Addendum 1 - County Blue Reprographics Distribution Planroom

advertisement
222 South Central Ave.
Suite 100
St. Louis, MO 63105
314.863.4994
www.bondarchitectsinc.com
Addendum 1
TO:
COMPANY:
- Edgar Velazquez
- Duane Emanuel
- Pre-bid meeting attendees
- Bev
FROM:
FAX NO/EMAIL:
- STLCo. Economic Council
- STLCo. Public Works
- County Blue Reprographics
ADDENDUM ISSUE DATE:
Holly Rudd
April 12, 2013
PROJECT:
evelazquez@slcec.com
repro@countyblue.com
ADDENDUM NUMBER:
1
PROJECT NO:
MET Center: 4th & 5th Floor
12024
TO ALL BIDDERS:
THIS ADDENDUM FORMS A PART OF THE CONTRACT DOCUMENTS AND MODIFIES THE ORIGINAL
DOCUMENTS DATED 3-13-13. PLEASE ACKNOWLEDGE RECEIPT OF THIS ADDENDUM ON THE BID FORM.
CHANGES TO THE PROJECT MANUAL
Table of Contents
1.
2.
Add in Table of Contents, "Technical Specifications for Asbestos Abatement"
Section exists at the end of Division 00.
Front End Spec Section - RFP & Instructions to Bidders
1. PLEASE NOTE: Contractors who received project manuals from County Blue Reprographics
have already received this change. This corrected document was swapped out prior to
Advertisement for Bid.
2. Modifies schedule dates.
Front End Spec Section - Form of Price Proposal
1. PLEASE NOTE: Contractors who received project manuals from County Blue Reprographics
have already received this change. This corrected document was swapped out prior to
Advertisement for Bid.
2. Section 4.1 (Alternates): Fill in the amount bid for the Alternate in the column entitled "Price" in
the appropriate space opposite the "Alternate" column and indicate the price is an increase to
the Base Bid Price by using the symbol "+."
Front End Spec Section - Advertisement for Bids
1. PLEASE NOTE: Contractors who received project manuals from County Blue Reprographics
have already received this change. This corrected document was swapped out prior to
Advertisement for Bid.
2. Modifies schedule date of pre-bid meeting.
011000 - Summary
Page 1 of 4
1.
2.
Section 1.4.B to read, "General Contractor shall award a contract(s) for the following
construction operations at Project Site. Those operations to be scheduled by General
Contractor, in a timely manner, concurrent with other work.
a. Add section 1.4.B.2 - "Building to remain sealed and dry during non-construction hours."
b. Add section 1.4.B.3 - "Hazardous debris to be removed by abatement contractor."
Add section 1.5.D - "Maintain access to fifth floor roof door, to be accessed by building staff as
needed for maintenance."
012500 - Substitution Procedures
1. PLEASE NOTE: Contractors who received project manuals from County Blue Reprographics
have already received this change. This corrected document was swapped out prior to
Advertisement for Bid.
2. Section 2.1.A to read, "See exhibit C-EDA required contracting provisions for construction
projects, Section 10 "Or Equal" clause."
3. Eliminate section 2.1.B
016000 - Product Requirements
1. PLEASE NOTE: Contractors who received project manuals from County Blue Reprographics
have already received this change. This corrected document was swapped out prior to
Advertisement for Bid.
2. Section 2.2.A to read, "Conditions for Consideration: See exhibit C-EDA required contracting
provisions for construction projects, Section 10 "Or Equal" clause."
3. Eliminate sections 2.2.A 1-5.
220517 - Sleeves and Sleeve Seals for Plumbing Piping
1. PLEASE NOTE: Contractors who received project manuals from County Blue Reprographics
have already received this spec section. Document was added prior to Advertisement for Bid.
2. Per Table of Contents, Add spec section 220517.
230713 - Duct Insulation
1. DELETE: From Specifications section 230713 Duct Insulation, paragraph 3.9 Indoor Duct and
Plenum Insulation Schedule.
2. ADD: To the specifications section 230713 Duct Insulation, Paragraph 3.9 Indoor Duct and
Plenum Insulation Schedule: The following table.
Duct Insulation Schedule
Duct Description
Duct location
Insulation
Thickness
Density
Supply - Rectangular
Between Roof and VAV
Lined, Mineral-Fiber board
1-1/2"
2-lb/c.f.
Supply - Rectangular
Between RTU and Roof
Lined, Mineral-Fiber board
3"
2-lb/c.f.
Supply - Round
All solid
Wrap, Mineral-Fiber Blanket
1-1/2"
1.5 lb/c.f.
Supply - Round
Flexible
Return - Rectangular
All
See specifications
All
Lined, Mineral-Fiber board
1/2" min.
2-lb/c.f.
Exhaust - All
Prep lab, Class room, fume
hoods
Plenum space
Wrap, Mineral-Fiber Blanket
1-1/2"
1.5 lb/c.f.
1/2" min.
2-lb/c.f.
Transfer Ducts
Lined, Mineral-Fiber board
Bathroom exhaust
does not need
insulation
Page 2 of 4
Bond Architects
CHANGES TO THE DRAWINGS
ARCHITECTURAL DRAWINGS
A2.0
1.
2.
3.
A8.0
1.
A12.1
1.
Floor Plans
Room 520 - Elec/ Data - Relocate door to south wall.
a. See attached sketch, "A2.0-1"
Modify Keyed Note #209 to read, "Remove vent & patch masonry at existing opening (approx.
5" x 16"). See detail 12/A8.0"
Modify Keyed Note #232 to read, " Provide floor leveling throughout areas of severe concrete
damage (generally west of column-3). Provide skim coat over sealant at existing electrical
penetrations, throughout"
Floor Plans
Add detail 12/A8.0 - Detail at exterior wall patch.
a. See attached sketch, "A8.0-1"
Door Schedule
Doors 502 & 503 - Under-cut 3/4"
MECHANICAL DRAWINGS
M1.2
1.
5th Floor HVAC Plan
See attached sketches, M1.2-1A, M1.2-1B and M1.2-1C
M2.2
1.
M3.1
1.
2.
Mechanical Sections & Details
ADD: To drawing sheet M2.2 – Detail Section A-A: Note 1: Contractor shall coordinate
supply and return rises with structural member and install offsets as needed to avoid structural
members.
Mechanical Schedules
ADD: To sheet M3.1 – Rooftop Unit Schedule: Note 8. Provide hail guard
See attached sketches M3.1-1A, M3.1-1B and M3.1-1C
M6.1
1.
2.
RTU Control
ADD: To sheet M6.1 – RTU-1 shall report filter status to BAS system
Clarify portion of control sequences, See attached re-issued sheet M6.1.
M6.2
1.
M6.3
1.
2.
3.
4.
5.
Exhaust Control
Clarify portion of control sequences, See attached re-issued sheet M6.2.
VAV Box & FPB Controls
DELETE: From sheet M6.3 from input/output summary table, Location: Kirksville, Missouri
ADD: To sheet M6.3 from input/output summary table, Location: Fifth Floor
DELETE: From sheet M6.3 from input/output summary table, Building Name-Army Reserve
Center
ADD: To sheet M6.3 from input/output summary table, Building Name- MET Center
Remove airflow monitor from parallel fan power units, See attached re-issued sheet M6.3.
Page 3 of 4
Bond Architects
ME1.4
1.
2.
3.
Mechanical & Electrical Roof Plan
DELETE: From sheet ME1.4 Key Note 4, Unit heaters are hung from 6th floor joists.
ADD: To sheet ME1.4 Key Note 4, "Unit heaters shall be hung from roof joist in 6th floor to
supply heat to 6th floor."
See attached sketch ME1.4-1.
PLUMBING DRAWINGS
P1.1
P1.2
P2.1
1.
See attached sketch P1.1-1
1.
See attached sketch P1.2-1
1.
See attached sketch P2.1-1
Plumbing Supply Plan
Plumbing Drainage Plan
Plumbing Riser Plan
ELECTRICAL DRAWINGS
E1.0
E1.1
1.
See attached, re-issued sheet
1.
See attached, re-issued sheet
1.
See attached, re-issued sheet
1.
See attached, re-issued sheet
5th Floor Electrical Power Plan
5th Floor Lighting Plan
E1.3
E1.6
Partial 4th Floor Lighting Plan
Electrical Schedules
LIST OF ATTACHMENTS
Spec section 220517
A2.0-1
A8.0-1
M1.2-1A
M1.2-1B
M1.2-1C
M3.1-1A
M3.1-1B
M3.1-1C
M6.1
M6.2
M6.3
ME1.4-1
P1.1-1
P1.2-1
P2.1-1
E1.0
E1.1
E1.3
E1.6
END OF ADDENDUM NO. 1
Page 4 of 4
Bond Architects
MET Center Renovation: 4th & 5th Floor
02/11
SECTION 220517 - SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
Section Includes:
1.
2.
3.
4.
5.
1.3
Sleeves.
Stack-sleeve fittings.
Sleeve-seal systems.
Sleeve-seal fittings.
Grout.
ACTION SUBMITTALS
A.
Product Data: For each type of product indicated.
PART 2 - PRODUCTS
2.1
SLEEVES
A.
Cast-Iron Wall Pipes: Cast or fabricated of cast or ductile iron and equivalent to ductile-iron
pressure pipe, with plain ends and integral waterstop unless otherwise indicated.
B.
Galvanized-Steel Wall Pipes: ASTM A 53/A 53M, Schedule 40, with plain ends and welded
steel collar; zinc coated.
C.
Galvanized-Steel-Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, zinc
coated, with plain ends.
D.
PVC-Pipe Sleeves: ASTM D 1785, Schedule 40.
E.
Galvanized-Steel-Sheet Sleeves: 0.0239-inch minimum thickness; round tube closed with
welded longitudinal joint.
F.
Molded-PE or -PP Sleeves: Removable, tapered-cup shaped, and smooth outer surface with
nailing flange for attaching to wooden forms.
G.
Molded-PVC Sleeves: With nailing flange for attaching to wooden forms.
SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
220517 - 1
MET Center Renovation: 4th & 5th Floor
2.2
02/11
SLEEVE-SEAL SYSTEMS
A.
Manufacturers: Subject to compliance with requirements, available manufacturers offering
products that may be incorporated into the Work include, but are not limited to, the following:
1.
2.
3.
4.
5.
B.
Description: Modular sealing-element unit, designed for field assembly, for filling annular
space between piping and sleeve.
1.
2.
3.
2.3
Advance Products & Systems, Inc.
CALPICO, Inc.
Metraflex Company (The).
Pipeline Seal and Insulator, Inc.
Proco Products, Inc.
Sealing Elements: EPDM-rubber interlocking links shaped to fit surface of pipe. Include
type and number required for pipe material and size of pipe.
Pressure Plates: Carbon steel.
Connecting Bolts and Nuts: Carbon steel, with corrosion-resistant coating, of length
required to secure pressure plates to sealing elements.
SLEEVE-SEAL FITTINGS
A.
Manufacturers: Subject to compliance with requirements, available manufacturers offering
products that may be incorporated into the Work include, but are not limited to, the following:
1.
B.
2.4
Presealed Systems.
Description: Manufactured plastic, sleeve-type, waterstop assembly made for imbedding in
concrete slab or wall. Unit has plastic or rubber waterstop collar with center opening to match
piping OD.
GROUT
A.
Standard: ASTM C 1107/C 1107M, Grade B, post-hardening and volume-adjusting, dry,
hydraulic-cement grout.
B.
Characteristics: Nonshrink; recommended for interior and exterior applications.
C.
Design Mix: 5000-psi, 28-day compressive strength.
D.
Packaging: Premixed and factory packaged.
PART 3 - EXECUTION
3.1
SLEEVE INSTALLATION
A.
Install sleeves for piping passing through penetrations in floors, partitions, roofs, and walls.
SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
220517 - 2
MET Center Renovation: 4th & 5th Floor
B.
02/11
For sleeves that will have sleeve-seal system installed, select sleeves of size large enough to
provide 1-inch annular clear space between piping and concrete slabs and walls.
1.
Sleeves are not required for core-drilled holes.
C.
Install sleeves in concrete floors, concrete roof slabs, and concrete walls as new slabs and walls
are constructed.
D.
Install sleeves for pipes passing through interior partitions.
1.
2.
3.
E.
3.2
Cut sleeves to length for mounting flush with both surfaces.
Install sleeves that are large enough to provide 1/4-inch annular clear space between
sleeve and pipe or pipe insulation.
Seal annular space between sleeve and piping or piping insulation; use joint sealants
appropriate for size, depth, and location of joint. Comply with requirements for sealants
specified in Section 079200 "Joint Sealants."
Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors
at pipe penetrations. Seal pipe penetrations with firestop materials. Comply with requirements
for firestopping specified in Section 078413 "Penetration Firestopping."
SLEEVE-SEAL-SYSTEM INSTALLATION
A.
Install sleeve-seal systems in sleeves in exterior concrete walls and slabs-on-grade at service
piping entries into building.
B.
Select type, size, and number of sealing elements required for piping material and size and for
sleeve ID or hole size. Position piping in center of sleeve. Center piping in penetration,
assemble sleeve-seal system components, and install in annular space between piping and
sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make a
watertight seal.
3.3
SLEEVE-SEAL-FITTING INSTALLATION
A.
Install sleeve-seal fittings in new walls and slabs as they are constructed.
B.
Assemble fitting components of length to be flush with both surfaces of concrete slabs and
walls. Position waterstop flange to be centered in concrete slab or wall.
C.
Secure nailing flanges to concrete forms.
D.
Using grout, seal the space around outside of sleeve-seal fittings.
3.4
SLEEVE AND SLEEVE-SEAL SCHEDULE
A.
Use sleeves and sleeve seals for the following piping-penetration applications:
1.
Concrete Slabs above Grade:
SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
220517 - 3
MET Center Renovation: 4th & 5th Floor
a.
b.
2.
02/11
Piping Smaller Than NPS 6: Galvanized-steel-pipe sleeves.
Piping NPS 6 and Larger: Galvanized-steel-pipe sleeves.
Interior Partitions:
a.
b.
Piping Smaller Than NPS 6: Galvanized-steel-pipe sleeves.
Piping NPS 6 and Larger: Galvanized-steel-sheet sleeves.
END OF SECTION 220517
SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
220517 - 4
202
7' - 2"
511
1B
COATS
205
502
9' - 6"
512
517
BREAK AREA
516
2' - 4 7/8"
4' - 10"
A10.0
232
12' - 11"
3
4A
227
219
7' - 1" 4B
7' - 0"
221
4B
5B
232
524
5' - 0"
201
6' - 5 1/4"
CLEAR
522
5' - 10"
CORRIDOR
523
17' - 5"
1B
OFFICE
524
11' - 7"
9' - 11 7/8"
11' - 7"
1B
1
2
OFFICE
501
1B
520
6' - 5 1/4"
521
523
17' - 9 3/8"
OPEN OFFICE
Add.1
515
211
3
1C
5B
D
218
3
7' - 4 1/2"
W
1B
15' - 8"
227
227
4B
5' - 10"
EQ.
232
3
ALIGN
16' - 9"
521
224
4A
233
5' - 0"
WOMEN
CORRIDOR
14' - 5"
9' - 9 1/8"
"
520
3
4A
201
515
1C
ELEC/ DATA
MECHANICAL
LAB STORAGE
207
1B
3
2' - 1"
6347 Plymouth Ave. St. Louis, MO 63133
222 South Central Ave Suite# 100 St. Louis, MO 63105
TEL: 314.863.4994 FAX: 314.863.4996
A10
EQ.
227
EXISTING
3 7/8"
E5
5
A8.0
MET Center Renovation: Fourth & Fifth
Floor
2
525
519
206
1B
201
518
JANITOR
503
204
CORRIDOR
MEN
1B
1' - 8"
2' - 0 1/2"
9' - 5"
519
1' - 8"
A10.0
A6
7' - 4 1/4"
3
6' - 5 1/4"
CLEAR
5' - 10"
1B
20' - 0"
7
10' - 0"
510
6' - 5 1/4" 2' - 6"
1B
224
2' - 0"
6' - 8"
19' - 10 5/8"
6' - 8 5/8"
6' - 0"
2' - 6" 1' - 6"
3/8"
SIM.
3
SIM.
31
SIM.
12024
4-9-12
Date:
Scale:
Reference Sheet:
A2.0
A2.0-1
4
EXISTING MASONRY
WALL, VERIFY
THICKNESS
+/- 1' - 0"
+/- 8"
SEE PLAN
V.I.F.
FURRING
PARTITION,
SEE PLAN
MASONRY PATCH,
MATCH EXISTING
EXTERIOR BRICK
+/- 5"
FINISH FLOOR
OVER FLOOR
LEVELING
PATCH RECESSED
FLOOR AREA. PROVIDE
FLOOR LEVELING
THROUGHOUT 5TH FL.
EXISTING CONC. SLAB
12
A8.0
E
DETAIL AT EXTERIOR WALL PATCH
1" = 1'-0"
Add.1
D
ADJACENT
PARTITION, WHERE
IT OCCURS ON PLAN
EXISTING EXT.
MASONRY WALL
EXISTING
EXTERIOR SILL
NEW ALUM.
SF WINDOW
D MET Center Renovation: Fourth & Fifth
Floor
INTERIOR P.LAM
WINDOW SILL (PL-4),
TYP. ALL WEST
WINDOWS
PATCH RECESSED
FLOOR AREA. PROVIDE
12024
FLOOR LEVELING
Date:
4-9-12
THROUGHOUT
5TH FL.
Scale:
Reference Sheet:
1"
4 HOUR RATING 6347 Plymouth Ave. St. Louis, MO 63133
PAINTABLE SEALANT
PROVIDED AT EXISTING
3-3/4" CLAY TILE/ BRICK
COLUMN SURROUND,
PER IBC 2009 TABLE
P.LAMMO
SILL 63105
222 South Central Ave Suite# 100 INTERIOR
St. Louis,
720.1(1)
PL-4 U.N.O.
TEL: 314.863.4994 FAX: 314.863.4996
REMOVE LOOSE DEBRIS
PL-3 IN LAB & PREP LAB
AT DAMAGED PORTIONS
A8.0
C
A8.0-1
509
510
8x10
CLASSROOM
8x10
CLASSROOM
G
125
125
G
100
12x10
14x12
1
S
12x12
1
N/A
40x22
RTU-1
G
100
1
N/A
VAV-3
G
125
T
G
125
36x20
22x12
32x12
12x26
P
E
150
1
N/A
40x12
36x12
A
M2.2
A
M2.2
MEN
5 JANITOR
50 519
503
2
SMOKE DETECTOR
SCALE: NTS
1
INSTALL SMOKE DETECTOR IN RETURN DUCT
MET Center Renovation: Fourth & Fifth
Floor
6347 Plymouth Ave. St. Louis, MO 63133
222 South Central Ave Suite# 100 St. Louis, MO 63105
TEL: 314.863.4994 FAX: 314.863.4996
12024
Date:
4/12/2013 M1.2-1A
Scale:
Reference Sheet:
6
7
E
150
4
842
EF-1
E
150
8x10
20X12
12x12
8x10
EF-2
E
150
CEF-1
CEF-2
8x10
12x12
E
150
M
M
E
150
CC
M2.2
M
M
1
BB
M2.2
E
150
E
150
MOTORIZED DAMPER
SCALE: NTS
1
INSTALL MOTORIZED DAMPERS. COORDINATE
VOLTAGE WITH ELECTRICAL CONTRACTOR
MET Center Renovation: Fourth & Fifth
Floor
6347 Plymouth Ave. St. Louis, MO 63133
222 South Central Ave Suite# 100 St. Louis, MO 63105
TEL: 314.863.4994 FAX: 314.863.4996
12024
Date:
4/12/2013
Scale:
Reference Sheet:
M1.2-1B
S
40x22
VAV-2
12x12
1
N/A
1
N/A
VAV-3
16x10
RTU-1
100
T
G
125
VAV-4
St. LOUIS COUNTY REVIEW COMMENTS
1
28x12
T
D
MEN
518
6X8
2
210
6x10
ELEC/ DATA
WORK AREA
520
504
2
210
10x10
MECHANICAL
521
WOMEN
502
8x10
1
F
70
VAV-6
CORRIDOR
OPEN OFFICE
522
E
150
T
8x10
E
175
1
N/A
20x12
E
125
501
14x10
6"x8
1
N/A
12x12
LOBBY/
RECEPTION
20x12
E
150
VAV-8
E
150
500
COATS
5 JANITOR
50 519
503
VAV-7
G
150
A
M2.2
A
M2.2
517
1
N/A
36x12
26X12
P
12x26
E
150
40x12
18x12
32x12
508
CORRIDOR
CORRIDOR
18x12
36x20
22x12
OFFICE
125
OFFICE
523
12x12
1
N/A
MET Center Renovation: Fourth & Fifth
Floor
6347 Plymouth Ave. St. Louis, MO 63133
222 South Central Ave Suite# 100 St. Louis, MO 63105
TEL: 314.863.4994 FAX: 314.863.4996
524
12024
Date:
4/12/2013
Scale:
Reference Sheet:
M1.2-1C
1
1
1
MET Center Renovation: Fourth & Fifth
Floor
6347 Plymouth Ave. St. Louis, MO 63133
222 South Central Ave Suite# 100 St. Louis, MO 63105
TEL: 314.863.4994 FAX: 314.863.4996
12024
Date:
4/12/2013
Scale:
Reference Sheet: M 3.1-1-A
1
1
1
MET Center Renovation: Fourth & Fifth
Floor
6347 Plymouth Ave. St. Louis, MO 63133
222 South Central Ave Suite# 100 St. Louis, MO 63105
TEL: 314.863.4994 FAX: 314.863.4996
12024
Date:
4/12/2013
Scale:
Reference Sheet: M 3.1-1-B
1
FIRE PROTECTION, DETECTION & ALARM
EQUIPMENT & SYSTEM COMPONENTS;
lp = 1.5 (To identify l refer to Table 4.1)
Fire sprinkler piping
x
x
x
x
x
HAZARDOUS EQUIPMENT & SYSTEM
COMPONENTS;
l = 1.5 (To identify l refer to Table 4.1)
Gas piping 1" or less (interior or exterior)
Gas piping > 1" (exterior)
x
1
x
x
2
OTHER GENERAL EQUIPMENT & SYSTEM
COMPONENTS;
l = 1.0
1
Roof Top
RTU-1 > 400 LBS x
EF-1, EF-2, CEF-1, CEF-2 <= 400 LBS
x
Equipment suspended from structure:
UH-1, UH-2, FBPs, VAVS > 20 LBS
VAVS <= 20 LBS
x
x
4
Wall mounted equipment:
GWH-1
x
x
2
x
x
Duct Work
40x22 Supply riser to RTU-1
l = 1.0
Other Supply and Return Duct
I = 1.0
x
x
x
Exhaust duct connected to
EF-1, EF-2,CEF-1, CEF-2
I = 1.0
Air Devices
I = 1.0
x
x
x
x
x
x
2
3
x
Spec 230548
x
2
x
2
x
2
x
6
1
MET Center Renovation: Fourth & Fifth
Floor
6347 Plymouth Ave. St. Louis, MO 63133
222 South Central Ave Suite# 100 St. Louis, MO 63105
TEL: 314.863.4994 FAX: 314.863.4996
12024
Date:
4/12/2013
Scale:
Reference Sheet: M 3.1-1-C
222 SOUTH CENTRAL AVE.
SUITE# 100
ST. LOUIS, MO 63105
TEL: 314.863.4994
FAX: 314.863.4996
www.bondwolfe.com
DO
1
RTU-1
DI
1
David Mason & Associates
Structural Engineers
MO Cert. of Auth. #
800 S. Vandeventer Ave.
St. Louis, MO 63110
314-534-1030 phone
314-534-1053 fax
RTU-1
CONTROL
PANEL
EXHAUST
FAN
RELIEF
DI
8
Custom Engineering
MEP Engineers
MO Cert. of Auth. # 000239
100 N. Broadway, #1875
St. Louis, MO 63102
314-802-0920 phone
314-802-0921 fax
THERE ARE 10 ZONE SENSORS
1
DA-T
DI-1: RTU-1 SHALL COMMUNICATE WITH THE BAS SYSTEM. BAS SHALL BE ABLE TO READ THE FOLLOWING FROM
THE RTU-1 CONTROLLER.
SPACE STATIC PRESSURE SENSOR
SEE PLAN SHEET M1.2
RA-SD
SA-SD
1
DISCHARGE AIR TEMPERATURE (ACTUAL AND SET POINT)
SUPPLY FAN SPEED
EXHAUST FAN SPEED
SMOKE ALARM STATUS
OCCUPANCY MODE
OUTSIDE AIR RESET TEMPERATURE AND SCALE
OUTSIDE AIR CFM
OUTSIDE AIR TEMPERATURE AND HUMIDITY
THE FOLLOWING SET POINTS SHALL BE ADJUSTABLE FROM THE BAS SYSTEM
1
H
L
DISCHARGE AIR TEMPERATURE
SA
1
OUTSIDE AIR RESET TEMPERATURE AND SCALE
RA
NOTE:
Supply fan, exhaust fan, filters, dampers,
coils, sensors and accessories referenced in this
sequence of operation shall be incorporated with
the RTU except where indicated otherwise on this
drawing.
1
DA-P
SEE PLAN SHEET M1.2
OUTSIDE AIR CFM
DO-1: OCCUPANCY OVERRIDE. IF RTU-1 IS IN UNOCCUPIED MODE THE BAS SHALL BE ABLE TO COMMAND RTU-1
INTO OCCUPIED MODE WHEN ACTIVATED BY A ZONE THERMOSTAT COMMAND DI-8.
RTU SEQUENCE OF CONTROLS
1. Economizer
A. The controller shall enter the economizer mode under the following condition.
OCCUPANCY
1. Outdoor air enthalpy is less than the reference enthalpy set point.
1. The controller shall enable occupancy under any one of the following conditions.
A. BAS communication signal determines occupancy is true.
B. The controller shall perform the following functions in economizer mode.
B. Timed override signal through space temperature sensor.
1. Modulate the outdoor air damper and return air damper positions to maintain the supply air temperature set point.
C. Optimal start sequence enabled.
MODULATION SEQUENCES
2. The controller shall perform the following functions in the occupied mode.
Project No:
1. Supply Fan Modulation
A. Modulate the outdoor air damper and return air damper to the minimum positions (return air damper modulates
inversely to the outdoor air damper).
B. Enable the supply fan upon closure of the outdoor air damper end switch.
C. Enable EF-1 and EF-2 thru the BMS 30 seconds after closure of the supply fan pressure switch.
STL Co. Economic Council
121 S. Meramec Ave. #900
St. Louis, MO 63105
MET Center Renovation:
Fourth & Fifth Floor
BUILDING STATIC PRESSURE
1
1. Outdoor air temperature is less than the supply air temperature set point.
C. All the parameters would be adjustable so you could have a 10 degree increase in discharge air setpoint at 0 deg F
giving you a setpoint of 65 and so on.
Date
4/12/2013
QA/QC
B. Exhaust Fan Modulation
1. The controller shall modulate the RTU exhaust fan speed thru a VFD based on a Space static pressure 0.5" W.G.
relative to the outside..
1. Heating
B. The controller shall perform the following functions in heating mode.
1. When the outdoor air temperature falls below 50 deg F (Adj.), the discharge air setpoint will be increaseD
1
1. Duct static pressure.
TEMPERATURE CONTROL SEQUENCE - Supply Air Temperature Control
A. The controller shall enter the heating mode under the following condition.
12024
Revisions
Description
A. The controller shall modulate the supply fan speed based on the following input.
1
OPTIMIZATION SEQUENCES
1. Active Head Pressure Control
A. The controller shall enable active head pressure control under any of the following conditions.
1. Cooling mode enabled.
2. Dehumidification mode enabled.
2. The controller shall perform the following functions when the active head pressure control sequence is enabled.
B. Modulate and stage the condenser fans to maintain the refrigeration pressure set point (air-cooled).
2. Cooling
A. The controller shall enter the cooling mode under the following condition.
ALARMS/SAFETIES - The following alarms and shutdowns shall be connected to the BMS and require manual reset:
1
1. Outdoor air temperature is greater than the supply air temperature set point.
B. The controller shall perform the following functions in cooling mode.
1. Modulate cooling capacity to maintain the supply air set point.
1.
Dirty filter alarm
2.
Smoke detection in RA and/or SA to alarm and shutdown RTU.
3.
SHUT DOWN:
1.
2.
S.A. fan off, VFD to 0%, Exhaust fan OFF, VFD to 0%
O.A damper closed/R.A. damper open
3.
Refrigerant solenoid valve closed
DATE:
3/13/2013
PERMIT DRAWINGS
RTU Control
M6.1
ROOM EXHAUST SYSTEMS
222 SOUTH CENTRAL AVE.
SUITE# 100
ST. LOUIS, MO 63105
TEL: 314.863.4994
FAX: 314.863.4996
www.bondwolfe.com
LAB ROOM 511 EXHAUST SYSTEM: THE LAB ROOM 511 EXHAUST SYSTEM SHALL BE ENABLED WHEN THE ROOFTOP UNIT IS IN OCCUPIED MODE AND PROOF OF SUPPLY FAN
OPERATION IS CONFIRMED. WHEN ENABLED EXHAUST FAN (EF-1) DAMPER SHALL OPEN. WHEN THE DAMPER IS PROVEN OPEN THE EXHAUST FAN (EF-1) SHALL START
AND THE FAN MOTOR SHALL MODULATE TO MAINTAIN AN EXHAUST RATE OF 1684 CFM (ADJUSTABLE). WHEN THE FUME HOOD EXHAUST FAN IS ENABLED BY A SWITCH ON
THE EXHAUST HOOD THE FUME HOOD EXHAUST FAN (CEH-1) DAMPER SHALL OPEN. WHEN THE DAMPER IS PROVEN OPEN THE FUME HOOD EXHAUST FAN (CEH-1) SHALL
START. THE CEH-1 MOTOR SHALL MODULATE TO MAINTAIN 1345 CFM (ADJUSTABLE) EXHAUST RATE. WHEN CEH-1 IS ENABLED EF-1 MOTOR SHALL MODULATE TO
EXHAUST 339 CFM (ADJUSTABLE). IF CEH-1 DAMPER DOES NOT PROVE OPEN OR IF THE AIR FLOW FALLS BELOW 90% OF THE SET RATE AN ALARM LIGHT SHALL BE
ACTIVATED AT THE FUME HOOD AND CEH-1 SHALL BE DISABLED AND EF-1 SHALL MODULATE TO 1684 CFM (ADJUSTABLE.)
PREP LAB ROOM 512 EXHAUST SYSTEM: THE PREP LAB ROOM 512 EXHAUST SYSTEM SHALL BE ENABLED WHEN THE ROOFTOP UNIT IS IN OCCUPIED MODE AND PROOF OF
SUPPLY FAN OPERATION IS CONFIRMED. WHEN ENABLED EXHAUST FAN (EF-2) DAMPER SHALL OPEN. WHEN THE DAMPER IS PROVEN OPEN THE EXHAUST FAN (EF-2)
SHALL START AND THE RAN MOTOR SHALL MODULATE TO MAINTAIN AN EXHAUST RATE OF 534 CFM (ADJUSTABLE). WHEN THE FUME HOOD EXHAUST FAN IS ENABLED BY
A SWITCH ON THE EXHAUST HOOD THE FUME HOOD EXHAUST FAN (CEH-2) DAMPER SHALL OPEN. WHEN THE DAMPER IS PROVEN OPEN THE FUME HOOD EXHAUST FAN
(CEH-1) SHALL START AND EF-2 SHALL BE DISABLED. THE CEH-1 MOTOR SHALL MODULATE TO MAINTAIN 900 CFM (ADJUSTABLE) EXHAUST RATE. WHEN CEH-2 IS DISABLED
BY THE SWITCH ON THE FUME HOOD THE ASSOCIATED DAMPER SHALL CLOSE AND EF-2 SHALL BE ENABLED. IF THE CEF-2 DAMPER DOES NOT PROVE OPEN OR IF THE AIR
FLOW FROM CEH-2 FALLS BELOW 90% OF THE SET RATE AN ALARM LIGHT SHALL BE ACTIVATED AT THE FUME HOOD AND CEH-2 SHALL BE DISABLED AND EF-2 SHALL BE
ENABLED.
CEF--2
DI
2
David Mason & Associates
Structural Engineers
MO Cert. of Auth. #
800 S. Vandeventer Ave.
St. Louis, MO 63110
314-534-1030 phone
314-534-1053 fax
DO
3
AI
3
VFD
Custom Engineering
MEP Engineers
MO Cert. of Auth. # 000239
100 N. Broadway, #1875
St. Louis, MO 63102
314-802-0920 phone
314-802-0921 fax
DI
6
1
MAD-O
MAD-O
AFM-I
AI
7
AO
7
DO
1
DO
2
AI
2
VFD
VFD
DI
2
DI
1
MAD-O
MAD-O
MAD-O
MAD-O
AI
5
AFM-I
FUME HOOD
AI
6
AFM-I
EF-2
AO
5
AO
4
AI
4
MAD-O
MAD-O
AO
6
FUME HOOD
Project No:
HARDWARE
INPUTS
FUME HOOD FAN SPEED
FUME HOOD FAN STATUS
DISCHARGE AIR DAMPER
DISCHARGE AIR DAMPER END SWITCH
AIR FLOW MONITOR
ON/OFF
AO-1,
AO-2,
AO-3
W/VFD
% SPEED
DI-1,
DI-2,
DI-3
RELAY
ON/OFF
RELAY
OPEN /
CLOSE
CONTACTOR
OPEN /
CLOSE
AO-4, AO-5,
AO-6, AO-7
AI-1, AI-2,
AI-3, AI-4
AI-5, AI-6, AI-7 CFM
CFM
X
X
X
VAV CONTROL
COND WATER RESET
CHLR DEM LIMIT
CHILLED WATER RESET
CHILLER OPTIMIZATION
OA LOCKOUT
HW OA RESET
BOILER OPTIMIZATION
TEMPERATURE
CONTROL
DEMAND VENTILATION
D/N SETBACK
ECONOMIZER
BUILDING STATIC
PRESSURE
DEMAND LIMIT
OPTIMUM START/STOP
START/STOP
SCHEDULED
RUNTIME
FLOW SENSOR
PSI PSG PSD
POSITION
TEMPERATURE
RELATIVE HUMIDITY
CO2 LEVEL
AUX CONTACT
CURRENT SWITCH
SWITCH CLOSURE
FLOW SWITCH
0-10V OR 4-20 MA
OUTPUT
PRESSURE SWITCH
PNEUMATIC TO
ELEC. TR.
EPT
CONTACTOR
UNITS
RELAY
SOLENOID
DEVICE
DO-1, DO-2,
DO-3
RELAY
FUME AND EXHAUST FANS
ANALOG
LOW LIMIT
DIGITAL
MAINTENANCE
ANALOG
HIGH LIMIT
DIGITAL
EQUIPMENT STATUS
ANALOG
OWNER: ST. LOUIS COUNTY
TAG
Date
4/12/2013
EMS FUNCTIONS
DIGITAL
POINT DESCRIPTION
QA/QC
ALARMS
BUILDING NAME: MET CENTER
FUME HOOD FAN
1
SOFTWARE
OUTPUTS
12024
Revisions
Description
INPUT/OUTPUT SUMMARY TABLE
LOCATION: FIFTH FLOOR
STL Co. Economic Council
121 S. Meramec Ave. #900
St. Louis, MO 63105
AI
1
DI
2
EF-1
MET Center Renovation:
Fourth & Fifth Floor
CEF-1
DI
1
X
X
X
X
X
X
X
X
DATE:
3/13/2013
PERMIT DRAWINGS
Exhaust
Control
M6.2
222 SOUTH CENTRAL AVE.
SUITE# 100
ST. LOUIS, MO 63105
TEL: 314.863.4994
FAX: 314.863.4996
www.bondwolfe.com
VARIABLE AIR VOLUME BOXES
DISCHARGE AIR TEMP SENSOR: A DISCHARGE AIR TEMP SENSOR SHALL BE PROVIDED ON EACH BOX FOR MONITORING PURPOSES.
DPR-O
DA-T
OCCUPIED MODE: WHEN THE ZONE TEMPERATURE IS BETWEEN THE OCCUPIED HEATING AND COOLING SETPOINTS (INSIDE THE BIAS), THE PRIMARY AIR DAMPER SHALL
BE AT THE MINIMUM CFM, THE REHEAT COIL SHALL BE DE-ENERGIZED. ON A RISE IN ZONE TEMPERATURE ABOVE THE COOLING SETPOINT, THE PRIMARY AIR DAMPER
SHALL INCREASE THE CFM AND THE REHEAT COIL REMAINS DE-ENERGIZED. ON A DROP IN ZONE TEMPERATURE BELOW THE HEATING SETPOINT, THE REHEAT COIL IS
ENERGIZED IN STEPS TO MEET THE HEATING DEMAND AND THE DAMPER IS CONTROLLED TO PROVIDE A MINIMUM CFM.
E
DISCHARGE AIR FROM
AIR HANDLING UNIT
David Mason & Associates
Structural Engineers
MO Cert. of Auth. #
800 S. Vandeventer Ave.
St. Louis, MO 63110
314-534-1030 phone
314-534-1053 fax
H
UNOCCUPIED (NIGHT SETBACK) MODE: ALL VAV BOXES SHALL BE AT MINIMUM POSITION. THE REHEAT VALVE SHALL BE CLOSED WHEN THE ZONE TEMPERATURE IS
BETWEEN THE UNOCCUPIED HEATING AND COOLING SET POINTS. ON A RISE IN ZONE TEMPERATURE ABOVE THE UNOCCUPIED COOLING SETPOINT, THE PRIMARY AIR
DAMPER SHALL INCREASE THE CFM (IF AVAILABLE) AND THE REHEAT COIL SHALL REMAIN DE-ENERGIZED. ON A DROP IN ZONE TEMPERATURE BELOW THE UNOCCUPIED
HEATING SETPOINT, THE REHEAT COIL SHALL BE ENERGIZED IN STEPS TO MEET THE HEATING DEMAND AND THE DAMPER REMAINS AT MINIMUM POSITION.
Custom Engineering
MEP Engineers
MO Cert. of Auth. # 000239
100 N. Broadway, #1875
St. Louis, MO 63102
314-802-0920 phone
314-802-0921 fax
INPUT/OUTPUT SUMMARY TABLE
LOCATION: FIFTH FLOOR
HARDWARE
SOFTWARE
OUTPUTS
INPUTS
ALARMS
EMS FUNCTIONS
BUILDING NAME: MET CENTER
DIGITAL
ANALOG
DIGITAL
ANALOG
DIGITAL
ANALOG
OWNER: ST. LOUIS COUNTY
VAV BOX
UNITS
ZONE TEMPERATURE SENSOR
AI-19
PROGRAMABLE
THERMOSTAT
X
DISCHARGE AIR TEMPERATURE SENSOR
AI-20
AVERAGING
X
ELECTRIC HEATING COIL
AO-10
SWITCH
ON/OFF
X
X
X
X
GAS FIRED UNIT HEATERS
GAS FIRED UNIT HEATERS WILL NOT BE CONNECTED TO BAS.
GAS FIRED UNIT HEATERS SHALL BE CONNECTED TO A HEAT ONLY THERMOSTAT LOCATED ON NEAREST INTERIOR COLUMN 60" AFF. UPON A DROP IN TEMPERATURE
Project No:
STL Co. Economic Council
121 S. Meramec Ave. #900
St. Louis, MO 63105
DEVICE
MET Center Renovation:
Fourth & Fifth Floor
TAG
POINT DESCRIPTION
12024
Revisions
Description
1
QA/QC
Date
4/12/2013
PARALLEL FAN POWERED UNITS: :
UNIT SHALL BE CONNECTED TO EXISTING CONTROL SYSTEM ON FOURTH FLOOR. CONTRACTOR SHALL VERIFY EXISTING CONTROLS AND SUPPLY UNIT COMPATIBLE WITH
EXISTING CONTROLS.
EACH AIR TERMINAL UNIT SHALL BE EQUIPPED WITH AND ADJUSTABLE DDC ZONE CONTROLLER. THE DDC CONTROLLER IS A MICROPROCESSOR THAT PROVIDES
ACCURATE, PRESSURE INDEPENDENT CONTROL THROUGH THE USE OF A PROPORTIONAL INTEGRAL DIGITAL CONTROL MODULE. THE CONTROLLER IS A
MICROPROCESSOR THE CONTROL MODULE MONITORS ZONE TEMPERATURE SETPOINTS, ZONE TEMPERATURE AND ITS RATE OF CHANGE AND AIR FLOW USING
DIFFERENTIAL PRESSURE SIGNAL FROM THE PRESSURE TRANSDUCER. THE CONTROL MODULE SENSES THE ZONE TEMPERATURE THROUGH A SENSING ELEMENT
LOCATED IN THE ZONE SENSOR. THE ZONE SENSOR UTILIZES A THERMISTOR TO VARY THE VOLTAGE OUTPUT IN RESPONSE TO THE CHANGES IN THE ZONE
TEMPERATURE. THE CONTROL MODULE VARIES THE PRIMARY AIR FROM THE ROOFTOP UNIT AS REQUIRED TO MEET ZONE COOLING SETPOINT. THE UNIT AIRFLOW IS
LIMITED BY THE MINIMUM AND MAXIMUM POSITION SETPOINTS. THE CONTROLLER SHALL INTERMITTENTLY START THE FAN UPON A CALL FOR HEAT. UPON A CALL FOR
FURTHER HEAT, THE ELECTRIC HEAT ASSOCIATED WITH THE UNIT SHALL BE ENABLED. A 2 DEG. BEAD BAND IS APPLICABLE TO PREVENT CYCLING.
DI
7
DO
4
PLENUM AIR
E
PRIMARY AIR
FROM RTU-1
FP1-3
H
SA TO SPACE
1
AFM
AI
5
MAD
AO
7
DATE:
3/13/2013
PERMIT DRAWINGS
VAV Box &
FPB Controls
DI
8
M6.3
1
EXISTING HOSE BIB ON ROOF
UH-2
S
5R-30
3
S
RTU-1
D
3#1, 1#6G, 1.5"C
S
D
7
5P-25,27,29
3/4" GAS PIPE
3" VTR
EXISTING HOSE BIB
TO REMAIN
1 1/4" GAS PIPE
1
MET Center Renovation: Fourth & Fifth
Floor
6347 Plymouth Ave. St. Louis, MO 63133
222 South Central Ave Suite# 100 St. Louis, MO 63105
TEL: 314.863.4994 FAX: 314.863.4996
12024
Date:
4/12/2013
Scale:
Reference Sheet: ME 1.4-1
EXISTING 1/2" CW PIPE UP
TO HOSE BIB ON ROOF
INSTALL DRAIN VALVE PIPE
WITH 3/4" COPPER PIPE TO
FLOOR DRAIN IN
MECHANICAL ROOM
REMOVE EXISTING 1/2" CW
PIPE AND VALVES
INSTALL 3/4" CW PIPE AND
BALL VALVE CONNECT TO
EXISTING CW PIPE
1
EXTEND 2-1/2" CW, 1-1/2"
CW, 1" CW AND 4"
SANITARY DRAIN UP TO 18"
ABOVE FINISHED FLOOR
OF 6TH FLOOR. CAP AT
TOP OF PIPE.
CUT & REMOVE 4" PVC
PIPE TO BELOW DRAIN
PIPE CONNECTION POINT
FIFTH FLOOR
MECHANICAL ROOM
WATER PIPE & HOSE BIB IN MECHANICAL ROOM
SCALE: NTS
1
REPIPE EXISTING PIPING & VALVES TO EXISTING HOSE BIB ON ROOF
MET Center Renovation: Fourth & Fifth
Floor
6347 Plymouth Ave. St. Louis, MO 63133
222 South Central Ave Suite# 100 St. Louis, MO 63105
TEL: 314.863.4994 FAX: 314.863.4996
12024
Date:
4/12/2013
Scale:
Reference Sheet:
P1.1-1
1
St. LOUIS COUNTY REVIEW COMMENTS
FD-1
FH1
LS-2
LAB STORAGE
LS-1
FH-1
GW-1
CW-1
BREAK AREA
1
WB-1
FD-1
516
FD-1
PREP. LAB
512
KS-1
CO-1
ES-1
MET Center Renovation: Fourth & Fifth
Floor
6347 Plymouth Ave. St. Louis, MO 63133
222 South Central Ave Suite# 100 St. Louis, MO 63105
TEL: 314.863.4994 FAX: 314.863.4996
12024
Date:
4/12/2013
Scale:
Reference Sheet: P1.2 - 1
1
FS - 1
St. LOUIS COUNTY REVIEW COMMENTS
FLOOR SINK - WATTS FS-740 12" SQUARE BY 8" DEEP,
WHITE PORCELAIN ENAMEL COATED INTERIOR, LOOSE
SET PORCELAIN ENAMEL COATED CAST IRON GRATE
1
MET Center Renovation: Fourth & Fifth
Floor
6347 Plymouth Ave. St. Louis, MO 63133
222 South Central Ave Suite# 100 St. Louis, MO 63105
TEL: 314.863.4994 FAX: 314.863.4996
12024
Date:
4/12/2013
Scale:
Reference Sheet: P2.1 - 1
GENERAL NOTES
1.
222 SOUTH CENTRAL AVE.
SUITE# 100
ST. LOUIS, MO 63105
TEL: 314.863.4994
FAX: 314.863.4996
www.bondwolfe.com
REFER TO SHEET E1.5 ONE-LINE DIAGRAM FOR FEEDER REQUIREMENTS FOR
TRANSFORMER AND PANELBOARDS.
PLAN NOTES
JUNCTION BOX OR WIREWAY SIZED AS REQUIRED.
ROUTE CONDUIT DOWN SIDE OF BUILDING TO ADJACENT ROOF.
3.5" CONDUIT ABOVE CEILING FROM JUNCTION BOX TO PANEL 5P. ROUTE CONDUIT
BELOW CEILING JOISTS AND ABOVE GRID CEILING.
REFER TO ONE-LINE DIAGRAM SHEET 1.5 FOR FEEDER SIZE. REFER TO TABLE 3.2 CODE
BLOCK, SHEET E0.0. CONTRACTOR SHALL HIRE A LICENSED STRUCTURAL ENGINEER
TO DESIGN AND SEAL PLANS & SPECS TO MEET SEISMIC REQUIREMENTS FOR CONDUIT
INSTALLATION & MOUNTING FROM MAIN DISTRIBUTION BOARD S/E TO PANEL 5P ON 5TH
FLOOR.
PROVIDE BUILDING PENETRATION AS REQUIRED FOR CONDUIT.
0
1
2
3
4
5
6
David Mason & Associates
Structural Engineers
MO Cert. of Auth. #
800 S. Vandeventer Ave.
St. Louis, MO 63110
314-534-1030 phone
314-534-1053 fax
Custom Engineering
MEP Engineers
MO Cert. of Auth. # 000239
100 N. Broadway, #1875
St. Louis, MO 63102
314-802-0920 phone
314-802-0921 fax
7
KEEPING PAD 4-INCH HEIGHT, 2-INCH PAST BASE OF TRANSFORMER ALL SIDES.
EXTEND CONDUIT ALONG ROOF TO MAIN ELECTRICAL ROOM THEN PENETRATE DOWN
TO EXISTING ELECTRICAL SERVICE ENTRANCE DISTRIBUTION BOARD. REFER TO
SHEET E1.5 FOR DISTRIBUTION BOARD ELEVATION AND REQUIRED MODIFICATIONS.
G
NOT USED.
F
44" 44"
CLASSROOM
NOT USED.
44" 44"
44"
CLASSROOM
509
3
510
29
CEILING MOUNTED POWER CORD REEL WITH 120V, 20A RECEPTACLE. PROVIDE
REELCRAFT L 5550 123 3A HEAVY DUTY POWER CORD REEL OR APPROVED EQUAL.
PROVIDE RECEPTACLE 120V, AT CEILING FOR CONNECTION TO REEL.
LAB
511
WITH DRYER INSTALLER.
5
3
1
44"
MEDIA
CLASSROOM
PROVIDE 4"X4" JUNCTION BOX AT 7 FT AFF FOR FUTURE MOTION SENSOR. PROVIDE
PLENUM RATED CABLE 4#22 FROM JUNCTION BOX TO 1ST FLOOR CCTV ROOM LOCATED
ADJACENT TO BUILDING MAIN ENTRANCE.
7 9
29
27
44"
3
1
5RA
5RA
9
5
7
44"
2 #10, 1 #10 GROUND IN 3/4" CONDUIT.
507
44"
1
5R
16
18
D
GAS FIRE WATER HEATER, 120V.
CORRIDOR
29
508
5RA
27
GFI
16
MEN
DED CKT
LAB STORAGE
25
5R
GFI
JANITOR
503
515 5R 18 20
COATS
518
519
BREAK AREA DED CKT
13
11
7
9
12
5R
MECHANICAL
GFI
DED CKT
5RA
17
5RA
502
5R
11
23
1
C
DED CKT GFI, 44"
26
521
WOMEN
5R
517
14
5RA
6
8
10
5R
4
DED CKT
11
520
504
10
5R
2
WEST STAIR
W5
DED CKT
DED CKT
OPEN OFFICE
501
21
14
8
4
2
5RA
44"
Project No:
CLOSET
513
OFFICE
523
1
CHEM
STORAGE
12024
Revisions
Description
Revised Circuits
Date
4-12-13
514
OFFICE
524
EAST STAIR
E5
17
B
26
14
5RA 6 8
CORRIDOR
500
5R
13
15
17
5R
19
21
14
12
24
5R 22
24
PREP. LAB
512
522
DED CKT
LOBBY/
RECEPTION
DED CKT
506
5R
4
6
DED CKT
4
26
10
5RA 12
CORRIDOR
STORAGE
GFI
516
DED CKT
505
16
CORRIDOR
GFI
ELEC/ DATA
WORK AREA
9
4
GFI, 44"
GFI
GFI
CONFERENCE
44"
44"
14
16
FIRE ALARM WATER FLOW SWITCH. PROVIDE CONNECTION TO FIRE ALARM SYSTEM AS
REQUIRED.
GFI GFI,
44" 44"
525
3
DDC UNIT FOR HVAC CONTROL, 120V.
44"
5
STL Co. Economic Council
121 S. Meramec Ave. #900
St. Louis, MO 63105
9
5
E
PROVIDE 4"X4" JUNCTION BOX ABOVE GRID CEILING AT STRUCTURE FOR FUTURE
CAMERA. PROVIDE SIAMESE PLENUM RATED CABLE WITH ONE RG-59 AND ONE 2#18
FROM JUNCTION BOX TO 1ST FLOOR CCTV ROOM LOCATED ADJACENT TO BUILDING
MAIN ENTRANCE.
MET Center Renovation:
Fourth & Fifth Floor
5
6
15
17
A
Craig Brewster
MO E-2000150002
PERMIT DRAWINGS
DATE:
N
1
5TH FLOOR POWER PLAN
SCALE: 1/8" = 1'-0"
3/13/2013
5TH FLOOR
Electrical
Power Plan
E1.0
222 SOUTH CENTRAL AVE.
SUITE# 100
ST. LOUIS, MO 63105
TEL: 314.863.4994
FAX: 314.863.4996
www.bondwolfe.com
LIGHTING NARRATIVE & FOOT-CANDLE LEVELS
1.
LIGHT FIXTURES WILL BE ON/OFF CONTROLLED BY A COMBINATION OF TOGGLE
SWITCHES AND OCCUPANCY SENSORS.
2. FOOT-CANDLE LEVELS BASED ON RECOMMENDATIONS BY ILLUMINATING ENGINEERING
SOCIETY (IES):
0
1
2
3
4
5
6
LAB AREAS: 50 FOOT-CANDLES.
PREP LAB AREAS: 50 FOOT-CANDLES.
CLASSROOMS: 50 FOOT-CANDLES.
OFFICES: 50 FOOT-CANDLES.
CONFERENCE ROOMS: 30 FOOT-CANDLES.
LOBBY & RECEPTION AREAS: 10 FOOT-CANDLES.
BREAK AREAS: 30 FOOT-CANDLES
STORAGE ROOMS: 10 FOOT-CANDLES
CORRIDORS: 5 FOOT-CANDLES
MECH/ELEC ROOMS: 30 FOOT-CANDLES
RESTROOMS: 5 FOOT-CANDLES
CLOSETS: 10 FOOT-CANDLES
JANITORS CLOSET: 10 FOOT-CANDLES
WORK AREAS: 30 FOOT-CANDLES
LOCKERS: 10 FOOT-CANDLES
7
David Mason & Associates
Structural Engineers
MO Cert. of Auth. #
800 S. Vandeventer Ave.
St. Louis, MO 63110
314-534-1030 phone
314-534-1053 fax
Custom Engineering
MEP Engineers
MO Cert. of Auth. # 000239
100 N. Broadway, #1875
St. Louis, MO 63102
314-802-0920 phone
314-802-0921 fax
G
PLAN NOTES
F
1
A
CLASSROOM
509
AE
A
A
AE
AE
510
AE
1
A
AE
A
AE LAB
A
LOCATE SWITCHPACK FOR OCCUPANCY SENSOR ABOVE CEILING.
AE
511
EX508
1
A
S
2
AE
AE
AE
1
30 CD
H
AE
H
AE
A
CONFERENCE
S 2
A
505
WOMEN
AE
502
C
H
A
A
MECHANICAL
30 CD
BE
B
H
30 CD
A
500
2
30 CD
30 CD
CORRIDOR
AE
EX
2
A
A
523
A
OFFICE
A
A
3
30 CD
1
2
EX
A
524
AE
A
A
Project No:
3
A
CLOSET
513
A
1
12024
Revisions
Description
Revised Circuits
Date
4-12-13
CHEM
STORAGE
514
F
EAST STAIR
AE
B
A
AE
3
WEST STAIR
W5
S
OFFICE
3
501
A
512
AE
A
H
A
S
OPEN OFFICE
AE
2
A
A
S
SPREP.ALAB
AE
A
1
522
LOBBY/
2
RECEPTION
2
3
1
F
AE
2 S
CE
EX
506
34 CD
A
S
4
AE
516
2
521
30 CD
A
AE
30 CD
H
STORAGE
520
BREAK AREA
A
AE
A
A
3
22
5P
B
S
AE
A
A
AE
1
3
1
518
B
A
A
A
A
EX
503
2
A
515
COATS S
ELEC/ DATA
504
A
A
3
1
2 S
2 S
94 CD
H
A
A
2
A
A
30 CD WORK AREA
A
3
LAB STORAGE
519
AE
A
5P
S
H
A
AE
JANITOR
H
MEN
30 CD
AE
24
AE
30 CD
H
D
AE
H
CORRIDOR
30 CD
AE
26
5P
S 2
2
30 CD H
AE
AE
H
A
A
A
S 2
A
EX
A
A
AE
A
A
EX
EX
AE
A
A
A
AE
517
507
A
1
EX 3
3
2
3
A
A
A
2
2
CORRIDOR
MEDIA
CLASSROOM
A
1
A
H
A
60 CD
H
2
A
A
2
525
S
S
A
H
AE
A
A
CORRIDOR
60 CD
2
E
A
H
S 2
A
60 CD
A
A
H
A
SWITCH TO TURN OFF ROW OF LIGHTS NEAREST WALL DURING PROJECTOR USE.
STL Co. Economic Council
121 S. Meramec Ave. #900
St. Louis, MO 63105
CLASSROOM
AE
MET Center Renovation:
Fourth & Fifth Floor
AE
PROVIDE FCPS-24S6 POWER SUPPLY FOR FIRE PROTECTION SIGNALING SERVICE, 120V,
3.2A. PROVIDE CONNECTION TO 5TH FLOOR FIRE ALARM DEVICES AS REQUIRED.
PROVIDE CONNECTION TO AHU SHUTDOWN AS REQUIRED. PROVIDE CONNECTION TO
BUILDING FIRE ALARM SYSTEM AS REQUIRED.
EX
E5
A
Craig Brewster
MO E-2000150002
PERMIT DRAWINGS
N
1
5TH FLOOR LIGHTING PLAN
DATE:
3/13/2013
5th Floor
Lighting Plan
SCALE: 1/8" = 1'-0"
E1.1
222 SOUTH CENTRAL AVE.
SUITE# 100
ST. LOUIS, MO 63105
TEL: 314.863.4994
FAX: 314.863.4996
www.bondwolfe.com
LIGHTING NARRATIVE & FOOT-CANDLE LEVELS
1.
LIGHT FIXTURES WILL BE ON/OFF CONTROLLED BY OCCUPANCY SENSORS.
2. FOOT-CANDLE LEVELS BASED ON RECOMMENDATIONS BY ILLUMINATING ENGINEERING
SOCIETY (IES):
CLASSROOM: 50 FOOT-CANDLES.
OFFICES: 50 FOOT-CANDLES.
STORAGE ROOMS: 10 FOOT-CANDLES
CORRIDORS: 5 FOOT-CANDLES
MECH ROOM: 30 FOOT-CANDLES
5
6
David Mason & Associates
Structural Engineers
MO Cert. of Auth. #
800 S. Vandeventer Ave.
St. Louis, MO 63110
314-534-1030 phone
314-534-1053 fax
Custom Engineering
MEP Engineers
MO Cert. of Auth. # 000239
100 N. Broadway, #1875
St. Louis, MO 63102
314-802-0920 phone
314-802-0921 fax
PLAN NOTES
7
EXISTING FCPS-24S6 POWER SUPPLY FOR FIRE PROTECTION SIGNALING SERVICE, 120V,
3.2A. PROVIDE CONNECTION TO NEW 4TH FLOOR FIRE ALARM DEVICES AS REQUIRED.
WALL MOUNT LIGHT FIXTURES IN THIS ROOM.
LOCATE SWITCHPACK FOR OCCUPANCY SENSOR ABOVE CEILING.
SWITCH TO TURN OFF ROW OF LIGHTS NEAREST WALL DURING PROJECTOR USE.
G
1
2
AE
A
A
A
4
E
AE
3 S
1
EX
60 CD
3
S
AE
2
AE
OFFICE SPACE
A
A
402
4P
25
60 CD
H
S
AE
EX
D
S
A
27
A
A
A
1
CLASSROOM
2
AE
H
AE
A
4
A
A
3 S
403 AE
A
EX
A
AE
C
A
A
A
400
60 CD
H
AE
Project No:
3
AE
B
EX
MECH. AREA
BE
2
B
A
1
405
BE
12024
Revisions
Description
Revised Circuits
Date
4-12-13
4
B
BE
CORRIDOR
H
30 CD
401
A
A
4P
CLASSROOM
S H
AE
CORRIDOR
A
AE
STL Co. Economic Council
121 S. Meramec Ave. #900
St. Louis, MO 63105
A
AE
MET Center Renovation:
Fourth & Fifth Floor
F
STORAGE
S 406
1
30 CD
3
B
EX
404
AE
F
A
EAST STAIR
E4
Craig Brewster
MO E-2000150002
PERMIT DRAWINGS
DATE:
3/13/2013
Partial 4th Floor
Lighting Plan
N
1
PARTIAL 4TH FLOOR LIGHTING PLAN
SCALE: 1/8" = 1'-0"
E1.3
EXISTING PANELBOARD: 4P
LOCATION: 4TH FLOOR ELEC RM
NEMA 1 ENCLOSURE
277/480V, 3PH, 4W, GR
VOLTAGE:
AMPS: 400A
LOAD
BREAKER
CKT
NO
A
P
VA
*
60
1 FPB-1
14681
1
*
35
1 FPB-2
9141
3
*
60
1 FPB-3
13933
5
PHASE LOADS VA
A
CKT
C
B
NO
NEW PANELBOARD: 5P
LOCATION: 5TH FLOOR ELEC RM
NEMA 1 ENCLOSURE
MOUNTING: SURFACE
VOLTAGE:
MAINS: 400 AMP MAIN BREAKER
AMPS: 400A
LOAD
BREAKER
VA
A
P
A
P
15
3 EXHAUST FAN EF-1
15
*
20
*
20
1 LTG RM 401, 402
1 LTG RM 403, 404, 405, 406
1357
25
1180
27
2357
110
2180
70
3 EXHAUST FAN EF-2
3 FUME HOOD EXHAUST FAN CEF-1
3 FUME HOOD EXHAUST FAN CEF-2
3 ROOF TOP UNIT RTU-1
3 45 KVA TRANSFORMER FOR PANEL 5R
PHASE LOADS VA
NO
300
14933
15
CKT
VA
10141
15
MOUNTING: SURFACE
MAINS: 400 AMP MAIN BREAKER
LOAD
BREAKER
15681
480/277V, 3PH, 4W, GR
222 SOUTH CENTRAL AVE.
SUITE# 100
ST. LOUIS, MO 63105
TEL: 314.863.4994
FAX: 314.863.4996
www.bondwolfe.com
A
1
300
3
300
5
150
7
150
9
10150
6150
11
13
440
15
440
17
440
19
440
21
23
25
27434
27
27434
29
6150
2440
6440
4440
3440
2741
2623
29971
27434
27434
0
31
0
33
0
0
0
35
13570
37
10220
39
11170
41
0
13570
10220
11170
67871
57285
LOAD
NO
5300
440
440
C
B
8300
4300
150
27434
CKT
BREAKER
A
P
2
VA
8000 VAV-1
40
1
4
4000 VAV-2
20
1
6
5000 VAV-3
25
1
8
10000 VAV-4
50
1
10
6000 VAV-5
30
1
12
6000 VAV-6
30
1
14
2000 VAV-7
15
1
16
6000 VAV-8
30
1
18
4000 VAV-9
20
1
20
3000 VAV-10
20
1
22
20
1
24
2301 LTG RMS 511-516
2183 LTG RMS 500-504, 508, 518-525
20
1
26
2537 LTG RMS 505, 506, 507, 509, 510
20
1
28
0
30
0
32
0
34
0
36
0
38
0
40
0
42
0
David Mason & Associates
Structural Engineers
MO Cert. of Auth. #
800 S. Vandeventer Ave.
St. Louis, MO 63110
314-534-1030 phone
314-534-1053 fax
Custom Engineering
MEP Engineers
MO Cert. of Auth. # 000239
100 N. Broadway, #1875
St. Louis, MO 63102
314-802-0920 phone
314-802-0921 fax
57117 VA CONNECTED LOAD
* PROVIDE NEW CIRCUIT BREAKER. NEW CIRCUIT BREAKER TO MATCH EXISTING
BREAKER MANUFACTURE AND AIC RATING.
TOTAL DEMAND LOAD
117.55 KVA
** EXISTING 20 AMP CIRCUIT BREAKER TO BE USED FOR NEW CIRCUIT.
TOTAL DEMAND LOAD
141.39 AMPS
I.C. 22000 RMS. SYM. AMPS
MOUNTING: SURFACE
AMPS: 125A
208/120V, 3PH, 4W, GR
VOLTAGE:
MAINS: 100 AMP MAIN BREAKER
MOUNTING: SURFACE
AMPS: 125A
BREAKER
A
LOAD
P
CKT
VA
NO
PHASE LOADS VA
A
CKT
C
B
NO
740
740
**
20
720
20
1 OFFICE 402 & CLASS. 403 RECEPTACLES
1 CLASSROOM 401, OFFICE 402 REC.
**
*
19
720
21
20
1 CLASSROOM 401, OFFICE 402 REC.
720
23
MET Center Renovation:
Fourth & Fifth Floor
208/120V, 3PH, 4W, GR
VOLTAGE:
NEW PANELBOARD: 5R
LOCATION: 5TH FLOOR ELEC RM
NEMA 1 ENCLOSURE
LOAD
VA
MAINS: 125 AMP MAIN BREAKER
BREAKER
A
LOAD
BREAKER
P
CKT
PHASE LOADS VA
NO
A
P
20
1 MEDIA CLASSROOM 507 RECEPTACLES
VA
720
1
A
20
1 MEDIA CLASSROOM 507 RECEPTACLES
720
3
20
1 MEDIA CLASSROOM 507 RECEPTACLES
720
5
20
1 WORK AREA 504 DED. CIRCUIT
800
7
20
1 WORK AREA 504 DED. CIRCUIT
800
9
1600
1600
20
1 CONFERENCE 505 RECEPTACLES
540
11
20
1 **
20
1 LOBBY/RECEPTION 500 DED. CIRCUIT
800
13
18
540 CLASSROOM 403 & MECH. 405 REC.
20
1 **
20
1 LOBBY/RECEPTION 500 DED. CIRCUIT
800
15
20
1 LOBBY/RECEPTION 500 & STORAGE 506
540
17
20
1 OPEN OFFICE 501 DED. CIRCUIT
800
19
20
800
21
20
1 OPEN OFFICE 501 DED. CIRCUIT
1 MEN 503, WOMEN 502, JANITOR 513
900
23
20
1 CLASSROOM 510 RECEPTACLES
720
25
20
1 CLASSRM. 509 & CLASSRM. 510 REC.
720
27
20
1 CLASSRM. 509 & MEDIA CLASSRM. 509
720
29
20
1 SPARE
0
31
20
1 SPARE
0
33
720
* PROVIDE NEW CIRCUIT BREAKER. NEW CIRCUIT BREAKER TO MATCH EXISTING
BREAKER MANUFACTURE AND AIC RATING.
20
** EXISTING 20 AMP CIRCUIT BREAKER TO BE USED FOR NEW CIRCUIT.
100
1 SPARE
3 PANEL 5RA
1260
1700
1340
3050
1600
1700
1520
1320
1320
0
0
0
35
37
0
2920
39
2660
41
4260
2920
2660
13570
10220
1
VA
BREAKER
A
P
2
720 MECH. 521 & CORR. 522 RECEPTACLE
20
1
4
720 OFFICE 523 RECEPTACLES
20
1
6
720 OFFICE 524 RECEPTACLES
20
1
8
800 BREAK AREA 516 DED. CIRCUIT
20
1
10
800 BREAK AREA 516 DED. CIRCUIT
20
1
12
720 LAB 511 RECEPTACLE
20
1
14
900 LAB STORAGE 515 WASHER REC.
20
1
540 BREAK AREA 516 REC.
20
1
30
2
16
2790
4260
LOAD
NO
1440
540 CLASSROOM 403 & CORR. 406 REC.
1120
C
B
1440
1440
16
720
CKT
18
2250 LAB STORAGE 515 DRYER REC.
20
2250
22
800 BREAK AREA 516 DED. CIRCUIT
20
1
24
800 BREAK AREA 516 DED. CIRCUIT
20
1
26
800 BREAK AREA 516 DED. CIRCUIT
20
1
28
600 UNIT HEATER UH-1 AT 6TH FLOOR
15
1
30
600 UNIT HEATER UH-2 AT 6TH FLOOR
15
1
20
1
32
0 SPARE
34
0 SPACE ONLY
36
0 SPACE ONLY
38
0 SPACE ONLY
40
0 SPACE ONLY
42
0 SPACE ONLY
1
STL Co. Economic Council
121 S. Meramec Ave. #900
St. Louis, MO 63105
EXISTING PANELBOARD: 4R
LOCATION: 4TH FLOOR ELEC RM
NEMA 1 ENCLOSURE
11170 VA CONNECTED LOAD
Project No:
TOTAL DEMAND LOAD
23.08 KVA
TOTAL DEMAND LOAD
64.06 AMPS
1
12024
Revisions
Description
Revised Circuits
Date
4-12-13
I.C. 22000 RMS. SYM. AMPS
NEW PANELBOARD: 5RA
LOCATION: 5TH FLOOR ELEC RM
NEMA 1 ENCLOSURE
208/120V, 3PH, 4W, GR
VOLTAGE:
MOUNTING: SURFACE
AMPS: 125A
BREAKER
1
MAINS: 100 AMP MAIN LUGS ONLY
LOAD
CKT
A
P
20
1 LAB 511 RECEPTACLES
VA
720
NO
1
20
1 LAB 511 RECEPTACLES
720
3
20
1 LAB 511 CEILING MOUNTED RECEPTACLES
720
5
20
1 LAB 511 CEILING MOUNTED RECEPTACLES
720
7
20
1 LAB 511 CEILING MOUNTED RECEPTACLES
540
9
20
1 GAS FIRED WATER HEATER
600
11
20
1 DDC PANEL FOR HVAC CONTROL
500
13
20
1 CONTROL POWER TO ROOF EXH FANS
500
15
20
1 ELEC 1 DATA RM RECEPTALCES
600
17
SPACE ONLY
0
19
SPACE ONLY
0
21
SPACE ONLY
0
23
SPACE ONLY
0
25
SPACE ONLY
0
27
SPACE ONLY
0
29
PHASE LOADS VA
A
B
CKT
C
NO
1440
1080
1260
1520
1340
1400
1300
900
1400
0
0
0
0
0
0
4260
3320
LOAD
VA
BREAKER
A
P
2
720 PREP LAB 512 RECEPTACLES
20
1
4
360 PREP LAB 512 RECEPTACLES
20
1
6
540 CLOSET 513 & STORAGE 514 REC.
20
1
8
800 PREP LAB 512 DED. RECEPTACLE
20
1
10
800 PREP LAB 512 DED. RECEPTACLE
20
1
12
800 PREP LAB 512 DED. RECEPTACLE
20
1
14
800 PREP LAB 512 DED. RECEPTACLE
20
1
16
400 MEDIA CLASSROOM 507 RECEPT
20
1
18
800 MEDIA CLASSROOM 507 RECEPT
20
1
20
0 SPACE ONLY
22
0 SPACE ONLY
24
0 SPACE ONLY
26
0 SPACE ONLY
28
0 SPACE ONLY
30
0 SPACE ONLY
4060 VA CONNECTED LOAD
TOTAL DEMAND LOAD
11.77 KVA
TOTAL DEMAND LOAD
32.67 AMPS
I.C. 22,000 RMS. SYM. AMPS
1
Craig Brewster
MO E-2000150002
PERMIT DRAWINGS
DATE:
3/13/2013
Electrical
Schedules
E1.6