222 South Central Ave. Suite 100 St. Louis, MO 63105 314.863.4994 www.bondarchitectsinc.com Addendum 1 TO: COMPANY: - Edgar Velazquez - Duane Emanuel - Pre-bid meeting attendees - Bev FROM: FAX NO/EMAIL: - STLCo. Economic Council - STLCo. Public Works - County Blue Reprographics ADDENDUM ISSUE DATE: Holly Rudd April 12, 2013 PROJECT: evelazquez@slcec.com repro@countyblue.com ADDENDUM NUMBER: 1 PROJECT NO: MET Center: 4th & 5th Floor 12024 TO ALL BIDDERS: THIS ADDENDUM FORMS A PART OF THE CONTRACT DOCUMENTS AND MODIFIES THE ORIGINAL DOCUMENTS DATED 3-13-13. PLEASE ACKNOWLEDGE RECEIPT OF THIS ADDENDUM ON THE BID FORM. CHANGES TO THE PROJECT MANUAL Table of Contents 1. 2. Add in Table of Contents, "Technical Specifications for Asbestos Abatement" Section exists at the end of Division 00. Front End Spec Section - RFP & Instructions to Bidders 1. PLEASE NOTE: Contractors who received project manuals from County Blue Reprographics have already received this change. This corrected document was swapped out prior to Advertisement for Bid. 2. Modifies schedule dates. Front End Spec Section - Form of Price Proposal 1. PLEASE NOTE: Contractors who received project manuals from County Blue Reprographics have already received this change. This corrected document was swapped out prior to Advertisement for Bid. 2. Section 4.1 (Alternates): Fill in the amount bid for the Alternate in the column entitled "Price" in the appropriate space opposite the "Alternate" column and indicate the price is an increase to the Base Bid Price by using the symbol "+." Front End Spec Section - Advertisement for Bids 1. PLEASE NOTE: Contractors who received project manuals from County Blue Reprographics have already received this change. This corrected document was swapped out prior to Advertisement for Bid. 2. Modifies schedule date of pre-bid meeting. 011000 - Summary Page 1 of 4 1. 2. Section 1.4.B to read, "General Contractor shall award a contract(s) for the following construction operations at Project Site. Those operations to be scheduled by General Contractor, in a timely manner, concurrent with other work. a. Add section 1.4.B.2 - "Building to remain sealed and dry during non-construction hours." b. Add section 1.4.B.3 - "Hazardous debris to be removed by abatement contractor." Add section 1.5.D - "Maintain access to fifth floor roof door, to be accessed by building staff as needed for maintenance." 012500 - Substitution Procedures 1. PLEASE NOTE: Contractors who received project manuals from County Blue Reprographics have already received this change. This corrected document was swapped out prior to Advertisement for Bid. 2. Section 2.1.A to read, "See exhibit C-EDA required contracting provisions for construction projects, Section 10 "Or Equal" clause." 3. Eliminate section 2.1.B 016000 - Product Requirements 1. PLEASE NOTE: Contractors who received project manuals from County Blue Reprographics have already received this change. This corrected document was swapped out prior to Advertisement for Bid. 2. Section 2.2.A to read, "Conditions for Consideration: See exhibit C-EDA required contracting provisions for construction projects, Section 10 "Or Equal" clause." 3. Eliminate sections 2.2.A 1-5. 220517 - Sleeves and Sleeve Seals for Plumbing Piping 1. PLEASE NOTE: Contractors who received project manuals from County Blue Reprographics have already received this spec section. Document was added prior to Advertisement for Bid. 2. Per Table of Contents, Add spec section 220517. 230713 - Duct Insulation 1. DELETE: From Specifications section 230713 Duct Insulation, paragraph 3.9 Indoor Duct and Plenum Insulation Schedule. 2. ADD: To the specifications section 230713 Duct Insulation, Paragraph 3.9 Indoor Duct and Plenum Insulation Schedule: The following table. Duct Insulation Schedule Duct Description Duct location Insulation Thickness Density Supply - Rectangular Between Roof and VAV Lined, Mineral-Fiber board 1-1/2" 2-lb/c.f. Supply - Rectangular Between RTU and Roof Lined, Mineral-Fiber board 3" 2-lb/c.f. Supply - Round All solid Wrap, Mineral-Fiber Blanket 1-1/2" 1.5 lb/c.f. Supply - Round Flexible Return - Rectangular All See specifications All Lined, Mineral-Fiber board 1/2" min. 2-lb/c.f. Exhaust - All Prep lab, Class room, fume hoods Plenum space Wrap, Mineral-Fiber Blanket 1-1/2" 1.5 lb/c.f. 1/2" min. 2-lb/c.f. Transfer Ducts Lined, Mineral-Fiber board Bathroom exhaust does not need insulation Page 2 of 4 Bond Architects CHANGES TO THE DRAWINGS ARCHITECTURAL DRAWINGS A2.0 1. 2. 3. A8.0 1. A12.1 1. Floor Plans Room 520 - Elec/ Data - Relocate door to south wall. a. See attached sketch, "A2.0-1" Modify Keyed Note #209 to read, "Remove vent & patch masonry at existing opening (approx. 5" x 16"). See detail 12/A8.0" Modify Keyed Note #232 to read, " Provide floor leveling throughout areas of severe concrete damage (generally west of column-3). Provide skim coat over sealant at existing electrical penetrations, throughout" Floor Plans Add detail 12/A8.0 - Detail at exterior wall patch. a. See attached sketch, "A8.0-1" Door Schedule Doors 502 & 503 - Under-cut 3/4" MECHANICAL DRAWINGS M1.2 1. 5th Floor HVAC Plan See attached sketches, M1.2-1A, M1.2-1B and M1.2-1C M2.2 1. M3.1 1. 2. Mechanical Sections & Details ADD: To drawing sheet M2.2 – Detail Section A-A: Note 1: Contractor shall coordinate supply and return rises with structural member and install offsets as needed to avoid structural members. Mechanical Schedules ADD: To sheet M3.1 – Rooftop Unit Schedule: Note 8. Provide hail guard See attached sketches M3.1-1A, M3.1-1B and M3.1-1C M6.1 1. 2. RTU Control ADD: To sheet M6.1 – RTU-1 shall report filter status to BAS system Clarify portion of control sequences, See attached re-issued sheet M6.1. M6.2 1. M6.3 1. 2. 3. 4. 5. Exhaust Control Clarify portion of control sequences, See attached re-issued sheet M6.2. VAV Box & FPB Controls DELETE: From sheet M6.3 from input/output summary table, Location: Kirksville, Missouri ADD: To sheet M6.3 from input/output summary table, Location: Fifth Floor DELETE: From sheet M6.3 from input/output summary table, Building Name-Army Reserve Center ADD: To sheet M6.3 from input/output summary table, Building Name- MET Center Remove airflow monitor from parallel fan power units, See attached re-issued sheet M6.3. Page 3 of 4 Bond Architects ME1.4 1. 2. 3. Mechanical & Electrical Roof Plan DELETE: From sheet ME1.4 Key Note 4, Unit heaters are hung from 6th floor joists. ADD: To sheet ME1.4 Key Note 4, "Unit heaters shall be hung from roof joist in 6th floor to supply heat to 6th floor." See attached sketch ME1.4-1. PLUMBING DRAWINGS P1.1 P1.2 P2.1 1. See attached sketch P1.1-1 1. See attached sketch P1.2-1 1. See attached sketch P2.1-1 Plumbing Supply Plan Plumbing Drainage Plan Plumbing Riser Plan ELECTRICAL DRAWINGS E1.0 E1.1 1. See attached, re-issued sheet 1. See attached, re-issued sheet 1. See attached, re-issued sheet 1. See attached, re-issued sheet 5th Floor Electrical Power Plan 5th Floor Lighting Plan E1.3 E1.6 Partial 4th Floor Lighting Plan Electrical Schedules LIST OF ATTACHMENTS Spec section 220517 A2.0-1 A8.0-1 M1.2-1A M1.2-1B M1.2-1C M3.1-1A M3.1-1B M3.1-1C M6.1 M6.2 M6.3 ME1.4-1 P1.1-1 P1.2-1 P2.1-1 E1.0 E1.1 E1.3 E1.6 END OF ADDENDUM NO. 1 Page 4 of 4 Bond Architects MET Center Renovation: 4th & 5th Floor 02/11 SECTION 220517 - SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. 1.2 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. SUMMARY A. Section Includes: 1. 2. 3. 4. 5. 1.3 Sleeves. Stack-sleeve fittings. Sleeve-seal systems. Sleeve-seal fittings. Grout. ACTION SUBMITTALS A. Product Data: For each type of product indicated. PART 2 - PRODUCTS 2.1 SLEEVES A. Cast-Iron Wall Pipes: Cast or fabricated of cast or ductile iron and equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop unless otherwise indicated. B. Galvanized-Steel Wall Pipes: ASTM A 53/A 53M, Schedule 40, with plain ends and welded steel collar; zinc coated. C. Galvanized-Steel-Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, zinc coated, with plain ends. D. PVC-Pipe Sleeves: ASTM D 1785, Schedule 40. E. Galvanized-Steel-Sheet Sleeves: 0.0239-inch minimum thickness; round tube closed with welded longitudinal joint. F. Molded-PE or -PP Sleeves: Removable, tapered-cup shaped, and smooth outer surface with nailing flange for attaching to wooden forms. G. Molded-PVC Sleeves: With nailing flange for attaching to wooden forms. SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING 220517 - 1 MET Center Renovation: 4th & 5th Floor 2.2 02/11 SLEEVE-SEAL SYSTEMS A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. 2. 3. 4. 5. B. Description: Modular sealing-element unit, designed for field assembly, for filling annular space between piping and sleeve. 1. 2. 3. 2.3 Advance Products & Systems, Inc. CALPICO, Inc. Metraflex Company (The). Pipeline Seal and Insulator, Inc. Proco Products, Inc. Sealing Elements: EPDM-rubber interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe. Pressure Plates: Carbon steel. Connecting Bolts and Nuts: Carbon steel, with corrosion-resistant coating, of length required to secure pressure plates to sealing elements. SLEEVE-SEAL FITTINGS A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. B. 2.4 Presealed Systems. Description: Manufactured plastic, sleeve-type, waterstop assembly made for imbedding in concrete slab or wall. Unit has plastic or rubber waterstop collar with center opening to match piping OD. GROUT A. Standard: ASTM C 1107/C 1107M, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout. B. Characteristics: Nonshrink; recommended for interior and exterior applications. C. Design Mix: 5000-psi, 28-day compressive strength. D. Packaging: Premixed and factory packaged. PART 3 - EXECUTION 3.1 SLEEVE INSTALLATION A. Install sleeves for piping passing through penetrations in floors, partitions, roofs, and walls. SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING 220517 - 2 MET Center Renovation: 4th & 5th Floor B. 02/11 For sleeves that will have sleeve-seal system installed, select sleeves of size large enough to provide 1-inch annular clear space between piping and concrete slabs and walls. 1. Sleeves are not required for core-drilled holes. C. Install sleeves in concrete floors, concrete roof slabs, and concrete walls as new slabs and walls are constructed. D. Install sleeves for pipes passing through interior partitions. 1. 2. 3. E. 3.2 Cut sleeves to length for mounting flush with both surfaces. Install sleeves that are large enough to provide 1/4-inch annular clear space between sleeve and pipe or pipe insulation. Seal annular space between sleeve and piping or piping insulation; use joint sealants appropriate for size, depth, and location of joint. Comply with requirements for sealants specified in Section 079200 "Joint Sealants." Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials. Comply with requirements for firestopping specified in Section 078413 "Penetration Firestopping." SLEEVE-SEAL-SYSTEM INSTALLATION A. Install sleeve-seal systems in sleeves in exterior concrete walls and slabs-on-grade at service piping entries into building. B. Select type, size, and number of sealing elements required for piping material and size and for sleeve ID or hole size. Position piping in center of sleeve. Center piping in penetration, assemble sleeve-seal system components, and install in annular space between piping and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make a watertight seal. 3.3 SLEEVE-SEAL-FITTING INSTALLATION A. Install sleeve-seal fittings in new walls and slabs as they are constructed. B. Assemble fitting components of length to be flush with both surfaces of concrete slabs and walls. Position waterstop flange to be centered in concrete slab or wall. C. Secure nailing flanges to concrete forms. D. Using grout, seal the space around outside of sleeve-seal fittings. 3.4 SLEEVE AND SLEEVE-SEAL SCHEDULE A. Use sleeves and sleeve seals for the following piping-penetration applications: 1. Concrete Slabs above Grade: SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING 220517 - 3 MET Center Renovation: 4th & 5th Floor a. b. 2. 02/11 Piping Smaller Than NPS 6: Galvanized-steel-pipe sleeves. Piping NPS 6 and Larger: Galvanized-steel-pipe sleeves. Interior Partitions: a. b. Piping Smaller Than NPS 6: Galvanized-steel-pipe sleeves. Piping NPS 6 and Larger: Galvanized-steel-sheet sleeves. END OF SECTION 220517 SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING 220517 - 4 202 7' - 2" 511 1B COATS 205 502 9' - 6" 512 517 BREAK AREA 516 2' - 4 7/8" 4' - 10" A10.0 232 12' - 11" 3 4A 227 219 7' - 1" 4B 7' - 0" 221 4B 5B 232 524 5' - 0" 201 6' - 5 1/4" CLEAR 522 5' - 10" CORRIDOR 523 17' - 5" 1B OFFICE 524 11' - 7" 9' - 11 7/8" 11' - 7" 1B 1 2 OFFICE 501 1B 520 6' - 5 1/4" 521 523 17' - 9 3/8" OPEN OFFICE Add.1 515 211 3 1C 5B D 218 3 7' - 4 1/2" W 1B 15' - 8" 227 227 4B 5' - 10" EQ. 232 3 ALIGN 16' - 9" 521 224 4A 233 5' - 0" WOMEN CORRIDOR 14' - 5" 9' - 9 1/8" " 520 3 4A 201 515 1C ELEC/ DATA MECHANICAL LAB STORAGE 207 1B 3 2' - 1" 6347 Plymouth Ave. St. Louis, MO 63133 222 South Central Ave Suite# 100 St. Louis, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 A10 EQ. 227 EXISTING 3 7/8" E5 5 A8.0 MET Center Renovation: Fourth & Fifth Floor 2 525 519 206 1B 201 518 JANITOR 503 204 CORRIDOR MEN 1B 1' - 8" 2' - 0 1/2" 9' - 5" 519 1' - 8" A10.0 A6 7' - 4 1/4" 3 6' - 5 1/4" CLEAR 5' - 10" 1B 20' - 0" 7 10' - 0" 510 6' - 5 1/4" 2' - 6" 1B 224 2' - 0" 6' - 8" 19' - 10 5/8" 6' - 8 5/8" 6' - 0" 2' - 6" 1' - 6" 3/8" SIM. 3 SIM. 31 SIM. 12024 4-9-12 Date: Scale: Reference Sheet: A2.0 A2.0-1 4 EXISTING MASONRY WALL, VERIFY THICKNESS +/- 1' - 0" +/- 8" SEE PLAN V.I.F. FURRING PARTITION, SEE PLAN MASONRY PATCH, MATCH EXISTING EXTERIOR BRICK +/- 5" FINISH FLOOR OVER FLOOR LEVELING PATCH RECESSED FLOOR AREA. PROVIDE FLOOR LEVELING THROUGHOUT 5TH FL. EXISTING CONC. SLAB 12 A8.0 E DETAIL AT EXTERIOR WALL PATCH 1" = 1'-0" Add.1 D ADJACENT PARTITION, WHERE IT OCCURS ON PLAN EXISTING EXT. MASONRY WALL EXISTING EXTERIOR SILL NEW ALUM. SF WINDOW D MET Center Renovation: Fourth & Fifth Floor INTERIOR P.LAM WINDOW SILL (PL-4), TYP. ALL WEST WINDOWS PATCH RECESSED FLOOR AREA. PROVIDE 12024 FLOOR LEVELING Date: 4-9-12 THROUGHOUT 5TH FL. Scale: Reference Sheet: 1" 4 HOUR RATING 6347 Plymouth Ave. St. Louis, MO 63133 PAINTABLE SEALANT PROVIDED AT EXISTING 3-3/4" CLAY TILE/ BRICK COLUMN SURROUND, PER IBC 2009 TABLE P.LAMMO SILL 63105 222 South Central Ave Suite# 100 INTERIOR St. Louis, 720.1(1) PL-4 U.N.O. TEL: 314.863.4994 FAX: 314.863.4996 REMOVE LOOSE DEBRIS PL-3 IN LAB & PREP LAB AT DAMAGED PORTIONS A8.0 C A8.0-1 509 510 8x10 CLASSROOM 8x10 CLASSROOM G 125 125 G 100 12x10 14x12 1 S 12x12 1 N/A 40x22 RTU-1 G 100 1 N/A VAV-3 G 125 T G 125 36x20 22x12 32x12 12x26 P E 150 1 N/A 40x12 36x12 A M2.2 A M2.2 MEN 5 JANITOR 50 519 503 2 SMOKE DETECTOR SCALE: NTS 1 INSTALL SMOKE DETECTOR IN RETURN DUCT MET Center Renovation: Fourth & Fifth Floor 6347 Plymouth Ave. St. Louis, MO 63133 222 South Central Ave Suite# 100 St. Louis, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 12024 Date: 4/12/2013 M1.2-1A Scale: Reference Sheet: 6 7 E 150 4 842 EF-1 E 150 8x10 20X12 12x12 8x10 EF-2 E 150 CEF-1 CEF-2 8x10 12x12 E 150 M M E 150 CC M2.2 M M 1 BB M2.2 E 150 E 150 MOTORIZED DAMPER SCALE: NTS 1 INSTALL MOTORIZED DAMPERS. COORDINATE VOLTAGE WITH ELECTRICAL CONTRACTOR MET Center Renovation: Fourth & Fifth Floor 6347 Plymouth Ave. St. Louis, MO 63133 222 South Central Ave Suite# 100 St. Louis, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 12024 Date: 4/12/2013 Scale: Reference Sheet: M1.2-1B S 40x22 VAV-2 12x12 1 N/A 1 N/A VAV-3 16x10 RTU-1 100 T G 125 VAV-4 St. LOUIS COUNTY REVIEW COMMENTS 1 28x12 T D MEN 518 6X8 2 210 6x10 ELEC/ DATA WORK AREA 520 504 2 210 10x10 MECHANICAL 521 WOMEN 502 8x10 1 F 70 VAV-6 CORRIDOR OPEN OFFICE 522 E 150 T 8x10 E 175 1 N/A 20x12 E 125 501 14x10 6"x8 1 N/A 12x12 LOBBY/ RECEPTION 20x12 E 150 VAV-8 E 150 500 COATS 5 JANITOR 50 519 503 VAV-7 G 150 A M2.2 A M2.2 517 1 N/A 36x12 26X12 P 12x26 E 150 40x12 18x12 32x12 508 CORRIDOR CORRIDOR 18x12 36x20 22x12 OFFICE 125 OFFICE 523 12x12 1 N/A MET Center Renovation: Fourth & Fifth Floor 6347 Plymouth Ave. St. Louis, MO 63133 222 South Central Ave Suite# 100 St. Louis, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 524 12024 Date: 4/12/2013 Scale: Reference Sheet: M1.2-1C 1 1 1 MET Center Renovation: Fourth & Fifth Floor 6347 Plymouth Ave. St. Louis, MO 63133 222 South Central Ave Suite# 100 St. Louis, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 12024 Date: 4/12/2013 Scale: Reference Sheet: M 3.1-1-A 1 1 1 MET Center Renovation: Fourth & Fifth Floor 6347 Plymouth Ave. St. Louis, MO 63133 222 South Central Ave Suite# 100 St. Louis, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 12024 Date: 4/12/2013 Scale: Reference Sheet: M 3.1-1-B 1 FIRE PROTECTION, DETECTION & ALARM EQUIPMENT & SYSTEM COMPONENTS; lp = 1.5 (To identify l refer to Table 4.1) Fire sprinkler piping x x x x x HAZARDOUS EQUIPMENT & SYSTEM COMPONENTS; l = 1.5 (To identify l refer to Table 4.1) Gas piping 1" or less (interior or exterior) Gas piping > 1" (exterior) x 1 x x 2 OTHER GENERAL EQUIPMENT & SYSTEM COMPONENTS; l = 1.0 1 Roof Top RTU-1 > 400 LBS x EF-1, EF-2, CEF-1, CEF-2 <= 400 LBS x Equipment suspended from structure: UH-1, UH-2, FBPs, VAVS > 20 LBS VAVS <= 20 LBS x x 4 Wall mounted equipment: GWH-1 x x 2 x x Duct Work 40x22 Supply riser to RTU-1 l = 1.0 Other Supply and Return Duct I = 1.0 x x x Exhaust duct connected to EF-1, EF-2,CEF-1, CEF-2 I = 1.0 Air Devices I = 1.0 x x x x x x 2 3 x Spec 230548 x 2 x 2 x 2 x 6 1 MET Center Renovation: Fourth & Fifth Floor 6347 Plymouth Ave. St. Louis, MO 63133 222 South Central Ave Suite# 100 St. Louis, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 12024 Date: 4/12/2013 Scale: Reference Sheet: M 3.1-1-C 222 SOUTH CENTRAL AVE. SUITE# 100 ST. LOUIS, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 www.bondwolfe.com DO 1 RTU-1 DI 1 David Mason & Associates Structural Engineers MO Cert. of Auth. # 800 S. Vandeventer Ave. St. Louis, MO 63110 314-534-1030 phone 314-534-1053 fax RTU-1 CONTROL PANEL EXHAUST FAN RELIEF DI 8 Custom Engineering MEP Engineers MO Cert. of Auth. # 000239 100 N. Broadway, #1875 St. Louis, MO 63102 314-802-0920 phone 314-802-0921 fax THERE ARE 10 ZONE SENSORS 1 DA-T DI-1: RTU-1 SHALL COMMUNICATE WITH THE BAS SYSTEM. BAS SHALL BE ABLE TO READ THE FOLLOWING FROM THE RTU-1 CONTROLLER. SPACE STATIC PRESSURE SENSOR SEE PLAN SHEET M1.2 RA-SD SA-SD 1 DISCHARGE AIR TEMPERATURE (ACTUAL AND SET POINT) SUPPLY FAN SPEED EXHAUST FAN SPEED SMOKE ALARM STATUS OCCUPANCY MODE OUTSIDE AIR RESET TEMPERATURE AND SCALE OUTSIDE AIR CFM OUTSIDE AIR TEMPERATURE AND HUMIDITY THE FOLLOWING SET POINTS SHALL BE ADJUSTABLE FROM THE BAS SYSTEM 1 H L DISCHARGE AIR TEMPERATURE SA 1 OUTSIDE AIR RESET TEMPERATURE AND SCALE RA NOTE: Supply fan, exhaust fan, filters, dampers, coils, sensors and accessories referenced in this sequence of operation shall be incorporated with the RTU except where indicated otherwise on this drawing. 1 DA-P SEE PLAN SHEET M1.2 OUTSIDE AIR CFM DO-1: OCCUPANCY OVERRIDE. IF RTU-1 IS IN UNOCCUPIED MODE THE BAS SHALL BE ABLE TO COMMAND RTU-1 INTO OCCUPIED MODE WHEN ACTIVATED BY A ZONE THERMOSTAT COMMAND DI-8. RTU SEQUENCE OF CONTROLS 1. Economizer A. The controller shall enter the economizer mode under the following condition. OCCUPANCY 1. Outdoor air enthalpy is less than the reference enthalpy set point. 1. The controller shall enable occupancy under any one of the following conditions. A. BAS communication signal determines occupancy is true. B. The controller shall perform the following functions in economizer mode. B. Timed override signal through space temperature sensor. 1. Modulate the outdoor air damper and return air damper positions to maintain the supply air temperature set point. C. Optimal start sequence enabled. MODULATION SEQUENCES 2. The controller shall perform the following functions in the occupied mode. Project No: 1. Supply Fan Modulation A. Modulate the outdoor air damper and return air damper to the minimum positions (return air damper modulates inversely to the outdoor air damper). B. Enable the supply fan upon closure of the outdoor air damper end switch. C. Enable EF-1 and EF-2 thru the BMS 30 seconds after closure of the supply fan pressure switch. STL Co. Economic Council 121 S. Meramec Ave. #900 St. Louis, MO 63105 MET Center Renovation: Fourth & Fifth Floor BUILDING STATIC PRESSURE 1 1. Outdoor air temperature is less than the supply air temperature set point. C. All the parameters would be adjustable so you could have a 10 degree increase in discharge air setpoint at 0 deg F giving you a setpoint of 65 and so on. Date 4/12/2013 QA/QC B. Exhaust Fan Modulation 1. The controller shall modulate the RTU exhaust fan speed thru a VFD based on a Space static pressure 0.5" W.G. relative to the outside.. 1. Heating B. The controller shall perform the following functions in heating mode. 1. When the outdoor air temperature falls below 50 deg F (Adj.), the discharge air setpoint will be increaseD 1 1. Duct static pressure. TEMPERATURE CONTROL SEQUENCE - Supply Air Temperature Control A. The controller shall enter the heating mode under the following condition. 12024 Revisions Description A. The controller shall modulate the supply fan speed based on the following input. 1 OPTIMIZATION SEQUENCES 1. Active Head Pressure Control A. The controller shall enable active head pressure control under any of the following conditions. 1. Cooling mode enabled. 2. Dehumidification mode enabled. 2. The controller shall perform the following functions when the active head pressure control sequence is enabled. B. Modulate and stage the condenser fans to maintain the refrigeration pressure set point (air-cooled). 2. Cooling A. The controller shall enter the cooling mode under the following condition. ALARMS/SAFETIES - The following alarms and shutdowns shall be connected to the BMS and require manual reset: 1 1. Outdoor air temperature is greater than the supply air temperature set point. B. The controller shall perform the following functions in cooling mode. 1. Modulate cooling capacity to maintain the supply air set point. 1. Dirty filter alarm 2. Smoke detection in RA and/or SA to alarm and shutdown RTU. 3. SHUT DOWN: 1. 2. S.A. fan off, VFD to 0%, Exhaust fan OFF, VFD to 0% O.A damper closed/R.A. damper open 3. Refrigerant solenoid valve closed DATE: 3/13/2013 PERMIT DRAWINGS RTU Control M6.1 ROOM EXHAUST SYSTEMS 222 SOUTH CENTRAL AVE. SUITE# 100 ST. LOUIS, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 www.bondwolfe.com LAB ROOM 511 EXHAUST SYSTEM: THE LAB ROOM 511 EXHAUST SYSTEM SHALL BE ENABLED WHEN THE ROOFTOP UNIT IS IN OCCUPIED MODE AND PROOF OF SUPPLY FAN OPERATION IS CONFIRMED. WHEN ENABLED EXHAUST FAN (EF-1) DAMPER SHALL OPEN. WHEN THE DAMPER IS PROVEN OPEN THE EXHAUST FAN (EF-1) SHALL START AND THE FAN MOTOR SHALL MODULATE TO MAINTAIN AN EXHAUST RATE OF 1684 CFM (ADJUSTABLE). WHEN THE FUME HOOD EXHAUST FAN IS ENABLED BY A SWITCH ON THE EXHAUST HOOD THE FUME HOOD EXHAUST FAN (CEH-1) DAMPER SHALL OPEN. WHEN THE DAMPER IS PROVEN OPEN THE FUME HOOD EXHAUST FAN (CEH-1) SHALL START. THE CEH-1 MOTOR SHALL MODULATE TO MAINTAIN 1345 CFM (ADJUSTABLE) EXHAUST RATE. WHEN CEH-1 IS ENABLED EF-1 MOTOR SHALL MODULATE TO EXHAUST 339 CFM (ADJUSTABLE). IF CEH-1 DAMPER DOES NOT PROVE OPEN OR IF THE AIR FLOW FALLS BELOW 90% OF THE SET RATE AN ALARM LIGHT SHALL BE ACTIVATED AT THE FUME HOOD AND CEH-1 SHALL BE DISABLED AND EF-1 SHALL MODULATE TO 1684 CFM (ADJUSTABLE.) PREP LAB ROOM 512 EXHAUST SYSTEM: THE PREP LAB ROOM 512 EXHAUST SYSTEM SHALL BE ENABLED WHEN THE ROOFTOP UNIT IS IN OCCUPIED MODE AND PROOF OF SUPPLY FAN OPERATION IS CONFIRMED. WHEN ENABLED EXHAUST FAN (EF-2) DAMPER SHALL OPEN. WHEN THE DAMPER IS PROVEN OPEN THE EXHAUST FAN (EF-2) SHALL START AND THE RAN MOTOR SHALL MODULATE TO MAINTAIN AN EXHAUST RATE OF 534 CFM (ADJUSTABLE). WHEN THE FUME HOOD EXHAUST FAN IS ENABLED BY A SWITCH ON THE EXHAUST HOOD THE FUME HOOD EXHAUST FAN (CEH-2) DAMPER SHALL OPEN. WHEN THE DAMPER IS PROVEN OPEN THE FUME HOOD EXHAUST FAN (CEH-1) SHALL START AND EF-2 SHALL BE DISABLED. THE CEH-1 MOTOR SHALL MODULATE TO MAINTAIN 900 CFM (ADJUSTABLE) EXHAUST RATE. WHEN CEH-2 IS DISABLED BY THE SWITCH ON THE FUME HOOD THE ASSOCIATED DAMPER SHALL CLOSE AND EF-2 SHALL BE ENABLED. IF THE CEF-2 DAMPER DOES NOT PROVE OPEN OR IF THE AIR FLOW FROM CEH-2 FALLS BELOW 90% OF THE SET RATE AN ALARM LIGHT SHALL BE ACTIVATED AT THE FUME HOOD AND CEH-2 SHALL BE DISABLED AND EF-2 SHALL BE ENABLED. CEF--2 DI 2 David Mason & Associates Structural Engineers MO Cert. of Auth. # 800 S. Vandeventer Ave. St. Louis, MO 63110 314-534-1030 phone 314-534-1053 fax DO 3 AI 3 VFD Custom Engineering MEP Engineers MO Cert. of Auth. # 000239 100 N. Broadway, #1875 St. Louis, MO 63102 314-802-0920 phone 314-802-0921 fax DI 6 1 MAD-O MAD-O AFM-I AI 7 AO 7 DO 1 DO 2 AI 2 VFD VFD DI 2 DI 1 MAD-O MAD-O MAD-O MAD-O AI 5 AFM-I FUME HOOD AI 6 AFM-I EF-2 AO 5 AO 4 AI 4 MAD-O MAD-O AO 6 FUME HOOD Project No: HARDWARE INPUTS FUME HOOD FAN SPEED FUME HOOD FAN STATUS DISCHARGE AIR DAMPER DISCHARGE AIR DAMPER END SWITCH AIR FLOW MONITOR ON/OFF AO-1, AO-2, AO-3 W/VFD % SPEED DI-1, DI-2, DI-3 RELAY ON/OFF RELAY OPEN / CLOSE CONTACTOR OPEN / CLOSE AO-4, AO-5, AO-6, AO-7 AI-1, AI-2, AI-3, AI-4 AI-5, AI-6, AI-7 CFM CFM X X X VAV CONTROL COND WATER RESET CHLR DEM LIMIT CHILLED WATER RESET CHILLER OPTIMIZATION OA LOCKOUT HW OA RESET BOILER OPTIMIZATION TEMPERATURE CONTROL DEMAND VENTILATION D/N SETBACK ECONOMIZER BUILDING STATIC PRESSURE DEMAND LIMIT OPTIMUM START/STOP START/STOP SCHEDULED RUNTIME FLOW SENSOR PSI PSG PSD POSITION TEMPERATURE RELATIVE HUMIDITY CO2 LEVEL AUX CONTACT CURRENT SWITCH SWITCH CLOSURE FLOW SWITCH 0-10V OR 4-20 MA OUTPUT PRESSURE SWITCH PNEUMATIC TO ELEC. TR. EPT CONTACTOR UNITS RELAY SOLENOID DEVICE DO-1, DO-2, DO-3 RELAY FUME AND EXHAUST FANS ANALOG LOW LIMIT DIGITAL MAINTENANCE ANALOG HIGH LIMIT DIGITAL EQUIPMENT STATUS ANALOG OWNER: ST. LOUIS COUNTY TAG Date 4/12/2013 EMS FUNCTIONS DIGITAL POINT DESCRIPTION QA/QC ALARMS BUILDING NAME: MET CENTER FUME HOOD FAN 1 SOFTWARE OUTPUTS 12024 Revisions Description INPUT/OUTPUT SUMMARY TABLE LOCATION: FIFTH FLOOR STL Co. Economic Council 121 S. Meramec Ave. #900 St. Louis, MO 63105 AI 1 DI 2 EF-1 MET Center Renovation: Fourth & Fifth Floor CEF-1 DI 1 X X X X X X X X DATE: 3/13/2013 PERMIT DRAWINGS Exhaust Control M6.2 222 SOUTH CENTRAL AVE. SUITE# 100 ST. LOUIS, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 www.bondwolfe.com VARIABLE AIR VOLUME BOXES DISCHARGE AIR TEMP SENSOR: A DISCHARGE AIR TEMP SENSOR SHALL BE PROVIDED ON EACH BOX FOR MONITORING PURPOSES. DPR-O DA-T OCCUPIED MODE: WHEN THE ZONE TEMPERATURE IS BETWEEN THE OCCUPIED HEATING AND COOLING SETPOINTS (INSIDE THE BIAS), THE PRIMARY AIR DAMPER SHALL BE AT THE MINIMUM CFM, THE REHEAT COIL SHALL BE DE-ENERGIZED. ON A RISE IN ZONE TEMPERATURE ABOVE THE COOLING SETPOINT, THE PRIMARY AIR DAMPER SHALL INCREASE THE CFM AND THE REHEAT COIL REMAINS DE-ENERGIZED. ON A DROP IN ZONE TEMPERATURE BELOW THE HEATING SETPOINT, THE REHEAT COIL IS ENERGIZED IN STEPS TO MEET THE HEATING DEMAND AND THE DAMPER IS CONTROLLED TO PROVIDE A MINIMUM CFM. E DISCHARGE AIR FROM AIR HANDLING UNIT David Mason & Associates Structural Engineers MO Cert. of Auth. # 800 S. Vandeventer Ave. St. Louis, MO 63110 314-534-1030 phone 314-534-1053 fax H UNOCCUPIED (NIGHT SETBACK) MODE: ALL VAV BOXES SHALL BE AT MINIMUM POSITION. THE REHEAT VALVE SHALL BE CLOSED WHEN THE ZONE TEMPERATURE IS BETWEEN THE UNOCCUPIED HEATING AND COOLING SET POINTS. ON A RISE IN ZONE TEMPERATURE ABOVE THE UNOCCUPIED COOLING SETPOINT, THE PRIMARY AIR DAMPER SHALL INCREASE THE CFM (IF AVAILABLE) AND THE REHEAT COIL SHALL REMAIN DE-ENERGIZED. ON A DROP IN ZONE TEMPERATURE BELOW THE UNOCCUPIED HEATING SETPOINT, THE REHEAT COIL SHALL BE ENERGIZED IN STEPS TO MEET THE HEATING DEMAND AND THE DAMPER REMAINS AT MINIMUM POSITION. Custom Engineering MEP Engineers MO Cert. of Auth. # 000239 100 N. Broadway, #1875 St. Louis, MO 63102 314-802-0920 phone 314-802-0921 fax INPUT/OUTPUT SUMMARY TABLE LOCATION: FIFTH FLOOR HARDWARE SOFTWARE OUTPUTS INPUTS ALARMS EMS FUNCTIONS BUILDING NAME: MET CENTER DIGITAL ANALOG DIGITAL ANALOG DIGITAL ANALOG OWNER: ST. LOUIS COUNTY VAV BOX UNITS ZONE TEMPERATURE SENSOR AI-19 PROGRAMABLE THERMOSTAT X DISCHARGE AIR TEMPERATURE SENSOR AI-20 AVERAGING X ELECTRIC HEATING COIL AO-10 SWITCH ON/OFF X X X X GAS FIRED UNIT HEATERS GAS FIRED UNIT HEATERS WILL NOT BE CONNECTED TO BAS. GAS FIRED UNIT HEATERS SHALL BE CONNECTED TO A HEAT ONLY THERMOSTAT LOCATED ON NEAREST INTERIOR COLUMN 60" AFF. UPON A DROP IN TEMPERATURE Project No: STL Co. Economic Council 121 S. Meramec Ave. #900 St. Louis, MO 63105 DEVICE MET Center Renovation: Fourth & Fifth Floor TAG POINT DESCRIPTION 12024 Revisions Description 1 QA/QC Date 4/12/2013 PARALLEL FAN POWERED UNITS: : UNIT SHALL BE CONNECTED TO EXISTING CONTROL SYSTEM ON FOURTH FLOOR. CONTRACTOR SHALL VERIFY EXISTING CONTROLS AND SUPPLY UNIT COMPATIBLE WITH EXISTING CONTROLS. EACH AIR TERMINAL UNIT SHALL BE EQUIPPED WITH AND ADJUSTABLE DDC ZONE CONTROLLER. THE DDC CONTROLLER IS A MICROPROCESSOR THAT PROVIDES ACCURATE, PRESSURE INDEPENDENT CONTROL THROUGH THE USE OF A PROPORTIONAL INTEGRAL DIGITAL CONTROL MODULE. THE CONTROLLER IS A MICROPROCESSOR THE CONTROL MODULE MONITORS ZONE TEMPERATURE SETPOINTS, ZONE TEMPERATURE AND ITS RATE OF CHANGE AND AIR FLOW USING DIFFERENTIAL PRESSURE SIGNAL FROM THE PRESSURE TRANSDUCER. THE CONTROL MODULE SENSES THE ZONE TEMPERATURE THROUGH A SENSING ELEMENT LOCATED IN THE ZONE SENSOR. THE ZONE SENSOR UTILIZES A THERMISTOR TO VARY THE VOLTAGE OUTPUT IN RESPONSE TO THE CHANGES IN THE ZONE TEMPERATURE. THE CONTROL MODULE VARIES THE PRIMARY AIR FROM THE ROOFTOP UNIT AS REQUIRED TO MEET ZONE COOLING SETPOINT. THE UNIT AIRFLOW IS LIMITED BY THE MINIMUM AND MAXIMUM POSITION SETPOINTS. THE CONTROLLER SHALL INTERMITTENTLY START THE FAN UPON A CALL FOR HEAT. UPON A CALL FOR FURTHER HEAT, THE ELECTRIC HEAT ASSOCIATED WITH THE UNIT SHALL BE ENABLED. A 2 DEG. BEAD BAND IS APPLICABLE TO PREVENT CYCLING. DI 7 DO 4 PLENUM AIR E PRIMARY AIR FROM RTU-1 FP1-3 H SA TO SPACE 1 AFM AI 5 MAD AO 7 DATE: 3/13/2013 PERMIT DRAWINGS VAV Box & FPB Controls DI 8 M6.3 1 EXISTING HOSE BIB ON ROOF UH-2 S 5R-30 3 S RTU-1 D 3#1, 1#6G, 1.5"C S D 7 5P-25,27,29 3/4" GAS PIPE 3" VTR EXISTING HOSE BIB TO REMAIN 1 1/4" GAS PIPE 1 MET Center Renovation: Fourth & Fifth Floor 6347 Plymouth Ave. St. Louis, MO 63133 222 South Central Ave Suite# 100 St. Louis, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 12024 Date: 4/12/2013 Scale: Reference Sheet: ME 1.4-1 EXISTING 1/2" CW PIPE UP TO HOSE BIB ON ROOF INSTALL DRAIN VALVE PIPE WITH 3/4" COPPER PIPE TO FLOOR DRAIN IN MECHANICAL ROOM REMOVE EXISTING 1/2" CW PIPE AND VALVES INSTALL 3/4" CW PIPE AND BALL VALVE CONNECT TO EXISTING CW PIPE 1 EXTEND 2-1/2" CW, 1-1/2" CW, 1" CW AND 4" SANITARY DRAIN UP TO 18" ABOVE FINISHED FLOOR OF 6TH FLOOR. CAP AT TOP OF PIPE. CUT & REMOVE 4" PVC PIPE TO BELOW DRAIN PIPE CONNECTION POINT FIFTH FLOOR MECHANICAL ROOM WATER PIPE & HOSE BIB IN MECHANICAL ROOM SCALE: NTS 1 REPIPE EXISTING PIPING & VALVES TO EXISTING HOSE BIB ON ROOF MET Center Renovation: Fourth & Fifth Floor 6347 Plymouth Ave. St. Louis, MO 63133 222 South Central Ave Suite# 100 St. Louis, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 12024 Date: 4/12/2013 Scale: Reference Sheet: P1.1-1 1 St. LOUIS COUNTY REVIEW COMMENTS FD-1 FH1 LS-2 LAB STORAGE LS-1 FH-1 GW-1 CW-1 BREAK AREA 1 WB-1 FD-1 516 FD-1 PREP. LAB 512 KS-1 CO-1 ES-1 MET Center Renovation: Fourth & Fifth Floor 6347 Plymouth Ave. St. Louis, MO 63133 222 South Central Ave Suite# 100 St. Louis, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 12024 Date: 4/12/2013 Scale: Reference Sheet: P1.2 - 1 1 FS - 1 St. LOUIS COUNTY REVIEW COMMENTS FLOOR SINK - WATTS FS-740 12" SQUARE BY 8" DEEP, WHITE PORCELAIN ENAMEL COATED INTERIOR, LOOSE SET PORCELAIN ENAMEL COATED CAST IRON GRATE 1 MET Center Renovation: Fourth & Fifth Floor 6347 Plymouth Ave. St. Louis, MO 63133 222 South Central Ave Suite# 100 St. Louis, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 12024 Date: 4/12/2013 Scale: Reference Sheet: P2.1 - 1 GENERAL NOTES 1. 222 SOUTH CENTRAL AVE. SUITE# 100 ST. LOUIS, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 www.bondwolfe.com REFER TO SHEET E1.5 ONE-LINE DIAGRAM FOR FEEDER REQUIREMENTS FOR TRANSFORMER AND PANELBOARDS. PLAN NOTES JUNCTION BOX OR WIREWAY SIZED AS REQUIRED. ROUTE CONDUIT DOWN SIDE OF BUILDING TO ADJACENT ROOF. 3.5" CONDUIT ABOVE CEILING FROM JUNCTION BOX TO PANEL 5P. ROUTE CONDUIT BELOW CEILING JOISTS AND ABOVE GRID CEILING. REFER TO ONE-LINE DIAGRAM SHEET 1.5 FOR FEEDER SIZE. REFER TO TABLE 3.2 CODE BLOCK, SHEET E0.0. CONTRACTOR SHALL HIRE A LICENSED STRUCTURAL ENGINEER TO DESIGN AND SEAL PLANS & SPECS TO MEET SEISMIC REQUIREMENTS FOR CONDUIT INSTALLATION & MOUNTING FROM MAIN DISTRIBUTION BOARD S/E TO PANEL 5P ON 5TH FLOOR. PROVIDE BUILDING PENETRATION AS REQUIRED FOR CONDUIT. 0 1 2 3 4 5 6 David Mason & Associates Structural Engineers MO Cert. of Auth. # 800 S. Vandeventer Ave. St. Louis, MO 63110 314-534-1030 phone 314-534-1053 fax Custom Engineering MEP Engineers MO Cert. of Auth. # 000239 100 N. Broadway, #1875 St. Louis, MO 63102 314-802-0920 phone 314-802-0921 fax 7 KEEPING PAD 4-INCH HEIGHT, 2-INCH PAST BASE OF TRANSFORMER ALL SIDES. EXTEND CONDUIT ALONG ROOF TO MAIN ELECTRICAL ROOM THEN PENETRATE DOWN TO EXISTING ELECTRICAL SERVICE ENTRANCE DISTRIBUTION BOARD. REFER TO SHEET E1.5 FOR DISTRIBUTION BOARD ELEVATION AND REQUIRED MODIFICATIONS. G NOT USED. F 44" 44" CLASSROOM NOT USED. 44" 44" 44" CLASSROOM 509 3 510 29 CEILING MOUNTED POWER CORD REEL WITH 120V, 20A RECEPTACLE. PROVIDE REELCRAFT L 5550 123 3A HEAVY DUTY POWER CORD REEL OR APPROVED EQUAL. PROVIDE RECEPTACLE 120V, AT CEILING FOR CONNECTION TO REEL. LAB 511 WITH DRYER INSTALLER. 5 3 1 44" MEDIA CLASSROOM PROVIDE 4"X4" JUNCTION BOX AT 7 FT AFF FOR FUTURE MOTION SENSOR. PROVIDE PLENUM RATED CABLE 4#22 FROM JUNCTION BOX TO 1ST FLOOR CCTV ROOM LOCATED ADJACENT TO BUILDING MAIN ENTRANCE. 7 9 29 27 44" 3 1 5RA 5RA 9 5 7 44" 2 #10, 1 #10 GROUND IN 3/4" CONDUIT. 507 44" 1 5R 16 18 D GAS FIRE WATER HEATER, 120V. CORRIDOR 29 508 5RA 27 GFI 16 MEN DED CKT LAB STORAGE 25 5R GFI JANITOR 503 515 5R 18 20 COATS 518 519 BREAK AREA DED CKT 13 11 7 9 12 5R MECHANICAL GFI DED CKT 5RA 17 5RA 502 5R 11 23 1 C DED CKT GFI, 44" 26 521 WOMEN 5R 517 14 5RA 6 8 10 5R 4 DED CKT 11 520 504 10 5R 2 WEST STAIR W5 DED CKT DED CKT OPEN OFFICE 501 21 14 8 4 2 5RA 44" Project No: CLOSET 513 OFFICE 523 1 CHEM STORAGE 12024 Revisions Description Revised Circuits Date 4-12-13 514 OFFICE 524 EAST STAIR E5 17 B 26 14 5RA 6 8 CORRIDOR 500 5R 13 15 17 5R 19 21 14 12 24 5R 22 24 PREP. LAB 512 522 DED CKT LOBBY/ RECEPTION DED CKT 506 5R 4 6 DED CKT 4 26 10 5RA 12 CORRIDOR STORAGE GFI 516 DED CKT 505 16 CORRIDOR GFI ELEC/ DATA WORK AREA 9 4 GFI, 44" GFI GFI CONFERENCE 44" 44" 14 16 FIRE ALARM WATER FLOW SWITCH. PROVIDE CONNECTION TO FIRE ALARM SYSTEM AS REQUIRED. GFI GFI, 44" 44" 525 3 DDC UNIT FOR HVAC CONTROL, 120V. 44" 5 STL Co. Economic Council 121 S. Meramec Ave. #900 St. Louis, MO 63105 9 5 E PROVIDE 4"X4" JUNCTION BOX ABOVE GRID CEILING AT STRUCTURE FOR FUTURE CAMERA. PROVIDE SIAMESE PLENUM RATED CABLE WITH ONE RG-59 AND ONE 2#18 FROM JUNCTION BOX TO 1ST FLOOR CCTV ROOM LOCATED ADJACENT TO BUILDING MAIN ENTRANCE. MET Center Renovation: Fourth & Fifth Floor 5 6 15 17 A Craig Brewster MO E-2000150002 PERMIT DRAWINGS DATE: N 1 5TH FLOOR POWER PLAN SCALE: 1/8" = 1'-0" 3/13/2013 5TH FLOOR Electrical Power Plan E1.0 222 SOUTH CENTRAL AVE. SUITE# 100 ST. LOUIS, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 www.bondwolfe.com LIGHTING NARRATIVE & FOOT-CANDLE LEVELS 1. LIGHT FIXTURES WILL BE ON/OFF CONTROLLED BY A COMBINATION OF TOGGLE SWITCHES AND OCCUPANCY SENSORS. 2. FOOT-CANDLE LEVELS BASED ON RECOMMENDATIONS BY ILLUMINATING ENGINEERING SOCIETY (IES): 0 1 2 3 4 5 6 LAB AREAS: 50 FOOT-CANDLES. PREP LAB AREAS: 50 FOOT-CANDLES. CLASSROOMS: 50 FOOT-CANDLES. OFFICES: 50 FOOT-CANDLES. CONFERENCE ROOMS: 30 FOOT-CANDLES. LOBBY & RECEPTION AREAS: 10 FOOT-CANDLES. BREAK AREAS: 30 FOOT-CANDLES STORAGE ROOMS: 10 FOOT-CANDLES CORRIDORS: 5 FOOT-CANDLES MECH/ELEC ROOMS: 30 FOOT-CANDLES RESTROOMS: 5 FOOT-CANDLES CLOSETS: 10 FOOT-CANDLES JANITORS CLOSET: 10 FOOT-CANDLES WORK AREAS: 30 FOOT-CANDLES LOCKERS: 10 FOOT-CANDLES 7 David Mason & Associates Structural Engineers MO Cert. of Auth. # 800 S. Vandeventer Ave. St. Louis, MO 63110 314-534-1030 phone 314-534-1053 fax Custom Engineering MEP Engineers MO Cert. of Auth. # 000239 100 N. Broadway, #1875 St. Louis, MO 63102 314-802-0920 phone 314-802-0921 fax G PLAN NOTES F 1 A CLASSROOM 509 AE A A AE AE 510 AE 1 A AE A AE LAB A LOCATE SWITCHPACK FOR OCCUPANCY SENSOR ABOVE CEILING. AE 511 EX508 1 A S 2 AE AE AE 1 30 CD H AE H AE A CONFERENCE S 2 A 505 WOMEN AE 502 C H A A MECHANICAL 30 CD BE B H 30 CD A 500 2 30 CD 30 CD CORRIDOR AE EX 2 A A 523 A OFFICE A A 3 30 CD 1 2 EX A 524 AE A A Project No: 3 A CLOSET 513 A 1 12024 Revisions Description Revised Circuits Date 4-12-13 CHEM STORAGE 514 F EAST STAIR AE B A AE 3 WEST STAIR W5 S OFFICE 3 501 A 512 AE A H A S OPEN OFFICE AE 2 A A S SPREP.ALAB AE A 1 522 LOBBY/ 2 RECEPTION 2 3 1 F AE 2 S CE EX 506 34 CD A S 4 AE 516 2 521 30 CD A AE 30 CD H STORAGE 520 BREAK AREA A AE A A 3 22 5P B S AE A A AE 1 3 1 518 B A A A A EX 503 2 A 515 COATS S ELEC/ DATA 504 A A 3 1 2 S 2 S 94 CD H A A 2 A A 30 CD WORK AREA A 3 LAB STORAGE 519 AE A 5P S H A AE JANITOR H MEN 30 CD AE 24 AE 30 CD H D AE H CORRIDOR 30 CD AE 26 5P S 2 2 30 CD H AE AE H A A A S 2 A EX A A AE A A EX EX AE A A A AE 517 507 A 1 EX 3 3 2 3 A A A 2 2 CORRIDOR MEDIA CLASSROOM A 1 A H A 60 CD H 2 A A 2 525 S S A H AE A A CORRIDOR 60 CD 2 E A H S 2 A 60 CD A A H A SWITCH TO TURN OFF ROW OF LIGHTS NEAREST WALL DURING PROJECTOR USE. STL Co. Economic Council 121 S. Meramec Ave. #900 St. Louis, MO 63105 CLASSROOM AE MET Center Renovation: Fourth & Fifth Floor AE PROVIDE FCPS-24S6 POWER SUPPLY FOR FIRE PROTECTION SIGNALING SERVICE, 120V, 3.2A. PROVIDE CONNECTION TO 5TH FLOOR FIRE ALARM DEVICES AS REQUIRED. PROVIDE CONNECTION TO AHU SHUTDOWN AS REQUIRED. PROVIDE CONNECTION TO BUILDING FIRE ALARM SYSTEM AS REQUIRED. EX E5 A Craig Brewster MO E-2000150002 PERMIT DRAWINGS N 1 5TH FLOOR LIGHTING PLAN DATE: 3/13/2013 5th Floor Lighting Plan SCALE: 1/8" = 1'-0" E1.1 222 SOUTH CENTRAL AVE. SUITE# 100 ST. LOUIS, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 www.bondwolfe.com LIGHTING NARRATIVE & FOOT-CANDLE LEVELS 1. LIGHT FIXTURES WILL BE ON/OFF CONTROLLED BY OCCUPANCY SENSORS. 2. FOOT-CANDLE LEVELS BASED ON RECOMMENDATIONS BY ILLUMINATING ENGINEERING SOCIETY (IES): CLASSROOM: 50 FOOT-CANDLES. OFFICES: 50 FOOT-CANDLES. STORAGE ROOMS: 10 FOOT-CANDLES CORRIDORS: 5 FOOT-CANDLES MECH ROOM: 30 FOOT-CANDLES 5 6 David Mason & Associates Structural Engineers MO Cert. of Auth. # 800 S. Vandeventer Ave. St. Louis, MO 63110 314-534-1030 phone 314-534-1053 fax Custom Engineering MEP Engineers MO Cert. of Auth. # 000239 100 N. Broadway, #1875 St. Louis, MO 63102 314-802-0920 phone 314-802-0921 fax PLAN NOTES 7 EXISTING FCPS-24S6 POWER SUPPLY FOR FIRE PROTECTION SIGNALING SERVICE, 120V, 3.2A. PROVIDE CONNECTION TO NEW 4TH FLOOR FIRE ALARM DEVICES AS REQUIRED. WALL MOUNT LIGHT FIXTURES IN THIS ROOM. LOCATE SWITCHPACK FOR OCCUPANCY SENSOR ABOVE CEILING. SWITCH TO TURN OFF ROW OF LIGHTS NEAREST WALL DURING PROJECTOR USE. G 1 2 AE A A A 4 E AE 3 S 1 EX 60 CD 3 S AE 2 AE OFFICE SPACE A A 402 4P 25 60 CD H S AE EX D S A 27 A A A 1 CLASSROOM 2 AE H AE A 4 A A 3 S 403 AE A EX A AE C A A A 400 60 CD H AE Project No: 3 AE B EX MECH. AREA BE 2 B A 1 405 BE 12024 Revisions Description Revised Circuits Date 4-12-13 4 B BE CORRIDOR H 30 CD 401 A A 4P CLASSROOM S H AE CORRIDOR A AE STL Co. Economic Council 121 S. Meramec Ave. #900 St. Louis, MO 63105 A AE MET Center Renovation: Fourth & Fifth Floor F STORAGE S 406 1 30 CD 3 B EX 404 AE F A EAST STAIR E4 Craig Brewster MO E-2000150002 PERMIT DRAWINGS DATE: 3/13/2013 Partial 4th Floor Lighting Plan N 1 PARTIAL 4TH FLOOR LIGHTING PLAN SCALE: 1/8" = 1'-0" E1.3 EXISTING PANELBOARD: 4P LOCATION: 4TH FLOOR ELEC RM NEMA 1 ENCLOSURE 277/480V, 3PH, 4W, GR VOLTAGE: AMPS: 400A LOAD BREAKER CKT NO A P VA * 60 1 FPB-1 14681 1 * 35 1 FPB-2 9141 3 * 60 1 FPB-3 13933 5 PHASE LOADS VA A CKT C B NO NEW PANELBOARD: 5P LOCATION: 5TH FLOOR ELEC RM NEMA 1 ENCLOSURE MOUNTING: SURFACE VOLTAGE: MAINS: 400 AMP MAIN BREAKER AMPS: 400A LOAD BREAKER VA A P A P 15 3 EXHAUST FAN EF-1 15 * 20 * 20 1 LTG RM 401, 402 1 LTG RM 403, 404, 405, 406 1357 25 1180 27 2357 110 2180 70 3 EXHAUST FAN EF-2 3 FUME HOOD EXHAUST FAN CEF-1 3 FUME HOOD EXHAUST FAN CEF-2 3 ROOF TOP UNIT RTU-1 3 45 KVA TRANSFORMER FOR PANEL 5R PHASE LOADS VA NO 300 14933 15 CKT VA 10141 15 MOUNTING: SURFACE MAINS: 400 AMP MAIN BREAKER LOAD BREAKER 15681 480/277V, 3PH, 4W, GR 222 SOUTH CENTRAL AVE. SUITE# 100 ST. LOUIS, MO 63105 TEL: 314.863.4994 FAX: 314.863.4996 www.bondwolfe.com A 1 300 3 300 5 150 7 150 9 10150 6150 11 13 440 15 440 17 440 19 440 21 23 25 27434 27 27434 29 6150 2440 6440 4440 3440 2741 2623 29971 27434 27434 0 31 0 33 0 0 0 35 13570 37 10220 39 11170 41 0 13570 10220 11170 67871 57285 LOAD NO 5300 440 440 C B 8300 4300 150 27434 CKT BREAKER A P 2 VA 8000 VAV-1 40 1 4 4000 VAV-2 20 1 6 5000 VAV-3 25 1 8 10000 VAV-4 50 1 10 6000 VAV-5 30 1 12 6000 VAV-6 30 1 14 2000 VAV-7 15 1 16 6000 VAV-8 30 1 18 4000 VAV-9 20 1 20 3000 VAV-10 20 1 22 20 1 24 2301 LTG RMS 511-516 2183 LTG RMS 500-504, 508, 518-525 20 1 26 2537 LTG RMS 505, 506, 507, 509, 510 20 1 28 0 30 0 32 0 34 0 36 0 38 0 40 0 42 0 David Mason & Associates Structural Engineers MO Cert. of Auth. # 800 S. Vandeventer Ave. St. Louis, MO 63110 314-534-1030 phone 314-534-1053 fax Custom Engineering MEP Engineers MO Cert. of Auth. # 000239 100 N. Broadway, #1875 St. Louis, MO 63102 314-802-0920 phone 314-802-0921 fax 57117 VA CONNECTED LOAD * PROVIDE NEW CIRCUIT BREAKER. NEW CIRCUIT BREAKER TO MATCH EXISTING BREAKER MANUFACTURE AND AIC RATING. TOTAL DEMAND LOAD 117.55 KVA ** EXISTING 20 AMP CIRCUIT BREAKER TO BE USED FOR NEW CIRCUIT. TOTAL DEMAND LOAD 141.39 AMPS I.C. 22000 RMS. SYM. AMPS MOUNTING: SURFACE AMPS: 125A 208/120V, 3PH, 4W, GR VOLTAGE: MAINS: 100 AMP MAIN BREAKER MOUNTING: SURFACE AMPS: 125A BREAKER A LOAD P CKT VA NO PHASE LOADS VA A CKT C B NO 740 740 ** 20 720 20 1 OFFICE 402 & CLASS. 403 RECEPTACLES 1 CLASSROOM 401, OFFICE 402 REC. ** * 19 720 21 20 1 CLASSROOM 401, OFFICE 402 REC. 720 23 MET Center Renovation: Fourth & Fifth Floor 208/120V, 3PH, 4W, GR VOLTAGE: NEW PANELBOARD: 5R LOCATION: 5TH FLOOR ELEC RM NEMA 1 ENCLOSURE LOAD VA MAINS: 125 AMP MAIN BREAKER BREAKER A LOAD BREAKER P CKT PHASE LOADS VA NO A P 20 1 MEDIA CLASSROOM 507 RECEPTACLES VA 720 1 A 20 1 MEDIA CLASSROOM 507 RECEPTACLES 720 3 20 1 MEDIA CLASSROOM 507 RECEPTACLES 720 5 20 1 WORK AREA 504 DED. CIRCUIT 800 7 20 1 WORK AREA 504 DED. CIRCUIT 800 9 1600 1600 20 1 CONFERENCE 505 RECEPTACLES 540 11 20 1 ** 20 1 LOBBY/RECEPTION 500 DED. CIRCUIT 800 13 18 540 CLASSROOM 403 & MECH. 405 REC. 20 1 ** 20 1 LOBBY/RECEPTION 500 DED. CIRCUIT 800 15 20 1 LOBBY/RECEPTION 500 & STORAGE 506 540 17 20 1 OPEN OFFICE 501 DED. CIRCUIT 800 19 20 800 21 20 1 OPEN OFFICE 501 DED. CIRCUIT 1 MEN 503, WOMEN 502, JANITOR 513 900 23 20 1 CLASSROOM 510 RECEPTACLES 720 25 20 1 CLASSRM. 509 & CLASSRM. 510 REC. 720 27 20 1 CLASSRM. 509 & MEDIA CLASSRM. 509 720 29 20 1 SPARE 0 31 20 1 SPARE 0 33 720 * PROVIDE NEW CIRCUIT BREAKER. NEW CIRCUIT BREAKER TO MATCH EXISTING BREAKER MANUFACTURE AND AIC RATING. 20 ** EXISTING 20 AMP CIRCUIT BREAKER TO BE USED FOR NEW CIRCUIT. 100 1 SPARE 3 PANEL 5RA 1260 1700 1340 3050 1600 1700 1520 1320 1320 0 0 0 35 37 0 2920 39 2660 41 4260 2920 2660 13570 10220 1 VA BREAKER A P 2 720 MECH. 521 & CORR. 522 RECEPTACLE 20 1 4 720 OFFICE 523 RECEPTACLES 20 1 6 720 OFFICE 524 RECEPTACLES 20 1 8 800 BREAK AREA 516 DED. CIRCUIT 20 1 10 800 BREAK AREA 516 DED. CIRCUIT 20 1 12 720 LAB 511 RECEPTACLE 20 1 14 900 LAB STORAGE 515 WASHER REC. 20 1 540 BREAK AREA 516 REC. 20 1 30 2 16 2790 4260 LOAD NO 1440 540 CLASSROOM 403 & CORR. 406 REC. 1120 C B 1440 1440 16 720 CKT 18 2250 LAB STORAGE 515 DRYER REC. 20 2250 22 800 BREAK AREA 516 DED. CIRCUIT 20 1 24 800 BREAK AREA 516 DED. CIRCUIT 20 1 26 800 BREAK AREA 516 DED. CIRCUIT 20 1 28 600 UNIT HEATER UH-1 AT 6TH FLOOR 15 1 30 600 UNIT HEATER UH-2 AT 6TH FLOOR 15 1 20 1 32 0 SPARE 34 0 SPACE ONLY 36 0 SPACE ONLY 38 0 SPACE ONLY 40 0 SPACE ONLY 42 0 SPACE ONLY 1 STL Co. Economic Council 121 S. Meramec Ave. #900 St. Louis, MO 63105 EXISTING PANELBOARD: 4R LOCATION: 4TH FLOOR ELEC RM NEMA 1 ENCLOSURE 11170 VA CONNECTED LOAD Project No: TOTAL DEMAND LOAD 23.08 KVA TOTAL DEMAND LOAD 64.06 AMPS 1 12024 Revisions Description Revised Circuits Date 4-12-13 I.C. 22000 RMS. SYM. AMPS NEW PANELBOARD: 5RA LOCATION: 5TH FLOOR ELEC RM NEMA 1 ENCLOSURE 208/120V, 3PH, 4W, GR VOLTAGE: MOUNTING: SURFACE AMPS: 125A BREAKER 1 MAINS: 100 AMP MAIN LUGS ONLY LOAD CKT A P 20 1 LAB 511 RECEPTACLES VA 720 NO 1 20 1 LAB 511 RECEPTACLES 720 3 20 1 LAB 511 CEILING MOUNTED RECEPTACLES 720 5 20 1 LAB 511 CEILING MOUNTED RECEPTACLES 720 7 20 1 LAB 511 CEILING MOUNTED RECEPTACLES 540 9 20 1 GAS FIRED WATER HEATER 600 11 20 1 DDC PANEL FOR HVAC CONTROL 500 13 20 1 CONTROL POWER TO ROOF EXH FANS 500 15 20 1 ELEC 1 DATA RM RECEPTALCES 600 17 SPACE ONLY 0 19 SPACE ONLY 0 21 SPACE ONLY 0 23 SPACE ONLY 0 25 SPACE ONLY 0 27 SPACE ONLY 0 29 PHASE LOADS VA A B CKT C NO 1440 1080 1260 1520 1340 1400 1300 900 1400 0 0 0 0 0 0 4260 3320 LOAD VA BREAKER A P 2 720 PREP LAB 512 RECEPTACLES 20 1 4 360 PREP LAB 512 RECEPTACLES 20 1 6 540 CLOSET 513 & STORAGE 514 REC. 20 1 8 800 PREP LAB 512 DED. RECEPTACLE 20 1 10 800 PREP LAB 512 DED. RECEPTACLE 20 1 12 800 PREP LAB 512 DED. RECEPTACLE 20 1 14 800 PREP LAB 512 DED. RECEPTACLE 20 1 16 400 MEDIA CLASSROOM 507 RECEPT 20 1 18 800 MEDIA CLASSROOM 507 RECEPT 20 1 20 0 SPACE ONLY 22 0 SPACE ONLY 24 0 SPACE ONLY 26 0 SPACE ONLY 28 0 SPACE ONLY 30 0 SPACE ONLY 4060 VA CONNECTED LOAD TOTAL DEMAND LOAD 11.77 KVA TOTAL DEMAND LOAD 32.67 AMPS I.C. 22,000 RMS. SYM. AMPS 1 Craig Brewster MO E-2000150002 PERMIT DRAWINGS DATE: 3/13/2013 Electrical Schedules E1.6