Grounding By ELASSAD Hakam Microelettrica Scientifica MS RESISTANCES ELECTRICITY The Electricity is produced & generated outside cities at high voltage On Nuclear plant On diesel ,or steam generateur On wind or photovoltaique On hydro plant NUCLEAR POWER PLANT Diesel Generation plant Steam power process Steam generator Photovoltaic plant WIND POWER PLANT Transmission & Distribution Electricity should be transported & distributed The transportation is made through Cables ( High voltage head over lines Transmission ) 63 , 132,220 , 330 , 400 or 750 kV the voltage vary from countries , distance , total power to be transported Etc. Head over lines Transmission & distribution process Sub-Station Types of Neutral Grounding in Power Distribution In industrial high voltage network , ground or earth is the reference point from which voltages are measured , a common return path for electrical current or direct physical connection to the earth Method of grounding (Earthing) To determine the Earthing mode a compromise between three requirements – Damp over voltages – Limit damage & disturbances cause by the earth fault – Provide simple selective protection devices Criteria to Choose Voltage level: The insulation level of material must be in accordance with induced over voltage at the time of Short circuit Insulation coordination : Ground fault current will induce locally over voltage which must be compatible with the insulation of components Limitation of Fault current : To reduce the electrodynamics stress on material , limit the induced voltage on telecommunication lines Grounding Method Insulated or Ungrounded Neutral Ungrounded system is no longer recommended No connection between Neutral & Ground Solidly earthed or direct Earthling The Neutral of Transformer or Generator is directly connected to ground by Bus Bar No limitation of Fault current Is usually used in low voltage 600 V and lower Impedance fault current Limitation There is three types By neutral grounding Resistor By Neutral grounding reactor By tuned reactor ( Petersen coil or ground fault neutralizer ) Through a Neutral Earthing Reactor The Neutral of Transformer is connected to earth through a Reactor The ground fault current should be at least 60% of the three phase fault current Reactor grounding is not considered as an alternative to the resistor grounding This solution is rarely used in industry or bear cities due to induced magnetic field Neutral grounding Reactor dry type PETERSEN COIL An Earthing reactor connected between the neutral of a system and earth and having relatively high value of reactance The reactive current to earth under fault conditions balances the capacitance current to earth so that the earth current at the fault is limited to practically zero Arc suppression coil (Peterssen coil ) Through a Neutral Earthing Resistor The Neutral of Transformer is connected to earth through a Resistor The fault current is limited to chosen value I f = (System Voltage /3)/R There is two types of resistors LOW RESISTANCE & HIGH RESISTANCE Neutral Grounding Resistor Low Resistance Grounding Connected to earth ground through low resistance Limits ground fault current to a 20 % of 3 phase fault current (10-3000 A) Resistor is connected between neutral of power source High Resistance Grounded Connected to earth ground through a high resistance Limits ground fault current to a few amperes (1-10 A is common) Commonly used on low voltage systems in industrial plants Used by utilities for large generators Where Do We Ground? Single source feeding bus Source connected Derive neutral with Y- or zig-zag transformer Connect grounding resistor to this derived neutral Where Do We Ground? Single transformer feeding bus Transformer secondary Y connected Connect grounding resistor to neutral of transformer Where Do We Ground? Single generator feeding bus Generator Y connected Connect grounding resistor to neutral of generator Where Do We Ground? Multiple sources feeding bus Sources Y or connected Derive neutral with Y or zig-zag transformer Connect grounding resistor to this derived neutral Where Do We Ground? Double-ended substation with normally open tie Transformers Y connected Connect grounding resistor to each transformer neutral NEUTRAL GROUNDING RESISTOR Neutral Earthing Resistor NGR is not a protection components NGR is installed to reduce the fault current before clearing the fault Phase - Neutral Voltage = V = System voltage / 3 V=U/1.732 Rated fault Current = V/R ( A ) Rated time (sec) Required Temperature Rise °K NOTA : IEEE-32-1990 is the only existing standards to design the resistor Rated Voltage NGR is inserted between the Neutral of Transformer ( secondary ) & Earth , The rated voltage of NGR = Phase to Neutral Voltage = System Voltage /3 Rated Fault Current I fault= (U/3)/ R Phase to Neutral Voltage / resistance value In High Resistance , The fault current =1 to 10 A In Low Resistance : The fault current = 10 to 3000A In case of NO indication we limit the fault current to the rated current of transformer Rated Time & temperature Rise Rated time = 10 sec , 30 sec or 1 minute /hour The time rating indicate the time that the NGR can operate under fault conditions without damage & without exceeding the specified temperature rise 385 °C for continuous rating 760°C for less than 10 minutes As per I EEE 32 Standards , Insulation As per IEEE 32 Standards the applied voltage should be = 2.25 times the line to neutral voltage + 2 kV EXTRACT FROM IEEE 32-1990 Resistances material Different kind of resistance material 1: Cast iron ( not used any more) 2: Liquid resistor ( not used any more) Stainless Steel ( AISI 304 , 430,310,32/20 or inconel 601 ) NiCr alloy Temperature Coefficient of resistance material Temperature coefficient = indicate the variation of resistivity of resistance material with temperature Resistance material used for NGR should have a high variation of resistivity to limit the fault current & keep the voltage constant The Stainless Steel AISI 430 is mostly used for NGR Protection Degree The NGR is a passive component , resistor will absorb the energy developed by the current during rated time and should evacuate it The Best Protection Degree for NGR = IP23 IP 55 type tests IP55 Sub station in the desert Egypt Components can be installed into Resistor RECOMMANDED Current & voltage transformer On or off load disconnectors ( contactors) Surge Arrestors Space heater Lamp Doors NOT RECOMMANDED Electronic devices like relays or others monitors ( temperature into resistors will reach very high level & cause damage to electronic accessories ROUTINE & Type Tests Routine Tests Visual Inspection Dimensional Check Measurement of Insulation Resistance Measurement of Resistance High Potential Test (Dielectric test @ 50Hz – 1min) Type Tests As per IEEE-32 Impulse tests are not required for Resistor Heat run tests = Temperature Rise tests , application of constant voltage during rated time measurement of current & resistance value at 0 sec up to end rated time Measurement of temperature rise by application of tempearture sensor Calculation of temperature rise tests as per following formula R2=R1*(1+αΔθ) α = Temperature coefficient of resistance material Δθ = Temperature Rise Temperature Rise tests & installation of temperature sensor The End