Building Wire - Taihan Electric Wire Co. Ltd

advertisement
Building wire provides the diversified wiring solution
today for various industrial and residential applications.
Taihan offers a complete line of building wire to meet the
requirements of the electrical industry.
Contents
04
ANNEALED COPPER CONDUCTOR
06
TFFN Type
08
THW Type
10
THHN/THWN Type
12
XHHW-2 Type
14
USE-2/RHH/RHW-2 Type
16
URD, Duplex Type
18
URD, Triplex Type
20
URD, Quadruplex Type
22
TC CONTROL CABLE Type
24
TC POWER CABLE Type
(THHN-THWN Type)
26
TC POWER CABLE Type
(XHHW-2 Type)
Building wire provides the diversified wiring solution
today for various industrial and residential applications.
Taihan offers a complete line of building wire to meet the
requirements of the electrical industry.
Contents
04
ANNEALED COPPER CONDUCTOR
06
TFFN Type
08
THW Type
10
THHN/THWN Type
12
XHHW-2 Type
14
USE-2/RHH/RHW-2 Type
16
URD, Duplex Type
18
URD, Triplex Type
20
URD, Quadruplex Type
22
TC CONTROL CABLE Type
24
TC POWER CABLE Type
(THHN-THWN Type)
26
TC POWER CABLE Type
(XHHW-2 Type)
ANNEALED COPPER CONDUCTOR
Annealed Copper Conductor
Solid and Stranded
This copper conductor is generally used for equipment and circuit grounding.
Soft-drawn bare annealed copper
APPLICATION
STANDARDS
General purpose for equipment and circuit grounding
ASTM B-3 : Soft-drawn-annealed copper wire
ASTM B-8 : Concentric-lay-stranded copper conductors
ASTM B-787 : 19 wire combination unilay-stranded
copper conductors
PRODUCT CONSTRUCTION
Conductor
Soft-drawn bare annealed copper
Building Wire
04
Conductor Size
AWG/MCM
No. of Strands
Nominal Outer Diameter
Copper Weight
inches
lbs/mft
14
Solid
0.064
12.4
12
Solid
0.081
19.8
10
Solid
0.102
31.4
8
Solid
0.129
50.0
8
7
0.146
51.0
6
Solid
0.162
79.4
Packaging
6
7
0.184
81.1
Master cutting lengths on non-returnable wooden reels
4
Solid
0.204
126.3
4
7
0.232
128.9
2
Solid
0.258
200.9
2
7
0.292
204.9
1
7
0.328
258.4
1/0
7
0.368
326.0
1/0
19
0.373
326.0
2/0
7
0.414
411.0
2/0
19
0.419
411.0
3/0
7
0.464
518.1
3/0
19
0.470
518.1
4/0
7
0.522
653.3
4/0
19
0.528
653.3
250
37
0.575
771.9
350
37
0.681
1,081.0
500
37
0.813
1,544.0
750
61
0.998
2,316.0
1,000
61
1.152
3,088.0
05
Building Wire
ANNEALED COPPER CONDUCTOR
Annealed Copper Conductor
Solid and Stranded
This copper conductor is generally used for equipment and circuit grounding.
Soft-drawn bare annealed copper
APPLICATION
STANDARDS
General purpose for equipment and circuit grounding
ASTM B-3 : Soft-drawn-annealed copper wire
ASTM B-8 : Concentric-lay-stranded copper conductors
ASTM B-787 : 19 wire combination unilay-stranded
copper conductors
PRODUCT CONSTRUCTION
Conductor
Soft-drawn bare annealed copper
Building Wire
04
Conductor Size
AWG/MCM
No. of Strands
Nominal Outer Diameter
Copper Weight
inches
lbs/mft
14
Solid
0.064
12.4
12
Solid
0.081
19.8
10
Solid
0.102
31.4
8
Solid
0.129
50.0
8
7
0.146
51.0
6
Solid
0.162
79.4
Packaging
6
7
0.184
81.1
Master cutting lengths on non-returnable wooden reels
4
Solid
0.204
126.3
4
7
0.232
128.9
2
Solid
0.258
200.9
2
7
0.292
204.9
1
7
0.328
258.4
1/0
7
0.368
326.0
1/0
19
0.373
326.0
2/0
7
0.414
411.0
2/0
19
0.419
411.0
3/0
7
0.464
518.1
3/0
19
0.470
518.1
4/0
7
0.522
653.3
4/0
19
0.528
653.3
250
37
0.575
771.9
350
37
0.681
1,081.0
500
37
0.813
1,544.0
750
61
0.998
2,316.0
1,000
61
1.152
3,088.0
05
Building Wire
TFFN TYPE
600V TFFN
PVC Insulation and Nylon Jacket, 600 Volts, 90°C
For commercial and industrial projects, TFFN is widely used for power distribution.
From service entrance and feeders to branch circuits, it can handle electrical wiring
needs most properly.
Bunch Stranded Copper
Conductor
PVC Insulation
Nylon Jacket
APPLICATION
STANDARDS
PRODUCT CONSTRUCTION
Applied for internal wiring of fixtures insulated with
polyvinyl chloride(PVC) and covered with protective
sheath of nylon intended for fixture raceways and fire
alarm circuits wiring as specified in the National
Electrical Code. The wire may be operated at 90℃
maximum continuous temperature in dry location.
ASTM B-3 and B-174
UL Standard 62 for fixture wire
UL Standard 1063 for machine tool wire
Conductor
Bare annealed bunch stranded conductor
Insulation
Flame-retardant, heat, abrasion and moisture-resistant PVC
with polyamide nylon
Identification Color
Black, White, Red, Green, Yellow, Blue, Orange, Gray, Purple, Pink
Print Legend
E57237 (UL) SIZE 600V TYPE TFFN OR GASOLINE AND OIL RESISTANT Ⅱ VW-1
Packaging
4×500、in a carton
2500、reels
Conductor
Size
Building Wire
06
Diameter
Insulation
Thickness
Jacket
Thickness
Approx. Overall
Diameter
Approx.
Weight
AWG
mm2
No. of
Strands
mm
mils
mm
mils
mm
mils
mm
mils
kg/km
lbs/1000ft
18
0.811
16/0.254
1.17
46.1
0.38
15
0.1
4
2.23
87.8
11.2
7.5
16
1.31
26/0.254
1.49
58.7
0.38
15
0.1
4
2.55
100.8
16.5
11.1
07
Building Wire
TFFN TYPE
600V TFFN
PVC Insulation and Nylon Jacket, 600 Volts, 90°C
For commercial and industrial projects, TFFN is widely used for power distribution.
From service entrance and feeders to branch circuits, it can handle electrical wiring
needs most properly.
Bunch Stranded Copper
Conductor
PVC Insulation
Nylon Jacket
APPLICATION
STANDARDS
PRODUCT CONSTRUCTION
Applied for internal wiring of fixtures insulated with
polyvinyl chloride(PVC) and covered with protective
sheath of nylon intended for fixture raceways and fire
alarm circuits wiring as specified in the National
Electrical Code. The wire may be operated at 90℃
maximum continuous temperature in dry location.
ASTM B-3 and B-174
UL Standard 62 for fixture wire
UL Standard 1063 for machine tool wire
Conductor
Bare annealed bunch stranded conductor
Insulation
Flame-retardant, heat, abrasion and moisture-resistant PVC
with polyamide nylon
Identification Color
Black, White, Red, Green, Yellow, Blue, Orange, Gray, Purple, Pink
Print Legend
E57237 (UL) SIZE 600V TYPE TFFN OR GASOLINE AND OIL RESISTANT Ⅱ VW-1
Packaging
4×500、in a carton
2500、reels
Conductor
Size
Building Wire
06
Diameter
Insulation
Thickness
Jacket
Thickness
Approx. Overall
Diameter
Approx.
Weight
AWG
mm2
No. of
Strands
mm
mils
mm
mils
mm
mils
mm
mils
kg/km
lbs/1000ft
18
0.811
16/0.254
1.17
46.1
0.38
15
0.1
4
2.23
87.8
11.2
7.5
16
1.31
26/0.254
1.49
58.7
0.38
15
0.1
4
2.55
100.8
16.5
11.1
07
Building Wire
THW TYPE
600V THW
PVC Insulation, 600 Volts, 75°C
THW is used for general purpose of wiring in residential, commercial and industrial
installations.
Copper Conductor
Heat-resistant PVC Insulation
APPLICATION
STANDARD
Generally used for wiring for the supply of electrical
power of residential, commercial, industrial buildings in
accordance with the National Electrical Code, maximum
continuous conductor temperature of 75℃ in wet or dry
locations.
UL 83 : Thermoplastic insulated wires and cables
Conductor
Size
PRODUCT CONSTRUCTION
AWG or
MCM
mm2
No. of
Strands
Diameter
mm
mils
Insulation
Thickness
mm
Approx. Overall
Diameter
mils
mm
mils
Approx.
Weight
Standard
Length
�
Ampacity
kg/km
lbs/
1000ft
Dry & Wet
m
ft
Conductor
14
2.08
1
1.63
64.1
0.76
30
3.2
126
27
18
15
915
3,000
Bare annealed solid or stranded conductor
14
2.08
7
1.85
72.7
0.76
30
3.5
138
29
19
15
915
3,000
12
3.31
1
2.05
80.8
0.76
30
3.7
146
39
26
20
915
3,000
12
3.31
7
2.32
91.5
0.76
30
3.9
155
42
28
20
915
3,000
10
5.26
1
2.588
101.9
0.76
30
4.2
165
59
40
30
915
3,000
10
5.26
7
2.95
116
0.76
30
4.5
178
62
42
30
915
3,000
Insulation
Abrasion, moisture, and heat-resistant PVC(Polyvinyl
chloride)
Identification Color
8
7
3.71
146
1.14
45
6.1
240
104
70
50
915
3,000
Black, White, Red, Green, Yellow, Brown, Blue, Orange,
Gray, Purple, Pink
6
13.3
7
4.67
184
1.52
60
7.9
310
169
114
65
915
3,000
4
21.2
7
5.89
232
1.52
60
9.1
357
250
168
85
915
3,000
Print Legend
3
26.7
7
6.60
260
1.52
60
9.8
386
306
206
100
915
3,000
E96723 (UL) SIZE 600V THW VW-1 (14AWG~1AWG)
E96723 (UL) SIZE 600V THW OR SUNLIGHT
RESISTANT VW-1
(1/0AWG and larger)
2
33.6
7
7.42
292
1.52
60
10.6
418
377
253
115
915
3,000
1
42.4
19
8.43
332
2.03
80
12.7
501
492
331
130
457
1,500
1/0
53.5
19
9.45
372
2.03
80
13.7
539
600
403
150
457
1,500
2/0
67.4
19
10.62
418
2.03
80
14.9
587
744
500
175
457
1,500
85.0
3/0
8.37
19
11.94
470
2.03
80
16.2
638
917
616
200
457
1,500
4/0
107
19
13.41
528
2.03
80
17.7
697
1,133
761
230
457
1,500
250
127
37
14.61
575
2.41
95
19.7
776
1,357
912
255
457
1,500
300
152
37
16.00
630
2.41
95
21.1
831
1,606
1,079
285
457
1,500
350
177
37
17.30
681
2.41
95
22.4
882
1,849
1,242
310
457
1,500
400
203
37
18.49
728
2.41
95
23.6
929
2,094
1,407
335
457
1,500
500
253
37
20.65
813
2.41
95
25.7
1,012
2,580
1,734
380
305
1,000
600
304
61
22.68
893
2.79
110
28.6
1,126
3,126
2,101
420
305
1,000
750
380
61
25.35
998
2.79
110
31.3
1,232
3,866
2,598
475
305
1,000
1,000
507
61
29.26
1,152
2.79
110
35.1
1,382
5,065
3,404
545
305
1,000
� : Per Table 310-16 of the National Electrical Code, 1996 edition.
Conditions : Not more than three conductors in raceway or cable or earth(directly buried), based on ambient temperature of 30℃.
Building Wire
08
09
Building Wire
THW TYPE
600V THW
PVC Insulation, 600 Volts, 75°C
THW is used for general purpose of wiring in residential, commercial and industrial
installations.
Copper Conductor
Heat-resistant PVC Insulation
APPLICATION
STANDARD
Generally used for wiring for the supply of electrical
power of residential, commercial, industrial buildings in
accordance with the National Electrical Code, maximum
continuous conductor temperature of 75℃ in wet or dry
locations.
UL 83 : Thermoplastic insulated wires and cables
Conductor
Size
PRODUCT CONSTRUCTION
AWG or
MCM
mm2
No. of
Strands
Diameter
mm
mils
Insulation
Thickness
mm
Approx. Overall
Diameter
mils
mm
mils
Approx.
Weight
Standard
Length
�
Ampacity
kg/km
lbs/
1000ft
Dry & Wet
m
ft
Conductor
14
2.08
1
1.63
64.1
0.76
30
3.2
126
27
18
15
915
3,000
Bare annealed solid or stranded conductor
14
2.08
7
1.85
72.7
0.76
30
3.5
138
29
19
15
915
3,000
12
3.31
1
2.05
80.8
0.76
30
3.7
146
39
26
20
915
3,000
12
3.31
7
2.32
91.5
0.76
30
3.9
155
42
28
20
915
3,000
10
5.26
1
2.588
101.9
0.76
30
4.2
165
59
40
30
915
3,000
10
5.26
7
2.95
116
0.76
30
4.5
178
62
42
30
915
3,000
Insulation
Abrasion, moisture, and heat-resistant PVC(Polyvinyl
chloride)
Identification Color
8
7
3.71
146
1.14
45
6.1
240
104
70
50
915
3,000
Black, White, Red, Green, Yellow, Brown, Blue, Orange,
Gray, Purple, Pink
6
13.3
7
4.67
184
1.52
60
7.9
310
169
114
65
915
3,000
4
21.2
7
5.89
232
1.52
60
9.1
357
250
168
85
915
3,000
Print Legend
3
26.7
7
6.60
260
1.52
60
9.8
386
306
206
100
915
3,000
E96723 (UL) SIZE 600V THW VW-1 (14AWG~1AWG)
E96723 (UL) SIZE 600V THW OR SUNLIGHT
RESISTANT VW-1
(1/0AWG and larger)
2
33.6
7
7.42
292
1.52
60
10.6
418
377
253
115
915
3,000
1
42.4
19
8.43
332
2.03
80
12.7
501
492
331
130
457
1,500
1/0
53.5
19
9.45
372
2.03
80
13.7
539
600
403
150
457
1,500
2/0
67.4
19
10.62
418
2.03
80
14.9
587
744
500
175
457
1,500
85.0
3/0
8.37
19
11.94
470
2.03
80
16.2
638
917
616
200
457
1,500
4/0
107
19
13.41
528
2.03
80
17.7
697
1,133
761
230
457
1,500
250
127
37
14.61
575
2.41
95
19.7
776
1,357
912
255
457
1,500
300
152
37
16.00
630
2.41
95
21.1
831
1,606
1,079
285
457
1,500
350
177
37
17.30
681
2.41
95
22.4
882
1,849
1,242
310
457
1,500
400
203
37
18.49
728
2.41
95
23.6
929
2,094
1,407
335
457
1,500
500
253
37
20.65
813
2.41
95
25.7
1,012
2,580
1,734
380
305
1,000
600
304
61
22.68
893
2.79
110
28.6
1,126
3,126
2,101
420
305
1,000
750
380
61
25.35
998
2.79
110
31.3
1,232
3,866
2,598
475
305
1,000
1,000
507
61
29.26
1,152
2.79
110
35.1
1,382
5,065
3,404
545
305
1,000
� : Per Table 310-16 of the National Electrical Code, 1996 edition.
Conditions : Not more than three conductors in raceway or cable or earth(directly buried), based on ambient temperature of 30℃.
Building Wire
08
09
Building Wire
THHN / THWN TYPE
600V THHN / THWN
PVC Insulation and Nylon Jacket, 600 Volts, 90°C Dry, 75°C Wet
For commercial and industrial projects, THHN/THWN is widely used for power
distribution. From service entrance and feeders to branch circuits, it can handle
electrical wiring needs most properly .
Copper Conductor
PVC Insulation
Nylon Jacket
APPLICATION
PRODUCT CONSTRUCTION
General purpose for building wiring insulated with
polyvinyl chloride(PVC) and covered with a tough
protective sheath of nylon intended for lighting and
power circuits wiring as specified in the National
Electrical Code. The wire may be operated at 90℃
maximum continuous temperature in dry locations
and in wet locations.
Conductor
STANDARDS
UL 83 : Thermoplastic insulated wires and cables
TYPE THHN : 90℃ dry
TYPE THWN : 75℃ wet or dry
Conductor
Bare annealed solid or stranded conductor
Insulation
Flame-retardant, heat, abrasion and moisture-resistant
PVC with polyamide nylon
Size
AWG or
MCM
Identification Color
Black, White, Red, Green, Yellow, Blue, Orange, Gray,
Purple, Pink
Print Legend
mm
1.63
mils
64.1
Approx. Overall
Diameter
mm
mils
mm
mils
mm
0.38
15
0.1
4
2.7
mils
106
Approx.
Weight
�Ampacity
kg/km
lbs/
1000ft
THWN
(75˚C)
THHN
(90˚C)
24
16
15
15
14
2.08
1
14
2.08
19
1.85
72.7
0.38
15
0.1
4
2.9
114
24
16
15
15
12
3.31
1
2.05
80.8
0.38
15
0.1
4
3.2
126
36
24
20
20
12
3.31
19
2.32
91.5
0.38
15
0.1
4
3.4
134
37
25
20
20
10
5.26
1
2.588
101.9
0.51
20
0.1
4
3.9
154
57
38
30
30
10
5.26
19
2.95
116
0.51
20
0.1
4
4.3
169
58
39
30
30
8
8.37
1
3.264
128.5
0.76
30
0.13
5
5.3
209
91
61
50
55
8
8.37
19
3.71
146
0.76
30
0.13
5
5.6
220
98
66
50
55
6
13.3
19
4.67
184
0.76
30
0.13
5
6.6
260
146
98
65
75
14AWG through 1AWG stranded :
E109010 (UL) SIZE 600V TYPE MTW OR THHN OR
THWN OR GASOLINE AND OIL RESISTANT Ⅱ VW-1
OR AWM
4
21.2
19
5.89
232
1.02
40
0.15
6
8.9
350
237
159
85
95
2
33.6
19
6.60
260
1.02
40
0.15
6
10.0
394
357
240
115
130
1
42.4
19
8.43
332
1.27
50
0.18
7
11.4
449
455
306
130
150
1/0
42.4
19
9.45
372
1.27
50
0.18
7
12.5
492
558
375
150
170
2/0
67.4
19
10.62
418
1.27
50
0.18
7
13.6
535
696
468
175
195
3/0
85.0
19
11.94
470
1.27
50
0.18
7
14.8
583
865
581
200
225
1/0 AWG and larger :
E109010 (UL) SIZE 600V TYPE MTW OR THHN OR
THWN OR GASOLINE AND OIL RESISTANT Ⅱ
SUNLIGHT RESISTANT VW-1 OR AWM
4/0
107
19
13.41
528
1.27
50
0.18
7
16.2
638
1,071
720
230
260
250
127
37
14.61
575
1.52
60
0.2
8
18.0
709
1,280
860
255
290
Packaging
300
152
37
16.00
630
1.52
60
0.2
8
19.3
760
1,518
1,020
285
320
350
177
37
17.30
681
1.52
60
0.2
8
20.6
811
1,759
1,182
310
350
400
203
37
18.49
728
1.52
60
0.2
8
21.7
854
1,994
1,340
335
380
500
253
37
20.65
813
1.52
60
0.2
8
23.9
941
2,470
1,660
380
430
�
10
No. of
Strands
Jacket
Thickness
14AWG through 10AWG solid :
E96723 (UL) SIZE 600V THHN OR THWN OR
GASOLINE AND OIL RESISTANT Ⅱ VW-1 OR AWM
14AWG and 12AWG : 4×500′in a carton, or 2500′reel
10AWG : 2×500′in a carton or 2500′reel
8AWG through 2AWG : 500′, 1000′, 2500′reel, and
cut to order
1AWG and larger : cut to order
Building Wire
mm2
Insulation
Thickness
Diameter
750
380
61
25.35
998
1.78
70
0.23
9
28.9
1,138
3,706
2,490
475
535
1,000
507
61
29.26
1,152
1.78
70
0.23
9
32.7
1,289
4,821
3,240
545
615
: Per Table 310-16 of the National Electrical Code, 1996 edition.
Conditions : Not more than three conductors in raceway or cable or earth(directly buried), based on ambient temperature of 30℃.
11
Building Wire
THHN / THWN TYPE
600V THHN / THWN
PVC Insulation and Nylon Jacket, 600 Volts, 90°C Dry, 75°C Wet
For commercial and industrial projects, THHN/THWN is widely used for power
distribution. From service entrance and feeders to branch circuits, it can handle
electrical wiring needs most properly .
Copper Conductor
PVC Insulation
Nylon Jacket
APPLICATION
PRODUCT CONSTRUCTION
General purpose for building wiring insulated with
polyvinyl chloride(PVC) and covered with a tough
protective sheath of nylon intended for lighting and
power circuits wiring as specified in the National
Electrical Code. The wire may be operated at 90℃
maximum continuous temperature in dry locations
and in wet locations.
Conductor
STANDARDS
UL 83 : Thermoplastic insulated wires and cables
TYPE THHN : 90℃ dry
TYPE THWN : 75℃ wet or dry
Conductor
Bare annealed solid or stranded conductor
Insulation
Flame-retardant, heat, abrasion and moisture-resistant
PVC with polyamide nylon
Size
AWG or
MCM
Identification Color
Black, White, Red, Green, Yellow, Blue, Orange, Gray,
Purple, Pink
Print Legend
mm
1.63
mils
64.1
Approx. Overall
Diameter
mm
mils
mm
mils
mm
0.38
15
0.1
4
2.7
mils
106
Approx.
Weight
�Ampacity
kg/km
lbs/
1000ft
THWN
(75˚C)
THHN
(90˚C)
24
16
15
15
14
2.08
1
14
2.08
19
1.85
72.7
0.38
15
0.1
4
2.9
114
24
16
15
15
12
3.31
1
2.05
80.8
0.38
15
0.1
4
3.2
126
36
24
20
20
12
3.31
19
2.32
91.5
0.38
15
0.1
4
3.4
134
37
25
20
20
10
5.26
1
2.588
101.9
0.51
20
0.1
4
3.9
154
57
38
30
30
10
5.26
19
2.95
116
0.51
20
0.1
4
4.3
169
58
39
30
30
8
8.37
1
3.264
128.5
0.76
30
0.13
5
5.3
209
91
61
50
55
8
8.37
19
3.71
146
0.76
30
0.13
5
5.6
220
98
66
50
55
6
13.3
19
4.67
184
0.76
30
0.13
5
6.6
260
146
98
65
75
14AWG through 1AWG stranded :
E109010 (UL) SIZE 600V TYPE MTW OR THHN OR
THWN OR GASOLINE AND OIL RESISTANT Ⅱ VW-1
OR AWM
4
21.2
19
5.89
232
1.02
40
0.15
6
8.9
350
237
159
85
95
2
33.6
19
6.60
260
1.02
40
0.15
6
10.0
394
357
240
115
130
1
42.4
19
8.43
332
1.27
50
0.18
7
11.4
449
455
306
130
150
1/0
42.4
19
9.45
372
1.27
50
0.18
7
12.5
492
558
375
150
170
2/0
67.4
19
10.62
418
1.27
50
0.18
7
13.6
535
696
468
175
195
3/0
85.0
19
11.94
470
1.27
50
0.18
7
14.8
583
865
581
200
225
1/0 AWG and larger :
E109010 (UL) SIZE 600V TYPE MTW OR THHN OR
THWN OR GASOLINE AND OIL RESISTANT Ⅱ
SUNLIGHT RESISTANT VW-1 OR AWM
4/0
107
19
13.41
528
1.27
50
0.18
7
16.2
638
1,071
720
230
260
250
127
37
14.61
575
1.52
60
0.2
8
18.0
709
1,280
860
255
290
Packaging
300
152
37
16.00
630
1.52
60
0.2
8
19.3
760
1,518
1,020
285
320
350
177
37
17.30
681
1.52
60
0.2
8
20.6
811
1,759
1,182
310
350
400
203
37
18.49
728
1.52
60
0.2
8
21.7
854
1,994
1,340
335
380
500
253
37
20.65
813
1.52
60
0.2
8
23.9
941
2,470
1,660
380
430
�
10
No. of
Strands
Jacket
Thickness
14AWG through 10AWG solid :
E96723 (UL) SIZE 600V THHN OR THWN OR
GASOLINE AND OIL RESISTANT Ⅱ VW-1 OR AWM
14AWG and 12AWG : 4×500′in a carton, or 2500′reel
10AWG : 2×500′in a carton or 2500′reel
8AWG through 2AWG : 500′, 1000′, 2500′reel, and
cut to order
1AWG and larger : cut to order
Building Wire
mm2
Insulation
Thickness
Diameter
750
380
61
25.35
998
1.78
70
0.23
9
28.9
1,138
3,706
2,490
475
535
1,000
507
61
29.26
1,152
1.78
70
0.23
9
32.7
1,289
4,821
3,240
545
615
: Per Table 310-16 of the National Electrical Code, 1996 edition.
Conditions : Not more than three conductors in raceway or cable or earth(directly buried), based on ambient temperature of 30℃.
11
Building Wire
XHHW-2 TYPE
600V XHHW-2
XLPE Insulation, 600 Volts, 90°C Wet or Dry
XLPE insulated XHHW-2 is an ideal wiring solution. Type XHHW-2 is well suited for
building wire for power distribution. It offers excellent dielectric, tensile strength and
cut resistance properties.
Copper Conductor
XLPE Insulation
APPLICATION
PRODUCT CONSTRUCTION
General purpose for building wiring insulated with crosslinked polyethylene(XLPE) for lighting and power circuit
wiring as specified in the National Electrical Code.
The wire may be operated at 90℃ maximum
continuous conductor temperature in wet or dry
locations.
Conductor
Conductor
Conductors shall be class B stranded annealed bare
conductor
Size
AWG or
MCM
Insulation
XLPE(cross-linked polyethylene)
Abrasion, heat and moisture resistant
mm
2
Insulation
Thickness
��Diameter
No. of
Strands
mm
mils
mm
mils
Approx. Overall
Diameter
mm
mils
Approx.
Weight
kg/km
lbs/
1000ft
�
Ampacity
14
2.08
1
1.63
64.1
0.76
30
3.3
132
25
17
15
14
2.08
7
1.85
72.7
0.76
30
3.5
140
25
17
15
12
3.31
1
2.05
80.8
0.76
30
3.7
148
35
24
20
STANDARD
Identification Color
12
3.31
7
2.32
0.76
30
4.0
160
40
27
20
5.26
1
2.588
102
0.76
30
4.2
168
55
37
30
UL 44 : Thermoplastic insulated wires and cables
Black, White, Red, Green, Yellow, Brown, Blue, Orange,
Gray
10
10
5.26
7
2.95
116
0.76
30
4.5
180
60
40
30
8
8.37
1
3.264
129
1.14
45
5.7
228
95
64
55
8.37
91.5
Print Legend
8
7
3.71
146
1.14
45
6.2
248
100
67
55
E113293 (UL) SIZE 600V TYPE XHHW-2
6
13.3
7
4.67
184
1.14
45
7.1
284
150
100
75
4
21.2
7
5.89
232
1.14
45
8.3
332
220
150
95
3
26.7
7
6.60
260
1.14
45
9.1
364
280
190
110
2
33.6
7
7.42
292
1.14
45
9.9
396
350
240
130
1
42.4
19
8.43
332
1.40
55
11.5
460
440
300
150
1/0
53.5
19
9.45
372
1.40
55
12.5
500
550
370
170
2/0
67.4
19
10.62
418
1.40
55
13.7
548
690
460
195
85.0
Packaging
14AWG and 12AWG : 2×500′in a carton, or 2500′reel
10AWG : 1×500′in a carton, or 2500′reel
8AWG and larger : cut to order
3/0
19
11.94
470
1.40
55
15.0
600
850
570
225
4/0
107
19
13.41
528
1.40
55
16.4
656
1,060
710
260
250
127
37
14.61
575
1.65
65
18.3
732
1,270
850
290
300
152
37
16.00
630
1.65
65
19.8
792
1,520
1,020
320
350
177
37
17.30
681
1.65
65
21.0
840
1,750
1,180
350
400
203
37
18.49
728
1.65
65
22.2
888
1,990
1,340
380
500
253
37
20.65
813
1.65
65
24.3
972
2,470
1,660
430
600
304
61
22.68
893
2.03
80
27.3
1,092
3,000
2,020
475
750
380
61
25.35
998
2.03
80
30.0
1,200
3,730
2,510
535
1,000
507
61
29.26
1,152
2.03
80
33.9
1,356
4,900
3,290
615
: Per Table 310-16 of the National Electrical Code, 1996 edition.
Conditions : Not more than three conductors in raceway or cable or earth(directly buried), based on ambient temperature of 30℃.
�� : These values are the outer diameter of the solid or concentric stranded class B conductor.
For stranded conductor, the compress stranding may be available to reduce the conductor diameter.
�
Building Wire
12
13
Building Wire
XHHW-2 TYPE
600V XHHW-2
XLPE Insulation, 600 Volts, 90°C Wet or Dry
XLPE insulated XHHW-2 is an ideal wiring solution. Type XHHW-2 is well suited for
building wire for power distribution. It offers excellent dielectric, tensile strength and
cut resistance properties.
Copper Conductor
XLPE Insulation
APPLICATION
PRODUCT CONSTRUCTION
General purpose for building wiring insulated with crosslinked polyethylene(XLPE) for lighting and power circuit
wiring as specified in the National Electrical Code.
The wire may be operated at 90℃ maximum
continuous conductor temperature in wet or dry
locations.
Conductor
Conductor
Conductors shall be class B stranded annealed bare
conductor
Size
AWG or
MCM
Insulation
XLPE(cross-linked polyethylene)
Abrasion, heat and moisture resistant
mm
2
Insulation
Thickness
��Diameter
No. of
Strands
mm
mils
mm
mils
Approx. Overall
Diameter
mm
mils
Approx.
Weight
kg/km
lbs/
1000ft
�
Ampacity
14
2.08
1
1.63
64.1
0.76
30
3.3
132
25
17
15
14
2.08
7
1.85
72.7
0.76
30
3.5
140
25
17
15
12
3.31
1
2.05
80.8
0.76
30
3.7
148
35
24
20
STANDARD
Identification Color
12
3.31
7
2.32
0.76
30
4.0
160
40
27
20
5.26
1
2.588
102
0.76
30
4.2
168
55
37
30
UL 44 : Thermoplastic insulated wires and cables
Black, White, Red, Green, Yellow, Brown, Blue, Orange,
Gray
10
10
5.26
7
2.95
116
0.76
30
4.5
180
60
40
30
8
8.37
1
3.264
129
1.14
45
5.7
228
95
64
55
8.37
91.5
Print Legend
8
7
3.71
146
1.14
45
6.2
248
100
67
55
E113293 (UL) SIZE 600V TYPE XHHW-2
6
13.3
7
4.67
184
1.14
45
7.1
284
150
100
75
4
21.2
7
5.89
232
1.14
45
8.3
332
220
150
95
3
26.7
7
6.60
260
1.14
45
9.1
364
280
190
110
2
33.6
7
7.42
292
1.14
45
9.9
396
350
240
130
1
42.4
19
8.43
332
1.40
55
11.5
460
440
300
150
1/0
53.5
19
9.45
372
1.40
55
12.5
500
550
370
170
2/0
67.4
19
10.62
418
1.40
55
13.7
548
690
460
195
85.0
Packaging
14AWG and 12AWG : 2×500′in a carton, or 2500′reel
10AWG : 1×500′in a carton, or 2500′reel
8AWG and larger : cut to order
3/0
19
11.94
470
1.40
55
15.0
600
850
570
225
4/0
107
19
13.41
528
1.40
55
16.4
656
1,060
710
260
250
127
37
14.61
575
1.65
65
18.3
732
1,270
850
290
300
152
37
16.00
630
1.65
65
19.8
792
1,520
1,020
320
350
177
37
17.30
681
1.65
65
21.0
840
1,750
1,180
350
400
203
37
18.49
728
1.65
65
22.2
888
1,990
1,340
380
500
253
37
20.65
813
1.65
65
24.3
972
2,470
1,660
430
600
304
61
22.68
893
2.03
80
27.3
1,092
3,000
2,020
475
750
380
61
25.35
998
2.03
80
30.0
1,200
3,730
2,510
535
1,000
507
61
29.26
1,152
2.03
80
33.9
1,356
4,900
3,290
615
: Per Table 310-16 of the National Electrical Code, 1996 edition.
Conditions : Not more than three conductors in raceway or cable or earth(directly buried), based on ambient temperature of 30℃.
�� : These values are the outer diameter of the solid or concentric stranded class B conductor.
For stranded conductor, the compress stranding may be available to reduce the conductor diameter.
�
Building Wire
12
13
Building Wire
USE-2 / RHH / RHW-2 TYPE
600V USE-2 / RHH / RHW-2
XLPE Insulation, 600 Volts, 90°C Wet or Dry
This wire provides an ideal wiring solution. Type USE-2/RHH/RHW-2 can be utilized as
underground service entrance. It offers excellent dielectric, tensile strength and cut
resistance properties.
Copper Conductor
XLPE Insulation
APPLICATION
STANDARDS
General purpose for wiring for lighting and powerresidential commercial, industrial buildings.
Suitable for use in circuits not exceeding 600 volts at
conductortemperatures not exceeding 90℃ in wet or
dry locations.
UL Standard 854 for Type USE-2
UL Standard 44 for Type RHH/RHW-2
Conductor
Size
PRODUCT CONSTRUCTION
AWG or
MCM
mm2
No. of
Strands
Insulation
Thickness
Diameter
Approx. Overall
Diameter
Approx.
Weight
lbs/
1000ft
�
Ampacity
mm
mils
mm
mils
mm
91.5
1.14
45
4.3
169
30
20.2
20
mils
kg/km
Conductor
12
3.31
7
2.32
Conductors shall be class B stranded annealed bare
conductor
10
5.26
7
2.95
116
1.14
45
5.1
201
48
32.1
30
8
8.37
7
3.71
146
1.52
60
6.9
272
76
51.0
55
Insulation
6
13.3
7
4.67
184
1.52
60
7.9
311
121
81.1
75
XLPE(cross-linked polyethylene)
Abrasion, heat and moisture resistant
4
21.2
7
5.89
232
1.52
60
9.4
370
192
128.9
95
3
26.7
7
6.6
260
1.52
60
9.9
390
242
162.5
110
Identification Color
2
33.6
7
7.42
292
1.52
60
10.9
429
305
204.9
130
Black, White, Red, Green, Yellow, Brown, Blue, Orange,
Gray
1
42.4
19
8.33
328
2.03
80
13
512
385
258.4
150
1/0
42.4
19
9.47
373
2.03
80
14.2
559
485
325.8
170
Print Legend
2/0
67.4
19
10.64
419
2.03
80
15.2
598
611
410.9
195
E111359 (UL) SIZE 600V TYPE USE-2 OR RHH OR
RHW-2
3/0
85.4
19
11.94
470
2.03
80
16.8
661
771
518.1
225
4/0
107
19
13.41
528
2.03
80
18.3
720
972
653.3
260
Packaging
250
127
37
14.61
575
2.41
95
20.3
799
1,149
771.9
290
14AWG : 2×500′in a carton or 2500′reel
12AWG and 10AWG : 1×500′in a carton or 2500′reel
8AWG and larger : cut to order
300
152
37
16
630
2.41
95
21.8
858
1,379
926.3
320
350
177
37
17.3
681
2.41
95
23.1
909
1,609
1,081
350
400
203
37
18.49
728
2.41
95
23.9
941
1,838
1,235
380
500
253
37
20.65
813
2.41
95
26.7
1,051
2,298
1,544
430
750
380
61
25.35
998
2.79
110
32.3
1,272
3,447
2,316
535
�: Per Table 310-16 of the National Electrical Code, 1996 edition.
Conditions : Not more than three conductors in raceway or cable or earth(directly buried), based on ambient temperature of 30℃.
Building Wire
14
15
Building Wire
USE-2 / RHH / RHW-2 TYPE
600V USE-2 / RHH / RHW-2
XLPE Insulation, 600 Volts, 90°C Wet or Dry
This wire provides an ideal wiring solution. Type USE-2/RHH/RHW-2 can be utilized as
underground service entrance. It offers excellent dielectric, tensile strength and cut
resistance properties.
Copper Conductor
XLPE Insulation
APPLICATION
STANDARDS
General purpose for wiring for lighting and powerresidential commercial, industrial buildings.
Suitable for use in circuits not exceeding 600 volts at
conductortemperatures not exceeding 90℃ in wet or
dry locations.
UL Standard 854 for Type USE-2
UL Standard 44 for Type RHH/RHW-2
Conductor
Size
PRODUCT CONSTRUCTION
AWG or
MCM
mm2
No. of
Strands
Insulation
Thickness
Diameter
Approx. Overall
Diameter
Approx.
Weight
lbs/
1000ft
�
Ampacity
mm
mils
mm
mils
mm
91.5
1.14
45
4.3
169
30
20.2
20
mils
kg/km
Conductor
12
3.31
7
2.32
Conductors shall be class B stranded annealed bare
conductor
10
5.26
7
2.95
116
1.14
45
5.1
201
48
32.1
30
8
8.37
7
3.71
146
1.52
60
6.9
272
76
51.0
55
Insulation
6
13.3
7
4.67
184
1.52
60
7.9
311
121
81.1
75
XLPE(cross-linked polyethylene)
Abrasion, heat and moisture resistant
4
21.2
7
5.89
232
1.52
60
9.4
370
192
128.9
95
3
26.7
7
6.6
260
1.52
60
9.9
390
242
162.5
110
Identification Color
2
33.6
7
7.42
292
1.52
60
10.9
429
305
204.9
130
Black, White, Red, Green, Yellow, Brown, Blue, Orange,
Gray
1
42.4
19
8.33
328
2.03
80
13
512
385
258.4
150
1/0
42.4
19
9.47
373
2.03
80
14.2
559
485
325.8
170
Print Legend
2/0
67.4
19
10.64
419
2.03
80
15.2
598
611
410.9
195
E111359 (UL) SIZE 600V TYPE USE-2 OR RHH OR
RHW-2
3/0
85.4
19
11.94
470
2.03
80
16.8
661
771
518.1
225
4/0
107
19
13.41
528
2.03
80
18.3
720
972
653.3
260
Packaging
250
127
37
14.61
575
2.41
95
20.3
799
1,149
771.9
290
14AWG : 2×500′in a carton or 2500′reel
12AWG and 10AWG : 1×500′in a carton or 2500′reel
8AWG and larger : cut to order
300
152
37
16
630
2.41
95
21.8
858
1,379
926.3
320
350
177
37
17.3
681
2.41
95
23.1
909
1,609
1,081
350
400
203
37
18.49
728
2.41
95
23.9
941
1,838
1,235
380
500
253
37
20.65
813
2.41
95
26.7
1,051
2,298
1,544
430
750
380
61
25.35
998
2.79
110
32.3
1,272
3,447
2,316
535
�: Per Table 310-16 of the National Electrical Code, 1996 edition.
Conditions : Not more than three conductors in raceway or cable or earth(directly buried), based on ambient temperature of 30℃.
Building Wire
14
15
Building Wire
URD, Duplex TYPE
600V URD, Duplex
XLPE Insulation, 600 Volts, 90°C
The cables are recommended for directly buried or installed in ducts for 600 volt
secondary distribution. Duplex cable is designed for application as a secondary in twowire, single-phase underground distribution systems operated at 600 volts or less. It can
be installed in direct burial or in ducts.
Aluminum Conductor
XLPE Insulation
APPLICATIONS
�Underground distribution from a power supply source
to the service entrance equipment of a building
�Maximum operating temperature of 90℃
�Direct burial application or in ducts
�600 volts
STANDARDS
ASTM B-230, B-231 and ICEA S-66-524
UL Standard 854 for Type USE
Phase Conductor
Code
Name
Size
Strands
AWG
Neutral
Insulation
Thickness
Size
mils
AWG
Strands
Single
Phase
Insulation
Thickness Conductor
Ampacity
Approx.
Overall
Diameter
Weight
lbs/1000ft
mils
inches
inches
Direct
Burial
In
Duct
Bard
8
7/w
60
8
7/w
60
0.262
0.524
76
70
70
Claflin
6
7/w
60
6
7/w
60
0.299
0.606
104
95
70
Delgado
4
7/w
60
4
7/w
60
0.345
0.700
138
125
90
Everett
2
7/w
60
2
7/w
60
0.403
0.806
189
187
100
PRODUCT CONSTRUCTION
Identification Color
Black phase conductors
Yellow striped neutral or numbering
Packaging
Master cutting lengths on non-returnable wooden reels
Building Wire
16
17
Building Wire
URD, Duplex TYPE
600V URD, Duplex
XLPE Insulation, 600 Volts, 90°C
The cables are recommended for directly buried or installed in ducts for 600 volt
secondary distribution. Duplex cable is designed for application as a secondary in twowire, single-phase underground distribution systems operated at 600 volts or less. It can
be installed in direct burial or in ducts.
Aluminum Conductor
XLPE Insulation
APPLICATIONS
�Underground distribution from a power supply source
to the service entrance equipment of a building
�Maximum operating temperature of 90℃
�Direct burial application or in ducts
�600 volts
STANDARDS
ASTM B-230, B-231 and ICEA S-66-524
UL Standard 854 for Type USE
Phase Conductor
Code
Name
Size
Strands
AWG
Neutral
Insulation
Thickness
Size
mils
AWG
Strands
Single
Phase
Insulation
Thickness Conductor
Ampacity
Approx.
Overall
Diameter
Weight
lbs/1000ft
mils
inches
inches
Direct
Burial
In
Duct
Bard
8
7/w
60
8
7/w
60
0.262
0.524
76
70
70
Claflin
6
7/w
60
6
7/w
60
0.299
0.606
104
95
70
Delgado
4
7/w
60
4
7/w
60
0.345
0.700
138
125
90
Everett
2
7/w
60
2
7/w
60
0.403
0.806
189
187
100
PRODUCT CONSTRUCTION
Identification Color
Black phase conductors
Yellow striped neutral or numbering
Packaging
Master cutting lengths on non-returnable wooden reels
Building Wire
16
17
Building Wire
URD, Triplex TYPE
600V URD, Triplex
XLPE Insulation, 600 Volts, 90°C
The cables are recommended for directly buried or installed in ducts for 600 volt
secondary distribution. Triplex cable is designed for application as a secondary in threewire, single-phase underground distribution systems operated at 600 volts or less. It can
be installed in direct burial or in ducts.
Aluminum Conductor
XLPE Insulation
APPLICATIONS
�Underground distribution from a power supply source
to the service entrance equipment of a building
�Maximum operating temperature of 90℃
�Direct burial application or in ducts
�600 volts
Size
Strands
AWG
Insulation
Thickness
Size
mils
AWG
Strands
Single
Approx.
Phase
Overall
Insulation
Thickness Conductor Diameter
mils
inches
inches
Ampacity
Weight
In
Duct
Direct
Burial
lbs/1000ft
6
7/w
60
6
7/w
60
0.299
0.646
143
95
70
STANDARDS
Vassar
4
7/w
60
4
7/w
60
0.345
0.754
203
125
90
ASTM B-230, B-231 and ICEA S-66-524
UL Standard 854 for Type USE
Stephens
2
7/w
60
4
7/w
60
0.403
0.842
264
165
120
Ramapo
2
7/w
60
2
7/w
60
0.403
0.874
294
165
120
Brenau
1/0
19/w
80
2
7/w
60
0.522
1.064
408
215
160
Bergen
1/0
19/w
80
1/0
19/w
80
0.522
1.133
465
215
160
Converse
2/0
19/w
80
1
19/w
80
0.566
1.174
502
245
180
Hunter
2/0
19/w
80
2/0
19/w
80
0.566
1.228
560
245
180
Packaging
Hollins
3/0
19/w
80
1/0
19/w
80
0.616
1.276
606
280
205
Master cutting lengths on non-returnable wooden reels
Rockland
3/0
19/w
80
3/0
19/w
80
0.616
1.336
678
280
205
Sweetbriar
4/0
19/w
80
2/0
19/w
80
0.672
1.389
739
315
240
Monmouth
4/0
19/w
80
4/0
19/w
80
0.672
1.457
828
315
240
Pratt
250
37/w
95
3/0
19/w
80
0.748
1.538
893
345
265
Wesleyan
350
37/w
95
4/0
19/w
80
0.851
1.736
1,166
415
320
Holyoke
500
37/w
95
300
37/w
95
0.979
2.008
1,607
495
395
Rider
500
37/w
95
350
37/w
95
0.979
2.035
1,663
495
395
Fairfield
750
61/w
110
500
37/w
95
1.188
2.086
2,304
615
525
Identification Color
Black phase conductors
Yellow striped neutral or numbering
18
Code
Name
Neutral
Erksine
PRODUCT CONSTRUCTION
Building Wire
Phase Conductor
19
Building Wire
URD, Triplex TYPE
600V URD, Triplex
XLPE Insulation, 600 Volts, 90°C
The cables are recommended for directly buried or installed in ducts for 600 volt
secondary distribution. Triplex cable is designed for application as a secondary in threewire, single-phase underground distribution systems operated at 600 volts or less. It can
be installed in direct burial or in ducts.
Aluminum Conductor
XLPE Insulation
APPLICATIONS
�Underground distribution from a power supply source
to the service entrance equipment of a building
�Maximum operating temperature of 90℃
�Direct burial application or in ducts
�600 volts
Size
Strands
AWG
Insulation
Thickness
Size
mils
AWG
Strands
Single
Approx.
Phase
Overall
Insulation
Thickness Conductor Diameter
mils
inches
inches
Ampacity
Weight
In
Duct
Direct
Burial
lbs/1000ft
6
7/w
60
6
7/w
60
0.299
0.646
143
95
70
STANDARDS
Vassar
4
7/w
60
4
7/w
60
0.345
0.754
203
125
90
ASTM B-230, B-231 and ICEA S-66-524
UL Standard 854 for Type USE
Stephens
2
7/w
60
4
7/w
60
0.403
0.842
264
165
120
Ramapo
2
7/w
60
2
7/w
60
0.403
0.874
294
165
120
Brenau
1/0
19/w
80
2
7/w
60
0.522
1.064
408
215
160
Bergen
1/0
19/w
80
1/0
19/w
80
0.522
1.133
465
215
160
Converse
2/0
19/w
80
1
19/w
80
0.566
1.174
502
245
180
Hunter
2/0
19/w
80
2/0
19/w
80
0.566
1.228
560
245
180
Packaging
Hollins
3/0
19/w
80
1/0
19/w
80
0.616
1.276
606
280
205
Master cutting lengths on non-returnable wooden reels
Rockland
3/0
19/w
80
3/0
19/w
80
0.616
1.336
678
280
205
Sweetbriar
4/0
19/w
80
2/0
19/w
80
0.672
1.389
739
315
240
Monmouth
4/0
19/w
80
4/0
19/w
80
0.672
1.457
828
315
240
Pratt
250
37/w
95
3/0
19/w
80
0.748
1.538
893
345
265
Wesleyan
350
37/w
95
4/0
19/w
80
0.851
1.736
1,166
415
320
Holyoke
500
37/w
95
300
37/w
95
0.979
2.008
1,607
495
395
Rider
500
37/w
95
350
37/w
95
0.979
2.035
1,663
495
395
Fairfield
750
61/w
110
500
37/w
95
1.188
2.086
2,304
615
525
Identification Color
Black phase conductors
Yellow striped neutral or numbering
18
Code
Name
Neutral
Erksine
PRODUCT CONSTRUCTION
Building Wire
Phase Conductor
19
Building Wire
URD, Quadruplex TYPE
600V URD, Quadruplex
XLPE Insulation, 600 Volts, 90°C
The cables are recommended for directly buried or installed in ducts for 600 volt
secondary distribution. Quadruplex cable is designed for application as a secondary in
three-phase, four-wire, underground distribution systems operated at 600 volts or less.
It can be installed in direct burial or in ducts.
Aluminum Conductor
XLPE Insulation
APPLICATIONS
�Underground distribution from a supply source to the service
entrance equipment of a building
�Maximum operating temperature of 90℃
�Direct burial application or in ducts
�600 volts
Size
Strands
AWG
Insulation
Thickness
Size
mils
AWG
Strands
Single
Approx.
Phase
Overall
Insulation
Thickness Conductor Diameter
mils
inches
inches
Ampacity
Weight
Direct
Burial
In
Duct
lbs/1000ft
4
7/w
60
4
7/w
60
0.345
0.845
270
120
85
Dyke
2
7/w
60
4
7/w
60
0.403
0.945
361
155
115
ASTM B-230, B-231 and ICEA S-66-524
UL Standard 854 for Type USE
Wittenberg
2
7/w
60
2
7/w
60
0.403
0.985
391
155
115
Notre Dame
1/0
19/w
80
2
7/w
60
0.522
1.231
562
200
150
PRODUCT CONSTRUCTION
Purdue
1/0
19/w
80
1/0
19/w
80
0.522
1.270
619
200
150
Syracuse
2/0
19/w
80
1
19/w
80
0.566
1.338
688
225
170
Black phase conductors
Yellow striped neutral or numbering
Lafayette
2/0
19/w
80
2/0
19/w
80
0.566
1.376
745
225
170
Swarthmore
3/0
19/w
80
1/0
19/w
80
0.616
1.449
832
250
195
Packaging
Davidson
3/0
19/w
80
3/0
19/w
80
0.616
1.497
903
250
195
Wake Forest
4/0
19/w
80
2/0
19/w
80
1.622
1.587
1,014
290
225
Earlham
4/0
19/w
80
4/0
19/w
80
1.672
1.632
1,103
290
225
Slippery Rock
350
37/w
95
4/0
19/w
80
0.851
2.054
1,632
385
305
Wofford
500
37/w
95
350
37/w
95
0.851
2.348
2,174
467
420
Windham
750
61/w
110
500
37/w
95
0.979
2.850
2,542
615
492
Identification Color
Master cutting lengths on non-returnable wooden reels
20
Code
Name
Neutral
Tulsa
STANDARDS
Building Wire
Phase Conductor
21
Building Wire
URD, Quadruplex TYPE
600V URD, Quadruplex
XLPE Insulation, 600 Volts, 90°C
The cables are recommended for directly buried or installed in ducts for 600 volt
secondary distribution. Quadruplex cable is designed for application as a secondary in
three-phase, four-wire, underground distribution systems operated at 600 volts or less.
It can be installed in direct burial or in ducts.
Aluminum Conductor
XLPE Insulation
APPLICATIONS
�Underground distribution from a supply source to the service
entrance equipment of a building
�Maximum operating temperature of 90℃
�Direct burial application or in ducts
�600 volts
Size
Strands
AWG
Insulation
Thickness
Size
mils
AWG
Strands
Single
Approx.
Phase
Overall
Insulation
Thickness Conductor Diameter
mils
inches
inches
Ampacity
Weight
Direct
Burial
In
Duct
lbs/1000ft
4
7/w
60
4
7/w
60
0.345
0.845
270
120
85
Dyke
2
7/w
60
4
7/w
60
0.403
0.945
361
155
115
ASTM B-230, B-231 and ICEA S-66-524
UL Standard 854 for Type USE
Wittenberg
2
7/w
60
2
7/w
60
0.403
0.985
391
155
115
Notre Dame
1/0
19/w
80
2
7/w
60
0.522
1.231
562
200
150
PRODUCT CONSTRUCTION
Purdue
1/0
19/w
80
1/0
19/w
80
0.522
1.270
619
200
150
Syracuse
2/0
19/w
80
1
19/w
80
0.566
1.338
688
225
170
Black phase conductors
Yellow striped neutral or numbering
Lafayette
2/0
19/w
80
2/0
19/w
80
0.566
1.376
745
225
170
Swarthmore
3/0
19/w
80
1/0
19/w
80
0.616
1.449
832
250
195
Packaging
Davidson
3/0
19/w
80
3/0
19/w
80
0.616
1.497
903
250
195
Wake Forest
4/0
19/w
80
2/0
19/w
80
1.622
1.587
1,014
290
225
Earlham
4/0
19/w
80
4/0
19/w
80
1.672
1.632
1,103
290
225
Slippery Rock
350
37/w
95
4/0
19/w
80
0.851
2.054
1,632
385
305
Wofford
500
37/w
95
350
37/w
95
0.851
2.348
2,174
467
420
Windham
750
61/w
110
500
37/w
95
0.979
2.850
2,542
615
492
Identification Color
Master cutting lengths on non-returnable wooden reels
20
Code
Name
Neutral
Tulsa
STANDARDS
Building Wire
Phase Conductor
21
Building Wire
TC CONTROL CABLE TYPE
600V TC CONTROL CABLE
TFFN, THWN or THHN Conductors, PVC Jacket, 600 Volts, 90°C
Copper Conductors
The cables are recommended for operation at 90°C maximum continuous conductor
temperature in dry location and 75°C for wet locations.
TFFN, THWN or
THHN Conductors
PVC Jacket
APPLICATIONS
STANDARDS
�Industrial control, lighting and signal circuits where
small diameter, flame retardant cables are required.
�Primary installations in cable trays, raceways or outdoor locations where supported by a messenger wire
�Approved for direct burial, Class 1, Div. 2 hazardous
locations per NEC� Article 501 and Class 1 circuits per
NEC� Article 725
UL Standard 1581 for CT use
UL Standard 1277 for direct burial and sunlight resistance
IEEE 383(70,000 Btu/hr) vertical cable tray flame tests
PRODUCT CONSTRUCTION
Conductor
Bare annealed copper per ASTM B-3
Class B stranding per ASTM B-8
Insulation
Heat resistant PVC with an oil and gasoline
resistant nylon jacket per UL 83 for Type THHN/THWN
and UL 62 for Type TFFN
Jacket
Heat, moisture and sunlight resistant PVC
Color Code ICEA Method 1, K-2
18AWG (7 strands) TFFN/PVC
No. of
Conductors
2(Flat)
2(Round)
3
4
5
6
7
9
10
12
15
16
19
20
25
30
37
Identification Color
ICEA S-66-524, Method 1, Table K-2 or
numbering with black insulation
Print Legend
E111360 (UL) SIZE 600V TYPE TC THHN OR THWN
{CDRS} SUNLIGHT RESISTANT DIRECT BURIAL
Packaging
Master cutting lengths on non-returnable wooden reels
Building Wire
22
Nominal
Nominal Jacket
Outer Diameter
Thickness
14AWG (7 strands) THHN-THWN/PVC
mils
inches
Shipping
Weight
per mft
45
45
45
45
45
45
45
45
45
45
45
60
60
60
60
60
60
0.18X0.26
0.27
0.28
0.30
0.32
0.35
0.37
0.44
0.45
0.46
0.49
0.51
0.57
0.58
0.65
0.69
0.75
41
42
50
60
71
80
89
112
127
156
169
191
214
226
285
330
390
12AWG (7 strands) THHN-THWN/PVC
2(Flat)
2(Round)
3
4
5
6
7
9
10
12
15
16
19
20
25
30
37
45
45
45
45
45
45
60
60
60
60
60
60
60
80
80
80
80
0.23X0.36
0.36
0.38
0.41
0.45
0.49
0.53
0.60
0.64
0.67
0.74
0.76
0.80
0.82
0.96
1.03
1.12
75
86
109
135
165
191
220
295
318
375
452
484
565
630
768
895
1,089
Nominal Jacket Approx Overall
Diameter
Thickness
mils
inches
Shipping
Weight
per mft
45
45
45
45
45
45
45
60
60
60
60
60
60
60
60
80
80
0.20X0.32
0.32
0.34
0.37
0.40
0.43
0.45
0.51
0.57
0.59
0.66
0.67
0.71
0.72
0.80
0.91
0.98
60
65
80
100
120
140
160
220
230
275
330
350
400
420
520
660
780
10AWG (7 strands) THHN-THWN/PVC
45
45
45
45
60
60
60
60
60
60
0.26X0.42
0.42
0.45
0.49
0.57
0.62
0.66
0.72
0.79
0.80
108
115
162
198
255
298
344
435
475
560
Conductor
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Tracer
Stripe
Base
Color
Black
Red
Blue
Orange
Yellow
Brown
Red
Black
Blue
Black
Orange Black
Yellow
Black
Brown
Black
Black
Red
Blue
Red
Orange
Red
Yellow
Red
Brown
Red
Black
Blue
Red
Blue
Orange
Blue
Yellow
Blue
Brown
Blue
Black Orange
Red
Orange
Blue
Orange
Yellow Orange
Brown Orange
Black
Yellow
Red
Yellow
Blue
Yellow
Orange Yellow
Brown Yellow
Black
Brown
Red
Brown
Blue
Brown
Orange Brown
Yellow Brown
Red Black-Blue
23
Building Wire
TC CONTROL CABLE TYPE
600V TC CONTROL CABLE
TFFN, THWN or THHN Conductors, PVC Jacket, 600 Volts, 90°C
Copper Conductors
The cables are recommended for operation at 90°C maximum continuous conductor
temperature in dry location and 75°C for wet locations.
TFFN, THWN or
THHN Conductors
PVC Jacket
APPLICATIONS
STANDARDS
�Industrial control, lighting and signal circuits where
small diameter, flame retardant cables are required.
�Primary installations in cable trays, raceways or outdoor locations where supported by a messenger wire
�Approved for direct burial, Class 1, Div. 2 hazardous
locations per NEC� Article 501 and Class 1 circuits per
NEC� Article 725
UL Standard 1581 for CT use
UL Standard 1277 for direct burial and sunlight resistance
IEEE 383(70,000 Btu/hr) vertical cable tray flame tests
PRODUCT CONSTRUCTION
Conductor
Bare annealed copper per ASTM B-3
Class B stranding per ASTM B-8
Insulation
Heat resistant PVC with an oil and gasoline
resistant nylon jacket per UL 83 for Type THHN/THWN
and UL 62 for Type TFFN
Jacket
Heat, moisture and sunlight resistant PVC
Color Code ICEA Method 1, K-2
18AWG (7 strands) TFFN/PVC
No. of
Conductors
2(Flat)
2(Round)
3
4
5
6
7
9
10
12
15
16
19
20
25
30
37
Identification Color
ICEA S-66-524, Method 1, Table K-2 or
numbering with black insulation
Print Legend
E111360 (UL) SIZE 600V TYPE TC THHN OR THWN
{CDRS} SUNLIGHT RESISTANT DIRECT BURIAL
Packaging
Master cutting lengths on non-returnable wooden reels
Building Wire
22
Nominal
Nominal Jacket
Outer Diameter
Thickness
14AWG (7 strands) THHN-THWN/PVC
mils
inches
Shipping
Weight
per mft
45
45
45
45
45
45
45
45
45
45
45
60
60
60
60
60
60
0.18X0.26
0.27
0.28
0.30
0.32
0.35
0.37
0.44
0.45
0.46
0.49
0.51
0.57
0.58
0.65
0.69
0.75
41
42
50
60
71
80
89
112
127
156
169
191
214
226
285
330
390
12AWG (7 strands) THHN-THWN/PVC
2(Flat)
2(Round)
3
4
5
6
7
9
10
12
15
16
19
20
25
30
37
45
45
45
45
45
45
60
60
60
60
60
60
60
80
80
80
80
0.23X0.36
0.36
0.38
0.41
0.45
0.49
0.53
0.60
0.64
0.67
0.74
0.76
0.80
0.82
0.96
1.03
1.12
75
86
109
135
165
191
220
295
318
375
452
484
565
630
768
895
1,089
Nominal Jacket Approx Overall
Diameter
Thickness
mils
inches
Shipping
Weight
per mft
45
45
45
45
45
45
45
60
60
60
60
60
60
60
60
80
80
0.20X0.32
0.32
0.34
0.37
0.40
0.43
0.45
0.51
0.57
0.59
0.66
0.67
0.71
0.72
0.80
0.91
0.98
60
65
80
100
120
140
160
220
230
275
330
350
400
420
520
660
780
10AWG (7 strands) THHN-THWN/PVC
45
45
45
45
60
60
60
60
60
60
0.26X0.42
0.42
0.45
0.49
0.57
0.62
0.66
0.72
0.79
0.80
108
115
162
198
255
298
344
435
475
560
Conductor
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Tracer
Stripe
Base
Color
Black
Red
Blue
Orange
Yellow
Brown
Red
Black
Blue
Black
Orange Black
Yellow
Black
Brown
Black
Black
Red
Blue
Red
Orange
Red
Yellow
Red
Brown
Red
Black
Blue
Red
Blue
Orange
Blue
Yellow
Blue
Brown
Blue
Black Orange
Red
Orange
Blue
Orange
Yellow Orange
Brown Orange
Black
Yellow
Red
Yellow
Blue
Yellow
Orange Yellow
Brown Yellow
Black
Brown
Red
Brown
Blue
Brown
Orange Brown
Yellow Brown
Red Black-Blue
23
Building Wire
TC POWER CABLE TYPE
600V TC POWER CABLE
THHN-THWN/PVC with Ground, 600 Volts, 90°C Dry, 75°C Wet
Grounding Conductor
The cables are recommended for operation at 90°C maximum continuous conductor
temperature in dry location and 75°C for wet locations.
Copper Conductor
THWN-THHN Conductors
PVC Jacket
APPLICATIONS
STANDARDS
�Industrial power to motors and other electrical devices
�Primary installations in cable trays, raceways or outdoor locations where supported by a messenger wire
�Approved for direct burial, Class 1, Div. 2 hazardous
locations per NEC� Article 501 and Class 1 circuits per
NEC� Article 725
UL Standard 1581 for CT use
UL Standard 1277 for direct burial and sunlight
resistance
IEEE 383(70,000 Btu/hr) vertical cable tray flame tests
PRODUCT CONSTRUCTION
Conductor
Bare annealed copper per ASTM B-8
Class B stranding per ASTM B-8 or B-787
Insulation
Heat resistant PVC with an oil and gasoline resistant
nylon jacket per UL 83 for Type THHN/THWN
Jacket
Heat, moisture and sunlight resistant PVC
Identification Color
ICEA S-66-524, Method 4
Print Legend
E111360 (UL) SIZE 600V TYPE TC THHN OR THWN
{CDRS} SUNLIGHT RESISTANT DIRECT BURIAL
Packaging
Master cutting lengths on non-returnable wooden reels
Conductor
Size
AWG/MCM
No. of
Strands
No. of
Conductor
8
8
6
6
4
4
2
2
1
1/0
2/0
3/0
4/0
8
8
6
6
4
4
2
1/0
2/0
3/0
4/0
7
7
7
7
7
7
7
7
19
19
19
19
19
7
7
7
7
7
7
7
19
19
19
19
3
3
3
3
3
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
4
4
4
1
2
3
4
24
Nominal Jacket
Thickness
Nominal
Outer Diameter
AWG
mils
inches
10
8
8
6
6
6
6
4
4
10
8
8
6
6
4
4
4
60
60
60
60
60
60
80
80
80
80
80
80
80
60
60
60
60
60
60
80
80
80
80
110
0.65
0.65
0.73
0.73
0.85
0.85
1.01
1.01
1.21
1.25
1.38
1.42
1.55
0.71
0.71
0.79
0.79
0.95
0.95
1.10
1.35
1.45
1.58
1.78
Shipping
Weight
per mft
315
285
430
380
705
655
990
910
1,205
1,460
1,840
2,190
2,750
385
352
543
492
825
757
1,230
1,810
2,450
2,665
3,500
Color Code - ICEA Method 4
Conductor Number
Building Wire
Ground
Size
Base Color
Black
Black
Black
Black
Printed Surface
1-ONE
2-TWO
3-THREE
4-FOUR
25
Building Wire
TC POWER CABLE TYPE
600V TC POWER CABLE
THHN-THWN/PVC with Ground, 600 Volts, 90°C Dry, 75°C Wet
Grounding Conductor
The cables are recommended for operation at 90°C maximum continuous conductor
temperature in dry location and 75°C for wet locations.
Copper Conductor
THWN-THHN Conductors
PVC Jacket
APPLICATIONS
STANDARDS
�Industrial power to motors and other electrical devices
�Primary installations in cable trays, raceways or outdoor locations where supported by a messenger wire
�Approved for direct burial, Class 1, Div. 2 hazardous
locations per NEC� Article 501 and Class 1 circuits per
NEC� Article 725
UL Standard 1581 for CT use
UL Standard 1277 for direct burial and sunlight
resistance
IEEE 383(70,000 Btu/hr) vertical cable tray flame tests
PRODUCT CONSTRUCTION
Conductor
Bare annealed copper per ASTM B-8
Class B stranding per ASTM B-8 or B-787
Insulation
Heat resistant PVC with an oil and gasoline resistant
nylon jacket per UL 83 for Type THHN/THWN
Jacket
Heat, moisture and sunlight resistant PVC
Identification Color
ICEA S-66-524, Method 4
Print Legend
E111360 (UL) SIZE 600V TYPE TC THHN OR THWN
{CDRS} SUNLIGHT RESISTANT DIRECT BURIAL
Packaging
Master cutting lengths on non-returnable wooden reels
Conductor
Size
AWG/MCM
No. of
Strands
No. of
Conductor
8
8
6
6
4
4
2
2
1
1/0
2/0
3/0
4/0
8
8
6
6
4
4
2
1/0
2/0
3/0
4/0
7
7
7
7
7
7
7
7
19
19
19
19
19
7
7
7
7
7
7
7
19
19
19
19
3
3
3
3
3
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
4
4
4
1
2
3
4
24
Nominal Jacket
Thickness
Nominal
Outer Diameter
AWG
mils
inches
10
8
8
6
6
6
6
4
4
10
8
8
6
6
4
4
4
60
60
60
60
60
60
80
80
80
80
80
80
80
60
60
60
60
60
60
80
80
80
80
110
0.65
0.65
0.73
0.73
0.85
0.85
1.01
1.01
1.21
1.25
1.38
1.42
1.55
0.71
0.71
0.79
0.79
0.95
0.95
1.10
1.35
1.45
1.58
1.78
Shipping
Weight
per mft
315
285
430
380
705
655
990
910
1,205
1,460
1,840
2,190
2,750
385
352
543
492
825
757
1,230
1,810
2,450
2,665
3,500
Color Code - ICEA Method 4
Conductor Number
Building Wire
Ground
Size
Base Color
Black
Black
Black
Black
Printed Surface
1-ONE
2-TWO
3-THREE
4-FOUR
25
Building Wire
TC POWER CABLE TYPE
600V TC POWER CABLE
XHHW-2/PVC with Ground, 600 Volts, 90°C Wet or Dry
Uncoated Copper Ground
Conductors
The cables are recommended for operation at 90°C maximum continuous conductor
temperature in wet or dry locations.
Uncoated Copper Conductors
XLPE Insulation
Fillers
Tape
PVC Jacket
APPLICATIONS
STANDARDS
�Industrial power to motors and other electrical devices
�Primary installations in cable trays, raceways or outdoor locations where supported by a messenger wire
�Approved for direct burial, Class 1, Div. 2 hazardous
locations per NEC� Article 501 and Class 1 circuits per
NEC� Article 725
UL Standard 1581 for CT use
UL Standard 1277 for direct burial and sunlight resistance
UL Standard 44 for rubber insulated wires and cables
IEEE 383(70,000 Btu/hr) vertical cable tray flame tests
Three Conductors with Grounding Conductor
PRODUCT CONSTRUCTION
Conductor
Bare annealed copper per ASTM B-8
Insulation
Conductor shall be insulated with cross-linked
polyethylene, meeting the requirements Type
XHHW-2 of UL 44
Identification Color
Size
Thickness (mils)
No. of
Strands
AWG or kcmil
8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1,000
Insulation
Jacket
45
45
45
45
55
55
55
55
55
65
65
65
80
80
60
60
80
80
80
80
80
80
80
110
110
110
110
140
7
7
7
7
19
19
19
19
19
37
37
37
61
61
Size
Print Legend
E111360 (UL) SIZE 600V TYPE TC XHHW-2
{CDRS} SUNLIGHT RESISTANT DIRECT BURIAL
Packaging
Master cutting lengths on non-returnable
wooden reels
Color Code - ICEA Method 4
26
�
Grounding
Conductor Size
Approx.
Net Weight
inches
AWG
lbs/1000ft
0.66
0.74
0.88
1.00
1.13
1.22
1.31
1.42
1.55
1.76
1.98
2.26
2.71
3.10
10
8
8
6
6
6
6
4
4
4
3
2
1
1/0
325
450
655
960
1,170
1,425
1,720
2,140
2,635
3,180
4,285
5,940
9,010
11,700
55
75
95
130
150
170
195
225
260
290
350
430
535
615
Nominal
Diameter
�Grounding
Conductor Size
Approx.
Net Weight
��
Ampacity
���
Ampacity-tray
44
60
76
104
120
136
156
180
208
232
280
344
428
55
75
95
130
150
170
195
225
260
290
350
430
535
��
Ampacity
Four Conductors with Grounding Conductors
ICEA S-66-524, Method 4
Building Wire
Nominal
Diameter
Conductor
Number
Base
Color
Printed
Surface
1
2
3
4
Black
Black
Black
Black
1-ONE
2-TWO
3-THREE
4-FOUR
No. of
Strands
AWG or kcmil
8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
7
7
7
7
19
19
19
19
19
37
37
37
61
Thickness (mils)
Insulation
Jacket
inches
AWG
lbs/1000ft
45
45
45
45
55
55
55
55
55
65
65
65
80
60
60
80
80
80
80
80
80
110
110
110
110
140
0.72
0.81
0.96
1.10
1.25
1.35
1.45
1.58
1.77
1.93
2.18
2.50
3.12
12
10
10
9
9
9
9
7
7
7
6
5
4
415
575
840
1,200
1,545
1,835
2,195
2,800
3,460
4,040
5,475
7,635
11,400
� : Grounding conductors per UL Standard 1277 for Type TC Tray Cable.
�� : Ampacity in accordance with the National Electrical Code for cables in raceway or directly buried, at the conductor temperature indicated in wet or dry locations, 30℃
ambient temperature.
���: Ampacity in accordance with Art. 318-11 of the National Electrical Code for cables installed in uncovered cable tray with or without maintained spacing,
at the conductor temperature indicated in wet or dry locations, 30℃ ambient temperature. Derating for more than three conductors per Note 8 is not required for cable in tray.
27
Building Wire
TC POWER CABLE TYPE
600V TC POWER CABLE
XHHW-2/PVC with Ground, 600 Volts, 90°C Wet or Dry
Uncoated Copper Ground
Conductors
The cables are recommended for operation at 90°C maximum continuous conductor
temperature in wet or dry locations.
Uncoated Copper Conductors
XLPE Insulation
Fillers
Tape
PVC Jacket
APPLICATIONS
STANDARDS
�Industrial power to motors and other electrical devices
�Primary installations in cable trays, raceways or outdoor locations where supported by a messenger wire
�Approved for direct burial, Class 1, Div. 2 hazardous
locations per NEC� Article 501 and Class 1 circuits per
NEC� Article 725
UL Standard 1581 for CT use
UL Standard 1277 for direct burial and sunlight resistance
UL Standard 44 for rubber insulated wires and cables
IEEE 383(70,000 Btu/hr) vertical cable tray flame tests
Three Conductors with Grounding Conductor
PRODUCT CONSTRUCTION
Conductor
Bare annealed copper per ASTM B-8
Insulation
Conductor shall be insulated with cross-linked
polyethylene, meeting the requirements Type
XHHW-2 of UL 44
Identification Color
Size
Thickness (mils)
No. of
Strands
AWG or kcmil
8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1,000
Insulation
Jacket
45
45
45
45
55
55
55
55
55
65
65
65
80
80
60
60
80
80
80
80
80
80
80
110
110
110
110
140
7
7
7
7
19
19
19
19
19
37
37
37
61
61
Size
Print Legend
E111360 (UL) SIZE 600V TYPE TC XHHW-2
{CDRS} SUNLIGHT RESISTANT DIRECT BURIAL
Packaging
Master cutting lengths on non-returnable
wooden reels
Color Code - ICEA Method 4
26
�
Grounding
Conductor Size
Approx.
Net Weight
inches
AWG
lbs/1000ft
0.66
0.74
0.88
1.00
1.13
1.22
1.31
1.42
1.55
1.76
1.98
2.26
2.71
3.10
10
8
8
6
6
6
6
4
4
4
3
2
1
1/0
325
450
655
960
1,170
1,425
1,720
2,140
2,635
3,180
4,285
5,940
9,010
11,700
55
75
95
130
150
170
195
225
260
290
350
430
535
615
Nominal
Diameter
�Grounding
Conductor Size
Approx.
Net Weight
��
Ampacity
���
Ampacity-tray
44
60
76
104
120
136
156
180
208
232
280
344
428
55
75
95
130
150
170
195
225
260
290
350
430
535
��
Ampacity
Four Conductors with Grounding Conductors
ICEA S-66-524, Method 4
Building Wire
Nominal
Diameter
Conductor
Number
Base
Color
Printed
Surface
1
2
3
4
Black
Black
Black
Black
1-ONE
2-TWO
3-THREE
4-FOUR
No. of
Strands
AWG or kcmil
8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
7
7
7
7
19
19
19
19
19
37
37
37
61
Thickness (mils)
Insulation
Jacket
inches
AWG
lbs/1000ft
45
45
45
45
55
55
55
55
55
65
65
65
80
60
60
80
80
80
80
80
80
110
110
110
110
140
0.72
0.81
0.96
1.10
1.25
1.35
1.45
1.58
1.77
1.93
2.18
2.50
3.12
12
10
10
9
9
9
9
7
7
7
6
5
4
415
575
840
1,200
1,545
1,835
2,195
2,800
3,460
4,040
5,475
7,635
11,400
� : Grounding conductors per UL Standard 1277 for Type TC Tray Cable.
�� : Ampacity in accordance with the National Electrical Code for cables in raceway or directly buried, at the conductor temperature indicated in wet or dry locations, 30℃
ambient temperature.
���: Ampacity in accordance with Art. 318-11 of the National Electrical Code for cables installed in uncovered cable tray with or without maintained spacing,
at the conductor temperature indicated in wet or dry locations, 30℃ ambient temperature. Derating for more than three conductors per Note 8 is not required for cable in tray.
27
Building Wire
www.taihan.com
Head Office
Insong Bldg.194-15, 1-ga, Hoehyeon-dong, Jung-gu, Seoul, Korea
Tel. 82-2-316-9114
Fax. 82-2-754-5493
Overseas Sales Team
Tel. 82-2-316-9425, 9430
Fax. 82-2-754-5481
Domestic Sales Team
Tel . 82-2-316-9267, 9310
Fax. 82-2-754-5493
R&D CENTER AND PLANTS
OVERSEAS SUBSIDIARIES
R & D Center
785, Gwanyang-dong,
Dongan-ku, Anyang,
Gyunggi-do, Korea
Anyang Plant
785, Gwanyang-dong,
Dongan-ku, Anyang,
Gyunggi-do, Korea
Shihung Plant
113-119, Shihung-dong,
Kumchon-gu, Seoul,
Korea
Ansan Plant
603, Seonggok-dong,
Danwon-ku, Ansan,
Gyunggi-do, Korea
Malesela Taihan Electric Cable(Pty) Ltd.
Vereeniging 1930, Steel Road,
Peacehaven Vereeniging 1939,
Gauteng, South Africa
Skytel Co., Ltd
Skytel Plaza Building
ChinggisKhan Ave-9,
Ulaanbaatar 210603, Mongolia
Tel. 82-31-420-9590
Fax. 82-31-423-2685
Tel. 82-31-420-9114
Fax. 82-31-423-2685
Tel. 82-2-890-9114
Fax. 82-2-892-9387
Tel. 82-31-490-5114
Fax. 82-31-491-3721
Tel. 27-16-450-8200
Fax. 27-16-423-3406
htth://www. m-tec.co.za
Tel. 976-11-318488
Fax. 976-11-318487
htth://www.skytel.com
OVERSEAS OFFICES
Kuala Lumpur Office
15th Floor, Kenanga
International, JL. Sultan
Ismail, 50250 Kuala
Lumpur, Malaysia
Riyadh Office
AI Akariyah Shopping
Center 2, Room No. 726,
Olaya Road, P.O.Box 201,
Riyadh, Saudi Arabia
Sanghai Office
A410 Far EastInternational
Plaza 319 Xian Xia Road
Changning District,
Shanghai, China
Philippines Office
10A Queen’s Street Dona
Rita Village Talamban
Cebu City 6000
Dubai Office
Flat no. 705, Al Safa
Tower, Sheikh Zayed
Road, Dubai, U.A.E
P.O.Box117561
Tailand Office
253, 26th Floor Asoke,
Sukhumvit 21 Road,
Klongtoeynua, Wattana,
Bangkok 10110, Thailand
Tel. 65-6842-5069
Fax. 65-6842-5076
Tel. 60-3-2161-8017
Fax. 60-3-2161-3628
Tel. 966-1-419-0227
Fax. 966-1-419-0262
Tel. 86-21-6235-1263
Fax. 86-21-6235-1267
Tel. 63-32-346-8799
Fax. 63-32-346-8799
Tel. 97-14-331-7233
Fax. 97-14-331-7322
Tel. 66-2-664-1464
Fax. 66-2-664-4002
�Specifications are subject to improvement or change without notice. Please contact your local agent or TAIHAN to confirm the latest product information
TPE-0701-0509
Singapore Office
629 Aljunied Road
#05-19 Cititech Industrial
Building, Singapore,
389838, Singapore
Download