To: All Plan Holders & Bidding Contractors From: Integrity Construction Services, LLC. (Construction Manager) Date: June 26, 2015 Re: Kirtland – Health Sciences Education and Training Center Addendum No. 2 This addendum is being issued for the purpose of modifying and/or clarifying the original Bidding Documents and shall take precedence over them. All work included herein shall be in accordance with the general requirements of the original bidding documents, except as specifically noted herein. This addendum is being sent to all known plan holders, suppliers, plan rooms, and governmental agencies having Bidding Documents. BID SCOPE CLARIFICATIONS: Item #1 Bid Package #1 – Sitework This bid package is to include all required topsoil within the proposed irrigation/hydroseed limits, with the exception of required topsoil for landscape beds (i.e. areas with plantings). Item #2 Bid Package #1 - Sitework This bid package is to provide and install (1) 2,500 gallon grease interceptor tank per plans and specifications. Item #3 Bid Package #1 - Sitework This bid package to provide and install 2-1/2” domestic water service line from proposed well location into mechanical room as clarified in this addendum. Item #4 Bid Package #3 – Landscaping, Pond and Irrigation This bid package is to include 45 mil EPDM pond liner per plans and specifications. 1 of 2 Item #5 Bid Package #24 – Painting and Staining For decorative metal railings (guardrail detail on Sheet A15), aluminum square tubing has been changed to carbon steel, prime painted by Bid Package #12 Structural and Miscellaneous Steel. Bid Package #24 – Painting and Staining is to provide finish painting in the field. CIVIL ITEMS: See Addendum No. 2 dated June 26, 2015 from Rowe Professional Services (1 page) Attachments: § Civil sheet 9 of 20 ARCHITECTURAL ITEMS: See Addendum No. 2 dated June 26, 2015 from Seidell Architects (4 pages) Attachments: § § § § § § § § § § Sheet A32 (1 page) Sheet S34 (1 page) Sheet FS2 (1 page) Sheet S0.1 (1 page) Sheet S0.4 (1 page) Sheet S1.3A (1 page) Sheet S2.4 (1 page) Sheet S5.6 (1 page) Walk-in Cooler Condensing Specifications (1 page) Walk-in Freezer Condensing Unit Specifications (1 page) MEP ITEMS: See Addendum No.2 dated June 26, 2015 from Nealis Engineering (13 pages) Attachments: § Mechanical Specification Section 15188 “HVAC Pumps” (3 pages) § Mechanical Specification Section 15720 “Air Handling Units” (3 pages) § Mechanical Specification Section 15542 “Dedicated Outdoor Air Systems and Make-up Air” (8 pages) § Mechanical Specification Section 15739 “Critical Cooling Units” (2 pages) § Mechanical Specification Section 15260 “Thermal Insulation” (9 pages) § Generator Gas Piping Detail (Drawing Sheet P2) (1 page) § Revised Lighting Control Panel (LCP-1) Schedule (Drawing Sheet E8) (1 page) 2 of 2 June 26, 2015 Project: Kirtland Community College Health Sciences Education and Training Center 4800 W. Four Mile Road Grayling, MI 49738 Re: Addendum #2 The following is a compliation of items to be addressed in Addendum #2. These reflect changes and clarifications from the Construction Set issued 6/8/2015 and previous Addendums. 1. Refer to Specification SECTION 05730 DECORATIVE METAL RAILINGS to allow the use of the following acceptable substitutions: a. Carbon steel railing system, factory primed and field painted 2. Refer to Specification SECTION 06402 INTERIOR ARCHITECTURAL WOODWORK AND CABINETRY; Add the following item for Metal Coat Racks shown on Detail 16/A47. Coat racks to be Bobrick Hat & Coat Rack Model 9944 – 4 hooks. 36” long. 22 ga. Stainless steel with exposed surfaces in architectural satin finish. 3. Refer to Specification SECTION 07531 EPDM SINGLE-PLY MEMBRANE ROOFING; Add 1.2,G Metal soffit shown on Detail 3/A13 to be Metal Sales Manufacturing Corporation, Lanced Soffit, Flat Face profile (no ribs), 12” Panel coverage, 26 ga., PVDF (Kynar 500) Finish, Concealed fasteners. 4. Refer to Specification SECTION 07531 EDPM SINGLE PLY MEMBRANE ROOFING adjusted due to specified EDPM membrane not available with reinforcing and also white in color. The following options will be accepted: a. Membrane Roofing to be fully adhered and reinforced TPO roofing, white in color. b. Or Membrane Roofing to be fully adhered and reinforced PVC roofing, white in color. 5. Refer to Specification SECTION 08330 OVERHEAD COILING DOORS Section 1.2,A; add the following acceptable manufacturer: a. Cookson 6. Refer to Specification SECTION 08333 SECURITY GRILLES Section 1.2,A; add the following acceptable manufacturer: a. Cookson b. Raynor 114 N. Court Avenue P.O. Box 2189 Gaylord, MI 49734 989.731.0372 115 S. Arcade Street P.O. Box 414 Gladwin, MI 48624 989.701.7096 7. Refer to Specification SECTION 08410 ALUMINUM ENTRANCES AND STOREFRONTS Section 1.2,A; add the following acceptable manufacturer: a. Tubelite 8. Refer to Specification SECTION 08710 DOOR HARDWARE; Door 102 with hardware set #4 shall be equipped with the following hardware: a. ADA approved gliding track by aluminum door manufacturer b. Lever handle with hook bolt emergency hardware by aluminum door manufacturer c. 1 ea. Mortise Lock MS1850-050 X 4550 MS LEVER 628 d. 1 ea. Mortise Cylinder I5307 X-I15401 26D 9. Refer to Specification SECTION 08710 DOOR HARDWARE; Door 201 is an aluminum door and aluminum frame. Frame 11 has been updated on Sheet A32. 10. Refer to Specification SECTION 08710 DOOR HARDWARE; Door 300 will be added to the door schedule: 3’-6” wide x 7’-0” tall steel insulated service door with exterior welded and painted hollow metal frame. Door hardware set #38. Sheet A32 is updated. The door shall be equipped with the following hardware: a. 3 ea Butt Hinges 35STHB 4545 NRP 26D b. 1 ea Storeroom Lock MR 115 BJSJ-SFL7+PDQ6 32D c. 1 ea Closer 7101 BC AL k0050 10 x 1 1/2LDW B4S 32D d. 1 ea kick plate e. 1 ea Sweep 354C AL f. 1 ea Threshold S205C AL g. 1 ea door seal 854C AL h. 1 ea drip cap 199A AL 11. Refer to Specification SECTION 08800 GLAZING: a. Regarding the entry window system with Vanceva Glass. Bid to include up to 4 colors to be selected by architect from standard colors with up to 4 layers per color. b. Exterior windows: Low-E coating shall be provided on all exterior window units. 12. Refer to Specification SECTION 09255 GYPSUM BOARD ASSEMBLIES, Section 1.2,D,6; shall be deleted. Refer to Specification SECTION 07210 BUILDING INSULATION for sound insulation information. 13. Refer to Specification SECTION 09310 CERAMIC TILE FLOORING- Tile items: a. Floors and ceilings in Locker Room Showers to be StonePeak Pangaea Series 2” x 2” (Tile #4). Color: Moon Shadow. Tile #1 on walls to remain as specified. Sheet A34 has been updated. b. Locker Room Shower thresholds to be marble thresholds. (not cultured as listed in Section 1.2,4,2) c. All floor tile locations to include waterproofing and crack isolation product under the floor tiles, as manufactured by Hydro-Ban or approved equal. d. All Tile #1 in restrooms to have additional schluter metal edging at the top of the tile wainscoting pattern. Addendum #2 Page 2 of 4 14. Refer to Specification SECTION 09512 ACOUSTICAL TILE CEILINGS Section 1.2, A; add the following acceptable manufacturer, with the exception that the acoustical and aesthetic properties match the specifications: a. USG 15. Refer to Specification SECTION 09660 RESILIENT FLOORS AND BASE- Wall base #2 changed to Johnsonite Masquerade Classic 5-1/4” White Wood Beech MW-MB6-Z. Sheet A34 has been updated. 16. Refer to Specification SECTION 09900 PAINTING AND STAINING; Kitchen walls to be full height epoxy paint (not FRP Panels). Sheet A43 has been corrected. Follow the Room Finish Schedule on Sheet A34. 17. Refer to Specification SECTION 09900 PAINTING AND STAINING, Section 1.3, I, 6: a. Exterior Exposed Structural Steel shall be: i. Factory applied finish- Imron Paint by DuPont- selected from standard colors ii. Touch-up weld joints in field to match 18. Refer to Specification SECTION 10650 OPERABLE PARTITIONS: clarification of product to be: a. Paired panel system b. With top and bottom mechanical seals c. Panels to have 16 gauge minimum steel welded frame. d. Header will be pre-drilled by others per manufacturer’s specifications. 19. Refer to Specification SECTION 10650 OPERABLE PARTITIONS Section 1.2, A; add the following acceptable manufacturer: a. Moderco 20. Refer to Specification SECTION 11450 FOOD SERVICE EQUIPMENT: a. See attached updated sheet FS2 for updated items. b. See attached specifications for Walk-In Cooler and Freezer condensing units. Rooftop curbs, chases, and flashing to be included in bid. c. Update to Item #6.2 MAKE-UP AIR UNIT i. Quantity: One (1), Manufacturer: Captive-Aire, Model: A2-D.500-G15 ii. Direct fired gas make up air furnace, 3400 cfm capacity, 208 volt 3 phase with down discharge, pitched roof curb and inlet hood with v-bank filters and motorized back draft damper for rooftop application. Ductwork by HVAC Contractor d. Update to Item #10 TILT SKILLET i. Quantity: One (1), Manufacturer: Vulcan, Model: VG30 ii. Braising Pan, Gas, 30-gallon capacity, 36" wide open base, manual tilt, 9" deep stainless steel pan with gallon markings, pouring lip & removable strainer, spring assist cover with drip edge, pan holder, thermostatic control, includes L faucet bracket, electric ignition, 12" stainless steel legs with adjustable flanged feet, 90,000 BTU 1. One (1) Natural Gas 2. One (1) 120v/60/1-ph, 9.0 amps, standard 3. One (1) Motor driven pan lift 4. One (1) Pouring Lip Strainer, for braising pan Addendum #2 Page 3 of 4 5. One (1) Draw-off Strainer, for braising pan 6. One (1) Model DBLTS 12NZL DOUBLE Pantry Deck-Mount Faucet, 12” swivel spout 7. One (1) Model FCTBRKT BP Enclosed box faucet bracket 8. One (1) Dormont Model 1675KIT2S48PS gas hose e. Added Item #17.1 DISHWASHER EXHAUST FAN i. Quantity: One (1), Manufacturer: Captive-Aire, Model: DU50HFA ii. One (1) Model DU50HFA 800 cfm capacity fan, 208 volt 1 phase with pre-wired disconnect switch, grease trough, ECM wiring package, hinging brackets and roof curb. Ductwork by HVAC Contractor. f. Update to Item #31.1 EXHAUST FAN i. Quantity: One (1), Manufacturer: Captive-Aire, Model: DU85HFA ii. One (1) 1700 cfm capacity fan, 208 volt 1 phase with pre-wired disconnect switch, grease trough, hinging brackets and roof curb. Ductwork by HVAC Contractor g. Update to Item #31.2 MAKE-UP AIR UNIT i. Quantity: One (1), Manufacturer: Captive-Aire, Model: A1-D.250-G10 ii. One (1) Direct fired gas make up air furnace, 1360 cfm capacity, 208 volt 1 phase with down discharge, pitched roof curb and inlet hood with v-bank filters and motorized back draft damper for rooftop application. Ductwork By HVAC Contractor. 21. Refer to Specification SECTION 12355 LABORATORY CASEWORK AND EQUIPMENT Section 1.2,G,1; add the following acceptable manufacturer: a. Farnell Contracting, Inc. (FCI) 22. Structural Clarifications, see the following attached sheets. a. S0.1: i. Refer to updated information on the special joist diagrams. ii. Note 1. under Metal Decking should indicate deck is to be painted; not galvanized. b. S0.4: This is a new sheet to clarify the “net” uplift pressures; versus the gross uplift pressures shown on sheet S0.2. c. S1.3A: Detail 43 is a new detail at the exterior walls on the north and south sides of the Community Room Lobby. d. S2.4: The metal deck in detail 19 should be indicated as painted; not galvanized. e. S5.6: Details 42 and 43 are new details. Attachments: Sheet A32, Sheet A34, FS2, S0.1, S0.4, S1.3A, S2.4, S5.6, Walk-in Cooler Condensing Unit Specifications, Walk-in Freezer Condensing Unit Specifications. END OF ADDENDUM #2 Addendum #2 Page 4 of 4 NATIONAL REFRIGERATION AND AIR CONDITIONING CANADA CORP. 159 ROY BLVD, PO BOX 2020 BRANTFORD, ON CANADA N3T 5Y6 NATIONAL REFRIGERATION will furnish equipment in accordance with this drawing and specifications, and subject to its published warranty. Approval of this drawing signifies that the equipment is acceptable under the provision of the job specifications. Any change made hereon by any person whomsoever subject to acceptance by NATIONAL REFRIGERATION at its home office. Order Item No: 2 BEHA008E6-HS2B EH-LINE HERMETIC CONDENSING UNITS-AIR DATE : 28 May 2015 PURCHASER : PROJECT : SUBMITTED BY : BILL STOMPF Dimensions shown are for standard unit less options. DIMENSIONS DIMENSION A 16 7/8 in DIMENSION B 24 7/8 in DIMENSION C 30 3/8 in DIMENSION D 4 in DIMENSION E DIMENSION F DIMENSION G 0 in DIMENSION H CONNECTIONS LIQUID SUCTION DRAIN WATER DISCHARGE PAN LOOP HOT GAS SIDE PORT HOT GAS INLET HOT GAS OUTLET OTHER SHIPPING WEIGHT REFRIGERANT CHARGE RECEIVER CAPACITY 3/8 in 5/8 in 149 lb 5 lb APPROVALS NOTES: PAGE 4 OF 8 NATIONAL REFRIGERATION AND AIR CONDITIONING CANADA CORP. 159 ROY BLVD, PO BOX 2020 BRANTFORD, ON CANADA N3T 5Y6 NATIONAL REFRIGERATION will furnish equipment in accordance with this drawing and specifications, and subject to its published warranty. Approval of this drawing signifies that the equipment is acceptable under the provision of the job specifications. Any change made hereon by any person whomsoever subject to acceptance by NATIONAL REFRIGERATION at its home office. Order Item No: 5 BEZA020L6-HS2B EZ-LINE SCROLL CONDENSING UNITS-AIR DATE : 28 May 2015 PURCHASER : PROJECT : SUBMITTED BY : BILL STOMPF Dimensions shown are for standard unit less options. DIMENSIONS DIMENSION A 19 7/8 in DIMENSION B 36 3/8 in DIMENSION C 30 3/8 in DIMENSION D 4 in DIMENSION E DIMENSION F DIMENSION G 0 in DIMENSION H CONNECTIONS LIQUID SUCTION DRAIN WATER DISCHARGE PAN LOOP HOT GAS SIDE PORT HOT GAS INLET HOT GAS OUTLET OTHER SHIPPING WEIGHT REFRIGERANT CHARGE RECEIVER CAPACITY 3/8 in 7/8 in 315 lb 11 lb APPROVALS NOTES: PAGE 8 OF 8 MEP Addendum #2 Date: June 26, 2015 To: Todd Seidell Architect P.O. Box 2189 Gaylord, MI 49734 Attn: Todd Seidell and/or Brittany Stripp Project: Kirtland Community College – Health Sciences Education and Training Center 4 Mile Road, Grayling, MI Notes By: Bo Reinhardt, Mark Wilkes, and Aaron Wosek Distribution: Nealis Engineering Project #15008 SCOPE OF WORK The following items are changes, additions, deletions, clarifications, and/or errors, and omissions in plans and specifications, and shall be considered by each Bidder in making and submitting his proposal. All of these items shall be considered a part of the Contract Documents. MECHANICAL (BID PACK #31 HVAC) M1 Reference Mechanical Specifications Sections: The following mechanical specification sections have been updated and are attached as part of this Addendum. The updated spec sections shall take the place of the original spec section provided as part of the bidding documents. A. 15188 HVAC Pumps: B. 15720 Air Handling Units C. 15260 Thermal Insulation 1. Note all refrigerant piping must be insulated with 3/4” Armaflex insulation. Must be equal to the Armaflex brand. 2. Note all underground ductwork shall be insulated per Section 15260. 3. All supply air duct above lay-in ceilings shall be insulated per Section 15260. 4. Return air ductwork above lay-in ceilings does not require insulation. Kirtland Community College – Health Sciences Education and Training Center MEP Addendum #2 June 26, 2015 M2 Reference Mechanical Specifications: The following mechanical specification sections have been added to the Mechanical Specification scope, and are attached as part of this Addendum. A. 15542 Dedicated Outdoor Air Systems and Make-Up Air Units B. 15739 Critical Cooling Units M3 Reference Mechanical Specifications Section 15926 Digital Control Equipment: A. The Temperature Control Contractor shall provide pricing for the Tridium Vykon with Niagara AX Platform Version 3.8, since the Niagara 4 platform is not available for pricing. Upgrade to the Niagara 4 platform is readily available with AS version 3.8, which will be coordinated at the time of submittal review. HTML 5 scripts may be included by the TCC in lieu of the current JAVA available. B. The TCC shall wire the Liebert critical cooling unit and associated condensing unit (CCU-1 & CCCU-1) controls and integrate the CCU into the BCS, via the CCU BacNet interface board (provided as part of the Liebert package). C. The kitchen ventilation equipment including the (2) hoods, (4) fans, and (2) make-up air units shall all be wired by the Temperature Control Contractor. Note that all control equipment, control relays, hood controls, VFD, etc., shall be provided as part of the Food Service Equipment Package, and CaptiveAire. The kitchen equipment shall not be integrated into the BCS. D. The VFDs for air handlers, AHU-139, AHU-140, kitchen Make-up air unit, MUA-1, dedicated outdoor air system, DOAS-1, and MUA-229 shall all be provided by the equipment manufacturer. E. All software, firmware, and hardware licenses shall be held by Kirtland College. No proprietary entities (JCI, Siemens, Honeywell, Trane, etc.) shall provide proprietary equipment for this project. F. Johnson Controls Inc., Corporate Office Branch is approved to procure and install the Tridium Vykon BCS. No proprietary JCI equipment is approved. M4 Reference Mechanical Schedule Sheets M9 and M10: The following are clarifications and additions to the original schedules: A. See Commercial Kitchen Exhaust Fan Schedule. (See FSE Package for further info): 1. KEF-3 shall be 208/60/1-phase. 2. KEF-4 model number shall be CaptiveAire DU50HFA, 208/60/1-phase. B. See Critical Cooling Unit Schedule: 1. The critical cooling unit condensing unit, CCCU-1, Liebert model number was listed incorrectly. The correct model number is MCD38W3YH7, and is 208/60/1-phase. Contact Alex Collins at Hedricks Associates 616-454-1218 for pricing and complete package information. C. See Commercial Kitchen Make-up Air Unit Schedule 1. MUA-2 shall be provided 208/60/1-phase. The total make-up air flow rate is 1700 CFM. D. Reference Mechanical Boiler Schedules: 1. The boiler supplier shall include one Lochinvar (1) BacNet interface board for each boiler (total of 5) included in the bid. Approved Voluntary Alternate Boiler Manufacturers shall also include a single BacNet board for each boiler provided. Page 2 Kirtland Community College – Health Sciences Education and Training Center MEP Addendum #2 June 26, 2015 E. Reference the Direct-Fired Make-Up Air Unit Schedule: 1. The total supply airflow rate for MUA-229 shall be 3500 CFM. See updated specifications as described above under Item M2-C. F. Reference VRF Schedules 1. The VRF supplier shall include integral condensate pumps with each evaporator. M5 Reference Mechanical Drawings Sheet M2 Storage Room 138: 1. The VRF heat pumps ZN-139A and ZN-139B are available in right-hand horizontal configuration only, therefore the heat pumps will need to be mirrored and installed against Storage 138 inner wall. Updated construction drawings will be available for construction. M6 Reference Mechanical Sheet M2 Type 1 Exhaust Ductwork: A. The Mechanical Contractor shall install the Type 1 kitchen hoods (total of 3), kitchen exhaust fans (total of 4), and provide and install all Type 1 and Type 2 ductwork, and associated materials. B. Wrap all Type 1 ductwork that serves Hood-1, Hood-2, and Hood-3 with zero-clearance 3-M Fire Barrier Duct Wrap 615+ or equal. Include 3M adhesives and install per manufacturer installation instructions. M7 Reference Mechanical Sheet M1: A. Reference VRF evaporator ZN-169: 1. The ZN-169 evaporator shall be an EVAP-18, 1.5 Ton, 580 CFM (medium speed). The zone damper package shall be unchanged. PLUMBING (BID PACKAGE #32) P1 Reference Gas Service and Plumbing Drawings Sheet P2: A. The natural gas meters and service shall be provided by Integrity Construction. B. The main building gas meter shall be installed where shown on Sheet P2. The total load is 6,141,916 Btu/Hr. C. An additional gas meter is being requested to be installed outdoors, to the south of Mechanical Room 126 next to the electrical generators. The gas meter (if approved by DTE Energy) shall be installed on a pole (exact location to be determined), and shall be high-pressure, 1/2 psi, sized for a total of 11,932,000 Btu/Hr. 1. Generators #1 & #2, Generator #3 (Alternate #E-3), and future Generator #4 shall be served by the new meter. 2. The Plumbing Contractor shall pipe gas to each generator. Install gas piping, valves, and gas regulators as shown on supplemental sketch Generator Gas Piping Detail attached as part of this document. 3. Break-out piping and associated valve and gas regulator to Generator #3 and list as line item for Alternate # E-2. P2 Reference Addendum #1 Install a 2” ball valve in lieu of the auto-fill valve described in Addendum #1 on the 2” irrigation piping branch that supplies the fire protection tank. The Fire Protection Contractor shall install a float valve in the tank that will automatically maintain the tank water level. Page 3 Kirtland Community College – Health Sciences Education and Training Center MEP Addendum #2 June 26, 2015 ELECTRICAL (BID PACKAGE #33) E1 Reference Electrical Lighting Floor Plan - Drawing Sheet E1L: A. VESTIBULE 100 – 1. Connect all light fixtures in this area to branch circuit LS1-3 as a night light circuit. B. LOBBY 101 and CONCOURSE 116 – 1. Connect all the non-emergency light fixtures THRU LCP-1 (R19) 3A-22. 2. Connect all emergency life-safety light fixtures to THRU LCP-1 (R4) LS1-3. 3. Connect all exit signs to branch circuit LS1-3. 4. Connect all occupancy sensors in this area as an INPUT TO LCP-1. 5. Change four (4) Type-F4 light fixtures currently shown in the Elevator Lobby Area to now be four (4) Type-F light fixtures. C. OPEN OFFICE 102 – 1. Add an Emergency Transfer Device (ETD-1) and connect two (2) Type-F8 light fixtures to branch circuit LS1-3 to as required. 2. Add two (2) Type-L light fixtures at the Reception Desk 103. Coordinate mounting with Architect/Engineer prior to installation. 3. Add a Type-EX exit sign fixture above the door leading to Lobby 101 and connect to branch circuit LS1-3. 4. Connect all the non-emergency light fixtures THRU LCP-1 (R21) 1A-5. 5. Connect all occupancy sensors in this area as an INPUT TO LCP-1. 6. Eliminate the occupancy sensor switchpack (SP) currently shown in Reception 103. D. STAIR 115 – 1. Connect all light fixtures in this area THRU LCP-1, (R6) LS1-13. 2. Connect all occupancy sensors in this area as an INPUT TO LCP-1. E. ELEVATOR PIT 172 – 1. Connect lighting to branch circuit 3A-16. F. ELEVATOR EQUIPMENT ROOM 171 – 1. Connect lighting to branch circuit 3A-20. G. CORRIDOR 181 – 1. Connect all emergency life-safety light fixtures to THRU LCP-1 (R10) LS1-5. 2. Connect all exit signs to branch circuit LS1-5. 3. Connect all occupancy sensors in this area as an INPUT TO LCP-1. H. CORRIDOR 156 & ALCOVE 162 – 1. Connect all emergency life-safety light fixtures to THRU LCP-1 (R12) LS1-5. 2. Connect all exit signs to branch circuit LS1-5. 3. Connect all occupancy sensors in this area as an INPUT TO LCP-1. I. SKILLS LAB 176 – 1. Add an Emergency Transfer Device (ETD-2) and connect one (1) Type-F1 light fixture and one (1) Type A2 light fixture to branch circuit LS1-5 as required. 2. Connect all exit signs to branch circuit LS1-5. Page 4 Kirtland Community College – Health Sciences Education and Training Center MEP Addendum #2 J. June 26, 2015 PROGRAM EXPANSION 189 – 1. Add an Emergency Transfer Device (ETD-1) and connect two (2) Type-A light fixtures to branch circuit LS1-5 as required. 2. Connect all exit signs to branch circuit LS1-5. K. BOOKSTORE STOCK ROOM – 1. Connect lighting to branch circuit 3A-1. L. BOOKSTORE AREA 119 – 1. Add an Emergency Transfer Device (ETD-2) and connect to the lighting currently shown as DMR#2 Zone-9 to branch circuit LS1-11 as required. 2. Designate the light fixture over the check-out counter as light fixture Type-F4. M. EXTERIOR BLDG. MNTD. – 1. Connect all Type-AA light fixtures and the two (2) Type-CC light fixtures mounted above Vestibule 100, THRU LCP-1, (R2) LS1-1. 2. Connect the remaining five (5) Type-CC light fixtures mounted in the main entrance canopy THRU LCP-1, (R17) 3B-14. E2 Reference Electrical Lighting Floor Plan - Drawing Sheet E2L: A. CONCOURSE 116 and STUDY AREAS 117 & 118 – 1. Change the light fixture identification tag for the one (1) Type-F4E light fixture and the four (4) Type-F4 light fixtures as currently shown, to now all be Type-F light fixtures. 2. Connect all the non-emergency light fixtures THRU LCP-1 (R19) 3A-22. 3. Connect all emergency life-safety light fixtures to THRU LCP-1 (R4) LS1-3. 4. Connect all exit signs to branch circuit LS1-3. 5. Connect all occupancy sensors in this area as an INPUT TO LCP-1. 6. Add a Type-OS10 occupancy sensor by the west column adjacent to Café Area 125, and orientate in the east facing direction. 7. Mount the Type-G1 wall sconce currently shown on the adjacent Operating Room 150 wall, under the stairs leading up to the second floor. B. COMMUNITY ROOM LOBBY 136 – 1. Change the light fixture identification tags for the six Type-F4 light fixtures as currently shown, to now be Type-F. 2. Connect all the non-emergency light fixtures THRU LCP-1 (R23) 3C-1. 3. Connect all emergency life-safety light fixtures to THRU LCP-1 (R16) LS1-7. 4. Connect all exit signs to branch circuit LS1-7. 5. Connect all occupancy sensors in this area as an INPUT TO LCP-1. C. I.T. CLOSET 137 – Connect lighting to branch circuit 3C-2. D. COMMUNITY ROOM “A” 139 – 1. Add an Emergency Transfer Device (ETD-2) and connect four (4) Type-CH1 light fixtures currently shown on DMR#1 Zone-4 to branch circuit LS1-17 as required. E. COMMUNITY ROOM “B” 140 – 1. Add an Emergency Transfer Device (ETD-2) and connect four (4) Type-CH1 light fixtures currently shown on DMR#1 Zone-8 to branch circuit LS1-19 as required. Page 5 Kirtland Community College – Health Sciences Education and Training Center MEP Addendum #2 June 26, 2015 F. FITNESS 130 – 1. Add an Emergency Transfer Device (ETD-2) and connect one (1) Type-A light fixture to branch circuit LS1-7 as required. G. WOMEN’S LOCKER 131 – 1. Add an Emergency Transfer Device (ETD-1) and connect one (1) Type-C1 light fixture to branch circuit LS1-7 as required. H. MEN’S LOCKER 132 – 1. Add an Emergency Transfer Device (ETD-1) and connect one (1) Type-C1 light fixture to branch circuit LS1-7 as required. I. CORRIDOR 129 – 1. Connect all emergency life-safety light fixtures to THRU LCP-1 (R14) LS1-7. 2. Connect all exit signs to branch circuit LS1-7. 3. Connect all occupancy sensors in this area as an INPUT TO LCP-1. J. CORRIDOR 149 – 1. Connect all emergency life-safety light fixtures to THRU LCP-1 (R18) LS1-7. 2. Connect all exit signs to branch circuit LS1-7. 3. Connect all occupancy sensors in this area as an INPUT TO LCP-1. K. CARDIAC SONOGRAPHY 143 – 1. Change the Type-A1 light fixture currently shown to now be a Type-A2 light fixture. 2. Eliminate the Type-OS8 occupancy sensor currently shown. L. PRIVACY ROOM 147 – 1. Relocate Dimming-Vacancy Sensor Switch currently shown, to now be mounted adjacent to the door. M. PROGRAM EXPANSION 189 – 1. Add a second Emergency Transfer Device (ETD-1) to this space (see Addendum Item No. E1(J) above) and connect two (2) more Type-A light fixtures to branch circuit LS1-5 as required. 2. Connect all exit signs to branch circuit LS1-5. N. CLASSROOM 153 – 1. Add an Emergency Transfer Device (ETD-2) and connect one (1) Type-A light fixture to branch circuit LS1-7 as required. O. PREP SCRUB ROOM 152 – 1. Add a Type-EX exit sign above the door leading to Classroom 153 and connect to branch circuit LS1-7. Page 6 Kirtland Community College – Health Sciences Education and Training Center MEP Addendum #2 June 26, 2015 P. COMMERCIAL KITCHEN 124 – 1. Change the designated “MS1” master control station currently shown, to now be “MS3”. 2. Add an Emergency Transfer Device (ETD-1) and connect two (2) Type-A light fixtures to branch circuit LS1-11 as required. 3. Add two (2) Type-OS1 occupancy sensors and a switchpack (SP) to control the west and north (dishwashing) area lighting. 4. Add an Emergency Transfer Device (ETD-1) and connect two (2) Type-A light fixtures and one (1) Type-A2 light fixture to branch circuit LS1-11 as required. 5. Add two (2) Type-OS1 occupancy sensors and a switchpack (SP) to control the middle (Hood-1 & 2) and east (Hood-3) area lighting. Q. CAFÉ AREA 125– 1. Add an Emergency Transfer Device (ETD-2) and connect to the lighting currently shown as DMR#2 Zone-1 to branch circuit LS1-11 as required. R. STAIR “B” 135 – 1. Connect all light fixtures in this area THRU LCP-1, (R8) LS1-13. 2. Connect all occupancy sensors in this area as an INPUT TO LCP-1. S. MECHANICAL AND ELECTRICAL 126 – 1. Connect lighting to branch circuit 3A-1. T. SHIPPING AND RECEIVING 121 – 1. Connect lighting to branch circuit 3A-1. 2. Connect all exit signs to branch circuit LS1-1. U. EXTERIOR BLDG. MNTD. – 1. Connect all Type-AA light fixtures THRU LCP-1, (R2) LS1-1. E3 Reference Electrical Lighting Floor Plan - Drawing Sheet E3L: A. STAIR “A” 115 – 1. Eliminate the one (1) Type-K4 light fixture currently shown on the south wall. The light fixture over the stairwell landing, that is to be installed, is currently shown on Drawing Sheet E1L. 2. Connect all light fixtures in this area THRU LCP-1, (R6) LS1-13. 3. Connect all occupancy sensors in this area as an INPUT TO LCP-1. B. ADMINISTRATION LOBBY 201 – 1. Change the two (2) Type-L4 light fixtures currently shown to now be two (2) Type-L light fixtures. 2. Change one (1) Type-A4 light fixture currently shown to now be a Type-A2 light fixture. 3. Add an Emergency Transfer Device (ETD-2) and connect to one (1) Type-A light fixture and two (2) Type-A2 light fixtures as required. 4. Connect all non-emergency light fixtures in this area THRU LCP-1, (R25) 2D-1. 5. Connect all occupancy sensors in this area as an INPUT TO LCP-1. C. UPPER CONCOURSE 228 & 237 – 1. Connect all emergency life-safety light fixtures to THRU LCP-1, (R20) LS1-15. 2. Connect all exit signs to branch circuit LS1-15. 3. Connect all occupancy sensors in this area as an INPUT TO LCP-1. 4. Connect the eight Type-P3 pendant light fixtures currently shown mounted above Lobby 101, THRU LCP-1, (R19) 3A-22. Page 7 Kirtland Community College – Health Sciences Education and Training Center MEP Addendum #2 E4 June 26, 2015 Reference Electrical Lighting Floor Plan - Drawing Sheet E4L: A. STAIR “B” 135 – 1. Eliminate the one (1) Type-K4 light fixture currently shown on the south wall. The light fixture over the stairwell landing, that is to be installed, is currently shown on Drawing Sheet E3L. 2. Connect all light fixtures in this area THRU LCP-1, (R8) LS1-13. 3. Connect all occupancy sensors in this area as an INPUT TO LCP-1. B. UPPER CONCOURSE 220 & 228 – 1. Connect all emergency life-safety light fixtures to THRU LCP-1, (R20) LS1-15. 2. Connect all exit signs to branch circuit LS1-15. 3. Connect all occupancy sensors in this area as an INPUT TO LCP-1. E5 Reference Electrical Power Floor Plan - Drawing Sheet E2P: A. SERVER ROOM 127 – 1. Change the branch circuit connections to the two (2) rack mounted UPS to now be two (2) NEMA L5-30P receptacles and connect to branch circuits 3A-32 and 3A-34 (See Addendum #2 Item No. E13 below for more details). B. SERVER ROOM 127 – 1. Connect the two (2) quad. 120V receptacles currently shown to branch circuit 3A-26 (See Addendum #2 Item No. E13 below for more details). C. SERVER ROOM 127 – 1. Connect the Critical Cooling Unit Evaporator (CCU-1) currently shown above, to new branch circuit 3A-36,38 (See Addendum #2 Item No. E13 below for more details). Unit will be provided with an integral disconnect (coordinate with the M.C.). D. STORAGE 138 – 1. Connect branch circuit 3C-31,33,35 to AHU-139 through a disconnect and VFD as required. E. STORAGE 140 – 1. Connect branch circuit 3C-38,40,42 to AHU-140 through a disconnect and VFD as required. E6 Reference Electrical Systems Floor Plan - Drawing Sheet E2S: A. I.T. CLOSET 137 – 1. Change the quantity of STP point-to-point shielded cables required at each of the two (2) low voltage STP (point-to-point) outlets from eight (8) as currently shown, to now be nine (9) cables required. E7 Reference Electrical Systems Floor Plan - Drawing Sheet E3S: A. TESTING 235 – 1. CLARIFICATION: All low voltage UTP Network Outlets currently shown in Testing 235, shall be fed through flexible conduit to modular (RJ45) connector receptacles mounted within surface mounted raceway on the adjacent wall. Page 8 Kirtland Community College – Health Sciences Education and Training Center MEP Addendum #2 E8 June 26, 2015 Reference Electrical Symbol Legend - Drawing Sheet E6: Include the following changes/revisions to the Electrical Symbol Legend and include under Division 17 and Bid Package #34. A. ELAPSED TIME INDICATOR CLOCK – 1. Based on DUKANE #24D40A. Rated for 24VAC operation and mounted within 4-gang recessed backbox as required per manufacturer’s installation requirements (VIF). B. REMOTE ON/OFF/RESET CONTROL UNIT FOR ELAPSED TIME INDICATOR CLOCK – 1. Based on DUKANE #24CC10. To operate independently of master PoE clock system and connected to designated digital elapsed time indicator clock. E9 Reference Electrical Symbol Legend - Drawing Sheet E6: A. IP CAMERAS, SPEAKERS, WIRELESS ACCESS POINTS, TELEVISION LOCATIONS, and PROJECTOR LOCATIONS – 1. All network cabling and connections to the outlets and/or equipment above shall be installed by the Division 17000 contractor and included with Bid Package #34. Revise the references in the Symbol Legend that refer the work to be done by the Electrical Contractor (E.C.). B. LOW VOLTAGE UTP NETWORK OUTLET – 1. CLARIFICATION: Revise the notes to designate MDF-1 in Main Server Room #127, and IDF-1 in I.T. Closet #157 as shown per the floor plans and described in the specifications. E10 Reference Interior Light Fixture Schedule - Drawing Sheet E7: A. TYPE-L – 1. Under the description, change to now be a 4’ light fixture. 2. Under the Catalog #, change to now be (1) #EL-120V-48-30K-D. E11 Reference Lighting Control Panel (LCP-1) Diagram - Drawing Sheet E8: A. Reference the attached Revised Lighting Control Panel (LCP-1) Diagram. Revise floor plan references to reflect the attached revised diagram. B. Change the LCP-1 model number to now be based on #LK32-120/277-S0-L3-M0-T2-HVB0. E12 Reference Electrical Riser Diagram - Drawing Sheet E9: A. #EDP-1 FEEDER WIRING AND CONDUIT – 1. See Alternate Add summaries in Addendum #2 Item No. E20 below for further base bid vs. alternate add. details. B. FIRE PUMP CONTROLLER (SERVICE DISCONNECT) – 1. Change the 1#3/0 (CU) G.E.C. currently shown to the metallic water pipe(s), to now be 1#6 (CU) G.E.C. to the metallic water pipe(s). C. MAIN DISTRIBUTION PANEL #MDP-1 – 1. Add a 60A/3P branch circuit breaker and connect to a new TVSS#MDP with 5#6 (CU), 1” EMT conduit. Added TVSS#MDP shall be based on Liebert #570YA12ARCG1S. Page 9 Kirtland Community College – Health Sciences Education and Training Center MEP Addendum #2 June 26, 2015 D. DISTRIBUTION PANEL #DP-1 – 1. Add a 60A/3P branch circuit breaker and connect to a new TVSS#1 with 5#6 (CU), 1” EMT conduit. Added TVSS#1 shall be based on Liebert #560YA12ARCG1S. E. DISTRIBUTION PANEL #DP-2 – 1. Add a 60A/3P branch circuit breaker and connect to a new TVSS#2 with 5#6 (CU), 1” EMT conduit. Added TVSS#2 shall be based on Liebert #560YA12ARCG1S. F. DISTRIBUTION PANEL #DP-3 – 1. Add a 60A/3P branch circuit breaker and connect to a new TVSS#3 with 5#6 (CU), 1” EMT conduit. Added TVSS#3 shall be based on Liebert #560YA12ARCG1S. E13 Reference Electrical Panel Schedules - Drawing Sheet E10: A. PANEL #3A – 1. Add a 20A/1P branch circuit breaker in circuit no. 22. 2. Add a 20A/1P branch circuit breaker in circuit no. 26. 3. Eliminate two (2) 30A/2P branch circuit breakers currently shown in circuit nos. 32 thru 38. 4. Add two (2) 30A/1P branch circuit breakers in circuit nos. 32 and 34. 5. Add a 15A/2P branch circuit breaker in circuit no. 36,38. 6. Change the 25A/2P branch circuit breaker currently shown in circuit no. 40,42, to now be a 35A/2P branch circuit breaker. 7. Revise the branch circuit descriptions as follows: a. #22: LIGHTS – LOBBY & CONCOURSE b. #26: “RECEPTS. – IT SERVER RM.” c. #32: “IT SERVER RACK #MDF – IT SERVER” d. #34: “IT SERVER RACK #MDF – IT SERVER” e. #36,38: “CRITICIAL COOLING (CCU-1) – IT SERVER” f. #40,42: “CRITICAL COOLING (CCCU-1) – IT OFFICE” 8. Include circuit breaker locks on circuit nos. 14, 16, 18, 26-42. B. PANEL #LS1 – a. Add “Emerg. Lights – 2nd Flr. & Stairwells” to spare circuit no. 13. b. Add “Emerg. Lights – Comm. Rm. A” to spare circuit no. 17. c. Add “Emerg. Lights – Comm. Rm. B” to spare circuit no. 19. E14 Reference Site Electrical Plan - Drawing Sheet SE1: A. FUTURE SITE LTG. NOTES – 1. Reduce the two (2) approx. 66’-0” underground conduit sleeves currently shown on the north side of the parking lot from the two (2) northern Type-SL5 site lighting fixture bases, to now only be a stubbed a minimum 2’-0” for future site lighting. B. U/G CONDUIT SLEEVES – 1. Add two (2) 4” underground PVC schedule-40 conduit sleeves under the roadway (just south of the west branching service drive) for underground communications utility services. Page 10 Kirtland Community College – Health Sciences Education and Training Center MEP Addendum #2 June 26, 2015 C. TYPE-BB FIXTURES MNTD WITHIN PERGOLA – 1. Change the “BID ALTERNATE #E4 ONLY” note for the five (5) Type-BB light fixtures currently shown mounted in the pergola to now be “BID ALTERNATE #E3 ONLY”, as noted in Specification Section #16010-4.03, in Supplementary Instructions to Bidders Part-11, and in Bid Proposal Form. D. SITE IP EXTERIOR CAMERAS – 1. Change the four (4) IP Cameras currently shown in the parking lot to all be IP Exterior Cameras as provided by the Owner and installed by the Division 17 Contractor in Bid Package #34. 2. Add a 3/4” PVC Sch.40 underground conduit sleeve from the north two (2) site cameras to Mechanical/Electrical Room 165. 3. Add a 3/4” PVC Sch.40 underground conduit sleeve from the south two (2) site cameras to Server Room 127. E. EMERGENCY PHONE TOWER (Reference Addendum #1 Item E10-(C)(4)) – 1. Change the mounting location for the emergency phone tower to now be located adjacent to the sidewalk. Coordinate location in the field with the Architect/Engineer. E15 Reference Type “SLx” Light Fixture and Concrete Base Detil - Drawing Sheet SE2: A. Change the designated 18’-0” pole height to now be 15’-0” to match the Exterior Light Fixture Schedule. B. Add Type-SL4 to the 15’-0” pole detail. E16 Reference Specification Section 16000 – Electrical General Provisions: Revise the following specifications sections accordingly: A. Specification Section 16000-1.05(B)(1) – 1. Submit electronic shop drawings on all equipment and materials indicated in the specifications or on drawings. Reference Supplementary Instructions to Bidders Section 00101 Part-28 for more details. B. Specification Section 16000-1.05(B)(3) – 1. Submittals shall be in electronic PDF format with the name of the Project, Architect, Engineer, and the submitting Contractor indicated on the cover sheet. E17 Reference Specification Section 16050 – Basic Materials and Methods: Revise/add to the following specification sections: A. Add the following line item as Specification Section 16050-2.02 – (H) Provide a dedicated neutral conductor for all single pole branch circuits as required. Multi-wire branch circuits with shared neutrals are NOT allowed, unless otherwise noted. B. Eliminate the word “existing” currently shown in the first line of Specification Section #16050-2.02(G)(1). Page 11 Kirtland Community College – Health Sciences Education and Training Center MEP Addendum #2 E18 June 26, 2015 Reference Specification Section 16700 – Fire Alarm Signal and Mass Notification System: Add the following line items to Specification Section 16700-3.05: A. (E) All system wiring shall be furnished and installed by the contractor. B. (F) All wiring shall be installed in electrical metallic tubing (EMT), or conduit, and must be installed and kept separate from all other building wiring. C. (G) All system components shall be securely supported independent of the wiring. Runs of conduit and wiring shall be straight, neatly arranged, properly supported, and installed parallel and perpendicular to walls and partitions. E19 Reference Specification Section 17200 – Fiber Optic A. CLARIFICATION – 1. The use of armored fiber is an acceptable alternative to standard fiber and innerduct. Reference Spec. Section 17200-3.01(A)(1). E20 Reference Construction Documents – Drawings and Specifications: CLARIFICATION: Include the following for the Electrical Base Bid and Add. Alternates (**Added below to summary originally distributed with Addendum #1): A. BASE BID – 1. GENERATOR #1 2. GENERATOR #2 3. PARALLELING GENERATOR CONTROLLER (PGC-1) AND ACCESSORIES 4. ATS#LS1 AND CONTROL WIRING 5. ATS#3 AND CONTROL WIRING 6. JUNCTION BOX FOR FUTURE ATS#1 7. JUNCTION BOX FOR FUTURE ATS#2 8. JUNCTION BOX FOR FUTURE ATS#4 9. TWO (2) PARALLEL 4” CONDUIT SLEEVES FROM EDP-1 TO FUTURE GENERATOR #3 10. TWO (2) PARALLEL 4” CONDUIT SLEEVES FROM EDP-1 TO FUTURE GENERATOR #4 11. ONE (1) 1” CONDUIT SLEEVE FROM PANEL #3B TO FUTURE GENERATOR #3 12. ONE (1) 1” CONDUIT SLEEVE FROM PANEL #3B TO FUTURE GENERATOR #4 13. ONE (1) 3/4” CONDUIT SLEEVE FROM PARALLEL GENSET CONTROLLER #PGC-1 TO FUTURE GENERATOR #3 14. ONE (1) 3/4” CONDUIT SLEEVE FROM PARALLEL GENSET CONTROLLER #PGC-1 TO FUTURE GENERATOR #4 15. **TWO (2) PARALLEL 4” CONDUIT SLEEVES FROM EDP-1 TO J-BOX ATS#1. 16. **TWO (2) PARALLEL 4” CONDUIT SLEEVES FROM EDP-1 TO J-BOX ATS#2. B. ADD. ALTERNATE #E1 – 1. ATS #1 AND CONTROL WIRING 2. **FEEDER WIRING FROM EDP-1 TO ATS#1 Page 12 Kirtland Community College – Health Sciences Education and Training Center MEP Addendum #2 June 26, 2015 C. ADD. ALTERNATE #E2 – 1. GENERATOR #3 AND CONTROL WIRING 2. ATS#2 AND CONTROL WIRING 3. **FEEDER WIRING FROM EDP-1 TO ATS#2 4. **FEEDER WIRING FROM GENERATOR #3 TO EDP-1 ATTACHED 1. Mechanical Specification Section 15188 “HVAC Pumps” 2. Mechanical Specifications Section 15720 “Air Handling Units” 3. Mechanical Specifications Section15542 “Dedicated Outdoor Air Systems and Make-Up Air Units” 4. Mechanical Specifications Section 15739 “Critical Cooling Units” 5. Mechanical Specifications Section 15260 “Thermal Insulation” 6. Generator Gas Piping Detail 7. Revised Lighting Control Panel (LCP-1) Schedule End of MEP Addendum #2 Page 13 Kirtland Community College Health Sciences Education and Training Center SECTION 15188 HVAC PUMPS PART 1 GENERAL 1.01 SECTION INCLUDES A. System lubricated circulators. B. In-line circulators. C. Vertical in-line pumps. D. Base mounted pumps. 1.02 RELATED REQUIREMENTS A. Section 15182 - Hydronic Piping. B. Section 15183 - Hydronic Specialties. 1.03 REFERENCE STANDARDS A. UL 778 - Standard for Motor-Operated Water Pumps; Underwriters Laboratories Inc.; Current Edition, Including All Revisions. 1.04 SUBMITTALS A. Product Data: Provide certified pump curves showing performance characteristics with pump and system operating point plotted. Include NPSH curve when applicable. Include electrical characteristics and connection requirements. B. Operation and Maintenance Data: Include installation instructions, assembly views, lubrication instructions, and replacement parts list. C. Maintenance Materials: Furnish the following for Owner's use in maintenance of project. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Armstrong Pumps Inc: www.armstrongpumps.com. B. ITT Bell & Gossett: www.bellgossett.com. C. Taco Inc.. D. Grundfos Company. 2.02 HVAC PUMPS - GENERAL A. Provide pumps that operate at specified system fluid temperatures without vapor binding and cavitation, are non-overloading in individual operation, and operate within 25 percent of midpoint of published maximum efficiency curve. B. Products Requiring Electrical Connection: Listed and classified by UL or testing agency acceptable to authority having jurisdiction as suitable for the purpose specified and indicated. 2.03 SYSTEM LUBRICATED CIRCULATORS A. Type: Horizontal shaft, single stage, direct connected with multiple speed or single speed (as listed on Pump Schedule) wet rotor motor for in-line mounting, for 140 psi (965 kPa) maximum working pressure, 230 degrees F (110 degrees C) maximum water temperature. B. Casing: Cast iron with flanged pump connections. C. Impeller, Shaft, Rotor: Stainless Steel. D. Bearings: Metal Impregnated carbon (graphite) and ceramic. E. Motor: Impedance protected, multiple speed, with external speed selector. F. Performance: See Pump Schedule G. Electrical Characteristics: 1. 115 volts, single phase, 60 Hz. 15188 HVAC PUMPS Page 1 of 3 Kirtland Community College Health Sciences Education and Training Center 2.04 INLINE CIRCULATORS A. Type: Horizontal shaft, single stage, direct connected, with resiliently mounted motor for in-line mounting, oil lubricated, for 125 psi (860 kPa) maximum working pressure. B. Casing: Cast iron, with flanged pump connections. C. Impeller: Non-ferrous keyed to shaft. D. Bearings: Oil-lubricated bronze sleeve. E. Shaft: Alloy steel with bronze sleeve, integral thrust collar. F. Seal: Mechanical seal, 225 degrees F (107 degrees C) maximum continuous operating temperature. G. Performance: See Pump Schedule H. Electrical Characteristics: See Pump Schedule. 2.05 VERTICAL IN-LINE PUMPS A. Provide Armstrong single stage, single suction vertical In-Line type pumps, with rising head to shut off pump characteristics. 1. Refer to the schedule for pump flows and heads and motor speed, efficiency, enclosure and power requirements. B. Type: Vertical, single stage, close coupled, radially split casing, for in-line mounting, for 175 psi (1200 kPa) working pressure. C. Construction: 1. Pump casing shall be cast iron, suitable for 175 psig (12 bar). 2. Working pressure at 140°f (60°c). 3. The casing shall be hydrostatically tested to 150% maximum working pressure. 4. The casing shall be radially split to allow removal of the rotating element without disturbing the pipe connections. 5. The casing shall be provided with npt threaded companion flanges, for the appropriate pump size, with gaskets and hardware. 6. Pump impeller shall be fully enclosed type. The impeller shall be keyed and secured to pump shaft by stainless steel fittings. 7. The pump shaft shall be a stainless steel stub shaft for frame 56 motors. The steel motor shaft shall be enclosed by a bronze shaft sleeve, on other motor frame sizes. 8. Coupling - Rigid spacer type of high tensile aluminum alloy. Coupling to be designed to be easily removed on site to reveal a space between the pump and motor shafts sufficient to remove all mechanical seal components for servicing and to be replaced without disturbing the pump or motor. 9. Mechanical Seals - Shall be Stainless Steel multi-spring outside balanced type with Viton secondary seal, carbon rotating face and silicon carbide stationary seat. Provide 316 stainless steel gland plate. Provide factory installed flush line with manual vent. D. E. Casing: Cast iron, with suction and discharge gage port, casing wear ring, seal flush connection, drain plug, flanged suction and discharge. F. Impeller: Bronze, fully enclosed, keyed directly to motor shaft or extension. 2.06 BASE MOUNTED PUMPS A. Type: Horizontal shaft, single stage, direct connected, radially or horizontally split casing, for 125 psi (860 kPa) maximum working pressure. B. Casing: Cast iron, with suction and discharge gage ports, renewable bronze casing wearing rings, seal flush connection, drain plug, flanged suction and discharge. C. Impeller: Bronze, fully enclosed, keyed to shaft. D. Bearings: Oil lubricated roller or ball bearings. 15188 HVAC PUMPS Page 2 of 3 Kirtland Community College Health Sciences Education and Training Center E. Shaft: Alloy steel with copper, bronze, or stainless steel shaft sleeve. F. Seal: Mechanical seal, 225 degrees F (107 degrees C) maximum continuous operating temperature. G. Seal: Packing gland with minimum four rings graphite impregnated packing and bronze lantern rings, 250 degrees F (121 degrees C) maximum continuous operating temperature. H. Drive: Flexible coupling with coupling guard. I. Baseplate: Cast iron or fabricated steel with integral drain rim. J. Performance: See Pump Schedule for GPM and Head data. K. Electrical Characteristics: See Pump Schedule. L. Include suction diffuser for each base-mounted pump inlet. PART 3 EXECUTION 3.01 PREPARATION A. Verify that electric power is available and of the correct characteristics. 3.02 INSTALLATION A. Install in accordance with manufacturer's instructions. B. Provide access space around pumps for service. Provide no less than minimum space recommended by manufacturer. C. Check, align, and certify alignment of base mounted pumps prior to start-up. D. Install base-mounted pumps on concrete housekeeping pad as shown on Enlarged Mechanical Room Plans. E. Provide side-stream filtration system for closed loop systems. Install across pump with flow from pump discharge to pump suction from pump tappings. END OF SECTION 15188 HVAC PUMPS Page 3 of 3 Kirtland Community College Health Sciences Education and Training Center SECTION 15720 AIR HANDLING UNITS PART 1 GENERAL 1.01 SECTION INCLUDES A. Packaged air handling units. 1.02 REFERENCE STANDARDS A. AMCA 210 - Laboratory Methods of Testing Fans for Aerodynamic Performance Rating; Air Movement and Control Association International, Inc.; 2007 (ANSI/AMCA 210, same as ANSI/ASHRAE 51). B. AMCA 300 - Reverberant Room Method for Sound Testing of Fans; Air Movement and Control Association International, Inc.; 2008. C. AMCA 301 - Methods for Calculating Fan Sound Ratings from Laboratory Test Data; Air Movement and Control Association International, Inc; 2007. D. AMCA 500-D - Laboratory Methods of Testing Dampers for Rating; 2012. E. ASHRAE Std 52.2 - Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size; 2012. F. ASHRAE Std 90.1 - Energy Standard for Buildings Except Low-Rise Residential Buildings; 2013, Including All Addenda (ANSI/ASHRAE/IES Std 90.1). G. NFPA 90A - Standard for the Installation of Air-Conditioning and Ventilating Systems; 2012. 1.03 SUBMITTALS A. Product Data: 1. Published Literature: Indicate dimensions, weights, capacities, ratings, gages and finishes of materials, and electrical characteristics and connection requirements. 2. Filters: Data for filter media, filter performance data, filter assembly, and filter frames. 3. Fans: Performance and fan curves with specified operating point clearly plotted, power, RPM. 4. Sound Power Level Data: Fan outlet and casing radiation at rated capacity. 5. Electrical Requirements: Power supply wiring including wiring diagrams for interlock and control wiring, clearly indicating factory-installed and field-installed wiring. B. Shop Drawings: Indicate assembly, unit dimensions, weight loading, required clearances, construction details, field connection details, and electrical characteristics and connection requirements. C. Maintenance Data: Include instructions for lubrication, filter replacement, motor and drive replacement, spare parts lists, and wiring diagrams. 1.04 EXTRA MATERIALS A. See Section 01 6000 - Product Requirements, for additional provisions. B. Supply one set for each unit of fan belts. PART 2 PRODUCTS 2.01 SEE SECTION 01600 FOR ADDITIONAL REQUIREMENTS. 2.02 MANUFACTURERS A. Daikin Applied; ______: www.daikinapplied.com. B. Trane Inc; ______: www.trane.com. 2.03 CASING CONSTRUCTION A. Casing: 1. Construct of one piece, insulated, double wall panels. 2. Provide mid-span, no through metal, internal thermal break. 15720 AIR HANDLING UNITS Page 1 of 3 Kirtland Community College Health Sciences Education and Training Center 3. 4. Construct outer panels of galvanized steel and inner panels of galvanized steel. Casing Air Pressure Performance Requirements: B. Access Doors: 1. Construction, thermal and air pressure performance same as casing. 2. Provide surface mounted handles on hinged, swing doors. C. Insulation: 1. Minimum 1" expanded foam, minimum R-4 per inch. 2. Completely fill all panel cavities in all directions preventing voids and settling. 3. Comply with NFPA 90A. 2.04 CASING A. Finish: 1. Indoor Units: a. Provide exterior, galvanized steel panels without paint. b. Color: Manufacturer's standard color. B. Left-Hand or Right-Hand coil and access panels. See Air Handler Schedule for required orientation. 2.05 FAN SECTION A. Type: Forward curved, single width, single inlet, centrifugal type fan. B. Variable-air-volume with maximum airflow listed on Air Handler Schedule. 2.06 FANS A. Performance Ratings: Determined in accordance with AMCA 210 and labeled with AMCA Certified Rating Seal. B. Sound Ratings: AMCA 301; tested to AMCA 300 and label with AMCA Certified Sound Rating Seal. C. Bearings: Self-aligning, grease lubricated, with lubrication fittings extended to exterior of casing with plastic tube and grease fitting rigidly attached to casing. D. Mounting: Locate fan and motor internally on welded steel base coated with corrosion resistant paint. Factory mount motor on slide rails. Provide access to motor, drive, and bearings through removable casing panels or hinged access doors. Mount base on vibration isolators. E. Motor Wiring Conduit: Factory wire fan motor wiring to the unit mounted variable frequency drive and external motor junction box. F. Inverter-rated motor, 208/60/3-phase. 2.07 BEARINGS AND DRIVES A. Shafts: Solid, hot rolled steel, ground and polished, with key-way, and protectively coated with lubricating oil. B. V-Belt Drive: Cast iron or steel sheaves, dynamically balanced, bored to fit shafts, and keyed. Variable and adjustable pitch sheaves for motors 15 hp and under selected so required rpm is obtained with sheaves set at mid-position; fixed sheave for 20 hp and over, matched belts, and drive rated as recommended by manufacturer or minimum 1.5 times nameplate rating of the motor. 2.08 COIL SECTION 2.09 COILS A. Casing: Provide access to both sides of coils. Enclose coils with headers and return bends exposed outside casing. Slide coils into casing through removable access panel. B. Water Heating Coils: 1. Headers: Cast iron, seamless copper tube, or prime coated steel pipe with brazed joints. 15720 AIR HANDLING UNITS Page 2 of 3 Kirtland Community College Health Sciences Education and Training Center 2. C. Configuration: Drainable, with threaded plugs for drain and vent; serpentine type with return bends on smaller sizes and return headers on larger sizes. Refrigerant Coils: 1. Refrigerant: Use only refrigerants that have ozone depletion potential (ODP) of zero and global warming potential (GWP) of less than 50. 2. Headers: Seamless copper tubes with silver brazed joints. 3. Liquid Distributors: Brass or copper venturi distributor with seamless copper distributor tubes. 4. Configuration: Down feed with bottom suction. 2.10 FILTER AND AIR CLEANER SECTION A. General: Provide filter sections with filter racks, minimum of one access door for filter removal, and filter block-offs to prevent air bypass. B. Throwaway Filters: 1. Media: 2 inch (50 mm) fiberglass with rigid supporting mesh across the leaving face, capable of operating up to a maximum of 500 fpm (2.54 m/s) without loss of efficiency and holding capacity. 2. Frame: Rigid. 3. Minimum Efficiency Reporting Value: 13 when tested in accordance with ASHRAE 52.2. 4. Refer to Section 15860. 2.11 DAMPER SECTION A. Outdoor air damper, 100% fresh air. B. Damper Blades: 1. Double-skin airfoil design with metal, compressible jamb seals and extruded-vinyl blade-edge seals on all blades. 2. Self-lubricating stainless steel or synthetic sleeve bearings. 3. Comply with ASHRAE 90.1 for rated maximum leakage rate. 4. Base all leakage testing and pressure ratings on AMCA 500-D. 5. Arrange in parallel or opposed-blade configuration. PART 3 EXECUTION 3.01 INSTALLATION A. Install in accordance with manufacturer's instructions. B. If provided in section, bolt sections together with gaskets. C. Install flexible duct connections between fan inlet and discharge ductwork and air handling unit sections. Ensure that metal bands of connectors are parallel with minimum one inch (25 mm) flex between ductwork and fan while running. D. Make connections to coils with unions or flanges. E. Hydronic Coils: 1. Hydronic Coils: Connect water supply to leaving air side of coil (counterflow arrangement). 2. Provide shut-off valve on supply line and lockshield balancing valve with memory stop on return line. 3. Locate water supply at bottom of supply header and return water connection at top. 4. Provide manual air vents at high points complete with stop valve. 5. Ensure water coils are drainable and provide drain connection at low points. F. Refrigerant Coils: Provide sight glass in liquid line within 12 inches (300 mm) of coil. G. Field-wire all factory provided controls for field installation. END OF SECTION 15720 AIR HANDLING UNITS Page 3 of 3 Kirtland Community College Health Sciences Education and Training Center SECTION 15542 DEDICATED OUTDOOR AIR SYSTEMS AND MAKE-UP AIR UNITS PART 1 GENERAL 1.01 SECTION INCLUDES A. Dedicated Outdoor Air System (DOAS). 1. 100% Outdoor Air Unit. 2. Direct-fired, natural gas burner. 3. Direct-expansion condenser section. 4. Dehumidification condenser section. 5. Variable-air-volume supply air fan. 6. BacNet control board. B. Direct-Fired Make-Up Air Unit 1.02 REFERENCE STANDARDS 1.03 SUBMITTALS A. Product Data: Provide data with dimensions, duct and service connections, accessories, controls, electrical nameplate data, and wiring diagrams. B. Shop Drawings: Indicate dimensions, duct and service connections, accessories, controls, electrical nameplate data, and wiring diagrams. C. Manufacturer's Instructions: Indicate rigging, assembly, and installation instructions. D. Operation And Maintenance Data: Include manufacturer's descriptive literature, operating instructions, installation instructions, maintenance and repair data, and parts listing. E. Factory Representative Equipment Start-up and Validation: When complete installation of the DOAS unit has taken place a factory authorized start-up shall take place. The start-up shall be prior to, or shall be concurrent with the system test and balance. Factory test and validation of the installation and operation shall be included. F. Warranty: Submit manufacturers warranty and ensure forms have been filled out in Owner s name and registered with manufacturer. PART 2 PRODUCTS 2.01 MANUFACTURERS A. DOAS System: Reznor Model YDMA-300 packaged unitary make-up air and ventilation unit. Contact Swaney Sales, Steve Swaney 616-247-1635 for pricing and ordering. 1. All others by Voluntary Alterate. B. Make-Up Air Unit: AbsolutAire Inc. Kalamazoo, MI. Contact Swaney Sales for ordering. 1. 2.02 DOAS UNIT A. Packaged unitary, roof top, downflow, variable air volume ventilation unit with DX cooling, dehumidification, and direct-fired natural gas burner. B. DX Cooling 1. Unit: High Capacity DX Cooling Makeup Air Units utilizing R410-A Refrigerant: 2. Furnish and install model YDMA for treatment of up to 100% constant outside air per plans and specifications. Unit shall be completely factory assembled, tested, internally wired, fully charged with Refrigerant R410A, and shipped as one piece. Unit shall consist of foam insulated weather-tight casing with optional field installed outdoor intake hood, compressors, air-cooled condenser coils, condenser fans, evaporator coils, supply fan, motors and drives, and unit controls. Packaged Cooling and Heating Units shall carry an ETL listing. Refrigerant System: 3. DX systems shall be designed to provide 10% to 100% incremental capacity control for treatment of up to 100% outside air with up to 80 degree F (27 degree C) dewpoint 15542 DEDICATED OUTDOOR AIR SYSTEMS AND MAKE-UP AIR UNITS Page 1 of 8 Kirtland Community College Health Sciences Education and Training Center 4. 5. 6. entering the unit. Unit shall have hermetic compressors with a scroll design with internal pressure relief and motor temperature winding protection. Compressor shall be equipped with reversal rotation protection. Refrigeration protection shall include low and high pressure switches, refrigerant circuit frost protection, liquid line filters/dryers and service gage ports. The unit shall have a factory installed refrigerant charges to provide unit performance as shown in the schedule. Low pressure switch shall operate at 35 psi or lower pressure. The auto reset low pressure switch shall not reset until the pressure rises about 50 psi. The manual reset high pressure switch shall operate above 600 psi with ± 15 psi. The unit will not reset without a user manually pushing the reset button and the refrigerant line pressure is below 400 psi. Refrigeration control shall include thermal expansion valves, external equalizers and distributors for each compressor circuit. a. The refrigerant system shall have a non user adjustable 5 minute minimum ON and minimum OFF timer circuit protection. The refrigerant circuit shall have an anti-cycle timer in addition to the minimum ON/OFF timer that prevents the compressor(s) from cycle on the minimum timer circuit. b. The refrigerant system shall include evaporator coil. The copper tube-aluminum plate fin evaporator coil shall be 4 rows with 14 fins per inch to meet leaving air performance as shown on the unit schedule. The multi-circuit evaporator coils shall be interlaced configuration. The entire coil face area shall be active with a single circuit or multiple circuit activation such that the entire coil face shall provide air cooling and dehumidification in part load operation. Split coil face design not acceptable because it does not allow full active face area for dehumidification in the part load operation. The evaporator coils shall be protected from frosting by a low temperature cutout. The factory installed froststat on each circuit shall interrupt power to the associated compressor when the temperature drops below 35°F. The frost stat shall not deactivate until the circuit temperature rises to 50°F. The coils shall be leak tested at the factory to ensure pressure integrity. The unit shall include air cooled condenser coils sized to provide the unit performance as shown in the mechanical schedule. The condenser coil shall be light weight 5/16 copper tubing with aluminum fins. The condenser shall be compact 2 row coil design with low refrigerant volume. The condenser coils shall NOT be aluminum micro-channel type design. c. The condensate drain pan shall be rust proof or high corrosion resistant 316 stainless steel. The drain outlet shall be attached to a double sloped drain pan with a minimum 1/8 inch per foot (10 mm per meter) slope. The drain pain shall collect potential condensate from all evaporator/condenser coils and distributor area in the air stream to prevent blow-off condensate reaching unprotected bottom unit surfaces. The unit shall have field supplied and installed P trap, in accordance with all local and area codes and Best Practices. The unit shall be supplied with high efficiency electronically commutated motors (ECM) for the condenser fans. The motors shall be rated for the necessary condenser coil airflows. The motors shall have an efficiency 89% or higher. The condenser fans shall be accessible for servicing. The condenser fan system shall be dynamically balanced at the factory and installed with vibration dampening to reduce ambient noise. The motor shall accept a 0-10v control signal and modulate based upon a command from the unit’s control systems. The motor shall provide the following diagnostics and safety features: Lockrotor/jam fault, over/under current protection, over temperature protection and under/over voltage protection. The condenser coils shall be copper tube and aluminum fin design. The coils shall be light weight and low refrigerant volume with the use of 5/16 copper tubing. The condenser coils shall NOT be aluminum micro-channel type design. The evaporator coil(s) shall be copper tube and aluminum fin design. The evaporator coils shall be interlaced, 4 row design maximizing latent performance as shown on the unit’s mechanical schedule. 15542 DEDICATED OUTDOOR AIR SYSTEMS AND MAKE-UP AIR UNITS Page 2 of 8 Kirtland Community College Health Sciences Education and Training Center 7. 8. C. Unit compressors shall have sound blankets. The sound blanks shall reduce ambient noise as demonstrated by sound performance sheets provided by manfacturer. Sound blankets shall come factory installed. Blankets shall be rated for outdoor use. Unit shall include DX based reheat. The method of reheat shall comply with ASHRAE 90.1 requirements. Unit shall include a dedicated compressor and refrigeration circuit using full condenser reheat or total heat of rejection to the supply airstream. The reheat coil position shall include a minimum separation of 10 inches (102 mm) from the cooling coil to eliminate re-evaporation of cooling coil condensate. The circuit shall be capable of delivering a nominal 13?F to 17?F temperature rise from the main evaporator temperature without the need for modulating the capacity for all entering outside air conditions. The reheat system shall modulate to maintain the user adjustable unit leaving air temperature setpoint while also maintaining a constant evaporator temperature setpoint. The reheat coil shall operate down to 50?F ambient temperature without the need of low ambient kit. The reheat coil shall provide greater than 7 COP efficiency at 65?Fdb/64?Fwb entering air temperature. Manufacturer shall show unit performance at above condition. The refrigerant circuits shall include thermal expansion valves with external equalizers. Service gage ports and refrigerant line filter dryers are factory installed as standard. Pre-cooling coils shall be two row depth with 6 fin per inch to minimize air pressure drop. Gas Heating 1. The system shall be provided with gas heat with the capacity shown the mechanical schedule. Gas heating system shall be factory install consisting of heat exchanger, venter fan, spark ignition system, control valves and all necessary safeties to provide a fully operational heating system ready for operation from the factory. The heat exchanger shall be constructed of 409 stainless steel for make-up air applications. The heat exchanger shall properly drain condensate or other water during the heating and cooling season. The system shall modulate both the gas and combustion air to maintain temperature setpoint(s) and thermal efficiency. The heat exchanger shall be capable of 100 degree (F) temperature rise for 100% outside air treatment. The heating system shall be certified to ANSI Standard Z83.8/CSA 2.6. The heat exchanger shall be 4 pass serpentine, non welded, constructed of 409 stainless steel. Safety Features shall consist but not limited to: a. Automatic discharge air limit control. b. Air proving pressure switch. c. Color coded wiring and matching terminal blocks. d. Circuit breaker protected transformers 2. The gas heating shall utilize natural gas. 3. Heating system shall have a minimum thermal efficiency of 91%. The thermal efficiency shall not fall below 90% through the modulated operational range. The Heat exchanger shall have condensate drain to remove and/or prevent water build up in the unit. The condensate shall not exceed 4 pH level. The condensate shall be piped to the appropriate building system for removal. 4. Provide 10:1 power vented modulation. The dual gas heat sections shall have a modulating gas valve for first section and a single stage gas value for the second section with spark ignition controls for both sections. The gas value shall modulate and stage to provide 10 to 100% capacity control. (10:1) The gas control shall consist of ignition boards, 2 speed venters, flame sensors, igniters, gas valves and associated safeties. The spark ignition boards shall have LED status & diagnostic. The unit shall lock out heating system banks for the following failures: venter pressure switch failure, ignition lockout, excessive limit switch losses and excessive flame sense losses. The gas control system shall be designed to maintain constant gas efficiency in all throughout the modulated range. The dual heat exchanger shall modulate/stage as follows: a. 10% - 50% Capacity = Bank 1 ON and modulating from 20-100%, Bank 2 OFF b. 50% - 100% Capacity = Bank 1 ON and modulating from 20-100%, Bank 2 100% Capacity. c. Gas burner condensate shall be piped insulated down through curb indoors to sanitary branch piping. 15542 DEDICATED OUTDOOR AIR SYSTEMS AND MAKE-UP AIR UNITS Page 3 of 8 Kirtland Community College Health Sciences Education and Training Center D. Unit shall have foam panel construction for all exterior surfaces and base. The foam insulation shall meet ASTM E-84 with a flame spread of 20 and smoke density of 300. No foam panel acceptable if unit construction exceeds R12 value, no exposed installation air stream and exceed flame safety characteristic of foam paneling. Outer casing shall be fabricated from G90 galvanized steel substrate with 60 gloss painted finish coat. Finish shall be rated for > 1000 salt spray hours. The cabinet design shall prevent condensation forming on the outside of the unit casing in operation via a dedicated thermal break from all internal components to the external surface. Fully gasketed, hinged doors of foam construction shall provide access to filters, dampers, evaporator coils section, supply fan section. Provide hinged single wall construction doors for the heater section and control section. On hinged doors frequently used for service (i.e. filter and coil access) The unit control panel section shall be laid out to provide separation of high and low voltage components per UL standards. High voltage contactors & distribution shall be touch safe. The control panels shall be hinged for easy access to the unit controls. For ease of service, all electrical components will be clearly identified with 1/2 inch (13 mm) diameter self adhesive labels to match the unit specific wiring diagram. The low voltage and unit controller access electrical panel shall be physically isolated from the high voltage section. The open door to the control section reveals the wiring diagrams, DDC programming instructions and all manuals and literature protected and permanently attached to the cover. Control transformers will incorporate integral, resettable circuit breaker protection. E. Supply Fan 1. The unit’s supply fan shall be direct drive with an ABB variable frequency drive allowing peak fan efficiency and system RPM. The fan system shall be made of galvanized steel. The impeller shall have RAL 5002 coating, directional arrows marketing. The fan sled shall allow up to 176°F (80°C) for the impeller and the motor shall allow ambient temperatures -4°F to 104°F (-20°C to 40°C). The impeller and motor shall be designed for continuous operation. The fan system shall utilize Zie Ziehl-Abegg patented rotating diffusor which reduces noise and helps increase overall system efficiency. The 7 blade, welded construction impeller shall be dynamically balanced at the factory with hub; admissible vibration level less than 2,8 mm/s (0.11 in/s) in conformity with ANSI/AMCA 204. a. The supply fan sled shall have slide out design for easy inspection and replacement. b. The fan sled shall also allow inspection of the gas or electric heat exchangers. c. The fan sled shall have rubber dampers to isolate and minimize vibration. d. The fan sled shall include Inlet cone with measuring device for airflow measurement. The packaged unit shall allow fan inlet differential pressure readings inside the control panel to measure supply fan CFM with an accuracy of +/-5%. The unit controller shall allow fan speed settings for occupied and unoccupied modes. The unit controller shall also allow fan speed settings for heating and cooling modes. The unit shall meet the schedule performance. The unit control system shall have test and balance function to allow permanent setting of the airflow(s) as shown in the mechanical schedule. e. The ABB frequency drive shall be factory installed with line reactor, ECM Filter and all necessary wiring per UL standard. The drive shall have built in menu drive display with test, start-up, maintenance and diagnostic assistant. The drive shall be factory programmed for 30 second soft start. The drive shall have the following protection and alarms: single phase, overvoltage trip limit, under voltage trip limit, over temperature, microprocessor fault, motor stall protection, motor over temperature. 2. Supply fan shall be control by duct static pressure. Duct static pressure sensor shall be unit mounted; sensing range 0 -2.5” w.c.; 24 Vac, 0-10V signal; ± 1% FS accuracy; 1/4” barb connections. Sensor shall have field installed 1/4” pneumatic tubing to the ductwork located 2/3 down the duct. Sequence: Whenever the supply fan is running in any mode, the fan speed shall varies to maintain the user selected duct static pressure setpoint. (Default 1”, adjustable range 0-2.5”) When the supply fan is OFF, the VFD supply fan signal will be 0%. (OFF) The control system shall limit the actual VFD range between a user adjusted minimum and maximum output setting with default values of 25% and 100% output - other mechanical limits may apply. 15542 DEDICATED OUTDOOR AIR SYSTEMS AND MAKE-UP AIR UNITS Page 4 of 8 Kirtland Community College Health Sciences Education and Training Center F. Intake & Section 1. Unit shall outdoor air hood design for 100% airflow to allow uniform coil velocity and filter loading. The motorized damper shall be spring return for closure during unit shutdown or power interruption. Outdoor air inlet hood shall include 1 inch (25 mm) permanent filters and screen. Hood filter and screen shall meet MERV 4 rating. (Dust mites, pollen, and water spray) Hood airflow shall not exceed 300 fpm intake velocity to prevent snow and rain entrainment. Units designed for 100% outside air intake only shall include an integrated transition section (without return air opening) designed specifically for 100% outside air introduction. 2. Units shall have fully integrated factory installed 100% motorized outdoor air damper. a. Damper Construction: The control damper shall be low leak with blade and jamb seals. The damper leakage shall not exceed 10 cfm per square foot at 4” sp. The damper shall be constructed of 16 gage galvanized steel with reinforcement to insure structural integrity. Blade edge seals shall be PVC coated polyester fabric suitable for -25°F to +180°F (-32°C to +83°C) mechanically locked into the blade edge. Jamb seals shall be flexible stainless steel metal, compression type to prevent leakage between end of the blade and the damper frame. Bearings shall be corrosion resistant, molded synthetic sleeve type turning in an extruded hole in the damper frame. Linkage shall be concealed out of airstream, within the damper frame to reduce pressure drop and noise and lessen the need for maintenance. b. The damper(s) shall be controlled from an external 0-10V input signal. Sensors/Signal: User supplied 0-10 volt, 2 wire signal. Independent power source. Sequence: The control system accepts a 0-10 volt signal that will position the damper from 0-100% open between the user set maximum and minimum settings. The damper shall modulate per the manufacturer recommendations to operated concurrently with the variable air volume supply air fan. G. Filters: The unit shall have factory installed 4” MERV 13 filters before the evaporator coils. The filters shall be accessible through a hinged door. None hinge door access is not acceptable. The filters shall be pleated V configuration with an average arrestance of 95%; MERV Rating 13 per ASHRAE 52.2-99. The filters shall be manufactured from recycled synthetic material with moisture & microbial growth resistant properties. The filter shall have less than 0.36” w.c. pressure drop at 500 fpm air velocity. The filter area shall be sized to handle the rated airflow as shown on the mechanical schedule. H. Roof Curb: The roof curb shall be 18" tall, full perimeter, 12 gage zinc coated steel with 2"x6" nailer, fiilled with high density sound attenuating insulation. I. Controls: The unit discharge air temperature shall be controlled as described under the Sequence of Operations. 1. The unit shall be supplied with a BacNet interface board. J. Include condensate neutralization kit for natural gas burner mounted in unit. Burner condensate shall be piped down through curb to nearest sanitary pipe. K. Options 1. A weatherproof convenience outlet shall be provided. The outlet shall be field powered utilizing an independent circuit form the main unit power. The circuit shall be 20 amp circuit with breaker and installed per local and state building codes. 2. Unit shall have factory installed phase lost protection. 3. Unit shall have a factory provided 5 year compressor warranty. 4. Unit shall have a factory provided 5 year gas heat exchanger warranty. 5. Unit shall have a factory provided 2 year all parts warranty. L. Factory-Authorized Start-up and Validation: 1. When installation of the DOAS unit is complete a factory-authorized start-up shall take place. The start-up shall be prior to, or shall be concurrent with the system test and balance. Factory test and validation of the installation and operation shall be included. 15542 DEDICATED OUTDOOR AIR SYSTEMS AND MAKE-UP AIR UNITS Page 5 of 8 Kirtland Community College Health Sciences Education and Training Center a. Northland Integrated Systems, 13969 Francis Way, Cedar Springs, MI. 49319. Phone: 616-439-3100. 2.03 DIRECT-FIRED MAKE-UP AIR UNIT A. Provide a direct gas-fired roof top heater with100% Outside Air variable volume blower. B. Provide self-contained packaged heaters that shall include the casing, modulating burner, DWDI FC scrolled centrifugal fan, fan motor & drives, variable frequency drive capable of 50% supply air reduction, and automatic controls to interlock to equipment and maintain space pressure. C. Provide a casing, which shall be a minimum 18-gauge, aluminized steel, welded to structural steel framing. Both interior and exterior structural steel shall be red-oxide primed. All exterior casing seams shall be weather resistant. All interior and exterior surfaces will be cleaned of all oil and grease. Painted exterior will consist of a high-quality prime coat and a finish coat of machine enamel with rust inhibitors. Color is selected by the owner. The insulation shall comply with UL standard 181 for erosion and NFPA 90A for fire resistance. All exposed edges will be coated to eliminate erosion. Fiberglass will be held in place with both adhesive and welded pins, per SMACNA standards. Provide a minimum of (2) hinged access doors with positive latching, watertight handles. All weather enclosure doors shall be painted on the interior as well as the exterior and shall include braces that lock the door open during servicing. D. Burner: The burner shall be a direct-fired type gas burner which shall be selected by the supplier/manufacturer to operate with low gas pressure 6.0" w.g. or less, specifically designed to burn natural gas below the maximum non-contaminating levels required by OSHA and the ACGIH. Burner shall have non-clogging, stainless steel baffles attached to a cast aluminum gas supply section with no moving parts. The burner shall be capable of a 30-to-1 turndown ratio and be designed for 100% thermal efficiency for the life of the equipment. The outdoor air velocity across the burner shall be constant and at an air velocity required for ANSI certification. The burner air velocity shall be constant at all times throughout the operation of the heater. No air from the indoor space shall be allowed to recirculate across the burner at any time. Service of and access to the burner igniter and flame rod shall be accomplished through an access door or panel. E. Burner Profile Adjustment System: shall consist of a means to monitor and adjust the pressure differential across the burner profile while the fan is running. The burner profile will remain fixed while in service and use. F. Pilot: the direct fired burner will consist of a direct spark ignition system, including an ignition module, spark igniter, and flame rod to verify burner low fire (pilot) ignition before allowing the main gas valve to fully open. G. Supply fan: shall be a double-width, double-inlet, centrifugal design, belt driven for the required air capacity. The motor shall be 1750 rpm, standard NEMA frame, Open Drip Proof (ODP) high eficiency inverter-rated, and mounted on an adjustable pivot base. The motor shall have a 1.15 service factor, suitable for continuous service at 120° F ambient temperature, and shall be wired for the specified voltage. The fan, motor, and drive shall be factory tested to ensure the specified air delivery (per ANSI standards) at the design total static pressure. The fan shaft shall be connected to the motor by a V-belt drive, capacity designed for 30% over the motor nameplate horsepower. The fan shaft shall be a turned, ground and polished solid shaft. A protective coating shall be applied to the shaft to minimize oxidation. Fan shall have ball bearings, and shall be designed for a minimum L10 life of 100,000. H. Controls: 1. Main Control Panel: shall be similar to NEMA 3R and contain all standard electrical components, such as [non] fused disconnect switch; motor starter; 120-volt and 24-volt transformers; control circuit fuses; flame control relay and a number-coded terminal strip. The control panel shall have a burner flame relay to lockout the flame in abnormal conditions. A remote flame reset button shall allow personnel to reset the burner at the 15542 DEDICATED OUTDOOR AIR SYSTEMS AND MAKE-UP AIR UNITS Page 6 of 8 Kirtland Community College Health Sciences Education and Training Center 2. 3. 4. 5. 6. 7. I. remote control panel. The complete control and safety system as well as the burner and gas manifold shall be factory tested. Temperature Controls: a. Discharge Temperature Control: b. A solid state temperature control system, located inside the control panel includes a sensing thermistor located in the supply fan discharge opening. The thermistor senses and controls discharge temperature. The temperature control for adjusting the discharge air temperature is located at [the main unit] [the remote panel]. c. Space Temperature Control: d. A solid-state temperature control system, located inside the control panel, shall have a sensing thermistor located in the space as shown on the plans. The thermistor senses and controls the room temperature in the occupied mode. A second thermistor, mounted in the heater discharge, controls the allowable maximum and minimum discharge temperature in response to the actual discharge temperature being sensed. Automatic Building Pressure Control [with Manual Override]: a. A space pressure controller shall be incorporated into the factory temperature controls that shall modulate the supply air fan to maintain an adjustable space pressure. Remote Control Panel: shall be provided and includes all necessary remote operating switches and circuit analyzer lights. The remote control panel shall be painted mild steel. Wiring to remote panel from the main control panel shall be accomplished with 120/1/60 and/or 24 volt wiring circuits. a. The remote control panel shall provide each heater with the following (choose): 1) a manual pressure-control potentiometer, 2) an occupied room temperature stat. (The stat room sensor shall be remote mounted where noted on the plan), 3) a room-temperature unoccupied cycle stat (the stat sensor remote shall be mounted where noted on the plan), 4) a programmable 7-Day time clock with a minimum of four (4) programmable on/off schedules per day, with battery back-up reserve. 5) a burner alarm horn with silence switch, 6) a [tamper proof, key operated] Summer/Off/Winter switch, 7) a [tamper proof, key operated] remote burner-flame reset switch, 8) a [tamper proof, key operated] manual/auto building pressure selector switch and, 9) These system circuit analyzer lights: 10) Power On 11) Fan On 12) Burner On 13) Low Temperature Alarm Low-Temperature Limit Switch: turns the fan motor off when cold air is being discharged from the heater. The minimum discharge temperature may be selected from 0°F to 70°F. An integral timer shall by-pass this switch for five (5) minutes on initial start-up. High-Temperature Limit Switch: turns the burner off when the discharge air temperature exceeds 130°F. The switch must then be manually reset at the heater. Gas manifold: shall be sized for the rated BTU (MBH) capacity as scheduled on the drawings. The gas manifold will be constructed in conformance to ANSI Standards [and Factory Mutual (FM) / Industrial Risk Insurers (IRI) insurance requirements]. Accessories (select each optional accessory needed): 1. High Gas Pressure Switches: a high gas-pressure switch located on the burner end of the gas manifold and shall turn the burner off when the gas pressure is too high. 2. Filtered Inlet Hood: this option includes filters accessible from the inlet hood face. Filters are a 2” aluminum mesh washable filter. 15542 DEDICATED OUTDOOR AIR SYSTEMS AND MAKE-UP AIR UNITS Page 7 of 8 Kirtland Community College Health Sciences Education and Training Center 3. 4. 5. 6. 7. Inlet Hood with Bird Screen: manufactured using the same gauge and metal type as the base unit and includes ½” x ½” galv. bird screen. Variable Frequency Drive: variable volume 100% OA models includes an automatic building pressure control, a variable frequency drive (VFD) for supply fan speed control and a burner profile damper with a pressure differential switch to control and maintain the proper burner airflow across the burner profile. Includes a building pressure differential switch to signal the VFD to vary fan speed as needed in response to the building negative or positive conditions. This diaphragm [photohelic] switch is mounted in the heater main control panel. The pressure sensing range shall be 0.01 to 0.20” W.C. with a null span of 0.01 to 0.03 inches water column. Roof Curb (horizontal units): provide a duct supply-air curb, 20" high flat curb, formed of heavy-gauge aluminized steel. Contractor shall shim the curb so that it is level and shall install a cant strip and wood nailer per detail on the plans. Gravity [Inlet / Discharge] Damper: a parallel blade damper is provided in a flange assembly which is shipped loose for field installation by others. Damper blades are constructed of fabricated aluminum and have adjustable weights for balancing. Provide a BacNet interface board for interconnection to the Tridium BCS. PART 3 EXECUTION 3.01 INSTALLATION A. Install in accordance with manufacturer's instructions. B. DOAS unit shall be installed exactly where shown to ensure the roof opening and supply air duct discharges between the correct roof trusses. There is no room for ductwork to run below the roof trusses. 1. Coordinate roof rough opening with Construction Manager and roofing contractor. 2. Coordinate supply air duct connection to curb and unit and duct transition from roof penetration down into truss bay. Note that the main 24"x24" outdoor air supply duct must run between trusses to allow piping tight to the trusses below. See Enlarged Mechanical Room Plan 126 for pipe routing and coordinate with plumbing plans. C. Temperature Control Contractor shall interconnect and integrate the BacNet interface board to BMS. See Sequence of Operations for more information. D. Connect natural gas piping to unit per manufacturer installation instructions. Field verify connection size. E. Provide factory authorized start-up and validation of DOAS unit. F. Provide final test and balance of system. END OF SECTION 15542 DEDICATED OUTDOOR AIR SYSTEMS AND MAKE-UP AIR UNITS Page 8 of 8 Kirtland Community College Health Sciences Education and Training Center SECTION 15739 CRITICAL COOLING UNITS PART 1 GENERAL 1.01 SECTION INCLUDES A. Critical Cooling Unit. B. Indoor, Water-cooled Critical Cooling Condensing Unit. C. Controls. 1.02 SUBMITTALS A. Product Data: Provide manufacturers literature and data indicating water, drain, and electrical characteristics and connection requirements. B. Operation and Maintenance Data: Include manufacturer's descriptive literature, operating instructions, installation instructions, maintenance and repair data. C. Warranty: Submit manufacturer's warranty and ensure forms have been filled out in Owner's name and registered with manufacturer. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Liebert Corporation; Model Evaporator: MMD36E7YHED0, Water-Cooled Condenser: MCD38W3YH7: www.liebert.com. 2.02 AIR CONDITIONING UNITS A. Description: Self contained water cooled, factory assembled, pre-wired and pre-piped unit, consisting of cabinet, fan, filters, with wall-mount controls and BacNet interface card to interconnect to the Tridium Vykon BCS. B. Assembly: For horizontal ceiling mounting to fit 24 x 48 inches (610 x 1220 mm) T-bar ceiling opening. C. Refrigerant: R407C. D. Evaporator: 3-ton, nominal, Liebert Mini-Mate. 1. DX evaporatorfilter drer, and TXV. 2. Direct-drive supply air blower. 3. Microprocessor control with audible and visual switch. 4. Maunufacturer supply non-locking disconnect switch. 5. Canister-style humidifier, 4.3 lbs/hr. 6. Condensate pump, powered from evaporator. 7. MERV-8 Filter. 8. Optional 48"x24" air distribution plenum. E. Condenser: Water-cooled interconnected to the water-cooled VRF heat pump water loop. 1. Indoor cabinet hung from building structure above lay-in ceiling. 2. 7/8" OD CU heat pump water supply and return piping connections with supply water temperature range 60 deg. F to 85 deg. F. 3. Hot-gas bypass. 4. DX refrigerant piping between condenser and evaporator. See manufacturer's installation instructions for refrigerant pipe sizes, and requirements. 2.03 CONTROL SYSTEM A. Microprocessor control panel with audible and visual alarms. B. Liebert model NIC-ENCL1 IntelliSlot Modbus adapter card. 1. Delivers WEB, Telnet, SNMP and EIA-485 MODBUS communication and control capabilities using one IntelliSlot Web/485 Adapter in an externally mounted steel enclosure for monitoring Liebert Datawave units. Delivers WEB, Telnet, SNMP, EIA-485 15739 CRITICAL COOLING UNITS Page 1 of 2 Kirtland Community College Health Sciences Education and Training Center MODBUS and BACnet IP communication and control capabilities using one IntelliSlot Web/485 Adapter in an externally mounted steel enclosure for monitoring Liebert DataMate and Mini-Mate2 units. The self-contained kit is intended for applications where internal mounting is difficult or not possible, and includes an external 120 VAC to 24 VAC. 2. Temperature Control Contractor shall interconnect adapter card and integrate controller to BCS. PART 3 EXECUTION 3.01 EXAMINATION A. Verify that ceiling system is ready to receive work and opening dimensions are as indicated on shop drawings. B. Verify that electric power is available and of the correct characteristics. 3.02 INSTALLATION A. Install in accordance with manufacturer's instructions. B. Coordinate installation of air conditioning unit with computer room ceiling installer. C. Pipe heat pump water supply and return to unit including strainer, isolation valve, return side circuit setter, and coil drain. Include flow-switch and pipe accessories per manufacturer's installation instructions. D. Pipe refrigerant piping between condenser and evaporator instrict accordance with manufacturer installation instructions. Provide 407C charge as needed. E. Install condensate pump and pipe to nearest gravity drained condensate main pipe. F. Install control panel, room thermostat controller, and interconnect to BCS. END OF SECTION 15739 CRITICAL COOLING UNITS Page 2 of 2 Kirtland Community College Health Sciences Education and Training Center SECTION 15260 THERMAL INSULATION PART 1 GENERAL This section includes thermal insulation specifications for all plumbing and HVAC equipment. 1.01 1.02 Quality Assurance: A. Bidders shall specialize in mechanical insulation application and have a minimum of three years experience, or pre-approval for bidding from the engineer. B. Furnish insulation, jackets, coverings, sealers, mastics, and adhesives with flame-spread index of 25 or less, and smoke-developed index of 50 or less, in accordance with the 2003 Michigan Mechanical Code (MMC), ASTM E-8, NFPA 255, or UL 723. C. Insulation shall be furnished and installed in compliance with the National Commercial & Industrial Insulation Standards, 5th Edition. Refer to www.insulation.org/index for manual information. D. Insulation shall meet standards specified by the American Society of Heating, Refrigeration, and Air-Conditioning Engineers, National Voluntary Consensus Standard 90.1 (1999), "Energy Efficient Design of New Buildings (ASHRAE 90.1-1999.) Performance Specification: A. Insulation materials furnished should meet the minimum thickness requirements of ASHRAE 90.1-1999. However, if other factors such as condensation control or personnel protection are to be considered, the selection of the thickness of insulation should satisfy the controlling factor. B. Insulation materials furnished and installed hereunder shall meet the fire hazard requirements of applicable building codes when tested in composite form per one of the following nominally equivalent test methods: 1. American Society for Testing of Materials 2. Underwriters' Laboratories, Inc. 3. National Fire Protection Association C. 1.03 ASTM E-84 UL 723 (CAN/ULC-S102-M88) NFPA 255 As specified in ASTM E-84, and the 2003 MMC, all insulation shall have a flame spread index of not more that 25, and a smoke-developed index of not more than 50 (MMC Section 602.) Submittals: A. Provide manufacturer data and installation sheets for each type of insulation material used. B. Provide (10) copies of bound shop drawings. Shop drawing submittals shall include: 1. Job Name 2. Supplier and contractor name, address, phone, and fax. 3. Material specifications and intended area of use. 15260 THERMAL INSULATION Page 1 of 9 Kirtland Community College Health Sciences Education and Training Center PART 2 PRODUCTS 2.01 Manufacturers: A. B. C. D. E. F. G. H. I. J. Owens Corning Certainteed Knauf 3M Insulation Solutions TVM Building Products Pabco-Childers Metals Armacell Engineered Foams (formerly Armstrong Insulation Company) TruBro McGuire Manufacturing Company Contact Nealis Engineering at 231-933-0510 for other insulation manufacturer approval. PART 3 MATERIALS Type 1 Non-Flexible, Jacketed, Fiberglass Pipe Insulation 1. 2. 3. 4. C. D. E. F. Fiberglass pipe Insulation Heavy density resin bonded inorganic fibers Formaldehyde Free Hinged sections to slip over pipe Smooth, reinforced, vapor retardant, all service jacket (ASJ) Longitudinal, pressure sensitive adhesive self-sealing lap seal and butt seal Approved for use up to 850 deg. F. Meets ASTM C 547 (mineral fiber insulation), ASTM 1136 (vapor barrier), ASTM C 795 (austenitic stainless steel) G. Meets 25/50 flame and smoke developed index, ASTM E-84, NFPA 90A Type 2 Non-Flexible, PVC Jacketed, Fiberglass Pipe Insulation 1. Same as Type A, except shall be securely covered with 15 mil PVC jacket. 2. Meets 25/50 flame and smoke developed index, ASTM E-84, NFPA 90A Type 3 Foil-backed, All Service Duct Wrap Insulation 1. 2. 3. 4. 5. Type 4 0.75 pounds per cubic feet (pcf) Thermal resistance, R = 3.5 hr-sf-F/Btu (1-1/2” thick) Foil, reinforced, kraft low permeance vapor retarder backing (foil-backed) Meets 25/50 flame and smoke developed index, ASTM E-84, NFPA 90A Paper-backed insulation typically does not meet ASTM E-84, and shall not be approved. Preformed Pipe and P-Trap Covers for ADA Barrier Free Lavatories and Sinks 1. Soft molded vinyl exterior 2. 1/8” thick with internal ribs 3. Shall fit 1-1/4” or 1-1/2” cast brass, tubular p-trap assemblies, and schedule 40 PVC ptraps 4. Bacteria and fungi resistance 5. White color, latex paintable 6. Ceanable 7. ASTM D-635 15260 THERMAL INSULATION Page 2 of 9 Kirtland Community College Health Sciences Education and Training Center 8. For specified use only Type 5 Flexible, Closed-Cell, Pipe Insulation 1. 2. 3. 4. 5. 6. 7. Type 6 Duct Liner for Thermal Insulation Purposes 1. 2. 3. 4. 5. 6. 7. 8. Type 7 Bonded glass fiber blanket Thermal Conductivity, K = 0.25 Btu-in/hr-SF-F R = 8.0 hr-sf-F/Btu (2” thick) Bacterial and fungi resistance ASTM C 1338 and ASTM G-21 (fungi), ASTM G-22 (bacteria) Meets 25/50 flame and smoke developed index, ASTM E-84, NFPA 90A Sheet metal contractor to provide and install duct liner Include manufacturer specified fasteners and adhesives See HVAC Ductwork Specification Section 15890 for further installation info Zero-Clearance Duct Wrap for Type 1, Grease-Laden Ductwork and Hoods 1. 2. 3. 4. 5. 6. 7. 8. Type 8 Closed-cell, flexible, elastomeric, piping insulation (Armaflex or Equal) Thermal Conductivity, K = 0.27 Btu-in/hr-sf-F Vapor transmission 0.08 perm-in Non CFC, HFC, HCFC, manufactured, and formaldehyde free Mold and mildew resistant Meets 25/50 flame and smoke developed index, ASTM E-84, NFPA 90A Include seam and butt joint adhesive Fire-resistant wrap consisting of inorganic blanket encapsulated with scrim-reinforced foil Used as alternative to 1 and 2 hour rated shaft assemblies Zero-clearance, two (2) hour fire rating Non-asbestos Zero smoke and fire developed index ASTM C 411, ASTM C 518, ASTM E-84, ASTM E-19, ASTM E-136, ASTM E-814 UL 1978 Include silicone seam sealants per manufacturer recommendations and specifications. Specialty Insulation Covers 1. 2. 3. 4. 5. 8. 9. 10. 11. Closed-cell, flexible, elastomeric, sheet or roll insulation 1” thick Thermal Conductivity, K = 0.27 Btu-in/hr-sf-F Vapor transmission 0.08 perm-in Non CFC, HFC, HCFC, manufactured, and formaldehyde free Mold and mildew resistant Meets 25/50 flame and smoke developed index, ASTM E-84, NFPA 90A Include seam and butt joint adhesive Field fabricated insulated sheet metal cover to cover chilled-water pump casing and flanges 12. Removable and reusable sheet metal cover 15260 THERMAL INSULATION Page 3 of 9 Kirtland Community College Health Sciences Education and Training Center Type 9 Radiant Floor and Snowmelt Insulation Three types of radiant floor and snowmelt insulation are approved for use. A. Insulated Tarp 1. 2. 3. 4. 5. 6. 7. High density closed-cell foam and high density polyethylene bubble-wrap sandwiched between cross-woven polyethylene sheets with reflective aluminum inner backing. Thickness = 3/4" Thermal resistance, R = 7.5 hr-sf-F/Btu Permeance = .002 perms Temperature rating = 180 deg. F to -60 deg. F Compressive strength for use up to 90 psi (12,960 lbf/sf), for use under sidewalks, residential and heavy equipment garages, garage aprons, and driveways. Not approved for other mechanical thermal insulation uses B. High Density Polystyrene Insulation with Vapor Barrier 1. 2. 3. 4. High density extruded polystyrene sheets Thickness = 1” Thermal resistance, R = 5.0 hr-sf-F/Btu Compressive strength to meet use a. 25 psi (3600 lbf/sf), typical for radiant floor heat, sidewalks, and residential garages. b. 40 psi (5760 lbf/sf), for light commercial garages, garage aprons, and driveways. c. 60 psi (8640 lbf/sf), for medium duty commercial garages, garage aprons, and driveways. d. 100 psi (14,400 lbf/sf), for heavy equipment garages, garage aprons, and driveways. e. Refer to structural engineering and architectural drawings and specifications for further information, and verify use with general contractor. 5. 6. 7. Install separate 4 mil polyethylene roll sheet underneath high density sheets for vapor barrier, permeance less than 0.08 perms ASTM D1621, ASTM E 96 Not approved for other mechanical thermal insulation uses. C. Aluminum Foil and Bubble Wrap Sheeting (Voluntary Alternate Only) 1. 2. 3. 4. 5. 6. 7. Two layers of polyethylene bubble wrap insulation and aluminum foil reflective surface sheeting. Thickness = 5/16” (may vary) Thermal resistance = not less than 3.5 hr-sf-F/Btu per ASTM C236 Temperature rating = 180 deg. F to -50 deg. F Permeance = less than 0.05 perms Compressive strength = 100 psi (14,400 lbf/sf) Not approved for other mechanical thermal insulation uses. 15260 THERMAL INSULATION Page 4 of 9 Kirtland Community College Health Sciences Education and Training Center 3.01 Accessories All insulation accessories shall meet state and local fire codes, and shall meet NFPA 90A for use within air plenums. . A. Closure Materials including butt strips, bands, wires, staples, mastics, adhesives, caulks or sealants, pressure-sensitive tapes. B. Support materials including hanger straps, hanger rods, saddles, and support rings, wire mesh, plastic ties, etc. C. Fastener materials including welded pin or adhesive pin mechanical fasteners, speed clips, pressure-sensitive tapes, caulks or sealants D. Jackets and Prefabricated Fitting Covers 1. PVC Jackets a. Minimum 0.028 inch thick b. Bacterial and mildew resistant c. Designed for exterior use 2. Aluminum Jackets a. Aluminum Alloy b. 0.010” thick c. Moisture barrier d. Smooth finish e. Include 45 or 90 degree short and long radius elbows, and end caps as necessary 3.02 Installation Instructions Refer to the following Insulation Schedule areas of insulation use and insulation thickness. PIPING INSULATION SCHEDULE Service Domestic Water Pipe, CW, HW Domestic Water Pipe, CW, HW Roof and Storm Drains Exposed Roof and Storm Drains P-Traps, HW and CW Piping Below ADA Barrier Free Lavatories and Sinks Heating Hot Water Pipe, HWS and HWR Heating Hot Water Pipe, HWS and HWR Chilled Water Pipe, CHWS and CHWR Condensate Piping in Unconditioned or Pipe Size Type Thickness Less than 4” 1 1/2" 4” and Greater 1 1" All Sizes 1 1" All Sizes 2 1" All Sizes 4 1/8" Less than 4” 1 1" 4” and Greater 1 1-1/2" All Sizes 1 1" All Sizes 1 1/2" 15260 THERMAL INSULATION Page 5 of 9 Kirtland Community College Health Sciences Education and Training Center Conditioned Spaces Exposed Condensate Piping Exposed Heating Hot Water Pipe, HWS and HWR Exposed Chilled Water Pipe, CHWS and CHWR Underground Hot Water Supply and Return Pipe Underground Snowmelt or Radiant Heat Piping Mains All Sizes 2 1/2" All Sizes 2 1" All Sizes 2 1" All Sizes 5 1" All Sizes 5 1" EQUIPMENT INSULATION SCHEDULE Type Supply Air Ductwork (Exposed ductwork shall not be insulated) Return Air Ductwork in Indirectly Conditioned Spaces Return Air Ductwork in Plenums or Conditioned Spaces Outdoor Supply and Return Ductwork Fresh Air (Outdoor Air) Ductwork - All Cases Combustion Air Duct Work - All Cases Exhaust Air Ductwork in Unconditioned, Concealed, Inaccessible Spaces Exhaust Air Ductwork in Plenums or Conditioned Spaces Relief Air Ductwork in Unconditioned, Concealed, Inaccessible Spaces Relief Air Ductwork in Plenums or Conditioned Spaces VRF Refrigerant Suction and Liquid Lined Chilled Water Pumps Equipment Size Insulation Type Thickness All Sizes 3 1-1/2" All Sizes N/A Not Required All Sizes Not Required Not Required All Sizes 6 2" All Sizes 3 2" All Sizes 3 2" All Sizes 3 1-1/2" All Sizes Not Required Not Required All Sizes 3 1-1/2" All Sizes Not Required Not Required All Sizes 5 3/4" All Sizes 8 1" 15260 THERMAL INSULATION Page 6 of 9 Kirtland Community College Health Sciences Education and Training Center Chilled Water Air Separators Radiant Floor and/or Snowmelt Underground Ductwork 3.03 All Sizes 8 1" All Sizes 9 See Spec Above All Sizes 9 Min. R-3.5 See Section 3.08 Below Installation A. General Instructions: 1. 2. 3. 4. 5. 6. 7. 8. B. Type 1, Pipe Insulation 1. 2. 3. 4. 5. C. Install all materials in strict accordance to manufacturer’s specifications. Install insulation after testing and testing approval is completed, in coordination with the mechanical contractor. Install insulation after heat tracing, or buried pipe tracing, is installed. Butt edges of insulation together, and seal joints with proper adhesives or jackets per manufacturer specifications. Seal insulation butt joints with 3” pressure-sensitive tape. Hot Water Systems: For hot water systems insulation is not required to be installed on valves, control valves, strainers, air separators, expansion tanks, and pump housings. See below for more info. Heat pump piping (HPWS/R) is not required to be insulated. All variable refrigerant flow (VRF) system refrigerant piping shall be insulated per the manufacturer installation instructions. Coordinate with VRF system supplier and certified refrigerant piping supplier. Clean all piping free of dirt, grease, flux, etc. Install insulation materials with smooth and even surfaces. Insulate each continuous run of piping with full-length units of insulation, with single cut piece to complete run. Do not use cut pieces or scraps abutting each other. Butt insulation joints firmly to ensure complete, tight fit over all piping surfaces. Butt pipe insulation against hanger inserts. Secure with self-sealing facing tabs or 3” wide pressure sensitive tape. On non-serviceable unions, flanges, pipe terminations etc., provide prefabricated fitting covers. On serviceable items use removable and reusable, prefabricated fitting covers. Type 2, PVC Jacketed Pipe Insulation 1. 2. 3. 4. Same as Type 1 insulation, with PVC jacket installed over pipe insulation. PVC jacketing shall be designed to fit over Type 1 insulation. Install PVC jacketing per manufacturer instructions. Install prefabricated PVC jacketing for: a. b. c. d. 5. Elbows End-Caps Chilled water systems listed below Non-serviceable hot water piping systems listed below. Secure PVC jacketing with approved PVC sealant and banding. 15260 THERMAL INSULATION Page 7 of 9 Kirtland Community College Health Sciences Education and Training Center D. Type 3, Foil-Backed All-Service Duct Insulation 1. Clean all ductwork free of dust and grease. Verify that ductwork is dry, and joints are tightly sealed, and joint sealant is applied. Completely cover all supply, outdoor air, and/or return and exhaust ductwork as specified in the Insulation Schedule. Remove a 2” piece of insulation from the foiled backing at the end of the piece of duct wrap to form an overlapping stapling and taping flap seam. Install duct wrap insulation with facing outside so that the tape flap overlaps the insulation and facing at the other end of the piece of duct wrap. Adjacent sections of duct wrap insulation shall be tightly butted with the 2" stapling and taping flap overlapping. If ducts are rectangular or square, install so insulation is not excessively compressed at corners. Staple seams at 6” on-center intervals with outward clinching 1/2” steel staples. Seal seams with 3” pressure sensitive tape. Cloth duct tape of any color or finish using reclaimed rubber adhesives is not approved for use. Where rectangular ducts are 24" (600mm) in width or greater, duct wrap insulation shall be additionally secured to the bottom of the duct with mechanical adhesive pinfasteners, and speed clips. 2. 3. 4. 5. 6. 7. 3.04 Preformed Pipe and P-Trap Covers for ADA Barrier Free Lavatories and Sinks A. ADA Barrier Free preformed pipe and p-trap covers shall be installed per manufacturer instructions where indicated on the Plumbing Drawings and Fixture Schedule. 1. Type 5, Flexible, Closed-Cell, Pipe Insulation 1. 2. 3.05 Clean all piping free of dirt, grease, flux, etc. Install insulation over all piping, unions, or flanges. Hot Water System Components: A. Install insulation on all equipment listed below. B. Insulation is not required on the following hot water systems: 1. 2. 3. 4. 5. 6. Valves Control Valves Strainers Air Separators Expansion Tanks Pumps C. Extend insulation without interruption through walls, floors and similar penetrations, except where otherwise indicated. D. Apply foam insulation between piping and pipe sleeves that penetrate exterior walls or floors, and seal with 100% silicone caulk. E. Do not insulate pipe that penetrates fire rated walls, floors, or ceilings. 15260 THERMAL INSULATION Page 8 of 9 Kirtland Community College Health Sciences Education and Training Center 3.07 Underground Piping: A. Insulate all snowmelt tubing between the point it leaves the snowmelt manifold (indoors) to the point it enters the concrete sidewalk slab. B. Provide smooth or level trench, clean of debris, between 18” and 24” below grade, for all underground piping. C. Provide pipe sleeves for all penetrations through walls and slabs. D. Install all underground fittings and unions per manufacturer specifications. E. Install a continuous, unbroken, vapor barrier over all underground piping insulation. F. Provide As-Built Drawings to engineer and owner showing the exact location and depth of all underground piping. G. Provide clean backfill, free of debris. 3.08 Underground Ductwork: A. Insulate around all underground ductwork with a minimum R-3.5 insulation. The installing contractor has their choice of using Type-9 rigid insulation, Insul-Tarp, or bubble-wrap insulation. In this case the bubble-wrap is approved as Base Bid, and is not a voluntary alternate only. END OF SECTION 15260 THERMAL INSULATION Page 9 of 9