Power Switching Centers General A metal-enclosed Power Switching Center incorporating load interrupter switches and power fuses has one single assembly rating. All major components such as switches, fuses, bus, and operating mechanism are coordinated electrically and mechanically, permitting economical high-voltage switching and protection. A key feature of this system is the “Building Block” approach to Power Switching Center design which allows almost unlimited application flexibility. This concept provides a simple solution to specific present and future requirements. Features: 쐍 Switch interrupter, 600A or 1200A continuous and load break capability, with 40 kA or 61 kA close and latch ratings. 쐍 4.16 kV or 13.8 kV nominal voltages, 60 kV and 95 kV BIL. 쐍 600A and 1200A main bus ratings. 쐍 Available with either current limiting fuses or expulsion fuses. 쐍 Indoor and outdoor construction. 쐍 Customer or Power Company metering units. 쐍 Electrical operation with automaticthrowover of two incoming sources. 쐍 Design that include potheads, roof bushings, special terminators and lightning arresters. CSI Section 16431 Siemens Electrical Products and Systems Specification Guide 69 5 Power Switching Centers Optional Features and Accessories 쐍 UL Listed Ratings 쐍 Shaft Connected Auxiliary Switches 쐍 Solenoid Instantaneous Open and / or Close 쐍 Manual Instantaneous Open and / or Close 쐍 Motor Operators to Close and Open 쐍 Spring Charged Indicator Switch 쐍 Operation Counter 쐍 Key Interlocks 쐍 Lightning Arresters 쐍 Weatherproofing 쐍 Special Terminations 쐍 Mechanical Interlocks to Grounding Switch 쐍 Grounding Blades 쐍 Automatic Transfer Systems 쐍 CT’s, PT’s, CPT’s — Drawout and Stationary 쐍 Instrumentation — Ammeter, Voltmeter, Watthour Meter, etc. 쐍 Anti-Single Phasing 쐍 Mimic Bus Power Switching Centers General A metal-enclosed Power Switching Center incorporating load interrupter switches and power fuses has one single assembly rating. All major components such as switches, fuses, bus, and operating mechanism are coordinated electrically and mechanically, permitting economical high-voltage switching and protection. A key feature of this system is the “Building Block” approach to Power Switching Center design which allows almost unlimited application flexibility. This concept provides a simple solution to specific present and future requirements. Features: 쐍 Switch interrupter, 600A or 1200A continuous and load break capability, with 40 kA or 61 kA close and latch ratings. 쐍 4.16 kV or 13.8 kV nominal voltages, 60 kV and 95 kV BIL. 쐍 600A and 1200A main bus ratings. 쐍 Available with either current limiting fuses or expulsion fuses. 쐍 Indoor and outdoor construction. 쐍 Customer or Power Company metering units. 쐍 Electrical operation with automaticthrowover of two incoming sources. 쐍 Design that include potheads, roof bushings, special terminators and lightning arresters. CSI Section 16431 Siemens Electrical Products and Systems Specification Guide 69 5 Power Switching Centers Optional Features and Accessories 쐍 UL Listed Ratings 쐍 Shaft Connected Auxiliary Switches 쐍 Solenoid Instantaneous Open and / or Close 쐍 Manual Instantaneous Open and / or Close 쐍 Motor Operators to Close and Open 쐍 Spring Charged Indicator Switch 쐍 Operation Counter 쐍 Key Interlocks 쐍 Lightning Arresters 쐍 Weatherproofing 쐍 Special Terminations 쐍 Mechanical Interlocks to Grounding Switch 쐍 Grounding Blades 쐍 Automatic Transfer Systems 쐍 CT’s, PT’s, CPT’s — Drawout and Stationary 쐍 Instrumentation — Ammeter, Voltmeter, Watthour Meter, etc. 쐍 Anti-Single Phasing 쐍 Mimic Bus Power Switching Centers Switch Components 햲 Stationary Contacts Hinge and jaw contacts are heavy castings capable of absorbing and dissipating the heat from the large short circuits which may be encountered. The contact pressure is maintained on these contacts with spring washers especially adapted to maintain suitable pressure. The retaining nuts prevent joint loosening due to vibration, shock, and operation. Special sealing designs effectively prevent the entrance of dust or dirt into the contact making area. The contact area maintains optimum current carrying ability and decreases heating. 햳 Arcing Chambers Stationary arcing contacts are located inside the arc chutes. They remain at the same potential as the main stationary contact. As the quick break blade is withdrawn from the arc chute, it parts with the stationary arcing contacts inside the chute. The chute is made from a specially prepared compound that evolves a gas to quickly extinguish the arc. 햴 Switch Insulators The insulating support for the main hinge and jaw contacts has excellent dielectric characteristics, is nontracking, non-combustible, nonhygroscopic, won’t age, and is easy to clean. 햵 Stored Energy Mechanism The opening and closing springs provide for quick make (rated fault closing) and quick break (rated load interruption). The switch mechanism shaft is driven by a chain and sprocket from the front operating handle. As the handle is rotated, it is directly connected to a sprocket which in turn chain drives the opening spring to a “charged” position. As the operator continues to rotate the handle, the charged spring is General driven off-center by the chain and releases its energy into rotating the operating shaft to operate. The switch blades will not move, in either a closing or opening direction, until the closing spring causes rotation in the operating shaft. Antifriction bearings provide for a smooth operating performance. The handle housing has provisions for multiple padlocking. The handles are non-removable, self-latching and padlockable in the open or closed positions. “Telltale” indicators show the switch position. 햶 Structure Welded frame design provides greater structural strength. 햷 Quick Break Blade The quick-break arcing blade is made of a special high-strength, high-conductivity material tipped with a tungsten arcing material. A quick-break spring charging mechanism is mounted on the blade that with an assist from the arcing chamber stationary contacts, prevents the opening until after the main contact gap is at the proper clearance spacing. Arcing blades and tips are designed to prevent arcing blades from hanging up in the stationary arcing contacts. 햸 Main Moveable Blades These blades are made of hard drawn copper bars, silver-plated at the contact points for long dependable operation. Power Switching Centers 5 70 Siemens Electrical Products and Systems Specification Guide CSI Section 16431 Power Switching Centers Ratings Table 5.1 Technical Indoor Air Interrupter Switch Ratings Voltage Ratings햲 햳 Nominal kV, RMS 햲 햳 Current Ratings햲 햳 Maximum Design kV, RMS 1-Min. Power Frequency Withstand kV, RMS 1.2 × 50 Impulse Withstand kV, BIL 4.16 4.76 19 60 7.2 8.25 26 75 13.8 15.0 36 95 14.4 15.5 50 110 23.0 25.8 60 125 34.5 38.0 80 150 34.5 38.0 95 200 Continuous Amperes RMS 600 1200 600 1200 600 1200 600 1200 600 1200 600 1200 600 1200 Load Interrupt Amperes RMS 600 1200 600 1200 600 1200 600 1200 Short-Time Ratings Momentary Asymmetrical kA, RMS 40 61 40 61 40 61 40 61 2-Sec kA, RMS 25 38 25 38 25 38 25 38 FaultClose Asymmetrical kA, RMS 40 61 40 61 40 61 40 61 600 40 25 40 600 40 25 40 600 40 25 40 Ratings apply to Stored Energy Operated Switches. Special ratings available — consult Siemens. UL and MET listings for specific application — consult Siemens. Table 5.2 Power Fuses Max Design KV System KV Interrupting Ratings RMS Symmetrical Amperes Maximum Continuous Current Nom. Equiv. 3Ø-MVA햲 Single Barrel Double Barrel Triple Barrel 200E 200E 200E 125E 125E 125E 125E 125E 125E 125E 125E 400E 400E 400E 250E 250E 250E 250E 250E 250E 250E 250E — — — — — — — — — — — — — — — 600E 750E — — — — — — — — Current Limiting Fuse 5.5 15.5 5.5 15.5 2.4 4.16 4.8 6.9 7.2 11.5 12.0 12.47 13.2 13.8 14.4 2.4 4.16 4.8 4.8 4.8 4.8 6.9 7.2 11.5 12.0 12.47 13.2 13.8 14.4 50,000 50,000 50,000 40,000 40,000 40,000 40,000 40,000 40,000 40,000 40,000 60,000 60,000 60,000 60,000 50,000 50,000 50,000 50,000 40,000 40,000 40,000 40,000 40,000 40,000 208 360 416 480 500 800 830 860 910 955 1000 250 430 500 500 500 500 596 620 800 830 860 910 955 1000 10E through 150E — — — 10E through 100E 175E through 450E — — — — 125E through 200E Expulsion Fuse — S & C Type SM or Westinghouse Type RBA 15.5 17 17,200 37,500 14,000 12,500 25,000 34,000 125 270 335 300 600 815 200E 400E 200E 200E 400E 400E — 720E햳 — — — — — — — — — — 5 Power Switching Centers 15.5 4.8 4.4 14.4 14.4 14.4 13.8 The 3 phase MVA = 1.73 × (kV) × (fuse interrupting kA) 햳 Double Barrel Fuse. Consult Siemens for dimensions. 햲 CSI Section 16431 Siemens Electrical Products and Systems Specification Guide 71 Power Switching Centers Non-UL / ANSI Standards The following figures depict the basic standard units available. For most applications, 42 in. (1067 mm) deep front accessible units will be adequate. The Dimensions 58 in. (1473 mm) deep front and rear accessible unit will be required for the following conditions: 쐍 Upfeed with main bus at top 쐍 쐍 Downfeed with pothead cable terminations Both current and potential transformers in a switch unit 42 Inch (1067 mm) Deep Units (Front Accessible)햲 Downfeed 5kV and 15kV Figure 1 Entrance Unit No Switch햳 Figure 4 Feeder Unit Unfused Switch Figure 3 Entrance Unit Fused Switch햴 Figure 2 Entrance Unit Unfused Switch Figure 5 Feeder Unit Fused Switch 42 Inch (1067 mm) Deep Units (Front Accessible)햲 Upfeed 5kV and 15kV Figure 6 Entrance Unit No Switch햳 Figure 8 Entrance Unit Fused Switch Figure 7 Entrance Unit Unfused Switch Figure 9 Feeder Unit Unfused Switch햵 Figure 10 Feeder Unit Fused Switch햴 햵 햲 42 Inch (1067 mm) Deep Units (Front Accessible) Tie and Metering 5kV and 15kV Figure 11 Tie unit Unfused Switch Figure 12 Tie unit No Switch Figure 13 Metering Unit햶 Figure 14 Transition to Motor Control or Metal-Clad Switchgear햷 58 Inch (1473 mm) Deep Units (Front and Rear Accessible)햸 Miscellanous 5kv and 15kv Figure 15 Feeder Unit-Upfeed햸 Unfused Switch Power Switching Centers 5 햲 Figure 16 Feeder Unit-Upfeed햸 Fused Switch Switch units can be furnished with up to 3 current transformers or 2 potential transformers and 3 distribution class surge arresters. Contact Siemens for dimensional information. 햳 If cable terminations are potheads, a 58 in. (1473 mm) deep unit is required with rear access to the potheads. 햴 Current limiting fuses only. 72 Figure 18 Cable-In-Out Unit Fused Switch Figure 17 Cable-In-Out Unit Unfused Switch 햵 A feeder unit with upfeed cable can be finished in a 42 in. (1067 mm) deep unit with the main bus at the bottom (See Figures 9 and 10). This results in an Inverted Switch (Figure 9) or Inverted Fuse Switch (Figure 10) that may not be desirable. In such a case, the configuration of Figures 15 or 16 can be furnished. 햶 For power company meter unit, width will be as needed to comply with power company requirments. Siemens Electrical Products and Systems Specification Guide 햷 Bus position to match location in motor control or switchgear. 58 in. (1473 mm) deep units required only when Figure 9 or Figure 10 are not desired. Note: For equipment that must be UL labeled, enclosures must be minimum 44 in. (1117 mm) deep and 60 in. (1524 mm) deep versus 42 in. (1067 mm) deep and 58 in. (1473 mm) deep. 햸 CSI Section 16431 Power Switching Centers UL and ANSI Units Dimensions Figures on this page depict the basic and standard units available. For most applications, 44 in. (1118 mm) deep front accessible units will be adequate. The 60 (1524 mm) deep front and rear accessible units will be required for the following conditions: 쐍 Upfeed with the main bus at the top 쐍 Downfeed with the main bus at the bottom 쐍 Downfeed with Pothead cable terminations 쐍 Both current and potential transformers in a switch unit 햷 44 Inch (1118 mm) Deep Entrance and Feeder Units 5kV and 15kV 90 in. (2886 mm) 44 in. 36 in. (1118 mm) (914 mm) Entrance Unit No Switch Downfeed햲 Entrance Unit Unfused Switch Downfeed햲 Tie Unit Unfused Switch 햲 햳 햴 햵 햶 햷 Entrance Unit Fused Switch Upfeed햳 햴햶 16 in. (406 mm) Transition Unit No Switch Feeder Unit Unfused Switch Downfeed햲 Metering Unit 햵 Feeder Unit Fused Switch Downfeed햳 햴햶 Entrance Metering Unit Invert for Upfeed. Invert for Downfeed. Inverted Unit only available with current limiting fuses. An Inverted Fused Switch may not be desirable. For power company meter unit, width will be as needed to comply with power company requirements. Refer details to Siemens for review. Unfused switch section available. All sections designed for use with Eye Bolt Lugs. Consult Siemens for other termination requirements. Note: For equipment that must be UL labeled, enclosures must be minimum 44 in. (1117 mm) deep and 60 in. (1524 mm) deep versus non UL labeled equipment 42 in. (1067 mm) deep and 58 in. (1473 mm) deep. 5 Power Switching Centers CSI Section 16431 Siemens Electrical Products and Systems Specification Guide 73 Power Switching Centers Guide Form Specifications General These specifications describe metalenclosed load interrupter switchgear assemblies consisting of fused and / or unfused load interrupter switches and auxiliary devices as shown on drawing no. _____________ and as described herein. Ratings The load interrupter switchgear will be nominally rated (4.16kV nominal, 4.76kV maximum, 60kV BIL) (13.8kV nominal, 15kV maximum, 95kV BIL). The equipment will be designed to withstand and protect against the effects of a fault condition of ______MVA at ________kV. Load interrupter switches shall be: Manual operated “close” and “open” in Units___________. Motor operated spring charging mechanism with latch and electrical release for “close” and “open” in Units_________. Switches shall be (600) (1200) ampere continuous in Units ____ and (600), (1200) in Units ______. Momentary and fault close rating shall be (40,000) (61,000) amperes. Fused switch continuous, fault close and interrupting ratings shall be dependent upon the specified fuse characteristics. Main bus rating shall be (600) (1200) amperes. Power Switching Centers 5 Enclosure Construction The load interrupter switchgear shall be (indoor) (outdoor) construction. Units shall be of individual frames of bolted steel construction. Full side sheets shall separate adjacent units. Each frame shall be adequately braced and vented to function properly under both normal operating and short circuit conditions. For non-UL, access to switch or switch / fuse compartments will be through single front door. The door shall be Kirk Key interlocked with the switch mechanism so that the switch must be in the open position before the door can be opened. Conversely, the door must be closed and locked and the key returned to the switch before the switch can be closed. Also included is a provision for padlocking. An inner plexiglass barrier in front of each switch is to be provided to prevent inadvertent access to the switch when changing fuses. For UL Listed, access to switch and / or fuse compartments will be through separate doors. The doors shall be mechanically interlocked with the air interrupter switch to prevent closing the switch with the door open and to prevent opening the door with switch closed. Kirk Key type interlock is an optional feature. Also included is a provision for padlocking. 74 Protective hinged screen steel barriers, retained with captive thumb screws, shall be provided to prevent inadvertent access to the switch when changing fuses. Where access to the rear is required, easily removable panels with handles shall be provided. An ample size safety window shall be provided in the door of each switch unit to allow observance of the position of the switch blades. Where meters and instruments are provided, they shall be isolated from any high voltage equipment by a grounded steel barrier. All external surfaces shall be cleaned, treated, and painted with a corrosionresistant paint. Color will be ANSI No. 61 light gray. Danger and / or Warning labels shall be attached to the switchgear in accordance with industry standard and OSHA requirements. Load interrupter switchgear assemblies shall be tested at the factory in accordance with NEMA and ANSI standards prior to shipment. The equipment will be shipped in sections as required to meet manufacturing and shipping restrictions. The sections will be constructed to permit lifting, rolling, or jacking in the field. Load Interrupter Switches Load interrupter switches shall be threepole, gang-operated stored energy type quick-make, quick-break operation. Incoming and feeder switches are to be arranged with hinged end of the switch blade “dead” in the open position. Fuses, when specified, will be located on hinged side of the switch. Switch handles shall be non-removable and located on front of the unit. The interrupter switch is to have separate main and arcing contacts to provide maximum endurance for fault close and load interrupting duty. The arcing contacts shall be spring loaded so that on opening they break after the main contacts, and on closing make after the main contacts. Arc interruption is to take place in an interruption chute. Fuses Fuses can be either current limiting or expulsion type. Current limiting is preferred because let-through current is limited and no expulsion of gases occur on interruption. Depending on choice, specify one of the following: Siemens Electrical Products and Systems Specification Guide Specifications Current Limiting Fuses: Fuses shall be of the fast replaceable current limiting type which will operate without explosive noise, expulsion of gas vapor, or foreign matter from the tube. The fuses shall be coordinated to meet the short circuit rating and continuous current ratings specified. Each fuse shall have an indicator to show if it has blown. Fuse contact shall be retained by a high-pressure locking device to prevent slip-out or blow-out during operation. Expulsion Fuses: Fuses shall be the expulsion type. The gases emitted on interruption shall be controlled and silenced by chambers designed for that purpose. They shall have an rms symmetrical interrupting rating of________ amperes at the operating voltage ____. Each fuse shall have an indicator to show it has blown. Fuses shall be furnished in a disconnect type mounting for ease in removal. Fuses shall be renewed using replacement fuse units, Fuses shall be S&C type SM or Westinghouse type RBA. Main and Ground Bus For non-UL, the main and ground bus will be bare tin-plated aluminum with a continuous and momentary rating as specified above. The main bus will be mounted on stand-off insulators. The ground bus shall have a short circuit rating equal to that of the integrated assembly and shall extend the full length of the switchgear line-up. For UL Listed, the three-phase copper bare main bus shall have continuous rating of 600, 1200, or 2000 amperes and shall be braced to withstand the full effect of a short circuit within the ratings of the interrupter switch and / or fuses applied to the equipment. All bus bar joints shall be plated silver on copper bus. Supports for the main bus shall be porcelain above 5kV. Each unit shall also contain a copper ground bus, accessible for connection to ground. Both ground bus and main bus shall have provisions for extension in either direction for future additions. Where bus bars are insulated for reliability or to allow closer spacing, insulation shall be extruded sleeving. Where joints are made, they shall be sealed with molded covers, or a void-free filler covered with suitable layers of insulation tape and mechanic protective tape. Optional Features Furnish optional features per page 69 for basic list of options. CSI Section 16431