1 2 3 4 5 6 7 8 9 10 ELECTRICAL SYMBOL SCHEDULE SYMBOL DESCRIPTION SYMBOL GENERAL ELECTRICAL SYMBOLS A. A ALL MOUNTING HEIGHTS INDICATED ARE FROM THE FINISH FLOOR TO THE CENTER OF THE BOX. C. ITEMS SHOWN DOTTED ARE TO BE REMOVED, ITEMS SHOWN WITH A LIGHT SCREENED LINE ARE EXISTING TO REMAIN. D. MN MOUNTING HEIGHT DESCRIPTION SYMBOL LIGHTING DEVICES SHALL BE MOUNTD AT THE HEIGHT INDICATED, UNLESS NOTED OTHERWISE. DEVICES MOUNTED IN BLOCK/BRICK WALLS SHALL CORRESPOND WITH BLOCK/BRICK COURSING. SEE MASONRY BACKBOX MOUNTING HEIGHT DETAIL. B. DESCRIPTION MOUNTING HEIGHT SYMBOL SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE (TYPE DENOTED) 46" MS MOTOR RATED SWITCH. 46" 'DEMOLITION' EXAMPLES: FLUORESCENT STRIP LIGHTING FIXTURE; FOR SUSPENDED MOUNTING HEIGHTS, SEE DRAWINGS. MOTOR STARTER SWITCH WITH MOTOR RUNNING PROTECTION (ADD RELAY IF CONTROL CONTACTS ARE REQUIRED). 46" DISCONNECT SWITCH - NON FUSED. 6'-0" DISCONNECT SWITCH - FUSED. 6'-0" MOTOR STARTER. 6'-0" COMBINATION STARTER/DISCONNECT SWITCH. 6'-0" T THERMOSTAT - WALL MOUNTED. PUSHBUTTON - SINGLE BUTTON, WALL MOUNTED. WALL MOUNTED LIGHTING FIXTURE; SEE REFLECTED CEILING PLAN FOR MOUNTING HEIGHT. B R LINEAR PENDANT LIGHTING FIXTURE; FOR SUSPENDED MOUNTING HEIGHTS, SEE DRAWINGS. ON NEW WORK LIGHTING, POWER AND SYSTEMS DRAWINGS, SCREENED ELECTRICAL ITEMS DENOTES EXISTING ITEMS TO REMAIN; SOLID ELECTRICAL ITEMS DENOTES NEW ITEMS, UNLESS NOTED OTHERWISE SYSTEMS CABLE DISTRIBUTION CABINET AS INDICATED AND SPECIFIED (FLUSH OR SURFACE AS INDICATED); VERIFY MOUNTING. DATA SYSTEMS CABLE DISTRIBUTION CABINET AS INDICATED AND SPECIFIED (FLOOR OR WALL AS INDICATED). PP AHU EXIT LIGHT-FACE SHOWN SHADED; PLAN INDICATES CEILING OR WALL MOUNTING AND DIRECTIONAL ARROWS. 30" - 36" F F PAGING/INTERCOM SPEAKER HORN ASSEMBLY- P.A. OR AS INDICATED (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). MOUNT 12" BELOW CEILING OR AS INDICATED. S F POWER POLE (DEVICES AS INDICATED) LOUD SPEAKER HORN ASSEMBLY- PA OR SOUND SYSTEM AS INDICATED; VERIFY MOUNTING HEIGHT. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). S MOTOR NUMBER; REFER TO MOTOR SCHEDULE S S V CONTACTOR (ENCLOSURE MOUNTED) (RATING, POLES AND MOUNTING AS INDICATED) M POKE-THRU'S, FLOOR BOXES, & FURNITURE CONNECTIONS POLE MOUNTED SITE LIGHTING FIXTURE - SINGLE SQUARE HEAD. # OF HEADS AS SHOWN. A POKE-THROUGH, FULLY RECESSED IN FLOOR. REFER TO FLOOR PLAN DRAWING FOR NUMBER OF RECEPTACLES AND VOICE AND DATA CABLES/DEVIVES. SWITCHBOARD WITH CONCRETE PAD: FLOOR MOUNTED. RELAY/CONNECTION CABINET; WALL MOUNTED, WITH TOP 6'-0". LIGHTING CONTROL PANELBOARD; WALL MOUNTED WITH TOP 6'-0". PL AUTOMATIC TRANSFER SWITCH; WALL OR FLOOR MOUNTED. ATS TRANSFORMER, WITH SIZE AS NOTED. SEE RISER DIAGRAM, SCHEDULE OR FLOOR PLANS; VERIFY. T PB 3 PULLBOX HH SINGLE POLE LIGHT SWITCH WITH LIGHTED PILOT LIGHT 46" SINGLE POLE LIGHT SWITCH 46" #V J #D OCCUPANCY SENSOR SWITCH 46" MOTOR CONTROL CENTER (W/CONCRETE PAD); FLOOR MOUNTED. K KEYED LIGHT SWITCH (POLES AS INDICATED) 46" PLUG-IN BUS DUCT SWITCH; SIZE AS INDICATED AND SPECIFIED. VERIFY MOUNTING HEIGHT. MC MOMENTARY CONTACT LIGHT SWITCH 46" D DIMMER LIGHT SWITCH 46" TS TIME-SWITCH 46" D M METER/SOCKET ASSEMBLY; MOUNT TOP AT 6'-0". LS L OS L OS BRANCH CIRCUIT, FEEDER, RACEWAY LL-1 2,4 PANELBOARD NAME - FLOOR BOX, FULLY RECESSED IN FLOOR. REFER TO FLOOR PLAN DRAWING FOR NUMBER OF RECEPTACLES AND VOICE AND DATA CABLES/DEVICES. SYSTEMS WALL BOX: #D INDICATES NO. OF DATA CABLES; #V INDICATES NO. OF VOICE CABLES. FLEXIBLE CONDUIT WHIP, CABLES AND DEVICES PROVIDED IN ELECTRIFIED FURNITURE BY LOW-VOLTAGE CONTRACTOR. PHOTOCELL - WALL, CEILING, OR ROOF MOUNTED; SEE DRAWINGS. 90" 84" OCCUPANCY DETECTOR - WALL OR CEILING CEILING MOUNT #D,#V BRANCH CIRCUITS (IN THE PANELBOARD) ARROW INDICATES HOMERUN CIRCUIT NUMBER, TYPICAL W 18" DUPLEX RECEPTACLE # RECEPTACLE (SINGLE) 18" E 18" DOUBLE DUPLEX RECEPTACLE (QUAD) INDICATES CONDUIT IS SURFACE MOUNTED # 90" (1) HIGH MOUNTED DUPLEX RECEPTACLE H (1) HIGH MOUNTED DUPLEX RECEPTACLE AND (1) LOW MOUNTED DUPLEX RECEPTACLE H/L 90"/18" IC INDICATES CONDUIT UP INDICATES CONDUIT DOWN DUPLEX RECEPTACLE W/ GROUND FAULT CIRCUIT INTERRUPTER (GFI) GFI POWER WALL BOX: # INDICATES NUMBER OF POWER CIRCUIT(S). POWER WHIP SUPPLIED BY FURNITURE VENDOR, INSTALLED BY ELECTRICAL CONTRACTOR. SPECIAL PURPOSE OUTLET; WALL OR RECESSED CEILING MOUNTED DATA OUTLET: (1"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). # INDICATES NUMBER OF DEVICES AND CABLES TO BE PROVIDED. IF NO NUMBERS ARE INDICATED, PROVIDE ONE. DATA AND VOICE OVER IP (VoIP) OUTLET: (1"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). #D,#V INDICATES NUMBER OF DEVICES AND CABLES TO BE PROVIDED. #D REPRESENTS DATA; #V REPRESENTS VOICE. IF NO NUMBERS ARE INDICATED, PROVIDE ONE OF EACH. 1"C,3#4,1#3G F WALL VoIP OUTLET (TELEPHONE): (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). PROVIDE ONE CABLE AND DEVICE UNLESS OTHERWISE NOTED. VOICE OVER IP (VoIP) OUTLET: (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). # INDICATES NUMBER OF DEVICES AND CABLES TO BE PROVIDED. IF NO NUMBERS ARE INDICATED, PROVIDE ONE. VOICE OUTLET, INTERCOM ONLY: (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). PROVIDE ONE CABLE AND DEVICE UNLESS OTHERWISE NOTED. D F MAGNETIC DOOR HOLD-OPEN (WALL MOUNTED); MOUNT PER DWGS. FL F SPRINKLER FLOW-SWITCH; MOUNT PER DWGS. TS F SPRINKLER TAMPER-SWITCH; MOUNT PER DWGS. 18" F S SMOKE DETECTOR-CEILING MOUNTED. AUXILIARY INPUT CONNECTOR. (1/2"C. BUSHED EMT TO ACCESSIBLE CEILING). 18" F H HEAT DETECTOR (RATE-OF-RISE) - CEILING MOUNTED. 136° F H HEAT DETECTOR (FIXED TEMPERATURE)- CEILING MOUNTED. F DUCT SMOKE DETECTOR; MOUNT PER DWGS. J INDICATES 1" CONDUIT, (3) NO. 4 AWG CONDUCTORS AND (1) NO. 3 GROUND WIRE J J. CALL BACK SWITCH. (1/2"C. BUSHED EMT TO ACCESSIBLE CEILING). 46" CM F 18" CS F CHLORINE GAS SENSOR; CEILING MOUNTED. N. O. P. GS F GAS SHUT-OFF; MOUNT PER DWGS. Q. F/S F FIRE/SMOKE DAMPER; MOUNT PER DWGS. (1) TV/VIDEO OUTLET MOUNTED HIGH AND (1) TV/VIDEO OUTLET MOUNTED LOW. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). SD 18" L. M. FIRE ALARM CONTROL MODULE; MOUNT PER DWGS. R. 18" 18" WIRELESS ACCESS POINT (DATA OUTLET): (1"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). PROVIDE ONE CABLE AND DEVICE, UNLESS OTHERWISE NOTED. MOUNT HIGH ON WALL OR ON CEILING AS INDICATED ON DWG. JUNCTION BOX WITH REQUIRED COVERPLATE - WALL OR CEILING MOUNT - PLAN INDICATES MOUNTING AND FUNCTION 18" 21000 141ST Avenue Rogers, Minnesota 55374 INDEPENDENT SCHOOL DISTRIC #728 815 HIGHWAY 10 ELK RIVER, MINNESOTA 55330 46" 20A CIRCUIT CONDUCTORS SHALL BE SIZED AS FOLLOWS 90"/18" DISTRIBUTION PANEL TV/VIDEO CAMERA, CLOSED CIRCUIT. (WALL OR CEILING MOUNTED, 3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). TV TV C CLOCK OUTLET. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). 90" B BELL/AUDIBLE DEVICE. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). 90" 120V CCT LENGTH 277V CCT LENGTH AWG < 75' < 75' 12 75' - 120' 75' - 280' 10 120' - 200' 280' - 450' 8 > 200' > 450' 6 PANEL 18" UPS OR INVERTER UPS SECURITY DEVICES ## S SECURITY DEVICE. ## INDICATES THE FOLLOWING: CM DC EL ES GB IR ML XP XS 48" 18" 18" DR S STANDARD BACKBOX MOUNTING HEIGHTS CONTROL MODULE DOOR CONTACTS (MONITORING) ELECTRIC LOCK ELECTRIC STRIKE GLASS BREAK DETECTOR INFARED DETECTOR MAGNETIC LOCK EXIT PUSHBUTTON, MOUNT AT ADA HT EXIT SENSOR CARD READER ROUGH-IN AT ADA HEIGHT N E TRANSFER SWITCH L 100" DRAW-OUT CIRCUIT BREAKER 92" 54" 46" CIRCUIT BREAKER 86" 3 KP S KEYPAD; VERIFY MOUNTING HEIGHT WITH DWGS. LA S LOCAL ALARM 46" MC S MASTER CONTROL STATION 46" MD S MD S GENERATOR GEN 60" 62" 64" 52" 46" 5 36" 12" 4 18" 46" 56" 2 54" 2 2 7 44" 46" 48" 38" 40" 30" 32" 22" 14" 1 6" 24" 6 20" 18" 1 1 36" 29" 16" 8" FINISHED FLOOR GENERAL NOTES: A. SWITCH NUMBER NOTES: MOTION DETECTOR; ARROW INDICATES DIRECTION. (WALL OR CEILING MOUNTED). 1. 2. FUSE SECURITY CAMERA, CLOSED CIRCUIT. (WALL OR CEILING MOUNTED, 3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). ELECTRICAL ABBREVIATIONS LIST 80" 3 72" FUSED SWITCH PHOTO-ELECTRIC TRANSMITTER; MOUNT PER DWGS. S 88" 70" 4" PHOTO-ELECTRIC RECEIVER; MOUNT PER DWGS. T P 3 68" 20" 46" 88" 78" 28" 18" 90" 76" 44" ELECTRIC EYE; MOUNT PER DWGS. 96" 94" 90" 84" TRANSFORMER DOOR RELEASE; MOUNT PER DWGS. S C e n t r a l: \ \ W a e - s r v - m n \ S t P a u l\ I S D 7 2 8 \ H S - R o g e r s \ 1 4 2 0 8 2 T h ir d W in g A d d it io n \ 0 6 _ E L E C \ R e v it 2 0 1 4 \ 1 4 2 0 8 2 _ E L E C ( C e n t r a l) .r v t 3 / 1 8 / 2 0 1 5 1 2 :5 4 :1 9 A M 46" TV H/L SURFACE RACEWAY ASSEMBLY. REFER TO ARCHITECTURAL AND ELECTRICAL PLANS FOR MOUNTING HEIGHT. PROVIDE AS SPECIFIED, UNLESS NOTED OTHERWISE. C:\_Revit_Project_Files\142082_ELEC (Central)_oabdi.rvt K. INSTALL CONCEALED CONDUIT WITH FLUSH J.B.'S IN WALLS AND CEILINGS UNLESS NOTED OTHERWISE. IN FINISHED AREAS WITH INACCESSIBLE WALLS OR CEILINGS, PROVIDE SURFACE (WIREMOLD) RACEWAY; PAINT TO MATCH COLOR OF ADJACENT WALL OR CEILING. RACEWAYS SHALL CONTAIN A GROUNDING CONDUCTOR. CIRCUITS SUPPLYING LINE TO NEUTRAL LOADS SHALL HAVE DEDICATED NEUTRALS, i.e. ONE NEUTRAL PER PHASE. NEUTRAL CONDUCTORS SHALL HAVE TRACER STRIPE ALONG ENTIRE LENGTH INDICATING ASSOCIATED PHASE. BUILDING CONDUCTORS SHALL BE THWN/THHN. CONDUCTORS IN UNDERGROUND CONDUIT OUTSIDE OF BUILDINGS SHALL BE XHHW. NUMBERS AT RECEPTACLES AND LUMINAIRES CORRESPOND DIRECTLY WITH PANELBOARD CIRCUIT NUMBERS AS SCHEDULED. BRANCH CIRCUIT WIRING AND HOMERUNS ARE NOT SHOWN FOR CLARITY. ACCURATE RECORD DRAWING INFORMATION IS TO BE PROVIDED AT THE PROJECT COMPLETION. TYPICAL THROUGHOUT. REFER TO SPECIFICATIONS FOR MATERIALS AND INSTALLATION REQUIREMENTS. REFER TO CONTRACT DOCUMENTS FOR SEQUENCE OF CONSTRUCTION AND PHASING OF THE CONTRACT. SWITCHES SHALL BE MOUNTED PER ADA REQUIREMENTS, 40" AFF. UNLESS OTHERWISE NOTED, RECEPTACLES AND TELECOMMUNICATION OUTLETS IN FINISHED AREAS SHALL BE MOUNTED 18" AFF. RECEPTACLES IN UN-FINISHED SPACES SHALL BE MOUNTED AT 48" OR 4" ABOVE WORK SURFACE. COORDINATE RECEPTACLE MOUNTING HEIGHTS WITH MILLWORK LOCATIONS, ARCHITECTURAL ELEVATIONS, AND MASONRY COURSING. CRITICAL DEVICES / EQUIPMENT, INCLUDING TELEPHONE, COMPUTER, SECURITY, AND FIRE ALARM, AFFECT ASSOCIATED SYSTEMS BUILDING-WIDE. THESE SYSTEMS MUST REMAIN OPERATIONAL DURING THE CONSTRUCTION. INDIVIDUAL DEVICES MAY BE DISCONNECTED AND/OR RECONNECTED DURING CONSTRUCTION. COORDINATE POWER OUTAGES WITH OWNER. PROVIDE TEMPORARY PANEL(S) AND/OR CIRCUIT(S) AS/IF NECESSARY TO MAINTAIN CONTINUITY. PROTECT FROM PHYSICAL AND DUST DAMAGE. THE BUILDING SHALL MAINTAIN POWER THROUGHOUT THE CONSTRUCTION PROCESS. COORDINATE ENERGIZATION OF NEW EQUIPMENT AND THE CORRESPONDING RECONNECTION OF EXISTING AFFECTED ELECTRICAL DISTRIBUTION EQUIPMENT. SEE RELATED PLUMBING AND HVAC DRAWINGS FOR LOCATION OF EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS. COORDINATE INTERCONNECTION REQUIREMENTS WITH EQUIPMENT SHOP DRAWINGS. WIRING FOR MISCELLANEOUS HVAC DEVICES AND CONTROLLERS SUCH AS DAMPER MOTORS, THERMOSTATS, DUCT SMOKE DETECTORS, FREEZESTATS, DIFFERENTIAL PRESSURE SWITCHES, OCCUPIED AND UNOCCUPIED SELECTOR SWITCHES, ALARM LIGHTS, ETC., NOT SHOWN ON ELECTRICAL DRAWINGS IS DIVISION 23 WORK. FIELD VERIFY EXISTING CONDITIONS. DISCREPANCIES BETWEEN THE DRAWING AND ACTUAL FIELD CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO BIDS. MAINTAIN EXISTING CIRCUIT CONTINUITY ON ALL SYSTEMS ON THE SITE THAT ARE EXISTING TO REMAIN. PROVIDE ALL CONDUIT HOMERUNS AS 3/4"C. MIN. COORDINATE ALL WORK WITH OTHER CONTRACTORS AND OWNER. ALL CUTTING AND PATCHING FOR DIV. 26 WORK SHALL BE UNDER SUPERVISION AND APPROVAL OF ARCHITECT. REMOVE AND/OR REINSTALL ELECTRICAL DEVICES IN ALL AREAS OF WORK AS REQUIRED AND REPLACE ANY ELECTRICAL DEVICES DAMAGED BY WORK. NOT ALL DEVICES MAY BE SHOWN ON DRAWINGS. PROVIDE ALL BOXES, FITTINGS, CONDUIT, WIRING, TERMINATIONS, EQUIPMENT, ETC, FOR A COMPLETE INSTALLATION. ROGERS HIGH SCHOOL THIRD WING ADDITION ONE LINE SYMBOLS R P 3. 4. 5. 6. 7. MOUNTING HEIGHT OF STANDARD BACKBOXES ONLY. REFER TO DRAWINGS AND DETAILS FOR MOUNTING HEIGHT OF OTHER BACKBOXES. MOUNTING HEIGHT FOR BACKBOXES MOUNT LOW IN WALL. MOUNTING HEIGHT FOR BACKBOXES MOUNTED NEAR MIDDLE OF WALL, INCLUDING DEVICES SUCH AS TOGGLE SWITCHES. MOUNTING HEIGHT FOR BACKBOXES MOUNTED HIGH IN WALL. STANDARD COUNTER TOP. STANDARD COUNTER TOP BACK SPLASH HEIGHT. STANDARD DESK TOP. STANDARD DESK TOP BACK SPLASH HEIGHT. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed PROFESSIONAL ENGINEER MINNESOTA under the laws of the State of BRADLEY R. JOHANNSEN Date 3/16/2015 43936 Registration Number ELECTRICAL SYMBOL NOTES Revisions 1P A AC G ACLG ADO AFF AFG AFI AHU AL ALT AMP AMPL ANNUN APPROX AQ-STAT ARCH ATS AUTO AUX AV AWG BATT BD BLDG BMS E I. VOLUME CONTROL. (1/2"C. BUSHED EMT TO ACCESSIBLE CEILING). TV/VIDEO OUTLET MOUNTED HIGH. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). EE S RECESSED CEILING MOUNTED DUPLEX RECEPTACLE W/ ADDITIONAL 10' FLEX CONDUIT SLACK (COILED) WITH GROUND WIRE; FOR FUTURE DEVICE RELOCATION. CABLE TRAY 90" 18" 18" A CONDUIT STUB - TERMINATION INDICATED BY NOTE FIRE ALARM BELL (WP FOR EXTERIOR MOUNTING). MICROPHONE OUTLET ( WALL OR CEILLING). (1/2"C. BUSHED EMT TO ACCESSIBLE CEILING). TV H CR S INDICATES CONDUIT ROUTED CONCEALED ABOVE FLOOR OR GRADE (IN CEILING OR WALL) 84" 90" TV/VIDEO OUTLET MOUNTED LOW. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING) TV L POWER AND MOTOR DEVICES INDICATES CONDUIT ROUTED BELOW OR IN FLOOR STRUCTURE OR BELOW GRADE OR AS NOTED. FIRE ALARM HORN/STROBE (COMBINATION) - 75Cd, U.N.O. (WALL OR CEILING MOUNTED). SPEAKER WITH BACKBOX (WALL OR CEILING); VERIFY MOUNTING HEIGHT. PA = SPEAKER FOR P.A. SYSTEM; V = WITH INTEGRAL VOLUME CONTROL KNOB. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). PROJECTOR OUTLET (WALL OR CEILING). P 18" VOICE AND DATA DEVICES # LS F. 46" J # MCC V P 46" FOUR-WAY LIGHT SWITCH OS HANDHOLE J THREE-WAY LIGHT SWITCH 4 84" H. H C 84" FIREMAN PHONE JACK; MOUNT TOP 54" AFF PLUS OR MINUS 2". F M EMERGENCY LIGHTING UNIT - TWO HEAD MOUNTING AS INDICATED ON DRAWINGS. POWER DISTRIBUTION AND EQUIPMENT E. 60" OR 62" MOTOR NAME; REFER TO MOTOR SCHEDULE (AHU-#) C FEEDER OR EQUIPMENT DRAWING NOTE. # FIRE ALARM STROBE (VISUAL) DEVICE - 75 Cd, U.N.O. (WALL OR CEILING MOUNTED). F MOTOR: # CIRCULAR PENDANT LIGHT FIXTURE; FOR SUSPENDED MOUNTING HEIGHTS, SEE DRAWINGS. KEYED NOTE F RELAY - VERIFY MOUNTING HEIGHT; SEE DRAWINGS. TRACK LIGHTING FIXTURE; LENGTH AND MOUNTING AS NOTED ON DRAWINGS. # FIRE ALARM HORN (AUDIBLE), WALL MOUNTED. F TV D. FIRE ALARM MANUAL PULL STATION; MOUNT TOP 46" AFF PLUS OR MINUS 2". F TELEPHONE TERMINAL CABINET; VERIFY MOUNTING. F E. B. C. G. SURFACE MOUNTED LIGHT FIXTURE (TYPE DENOTED) 'EXISTING TO REMAIN' EXAMPLES: A. FIRE ALARM CONTROL PANEL (MASTER); MOUNT TOP 62" AFF PLUS OR MINUS 2". EQUIPMENT RACK: ABBREVIATION FOR SYSTEM SERVED AND SPECIFIED; VERIFY MOUNTING. EQ RECESSED LIGHT FIXTURE (TYPE DENOTED) F MOUNTING HEIGHT FIRE ALARM DEVICES LOCAL DISTRIBUTED SOUND SYSTEM WALL OR FLOOR AMPLIFIER ASSEMBLY; VERIFY MOUNTING. AMP TEL ON DEMOLITION DRAWINGS, DASHED ELECTRICAL ITEMS DENOTES EXISTING ITEMS TO BE REMOVED; SOLID SCREENED ELECTRICAL ITEMS DENOTES EXISTING ITEMS TO REMAIN, UNLESS NOTED OTHERWISE DESCRIPTION FIRE ALARM ANNUNCIATOR PANEL; MOUNT TOP AT 72" AFF. MOTOR RATED SWITCH AND PILOT. LIGHT FIXTURE ON EMERGENCY CIRCUIT SYMBOL COMMUNICATION DEVICES MS&P MSS MOUNTING HEIGHT DESCRIPTION POWER AND MOTOR DEVICES RECESSED FLUORESCENT LIGHT FIXTURE (TYPE DENOTED) GENERAL ELECTRICAL NOTES H C CAB CATV CB CCTV CKT CLG COMB 1 POLE (2P, 3P, 4P, ETC.) AMPERE ABOVE COUNTER OR AIR CONDITIONER ABOVE CEILING AUTOMATIC DOOR OPENER ABOVE FINISHED FLOOR ABOVE FINISHED GRADE ARC FAULT CIRCUIT INTERRUPTER AIR HANDLING UNIT ALUMINUM ALTERNATE AMPERE AMPLIFIER ANNUNCIATOR APPROXIMATELY AQUASTAT ARCHITECT, ARCHITECTURAL AUTOMATIC TRANSFER SWITCH AUTOMATIC AUXILIARY AUDIO VISUAL AMERICAN WIRE GAUGE BATTERY BOARD BUILDING BUILDING MANAGEMENT SYSTEM CONDUIT CABINET CABLE TELEVISION CIRCUIT BREAKER CLOSED CIRCUIT TELEVISION CIRCUIT CEILING COMBINATION CMPR CONN CONST CONT CONTR CONV CP CRT CT CTR CU DCP COMPRESSOR CONNECTION CONSTRUCTION CONTINUATION OR CONTINUOUS CONTRACTOR CONVECTOR CIRCULATING PUMP CATHODE-RAY TUBE CURRENT TRANSFORMER CENTER COPPER DEPT EX HTR HV HWP DOMESTIC WATER CIRCULATING PUMP DEPARTMENT EXISTING TO REMAIN HEATER HIGH VOLTAGE HYDRONIC WATER PUMP IC IG IMC INCAND IR I/W INTERRUPTING CAPACITY ISOLATED GROUND INTERMEDIATE METAL CONDUIT INCANDESCENT INFRARED INTERLOCK WITH J-BOX JUNCTION BOX KV KVA KVAR KW KWH KILOVOLT KILOVOLT-AMPERE KILOVOLT-AMPERE REACTIVE KILOWATT KILOWATT HOUR LOC LT LTG LTNG LV LOCATE OR LOCATION LIGHT LIGHTING LIGHTNING LOW VOLTAGE MAX MAG.S M/C MC MCB MCC MDC MDP MFR MFS MAXIMUM MAGNETIC STARTER MOMENTARY CONTACT MECHANICAL CONTRACTOR MAIN CIRCUIT BREAKER MOTOR CONTROL CENTER MAIN DISTRIBUTION CENTER MAIN DISTRIBUTION PANEL MANUFACTURER MAIN FUSED DISCONNECT SWITCH MANHOLE MICROPHONE MINIMUM MISCELLANEOUS MAIN LUGS ONLY MANUAL MOTOR STARTER MULTIOUTLET ASSEMBLY MOTOR STARTER PANELBOARD MAIN SWITCHBOARD MOUNT EMPTY CONDUIT MANUAL TRANSFER SWITCH MOTOR, MOTORIZED PA PB PE PED PF PH PNL PP PR PRI PROJ PRV PT PVC NIC NL N.O. NPF NTS NORMALLY CLOSED NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION NON-FUSED SAFETY DISCONNECT SWITCH NOT IN CONTRACT NEW LOCATION NORMALLY OPEN NORMAL POWER FACTOR NOT TO SCALE OH OL OVERHEAD OVERLOADS MH MIC MIN MISC MLO MMS MOA MSP MSBD MT MT.C MTS MTR N.C. NEC NEMA NFDS PWR PUBLIC ADDRESS PULL BOX OR PUSHBUTTON PNEUMATIC ELECTRIC PEDESTAL POWER FACTOR PHASE PANEL POWER POLE PAIR PRIMARY PROJECTION POWER ROOF VENTILATOR POTENTIAL TRANSFORMER POLYVINYL CHLORIDE (CONDUIT) POWER QUAN QUANTITY RCPT REQD RL RSC RTU RECEPTACLE REQUIRED RELOCATED RIGID STEEL CONDUIT ROOF TOP UNIT SC SEC SHT SIM S/N SPEC SPKR SP SR SS SSW S/S STA STD SURF SURFACE CONDUIT SECONDARY SHEET SIMILAR SOLID NEUTRAL SPECIFICATION SPEAKER SPARE SURFACE RACEWAY STAINLESS STEEL SELECTOR SWITCH STOP/START PUSHBUTTONS STATION STANDARD SURFACE MOUNTED SW SWBD SYM SYS TEL TERM TL TR T-STAT TTC TV TVTC TYP UE UG UH UT UV SWITCH SWITCHBOARD SYMMETRICAL SYSTEM TELEPHONE TERMINAL TWIST LOCK TAMPER RESISTANT THERMOSTAT TELEPHONE TERMINAL CABINET TELEVISION TELEVISION TERMINAL CABINET TYPICAL @ ' " # Ø C P ANGLE AT FEET INCHES NUMBER PHASE CENTER LINE PLATE A2 EXAMPLE 1: LIGHTING FIXTURE TYPE "A" IS CONNECTED TO CIRCUIT 12 AND CONTROLLED BY SWITCH "b". 12b * P2D/I * 2aba UNDERGROUND ELECTRICAL UNDERGROUND UNIT HEATER UNDERGROUND TELEPHONE UNIT VENTILATOR OR ULTRAVIOLET E 14 16c V VA VDT VERT VFD VoIP VOL VOLT VOLT-AMPERES VIDEO DISPLAY TERMINAL VERTICAL VARIABLE FREQUENCY DRIVE VOICE OVER IP VOLUME W W/ WG WH W/O WP WATT WITH WIRE GUARD WATER HEATER WITHOUT WEATHERPROOF XFMR XFR TRANSFORMER TRANSFER 7,9 THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER. d D600 EXAMPLE 2: THE FIXTURE TYPE SHOWN AS A NUMERATOR INDICATES ALL LIGHTING FIXTURES IN THE ROOM OR SPACE ARE THE SAME TYPE. THE CIRCUIT NUMBER AND SWITCH DESIGNATION SHOWN AS A DENOMINATOR INDICATES ALL LIGHTING FIXTURES IN THE ROOM OR SPACE ARE CONNECTED TO THE SAME CIRCUIT, CONTROLLED BY THE SAME SWITCHES, CENTER/OUTBOARD MULTILEVEL SWITCHING. DEVICES. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE: SPLIT DUPLEX RECEPTACLE IS CONNECTED TO CIRCUIT 16 AND ONE RECEPTACLE OUTLET IS CONTROLLED BY SWITCH "c". THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE: SINGLE POLE SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY "d". WALL BOX DIMMER WITH SIZE AS INDICATED AT DEVICE. EXAMPLE: 600 WATT WALL BOX DIMMER TO CONTROL LIGHTING FIXTURES INDICATED BY "e". SEE SPECIFICATIONS FOR WATTAGE IF NOT INDICATED. 1,3,5 SPECIAL CONNECTIONS. THE EQUIPMENT IS INDICATED BY A NUMBER IN A CIRCLE. SEE THE MOTOR AND EQUIPMENT SCHEDULE FOR THE LOAD DESCRIPTION AND TYPE OF CONNECTION. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO THE SYMBOL. EXAMPLE: EQUIPMENT NO. 1; 3 PHASE CONNECTION TO CIRCUITS 1, 3, 5. SF-1 2,4,6 LPN-102 EXIT LIGHTS. STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES DIRECTIONAL ARROW ON ILLUMINATED FACE(S). THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. EXAMPLE: THE WALL MOUNTED EXIT LIGHT TYPE "E" WITH SINGLE FACE AND DIRECTIONAL ARROW IS CONNECTED TO CIRCUIT 14. e 1 T1 MOTOR CONNECTIONS. THE MOTOR IS INDICATED BY A NUMBER WITHIN OR CHARACTERS ADJACENT TO THE MOTOR SYMBOL. SEE THE MOTOR AND EQUIPMENT SCHEDULE FOR THE MOTOR DESCRIPTION AND ELECTRICAL REQUIREMENTS. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO THE SYMBOL. EXAMPLE: MOTOR SF-1; 3 PHASE CONNECTION TO CIRCUITS 2, 4, 6. 1 #10 H1 ELECTRIC HEATER CONNECTIONS. THE HEATER TYPE IS INDICATED BY A NUMBER FOLLOWING THE UPPER CASE LETTER "H". SEE THE HEATER SCHEDULE FOR ELECTRICAL REQUIREMENTS. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO THE HEATER. EXAMPLE: ELECTRIC BASEBOARD HEATER TYPE "H1" CONNECTED TO CIRCUITS 7, 9. TRANSFORMERS. THE TRANSFORMER TYPE IS INDICATED BY A NUMBER FOLLOWING THE UPPER CASE LETTER "T". SEE THE TRANSFORMER SCHEDULE OR THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND REQUIREMENTS. EXAMPLE: TRANSFORMER TYPE "T1". PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR DESIGNATION CODES. SPECIAL NOTE. SEE THE SPECIAL NOTES ON THAT SHEET FOR THE NOTE NUMBER INDICATED IN THE HEXAGON. CONDUIT SHOWN WITHOUT SLASH MARKS SHALL CONTAIN 2 # 12 CONDUCTORS IN 3/4" CONDUIT UNLESS SPECIFIC EQUIPMENT REQUIRES A DIFFERENT SIZE. CONDUIT SHOWN WITH SLASH MARKS SHALL CONTAIN 1 # 12 CONDUCTOR PER SLASH MARK IN 3/4" CONDUIT UNLESS A CONDUCTOR AND CONDUIT SIZE IS SHOWN ADJACENT TO THE SLASH MARKS. SLASH MARK INDICATORS ARE: SHORT STRAIGHT=PHASE CONDUCTOR, LONG STRAIGHT=NEUTRAL CONDUCTOR, SHORT BENT ENDED=SWITCH LEGS, LONG STRAIGHT WITH A DOT=GROUND CONDUCTOR, CHEVRON=CATEGORY 6, HALF CHEVRON=CATEGORY 3, TWIST=SHIELDED TWISTED PAIR, CONCENTRIC CIRCLE AND DOT=COAX CABLE. LPN-102 1,3,5 HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD DESIGNATION IS SHOWN ADJACENT TO THE HOME RUN ARROW AS A NUMERATOR AND THE CIRCUIT DESIGNATION IS SHOWN AS THE DENOMINATOR. CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANELBOARD SCHEDULE WITH THE CORRESPONDING PANELBOARD AND CIRCUIT DESIGNATION. EXAMPLE: HOME RUN TO PANELBOARD LPN-102; CIRCUITS 1, 3, 5. SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS. Description Date ELECTRICAL DRAWINGS E0.00 E0.01 E0.02 E0.11 E0.21 E1.11 E1.21 E1.22 E2.11 E2.21 E3.11 E3.21 E4.00 E4.11 E4.21 E5.00 E6.00 E6.01 ELECTRICAL SYMBOLS AND ABBREVIATIONS ELECTRICAL SITE PLAN - DEMOLITION ELECTRICAL SITE PLAN - REMODEL MAIN LEVEL PLAN - DEMOLITION UPPER LEVEL PLAN - DEMOLITION MAIN LEVEL PLAN - LIGHTING UPPER LEVEL PLAN - LIGHTING CAFETERIA LIGHTING PLAN - ALTERNATE #1 MAIN LEVEL PLAN - POWER UPPER LEVEL PLAN - POWER MAIN LEVEL PLAN - SYSTEMS UPPER LEVEL PLAN - SYSTEMS PENTHOUSE AND ROOF PLAN - ELECTRICAL OVERALL MAIN LEVEL FLOOR PLAN OVERALL UPPER LEVEL FLOOR PLAN POWER RISER DIAGRAM MOTOR AND LUMINAIRE SCHEDULES PANELBOARD AND LIGHT RELAY CONTROL PANEL SCHEDULES Comm: 142082 Date: 3/16/2015 Drawn: O. ABDI Check: S. CHHUM North ELECTRICAL SYMBOLS AND ABBREVIATIONS Scale: As indicated E0.00 Num