows:
A device designed to open and close a circuit by nonautomatic means and to open the circuit automatically
on a predetermined overcurrent without damage to itself
when properly applied within its rating.
Note the text in italics. In the eyes of the code, that definition
sets circuit breakers apart from any other protective device and
establishes their role as primary overcurrent protective switches
in all types of electrical circuits. UL listing (and CSA Certification)
requires additionally that regular testing on circuit breakers be
conducted by UL and CSA at the manufacturer’s plant to monitor
construction and verify their performance.
➆
0.02
0.01
0.005
0.002
0.001
0.0005
FAZ-NA(RT) miniature circuit breakers
30 40 50
Multiples of In
The Eaton series new miniature molded-case circuit breaker line
includes two types: the FAZ-NA with traditional box terminals for
multiple wires, and the FAZ-RT which accommodates ring-tongue
terminals.
The advantages of a current-limiting device
1.05
1.13
1.30
1.45
As already mentioned, all Eaton series FAZ devices are
current-limiting by design. In the case of the UL 489 devices,
they are also classified by UL/CSA in that manner and are
marked on the label.
A circuit breaker that is marked as a current-limiting device
is one that does not use a fusible element and, when operating
within its current-limiting range, limits the let-through energy
(I2t) to less than the energy of a half-cycle wave of the available
symmetrical current.
t (s)
7200
3600
1200
600
300
120
60
30
The label on FAZ-NA(RT) devices lists the actual let-through
energy (I2t = 60 kA2 s) and peak let-through current (6.2 kA)
at the maximum interrupting rating of 10 kA.
10
5
2
1
0.5
Current-limiting circuit breakers substantially reduce the amount
of damage sustained by downstream components in the event
of a high short-circuit fault by clearing the fault in the shortest
amount of time possible due to the quick separation of its
contacts and ensuing extinction of the arc current.
D
0.2
0.1
0.05
Z
B
C
K
S
HACR and SWD
FAZ-NA(RT) circuit breakers are also marked “HACR” for
use in heating, air conditioning, and refrigeration applications.
In addition, the abbreviation “SWD” on the label indicates
that the devices are suitable for switching fluorescent lighting
loads on a regular basis.
0.02
0.01
0.005
0.002
0.001
0.0005
1
2
3
4 5 6 7 8 9 10
15 20
30 40 50
Multiples of In
40
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
Technical Data
Miniature circuit breaker application
FAZ circuit breakers
TECHNICAL DATA
Short-circuit markings on FAZ devices
Below is a tabulated summary of short-circuit rating values that
apply to the FAZ line of supplementary protectors and moldedcase circuit breakers.
It is important to keep in mind that short-circuit markings
on FAZ supplementary protectors (UL 1077) and FAZ-NA(RT)
molded-case circuit breakers (UL 489) must not be interpreted
in the same manner.
Supplementary protectors have short-circuit markings in
association with upstream primary overcurrent protective
devices. Conversely, molded-case circuit breakers are primary
overcurrent protective devices, and their ratings thus refer
to their short-circuit interrupting capability.
Short-Circuit Rating Values for FAZ Supplementary Protectors and Branch Circuit Breakers
Description
Trip
Characteristic
Maximum
Amperes
Maximum
Volts
Short-Circuit
Rating
0.5–35A
40–63A
0.5–63A
0.5–40A
277 Vac
277 Vac
48 Vdc
277 Vac
48 Vdc
480Y/277 Vac a
480Y/277 Vac a
96 Vdc
480Y/277 Vac a
96 Vdc
10 kA
FAZ Supplementary Protectors (UL 1077)
Single-pole, single-pole + neutral
B and C
D, K, S, and Z
Two-, three-, four-pole
Two poles in series
Two-, three-, four-pole
Two poles in series
B and C
D, K, S, and Z
0.5–35A
40–63A
6–25A
0.5–40A
5 kA
10 kA
5 kA
10 kA
10 kA
5 kA
10 kA
5 kA
10 kA
FAZ-NA(RT) Branch Circuit Breakers (UL 489)
Single-pole
B, C and D
0.5–32A
277 Vac
10 kA
Single-pole—(NA) only
Two-, three-pole
35–40A
0.5–40A
0.5–32A
240 Vac
48 Vdc
480Y/277 Vac a
10 kA
10 kA
10 kA
35–40A
0.5–40A
240 Vac
96 Vdc
10 kA
10 kA
15–25A
14 kA
13–20A
277 Vac
480Y/277 Vac a
277 Vac
480Y/277 Vac a
2–40A
2–40A
125 Vdc
250 Vdc
10 kA
10 kA
B, C and D
B, C and D
Two-pole—(NA) only
C and D
FAZ-NA(RT) Branch Circuit Breakers (UL 489)
Single-pole
B and C
Two-, three-pole
Single-pole
Two-, three-pole
B and C
D
D
FAZ-(NA)-DC Branch Circuit Breakers (UL 489)
Single-pole
C
Two poles in series
C
15–25A
13–20A
14 kA
14 kA
14 kA
a A circuit breaker with a 480Y/277 Vac rating can be applied in a solidly grounded circuit where the nominal voltage of any conductor to ground does not exceed the lower value of the circuit
breaker’s rating (e.g., 277 Vac) and the nominal voltage between any two conductors does not exceed its higher value (480 Vac). These ratings typically can be found on protective devices such
as molded-case circuit breakers and self-protected “Type E” combination motor controllers.
Eaton corporation UL 489 and UL 1077 DIN Rail Miniature Circuit Breakers
www.comoso.com
41
Eaton Corporation
Electrical Sector
1111 Superior Avenue
Cleveland, OH 44114 USA
Eaton.com
© 2013 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. PG01101009E / Z13096
January 2013
Eaton is a registered trademark
of Eaton Corporation.
All other trademarks are property
of their respective owners.
www.comoso.com