N - City of Pittsburg

advertisement
CONTRACT 2013-24B
DOVER WELL PUMP STATION
OCTOBER, 2015
N
N
PROJECT
LOCATION
PROJECT
LOCATION
9
1
CITY OF PITTSBURG
10/20/15
BID SET
CONTRACT 2013-24B
10/20/15
DOVER
PRODUCTION WELL
ELECTRICAL LOG
DOVER
PRODUCTION WELL
PROFILE
Description
Depth
CONTRACT 2013-24B
DOVER
TEST HOLE
LITHLOGY
N
THE DATA PROVIDED ON THIS SHEET IS FOR
INFORMATION PURPOSES. SEE SHEET M-4
FOR INFORMATION REGARDING THE PUMP
AND PEDESTAL INSTALLATION.
10/20/15
ACCESSORY PIPE
ORIENTATION
10/20/15
CONTRACT 2013-24B
10/20/15
CONTRACT 2013-24B
10/20/15
CONTRACT 2013-24B
10/20/15
CONTRACT 2013-24B
10/20/15
CONTRACT 2013-24B
10/20/15
CONTRACT 2013-24B
10/20/15
CONTRACT 2013-24B
CONTRACT 2013-24B
PRESSURE GAUGE DETAIL
AIR RELEASE AND
VACUUM VALVE DETAIL
A
TIE-ROD ASSEMBLY DETAIL
D
B
SAMPLE TAP DETAIL
E
M-1
10/20/15
CONTRACT 2013-24B
10/20/15
PRODUCTION CASING AIR VENT
PUMP PEDESTAL - MECHANICAL
A
M-1
PRESSURE TRANSMITTER
E
M-1
B
M-1
CONTRACT 2013-24B
10/20/15
LEVEL TRANSDUCER
HOSE RACK
C
M-1
A
M-1
10/20/15
10/20/15
10/20/15
10/20/15
=
= DUPLEX OUTLET, 20A, 120V, GROUNDED; +15'' MIN.
CONDUIT, EXPOSED; OR CONCEALED IN
WALL OR CEILING
=
CONDUIT, UNDERGROUND
=
CONDUIT, EXISTING
= GROUND WIRE
= PANELBOARD
= MOTOR, FRACTIONAL HP
= MOTOR STARTER - MAGNETIC
PB
= CHART RECORDER
= DUPLEX OUTLET, ISOLATED GROUND, 20A 120V, GROUNDED;
+15'' MIN.
CIT
= CHLORINE INDICATING TRANSMITTER
= FOURPLEX OUTLET, 20A, 120V, GROUNDED; +15'' MIN.
CMP
= CHLORINE METERING PUMP
CRT
= CHLORINE RESIDUAL TRANSMITTER
= JUNCTION BOX; CEILING OR WALL
= TRANSFORMER
= MOTOR, 1HP OR ABOVE
CR
= SPECIAL OUTLET, AS NOTED
= POINT OF INTERCEPTION
SENSORS AND INSTRUMENTS:
= DUPLEX OUTLET, GFI PROTECTED, 20A, 120V, GROUNDED; +15''
MIN.
J
= BRANCH CIRCUIT HOMERUN
FRT
= FLOURIDE RESIDUAL TRANSMITTER
DPS
= DIFFERENTIAL PRESSURE SWITCH
FIT
= FLOW INDICATING TRANSMITTER
= THERMOSTAT; +60'' U.O.N.
= DISCONNECT SWITCH, FUSED U.O.N
= MECHANICAL EQUIPMENT DESIGNATION
= COMBINATION STARTER DISCONNECT
= CIRCUIT BREAKER
= PULLBOX (PB) OR MANHOLE (MH)
= CONTACTOR OR RELAY COIL
FLS
HPS
= FLOW SWITCH
= HIGH PRESSURE SWITCH
= SMOKE DETECTOR
= FLUORESCENT FIXTURE, RECESSED
= FLUORESCENT FIXTURE, SURFACE
= WALLPACK FIXTURE
= SPOT OR FLOOD LIGHT
= INTRUSION SWITCH
= INTRUSION RESET BUTTON
LPS
LCV
= LOW PRESSURE SWITCH
= LIMIT CONTROL VALVE
LFS
= LEVEL FLOAT SWITCH
LIT
= LEVEL INDICATING TRANSMITTER
LLS
= LOW LEVEL SWITCH
PCV
= PUMP CONTROL VALVE
= EXIT & EMERGENCY
= FIXTURE DESIGNATION
= CONDUIT TURNS DOWN OR DOWN
= UTILITY REVENUE METER
= SWITCH, S.P.S.T.; +48'' MAX.
3
= SWITCH, 3-WAY; +48'' MAX.
P
= SWITCH, W/ PILOT LIGHT; +48'' MAX.
TS
= SWITCH, THERMAL; +48'' MAX.
K
= SWITCH, KEY OPERATED; +48'' MAX.
M
m
BT
a
PIT
= PRESSURE INDICATING TRANSMITTER
SOL
= SOLENOID VALVE
TSH
= TEMPERATURE SWITCH HIGH
= SWITCH, MOTOR RATED; MOUNTED AT UNIT U.O.N.
= SWITCH, MOTION; +48'' MAX.
ULT
= TIMER SWITCH; +48'' MAX.
= ULTRASONIC LEVEL TRANSMITTER
= ULTRASONIC LEVEL SESNOR
= SUBSCRIPT LETTER ADJACENT TO SYMBOL INDICATES CONTROL
= OCCUPANCY SENSOR
= ANTENNA YAGI
OTHER:
= INDICATES CONDUIT SCHEDULE NUMBER
= INDICATES REVISON NUMBER
= INDICATES REFERENCE NUMBER OF SHEET NOTE
3
I&C
= NUMBER ADJACENT TO SYMBOL INDICATES CIRCUIT
NUMBER ON PANELBOARD
= INSTALL & CONNECT
F&I
= FURNISH AND INSTALL
+24"
= INDICATES MOUNTING HEIGHT TO CENTER OF DEVICE A.F.F.
ATS
= AUTOMATIC TRANSFER SWITCH
AFF
= ABOVE FINISH FLOOR (OR A.F.F.)
AFG
= ABOVE FINISHED GRADE (OR A.F.G.)
CKT
= CIRCUIT
E.C.
= ELECTRICAL CONTRACTOR
GFI
= GROUND FAULT PROTECTED CIRCUIT OR OUTLET
MAX.
= MAXIMUM
MIN.
= MINIMUM
NIC
= NOT IN CONTRACT
WP
= ADJACENT TO SYMBOL INDICATES WEATHER PROOF DEVICE
(OR W.P.)
WPIUC
= ADJACENT TO SYMBOL INDICATES WEATHER PROOF DEVICE
W/ IN-USE COVER
U.O.N.
= UNLESS OTHERWISE NOTED
PDP
= POWER DISTRIBUTION PANEL
HP
= HORSE POWER
MS
= MOTOR STARTER
A/C
= AIR CONDITIONER
LP
= LIGHTING PANEL
(N)
= NEW
(E)
= EXISTING
TVSS
= TRANSIENT VOLTAGE SURGE SUPRESSION
SSRV
= SOLID STATE REDUCED VOLTAGE STARTER
VFD
= VARIABLE FREQUENCY DRIVE
= MOTION SENSOR - ONE WAY
= MOTION SENSOR - TWO WAY
CAM
= (F) CAMERA (NOT IN CONTRACT)
IN GENERAL - DASHED SYMBOLS DENOTE EXISTING
SYMBOLS INDICATED ABOVE MAY NOT NECESSARILY APPEAR
AS PART OF THESE DRAWINGS IF NOT REQUIRED.
= SWITCH PACK
= PHOTO CELL
JOE PREVENDAR P.E. CA EE 16581
joe@epsfresno.com
10/20/15
Know what's below.
Call before you dig.
GARY OLSEN P.E. CA EE 8283
gary@epsfresno.com
JOB: LS-13-160
DATE: AUG 2015
FILE: LS160-01SYM
PLOT: 9/11/2015 1:36 PM / 0.5:1
DSGN: JPP
DRWN: AVS
EPS IS RESPONSIBLE FOR ELECTRICAL SYSTEMS DESIGN ONLY. EPS IS
NOT RESPONSIBLE FOR ELECTRICAL SAFETY WORK PROCEDURES
AND/OR USE OF REQUIRED PERSONAL PROTECTIVE EQUIPMENT, SEE
NFPA 70E "STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE''
AND OSHA 29 CFR. CONTRACTOR MUST READ SPECIFICATIONS AND
INSTALL MATERIAL AS PER SPECIFICATIONS AND/OR PLANS OR AS PER
E.P.S. APPROVAL. PLANS AND SPECIFICATIONS ONLY APPLY TO THE
PROJECT FOR WHICH THEY WERE CREATED.
PROFESSIONAL AND CONSULTING
ELECTRICAL ENGINEERING
4049 N FRESNO ST, FRESNO , CA 93726
P: (559) 221-7230 F: (559) 221-0507
ABOVE GRADE - HOT DIPPED GALVANIZED RIGID STEEL CONDUIT TO BE
USED FOR ALL EXTERIOR AND INTERIOR LOCATIONS ABOVE GRADE OR
ELSEWHERE SHOWN ON PLANS. ALL RIGID CONDUIT AND FITTINGS TO BE
THREADED. USE OF SET SCREW OR COMPRESSION TYPE CONNECTOR IS
PROHIBITED. MEYERS HUBS TO BE USED ON ALL EXTERIOR PANEL
CONNECTIONS.
BELOW GRADE - RIGID PVC NONMETALLIC CONDUIT SCHEDULE 40 TO BE
USED FOR ALL UNDERGROUND LOCATIONS AND BELOW VAPOR BARRIER OF
SLAB. NO CONDUITS SHALL BE INSTALLED TO REDUCE THE STRUCTURAL
INTEGRITY OF FOOTINGS.
CHEMICAL BUILDINGS AND CORROSIVE ATMOSPHERES - RIGID PVC
NONMETALLIC CONDUIT SCHEDULE 80 TO BE USED FOR ALL INTERIOR
LOCATIONS ABOVE GRADE IN CHEMICAL BUILDINGS AND CORROSIVE
ENVIRONMENTS.
0
1
2
THROUGH CONCRETE SLABS AND EXTERIOR CORROSIVE ATMOSPHERES PVC COATED GALVANIZED RIGID STEEL CONDUIT MINIMUM 40 MIL
FACTORY COATING TO BE USED FOR ALL EXPOSED CONDUITS THROUGH
CONCRETE SLABS (MINIMUM 12'' ABOVE AND BELOW SLAB) AND ALL
EXTERIOR LOCATION CORROSIVE ATMOSPHERES. USE MANUFACTURERS'
SPECIFIED TOOLS AND PROCEDURES FOR INSTALLATION.
4
MOTOR OR SENSOR CONNECTIONS - LIQUID TIGHT FLEXIBLE METAL
CONDUIT (UV RESISTANT) TO ONLY BE USED ON CONNECTIONS TO MOTORS
OR SENSORS. MAXIMUM LENGTH TO BE 30''.
JUNCTION BOXES - MINIMUM SIZE PER NEC. EXPOSED LOCATION, 1 AND 2
GANG TO BE CAST IRON DEVICE BOXES TYPE FS/FD SUITABLE FOR WET
LOCATIONS. EXPOSED LOCATION EXTERIOR LARGER SIZES CONTINUOUS
HINGE TYPE 4, CORROSIVE LOCATIONS CONTINUOUS HINGE TYPE 4X
STAINLESS STEEL.
GROUND CONNECTIONS - GROUND CONNECTIONS TO BE EXOTHERMIC
CADWELD (ALL 600 AMP OR LARGER SERVICE) OR BURNDY HYDRAULIC
COMPRESSION CONNECTORS. GROUND BUS CONNECTIONS TO BE CRIMP
LUG TYPE WITH BOLTED CONNECTION TO GROUND BUS.
480 VOLT AND BELOW POWER WIRING TO BE THWN-2 600 VOLT, ALL
POWER CONNECTIONS TO BE TREATED WITH ANTIOXIDANT COMPOUND.
*** CONTACT EPS TO SCHEDULE AN ELECTRICAL PRECONSTRUCTION
MEETING PRIOR TO COMMENCING CONSTRUCTION ***
JOE PREVENDAR P.E. CA EE 16581
joe@epsfresno.com
10/20/15
Know what's below.
Call before you dig.
GARY OLSEN P.E. CA EE 8283
gary@epsfresno.com
JOB: LS-13-160
DATE: AUG 2015
FILE: LS160-02SP
PLOT: 9/11/2015 1:35 PM / 0.5:1
DSGN: JPP
DRWN: AVS
EPS IS RESPONSIBLE FOR ELECTRICAL SYSTEMS DESIGN ONLY. EPS IS
NOT RESPONSIBLE FOR ELECTRICAL SAFETY WORK PROCEDURES
AND/OR USE OF REQUIRED PERSONAL PROTECTIVE EQUIPMENT, SEE
NFPA 70E "STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE''
AND OSHA 29 CFR. CONTRACTOR MUST READ SPECIFICATIONS AND
INSTALL MATERIAL AS PER SPECIFICATIONS AND/OR PLANS OR AS PER
E.P.S. APPROVAL. PLANS AND SPECIFICATIONS ONLY APPLY TO THE
PROJECT FOR WHICH THEY WERE CREATED.
PROFESSIONAL AND CONSULTING
ELECTRICAL ENGINEERING
4049 N FRESNO ST, FRESNO , CA 93726
P: (559) 221-7230 F: (559) 221-0507
ABOVE GRADE - HOT DIPPED GALVANIZED RIGID STEEL CONDUIT TO BE
USED FOR ALL EXTERIOR AND INTERIOR LOCATIONS ABOVE GRADE OR
ELSEWHERE SHOWN ON PLANS. ALL RIGID CONDUIT AND FITTINGS TO BE
THREADED. USE OF SET SCREW OR COMPRESSION TYPE CONNECTOR IS
PROHIBITED. MEYERS HUBS TO BE USED ON ALL EXTERIOR PANEL
CONNECTIONS.
BELOW GRADE - RIGID PVC NONMETALLIC CONDUIT SCHEDULE 40 TO BE
USED FOR ALL UNDERGROUND LOCATIONS AND BELOW VAPOR BARRIER OF
SLAB. NO CONDUITS SHALL BE INSTALLED TO REDUCE THE STRUCTURAL
INTEGRITY OF FOOTINGS.
CHEMICAL BUILDINGS AND CORROSIVE ATMOSPHERES - RIGID PVC
NONMETALLIC CONDUIT SCHEDULE 80 TO BE USED FOR ALL INTERIOR
LOCATIONS ABOVE GRADE IN CHEMICAL BUILDINGS AND CORROSIVE
ENVIRONMENTS.
THROUGH CONCRETE SLABS AND EXTERIOR CORROSIVE ATMOSPHERES PVC COATED GALVANIZED RIGID STEEL CONDUIT MINIMUM 40 MIL
FACTORY COATING TO BE USED FOR ALL EXPOSED CONDUITS THROUGH
CONCRETE SLABS (MINIMUM 12'' ABOVE AND BELOW SLAB) AND ALL
EXTERIOR LOCATION CORROSIVE ATMOSPHERES. USE MANUFACTURERS'
SPECIFIED TOOLS AND PROCEDURES FOR INSTALLATION.
MOTOR OR SENSOR CONNECTIONS - LIQUID TIGHT FLEXIBLE METAL
CONDUIT (UV RESISTANT) TO ONLY BE USED ON CONNECTIONS TO MOTORS
OR SENSORS. MAXIMUM LENGTH TO BE 30''.
0
1
2
JUNCTION BOXES - MINIMUM SIZE PER NEC. EXPOSED LOCATION, 1 AND 2
GANG TO BE CAST IRON DEVICE BOXES TYPE FS/FD SUITABLE FOR WET
LOCATIONS. EXPOSED LOCATION EXTERIOR LARGER SIZES CONTINUOUS
HINGE TYPE 4, CORROSIVE LOCATIONS CONTINUOUS HINGE TYPE 4X
STAINLESS STEEL.
4
GROUND CONNECTIONS - GROUND CONNECTIONS TO BE EXOTHERMIC
CADWELD (ALL 600 AMP OR LARGER SERVICE) OR BURNDY HYDRAULIC
COMPRESSION CONNECTORS. GROUND BUS CONNECTIONS TO BE CRIMP
LUG TYPE WITH BOLTED CONNECTION TO GROUND BUS.
480 VOLT AND BELOW POWER WIRING TO BE THWN-2 600 VOLT, ALL
POWER CONNECTIONS TO BE TREATED WITH ANTIOXIDANT COMPOUND.
*** CONTACT EPS TO SCHEDULE AN ELECTRICAL PRECONSTRUCTION
MEETING PRIOR TO COMMENCING CONSTRUCTION ***
(B) - 8' LED STRIP - DUST AND MOISTURE TIGHT, RAPID START, ANY
TEMPERATURE, 120V ELECTRONIC BALLAST
8' LITHONIA FEM8LED LINEAR ROUGH SERVICE, ACRYLIC CLEAR DEEP LENS,
78 WATTS, 4100K, WITH MOUNTING BRACKETS OR EQUAL; HOLOPHANE
EMS8LED 9L IMAFL, LINEAR INDUSTRIAL LED, LENS & GASKETED WITH
STAINLESS STEEL CLIPS, MVOLT, FROSTED ACRYLIC LENS, 4100K.
(C1) - LED WALL PACK INDOOR/OUTDOOR W/ PE, MOTION DETECTOR &
OVERRIDE SWITCH
HOLOPHANE WALLPACK IV W4GLED-10C-1000-40K-T3M-MVOLT-PE-BZ,
LITHONIA TWH LED 10C 1000 40K T3M MVOLT
OR EQUAL
OUTDOOR WEATHERPROOF MOTION DETECTOR
WATTSTOPPER EW OR EQUAL
Know what's below.
Call before you dig.
JOE PREVENDAR P.E. CA EE 16581
joe@epsfresno.com
10/20/15
GARY OLSEN P.E. CA EE 8283
gary@epsfresno.com
JOB: LS-13-160
DATE: AUG 2015
FILE: LS160-03BP
PLOT: 9/11/2015 1:33 PM / 0.5:1
DSGN: JPP
DRWN: AVS
EPS IS RESPONSIBLE FOR ELECTRICAL SYSTEMS DESIGN ONLY. EPS IS
NOT RESPONSIBLE FOR ELECTRICAL SAFETY WORK PROCEDURES
AND/OR USE OF REQUIRED PERSONAL PROTECTIVE EQUIPMENT, SEE
NFPA 70E "STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE''
AND OSHA 29 CFR. CONTRACTOR MUST READ SPECIFICATIONS AND
INSTALL MATERIAL AS PER SPECIFICATIONS AND/OR PLANS OR AS PER
E.P.S. APPROVAL. PLANS AND SPECIFICATIONS ONLY APPLY TO THE
PROJECT FOR WHICH THEY WERE CREATED.
PROFESSIONAL AND CONSULTING
ELECTRICAL ENGINEERING
4049 N FRESNO ST, FRESNO , CA 93726
P: (559) 221-7230 F: (559) 221-0507
METER SECTION
METER SOCKET PER PG&E
STANDARDS
LIGHT
60''
PORTABLE GENERATOR
BY OTHERS
MECHANICAL
INTERLOCK
CB
GENERATOR PLUG ARKTITE RECEPTACLE CAT AR4041
400A (MALE) 4W-4P
LIGHT
SWITCH
CB
LOCKABLE 120V 20A GFI
OUTDOOR RECEPTACLE
400A RECEPTACLE
PER CITY SPEC
REVERSE SERVICE STYLE 2
400/3
UTILITY
METERING
M
ALL SECTIONS ARE
20'' DEEP
SURGE
PROTECTION
DEVICE
240kA/
POWER
MONITOR
I.L.
400A-3P
SERVICE
DISCONNECT
SHIPPING SPLIT
24''
20''
20''
20''
20''
SECTION 1
SECTION 2
SECTION 3
SECTION 4
SECTION 5
400A-3P
GENERATOR
DISCONNECT
TESCO SERVICE PEDESTAL
OR APPROVED EQUAL
30/3
400A-480/277V-42kAIC-CU
30''
400/3
5
40/2
250/3
HMCP
26''
9
1
15KVA XFMR
480-120/240V
400A-3P TM
8
VFD
OID
15
20
100/2
12
10
LINE CONDUIT AREA
11
PANEL
`LP'
VFD
16
SSRV
21
14
2
dV/dT
90''
11
7
17
6
VFD
150 HP
50°C
TVSS
SSRV
NOTE:
PLC
ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL A SECOND ARKTITE
RECEPTACLE (MALE) TO REPLACE (E) MALE GENERATOR PLUG ON THE
BODEGA WELL.
I.L.
NOTES:
12''
9.5''
A
6
REACTOR
LOAD CONDUIT
AREA
10
3
1) VFD - RATED 150% FLA FOR 60 SECONDS
4
2) POWER METER - ELECTRO-IND SHARK 200 W/ ETHERNET OR EQUAL
3) SSRV RATED 125% FLA
150
40A-2P TM
100A-2P TM
WELL
15kVA
TRANSFORMER
HEATER
HEATER
HEATER
HEATER
NOTES:
1) NEMA 1G ENCLOSURE
2) OPERATOR CONTROLS BETWEEN 46" AND 66"
3) VFD RATED 150% FLA FOR 60 SECONDS - HEAVY DUTY
4) REDUNDANT COOLING FANS
JOE PREVENDAR P.E. CA EE 16581
joe@epsfresno.com
10/20/15
GARY OLSEN P.E. CA EE 8283
gary@epsfresno.com
DATE: AUG 2015
JOB: LS-13-160
FILE: LS160-04SL
PLOT: 9/11/2015 1:31 PM / 0.5:1
DSGN: JPP
DRWN: AVS
EPS IS RESPONSIBLE FOR ELECTRICAL SYSTEMS DESIGN ONLY. EPS IS
NOT RESPONSIBLE FOR ELECTRICAL SAFETY WORK PROCEDURES
AND/OR USE OF REQUIRED PERSONAL PROTECTIVE EQUIPMENT, SEE
NFPA 70E "STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE''
AND OSHA 29 CFR. CONTRACTOR MUST READ SPECIFICATIONS AND
INSTALL MATERIAL AS PER SPECIFICATIONS AND/OR PLANS OR AS PER
E.P.S. APPROVAL. PLANS AND SPECIFICATIONS ONLY APPLY TO THE
PROJECT FOR WHICH THEY WERE CREATED.
PROFESSIONAL AND CONSULTING
ELECTRICAL ENGINEERING
4049 N FRESNO ST, FRESNO , CA 93726
P: (559) 221-7230 F: (559) 221-0507
480V
3Ø
18 PULSE
CPT
N
120VAC
CONTROL
POWER
AVAILABLE
PUMP CALL
DELAY
`PLC' `DI'
PUMP IN:
HAND
CONTROL
POWER
H-O-A
H
xoo
TE
oox
H
xoo
TE
oox
CONTROL
POWER ON
PUMP CALL
A
xo
CALL
DOOR MOUNT
DISPLAY
H
VFD
VFD FAULT
ox
VFD RUN
PRE-LUBE
SOLENOID
`PLC' `DO'
PUMP CALL CR
TELEMETRY
MTS - MOTOR
THERMOSTAT
SWITCH
ADJUSTIBLE SPEED DRIVE AC
CONTROLLER 150% FLA FOR 1
MIN.
`PLC' `DI'
START ON
DELAY
0-5 MIN.
VFD
RUN
MANUAL SPEED
POTENTIOMETER
PRE-LUBE START
DELAY
ONE SHOT
TIMER
BST - BACKSPIN TIMER
ONE SHOT PULSE AFTER PUMP SHUTDOWN
VFD
FAULT
`PLC' `AO'
FAULT
SPEED REFERENCE
PUMP TO WASTE TIMER
4-20mA
FREEZE
ETHERNET COM
LINK TO PLC
PUMP TO WASTE SOLENOID VALVE
SOLENOID
DEENERGIZED
VALVE OPENS TO
WASTE
SSRV START
SSRV
`PUMP CONTROL VALVE'
RUN
VFD RUNNING
NC
C
NO
CHLORINE
CHEMICAL
PUMP
CONTROL
FLUORIDE
CHEMICAL
PUMP
CONTROL
I.L.
UL APPROVED
OL ALGORITHM
`PLC' `DI'
HPS
ON
PUMP
HIGH
PRESSURE
TRIP
TDON
0-5 MIN.
240V, 20A RATED
CL
CHEM PUMP ON
FAULT
WELL
MOTOR
120V
FROM
`LP'
PUMP FAIL
DOOR MOUNT
DISPLAY
VALVE LIMIT SWITCH NORMALLY CLOSED
HELD OPEN BY TELLTALE CAM WHEN VALVE
FULLY OPEN
2CR KEEPS PUMP ON UNTIL VALVE
FULLY OPEN ON SHUTDOWN
3CR KEEPS PUMP FROM STARTING IF
VALVE NOT OPEN AFTER POWER FAIL
CHEMICAL
PUMP(S) ON
TO CPP
120V, 20A RATED
FL
CHEM PUMP ON
JOE PREVENDAR P.E. CA EE 16581
joe@epsfresno.com
10/20/15
Know what's below.
Call before you dig.
GARY OLSEN P.E. CA EE 8283
gary@epsfresno.com
JOB: LS-13-160
DATE: AUG 2015
FILE: LS160-05CD
PLOT: 9/11/2015 1:30 PM / 0.5:1
DSGN: JPP
DRWN: AVS
EPS IS RESPONSIBLE FOR ELECTRICAL SYSTEMS DESIGN ONLY. EPS IS
NOT RESPONSIBLE FOR ELECTRICAL SAFETY WORK PROCEDURES
AND/OR USE OF REQUIRED PERSONAL PROTECTIVE EQUIPMENT, SEE
NFPA 70E "STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE''
AND OSHA 29 CFR. CONTRACTOR MUST READ SPECIFICATIONS AND
INSTALL MATERIAL AS PER SPECIFICATIONS AND/OR PLANS OR AS PER
E.P.S. APPROVAL. PLANS AND SPECIFICATIONS ONLY APPLY TO THE
PROJECT FOR WHICH THEY WERE CREATED.
PROFESSIONAL AND CONSULTING
ELECTRICAL ENGINEERING
4049 N FRESNO ST, FRESNO , CA 93726
P: (559) 221-7230 F: (559) 221-0507
PLC
GE 90/30
OR
PAC R31
ELECTRICAL CONTRACTOR
TO VERIFY HEIGHT AND DIRECTION
W/ RADIO SURVEY
LIGHTNING
ARRESTER
MDS iNET
SERIES II
2900 RADIO
120VAC UPS
240 MINUTE BATTERY BACKUP,
APC OR EQUAL
NOTE: RADIO FREQUENCY & PROTOCOL PER CITY STANDARD
24VDC
POWER SUPPLY
PORT EXPANDER
15" COLOR LCD
KEYPAD & TOUCHSCREEN
GE 1C754V5115CTD
QUICK PANEL
A. GENERAL
THE WELL PUMP HAS 3 MODES OF OPERATION: REMOTE RATIO, AUTO FLOW AND HAND.
THESE MODES ARE SELECTED BY A SELECTOR SWITCH ON THE PUMP STARTER. THE PUMP
STARTER IS A VARIABLE FREQUENCY DRIVE WHICH VARIES PUMP SPEED TO MAINTAIN A
FLOW SET POINT. THE INTENT IS TO MAINTAIN POTABLE WATER TDS (TOTAL DISSOLVED
SOLIDS) BELOW STATE REQUIREMENTS.
THE STARTUP SEQUENCE IS AS FOLLOWS:
1. WELL IS CALLED BY WTP SCADA OPERATOR OR TIME OF DAY CLOCK
2. WELL PUMP VFD STARTS.
3. THE PUMP RAMPS UP TO PUMP TO A FLOW SET POINT. PUMP SPEED IS
MODULATED THROUGH A PI CONTROLLER TO MAINTAIN FLOW. THE WELL LEVEL
IS MONITORED. AT A LOW WELL LEVEL SET POINT THE MOTOR SPEED WILL
AUTOMATICALLY BE REDUCED TO ENSURE THE WELL DOES NOT BREAK SUCTION.
A PRESSURE AND LEVEL SET POINTS ARE USER ADJUSTABLE.
THE SHUTDOWN SEQUENCE IS AS FOLLOWS:
4. PUMP WILL RUN UNTIL AN ADJUSTABLE LOW FLOW RATE IS RUN AT FOR AN
ADJUSTABLE TIME PERIOD OR IF THE HIGH PRESSURE SWITCH SENSES HIGH
PRESSURE OR IF LOW WELL LEVEL CUTOFF IS REACHED.
5. AN ADJUSTABLE BACKSPIN TIMER STARTS TIMING ON PUMP SHUTDOWN
PREVENTING PUMP RESTART UNTIL THE WATER COLUMN HAS SETTLED.
B.
MODES OF OPERATION
1. REMOTE RATIO MODE: A FLOW SET POINT IS SENT VIA RADIO TELEMETRY TO
RATIO WELL FLOW TO WATER TREATMENT PLANT FLOW.
2. AUTO FLOW MODE: THE AUTO MODE IS CONTROLLED USING TIME OF DAY TO
START THE PUMP AND THEN MODULATING SPEED TO CONTROL TO A FLOW SET
POINT.
3. HAND MODE: THE HAND MODE IS A MAINTENANCE TEST MODE TO RUN THE
PUMP LOCALLY WITH THE MANUAL POTENTIOMETER CONTROLLING SPEED.
C.
CHLORINATION INJECTION (FUTURE)
1. AUTO FLOW MODE: AUTO INJECTS CHEMICAL WHENEVER THE WELL PUMP
MOTOR IS RUNNING. THE RATE IS RATIOED TO MEASURED WELL FLOW.
2. AUTO FIXED MODE: AUTO INJECTS CHEMICAL WHENEVER THE WELL PUMP
MOTOR IS RUNNING. THE RATE IS MANUALLY SET.
3. JOG MODE: JOG OPERATION IS A MAINTENANCE TEST MODE THAT RUNS THE
CHEMICAL PUMP WHEN THE BUTTON IS PRESSED.
JOE PREVENDAR P.E. CA EE 16581
joe@epsfresno.com
10/20/15
Know what's below.
Call before you dig.
GARY OLSEN P.E. CA EE 8283
gary@epsfresno.com
JOB: LS-13-160
DATE: AUG 2015
FILE: LS160-06PLC
PLOT: 9/11/2015 1:29 PM / 0.5:1
DSGN: JPP
DRWN: AVS
EPS IS RESPONSIBLE FOR ELECTRICAL SYSTEMS DESIGN ONLY. EPS IS
NOT RESPONSIBLE FOR ELECTRICAL SAFETY WORK PROCEDURES
AND/OR USE OF REQUIRED PERSONAL PROTECTIVE EQUIPMENT, SEE
NFPA 70E "STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE''
AND OSHA 29 CFR. CONTRACTOR MUST READ SPECIFICATIONS AND
INSTALL MATERIAL AS PER SPECIFICATIONS AND/OR PLANS OR AS PER
E.P.S. APPROVAL. PLANS AND SPECIFICATIONS ONLY APPLY TO THE
PROJECT FOR WHICH THEY WERE CREATED.
PROFESSIONAL AND CONSULTING
ELECTRICAL ENGINEERING
4049 N FRESNO ST, FRESNO , CA 93726
P: (559) 221-7230 F: (559) 221-0507
CONCRETE CONDITION: SAW CUT EXISTING (FLUSH) AND
PATCH BACK W/ MIN 5'' THICK CONCRETE SLAB (MIN 6 STACK
MIX), MATCH EXISTING FINISH
LEGEND
TYPICAL 3 4 "x10' COPPER CLAD GROUND
ROD, MIN. 12" FROM EDGE OF SLAB AND 10'
FROM GROUND ROD IN SERVICE SECTION
NEUTRAL BUS TO GROUND BUS BOND
CONNECTION
GROUND ROD
COMPRESSION LUG CONNECTION
BOLTED TO GROUND BUS 3 " 2-HOLE BOLTED CONNECTION
8
USING BELLEVILLE WASHER
GROUND CLAMP
THERMO WELD
OR BURNDY
COMPRESSION
UNPAVED CONDITION: EARTH BACKFILL PER SPECS.
12"
MIN
WARNING!
GFI
36"
MIN
BOND TO INCOMING METAL COLD
WATER PIPE IF AVAILABLE
BOND TO REBAR
FIXED GUARD POSTS PER
PG&E REQUIREMENTS.
SEE DETAIL THIS SHEET.
SPACE PER RULE 16
24"
24"
EARTH BACKFILL PER SPECS.
GR
UNDERGROUND CONDUITS (ELEC., COMM., EMS, ETC.)
NUMBER AND SIZE OF CONDUITS AS INDICATED ON PLANS
#4/0 BARE CU UFER GROUND,
MINIMUM LENGTH 25', MINIMUM
3" CONCRETE ENCASEMENT
#4/0 CU
PRECAST CONCRETE PAD PER
PG&E REQUIREMENTS
WARNING TAPE
GROUND BUS
#4/0 CU
TRANSFORMER PER
PG&E REQUIREMENTS
24"
FINISHED GRADE
"REMOVAL OF THIS LINK REMOVES
CUSTOMER GROUNDING TO
NEUTRAL OF SUPPLY"
#4/0 BARE CU
GR
ASPHALT CONDITION: SAW CUT EXISTING (6" SPACING BOTH
SIDES) AND PATCH BACK W/ MIN 5'' ASPHALT (TYPE B) PLACE
IN TWO LIFTS OF 2'' OVER 3'', 3 8"Ø MAX AGGREGATE SIZE (BY
PAVING CONTRACTOR), APPLY ASPHALT BINDER AT EXISTING
PAVEMENT EDGES IMMEDIATELY PRIOR TO PLACING TRENCH
RESURFACING
6"
UTILITY DISCONNECT LINK, READILY
ACCESSIBLE. MARKED:
N
GROUND ROD
(TYPICAL OF 2)
PRECAST PAD OPENINGS
36"
SAND BACKFILL OR CONCRETE SLURRY PER SPECS. EXCEPT FOR
UNDERGROUND POWER RUNS OF GREATER THAN 600 VOLTS
TO GROUND WHICH SHALL BE CONCRETE SLURRY ENCASED.
6"
3"
11 2"
11 2 "
REMOVABLE GUARD POST
PER PG&E REQUIREMENTS.
SEE DETAIL THIS SHEET.
SPACE PER RULE 16
CONCRETE ENCASEMENT: 2000 PSI SLURRY, TYPICAL ALL
UNDERGROUND CONDUITS, 3 8 "Ø MAX AGGREGATE SIZE
TOP VIEW
2"
APPROVED GROUND CLAMP
3"
#2 SOLID/STRANDED
AWG CU GROUND WIRE
8"
MIN
FINISH
GRADE
NOTE: SERVICE GROUND SIZE AS SHOWN OR AS PER TABLE 250-94-CEC
(CURRENT). ALL GROUND CONDUCTORS TO BE COPPER.
GROUND CLAMP
2"
6'' ABOVE SLAB
GROUND CLAMP
5 "x8' GROUND ROD,
8
COPPERCLAD WITH MIN
6' BETWEEN RODS
1 "x3"x3"x1 1 " ANGLE
4
2
BRACKET - SEE NOTE 4
VERIFY NUMBER OF SECTION(S)
ON PLAN(S)/ELEVATION(S)
SEE NOTES 3 & 5
SIDE VIEW
(CUT THROUGH AT CONDUIT OPENINGS)
INCOMING AND
OUT GOING CONDUITS
A
A
3 " BOLT, WASHERS,
8
LOCK WASHERS & NUT
- SEE NOTE 4
SET BRANCH
CONDUITS OPPOSITE
EACH OTHER
NOTES:
1)
DRAIN
PLAN VIEW
HILTI KWIK - BOLT
ANCHOR (TYPICAL) SEE NOTE 3
TRANSFORMER PAD SIZE & QUANTITY OF GUARD POSTS PER PG&E RULE 16.
2) ALL PG&E RULE 16 APPLY.
= FIXED
LOCKING
STEEL LID
LOCKJAW TYPE
SEAL CONDUITS WITH
DUCT SEAL
= REMOVABLE
FINISH GRADE
GROUT
SEE NOTES 1 & 2
CONCRETE PULLBOX
WITH EXTENSION
3 "x3 3 " SS HILTI
4
8
KWIK-BOLT AT EACH
CORNER OF
ENCLOSURE AS
SHOWN ABOVE
CLAMP TO MOTOR
FEED
TACK WELD CLAMP
TO STAINLESS STEEL
LABEL MOUNT
3"
PVC
12 GAUGE
STAINLESS STEEL
6" MIN
INSTALL TAR PAPER
BETWEEN ROCK &
GROUT & UP 1 1 4 " ON
ALL SIDES & SLOPED
DOWN TOWARD DRAIN
IN CENTER OF BOX
1 1 2"
3
4" CRUSHED ROCK
BASE (TYPICAL)
(SEE LABEL ABOVE)
1"x3" PVC SLEEVE FOR
DRAIN STUB INTO
ROCK
3"
SIDE VIEW A-A
AT MOTOR
STAINLESS
STEEL BOLTS
OR SCREWS
MCC-______________
(MOTOR CONTROL CENTER)
PUMP _____________
(MOTOR DESCRIPTION)
____ HP
(HORSEPOWER)
WHITE LAMICOID W/ BLACK LETTERS
AT STARTER
CHRISTY N9 (#3 1/2), N30 (#5), N36 (#6) OR LARGER PULLBOXES SIMILAR
NOTES:
Know what's below.
Call before you dig.
1)
FOR INDOORS - 1 1 2 " HIGH HOUSEKEEPING PAD. 2" WIDE ALONG BACK,
BOTH SIDES AND FRONT.
2)
FOR OUTDOORS - 3 1 2" HIGH HOUSEKEEPING PAD. 2" WIDE ALONG
BACK, BOTH SIDES AND AS SHOWN ON PLANS FOR FRONT.
3)
4 ANCHORS FOR 1ST SECTION AND 2 ANCHORS FOR EACH OTHER
SECTION.
4)
2 FOR 1ST SECTION AND 1 FOR EACH OTHER SECTION.
5)
FOR CONCRETE WALL. USE 3 8"x3 3 4" HILTI KWIK-BOLT.
FOR STUD WALL. USE 3 8"x3" LAG BOLTS.
JOE PREVENDAR P.E. CA EE 16581
joe@epsfresno.com
10/20/15
GARY OLSEN P.E. CA EE 8283
gary@epsfresno.com
JOB: LS-13-160
DATE: AUG 2015
FILE: LS160-07DT
PLOT: 9/11/2015 1:27 PM / 0.5:1
DSGN: JPP
DRWN: AVS
EPS IS RESPONSIBLE FOR ELECTRICAL SYSTEMS DESIGN ONLY. EPS IS
NOT RESPONSIBLE FOR ELECTRICAL SAFETY WORK PROCEDURES
AND/OR USE OF REQUIRED PERSONAL PROTECTIVE EQUIPMENT, SEE
NFPA 70E "STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE''
AND OSHA 29 CFR. CONTRACTOR MUST READ SPECIFICATIONS AND
INSTALL MATERIAL AS PER SPECIFICATIONS AND/OR PLANS OR AS PER
E.P.S. APPROVAL. PLANS AND SPECIFICATIONS ONLY APPLY TO THE
PROJECT FOR WHICH THEY WERE CREATED.
PROFESSIONAL AND CONSULTING
ELECTRICAL ENGINEERING
4049 N FRESNO ST, FRESNO , CA 93726
P: (559) 221-7230 F: (559) 221-0507
ROSEMOUNT 3051TG
PRESSURE TRANSMITTER W/ LCD DISPLAY
0-100 PSI OR EQUAL
PELCO PENDANT CAMERA
AND ENCLOSURE OR EQUAL
ROOF
FIELD SENSOR DEVICE (TR-16 4-20mA)
CABLE OR CONDUIT - SEE NOTES BELOW
90° CONNECTOR
ROSEMOUNT
SINGLE GANG WEATHERPROOF OUTLET
BOX W/ BLANK COVER
1
FIELD
TERMINALS
2"
STEEL
CONDULET
3
306RT2 THREADED
STYLE MANIFOLD
TWO-VALV E
(FUTURE)
PELCO DIGITAL RECORDER OR
EQUAL (NOT IN CONTRACT)
SEE
NOTE 4
LFMC
CONNECTOR
W/ 3 4" TO
1 " RE
2
BUSHING
4"
MIN
1''C W/
CAT 5E-POE
ROOF FASCIA
4 "RMC
#18 TSP
GUTTER &
DOWNSPOUT
3" GALVANIZED STEEL
CHANNEL
PIPE
FINISH
GRADE
W/
TO
CONTROL
PANEL
36"
MIN
30"
PELCO PENDANT
CAMERA AND
ENCLOSURE OR
EQUAL
12"DIAx36" CONCRETE
FOUNDATION
21'' COLOR
MONITOR
PVC COATED RMC
CAT-5E TO
ETHERNET
SWITCH AT PLC
SITE CONTROL ROOM
PVC
NOTES:
NOTE:
1)
IF FIELD SENSOR DEVICE IS FURNISHED W/ CONDUIT CONNECTION
PROVISIONS, CONNECT WITH LFMC.
NOTES:
2)
IF FIELD SENSOR DEVICE IS EQUIPPED ONLY W/ LIQUIDTIGHT CABLE,
RUN INTO WEATHERPROOF OUTLET BOX THROUGH LIQUIDTIGHT
CABLE CONNECTOR.
1) ELECTRICAL CONTRACTOR TO PROVIDE CONDUITS FOR CAMERAS AS
SHOWN. ALL CAMERA EQUIPMENT AND ENCLOSURES TO BE SUPPLIED
AND INSTALLED BY CITY. ELECTRICAL CONTRACTOR SHALL COORDINATE
WITH CAMERA INSTALLER.
1) PELCO SARIX IME SERIES VANDAL RESISTANT PENDANT NETWORK
MINI-DOME (NOT IN CONTRACT)
2) PELCO SWM CORNER 3 PART PENDANT MOUNT (NOT IN CONTRACT)
3) PELCO DX 4700 VIDEO RECORDER (NOT IN CONTRACT)
4) PROVIDE WALL MOUNT VENTED NEMA 1 ENCLOSURE W/ SEE THRU
DOOR (FUTURE)
SEE NOTE 1
RUN
OIT
FAULT
3/4" FLEXTITE
MAXIMUM 12" TO
3/4"C
SEE NOTE 2
HOA
MANUAL
SPEED
POT
VENTS
POWER
HEATSINK THRU
BACK WITH
WEATHERPROOF
SHROUD
VFD
ELECTRONICS
REDUNDANT
COOLING FANS
SEE NOTE 1
FRONT
NOTES:
1)
PMC/BETA VL4513 W/ TE-10 DRY BOX AND MP-11 CABLE TERMINATOR
SEALED REFERENCE VOLUME FILLED WITH DRY NITROGEN OR EQUAL
2)
THIS IS THE 2-WIRE TWISTED PAIR THAT SUPPLIES THE 9-30VDV
EXCITATION AND RETURNS THE 4-20MA CURRENT PROPORTIONAL TO
PRESSURE/LEVEL, 4MA - THE MINIMUM AND 20MA = THE MAXIMUM
JOE PREVENDAR P.E. CA EE 16581
joe@epsfresno.com
10/20/15
Know what's below.
Call before you dig.
GARY OLSEN P.E. CA EE 8283
gary@epsfresno.com
JOB: LS-13-160
DATE: AUG 2015
FILE: LS160-08DTA
PLOT: 9/11/2015 1:25 PM / 0.5:1
DSGN: JPP
DRWN: AVS
EPS IS RESPONSIBLE FOR ELECTRICAL SYSTEMS DESIGN ONLY. EPS IS
NOT RESPONSIBLE FOR ELECTRICAL SAFETY WORK PROCEDURES
AND/OR USE OF REQUIRED PERSONAL PROTECTIVE EQUIPMENT, SEE
NFPA 70E "STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE''
AND OSHA 29 CFR. CONTRACTOR MUST READ SPECIFICATIONS AND
INSTALL MATERIAL AS PER SPECIFICATIONS AND/OR PLANS OR AS PER
E.P.S. APPROVAL. PLANS AND SPECIFICATIONS ONLY APPLY TO THE
PROJECT FOR WHICH THEY WERE CREATED.
PROFESSIONAL AND CONSULTING
ELECTRICAL ENGINEERING
4049 N FRESNO ST, FRESNO , CA 93726
P: (559) 221-7230 F: (559) 221-0507