Streamline star delta motor starters Insulated enclosed type 7.5 to 75kW NEW ❍ Quality design at an economical price ❍ Insulated enclosure IP 67 protection ❍ Standard electronic motor protection with improved phase loss protection, class 10 trip overload curve ❍ RZ7 Electronic timer with adjustable change-over time (1.5 to 30 seconds) ❍ Complete with stop/start and reset pushbuttons IP 66 protection kW @ Main & Delta 400/415 V AC contactors 3...7.5 CA 7-9 Star contactors CA 7-9 Standard overload 1) CEP 7-M32-12-10 Overload setting range 2) (A) 3.7-12 SDS 7-7.5 11 CA 7-12 CA 7-9 CEP 7-M32-32-10 12-32 SDS 7- 11 3...7.5 CA 7-9 CA 7-9 CEP 7-M32-12-10 3.7-12 SDS 7-7.5L 3) 11 CA 7-12 CA 7-9 CEP 7-M32-32-10 12-32 SDS 7-11L 3) 15 CA 7-16 CA 7-9 CEP 7-M32-32-10 12-32 SDS 7-15L 18.5 CA 7-23 CA 7-12 CEP 7-M32-32-10 12-32 SDS 7-18.5L 22 CA 7-23 CA 7-16 CEP 7-M32-32-10 12-32 SDS 7-22L 30...37 CA 7-37 CA 7-23 CEP 7-M45-45-10 14-45 SDS 7-37L 37...45 CA 7-60 CA 7-30 CEP 7-M85-85-10 26-85 SDS 7-45 55 CA 7-60 CA 7-37 CEP 7-M85-85-10 26-85 SDS 7-55 75 CA 7-85 CA 7-43 CEP 7-M85-85-10 26-85 SDS 7-75 Application The streamline SDS 7 starters reduce motor starting current to one third of the DOL start current with a resultant reduction in starting torque to one third. Six motor leads are required for star/delta starting. Dimensions (mm) Height Width Depth SDS 7-7.5-SDS 7-11 280 190 180 SDS 7-7.5L...SDS 7-37L 280 280 180 SDS 7-45...SDS 7-75 380 280 180 Changeover timer The SDS 7 starters are fitted with a compact RZ7 electronic timer with adjustable changeover time giving a range of 1.5 to 30 seconds. The timer also includes a fixed transition time of 50-65 mSecs. The latest technology in contactors and motor protection The starters are fitted with the latest ACS-CA 7 contactors and the unique CEP 7 electronic overload. The CEP 7 provides rapid phase loss protection and offers reduced heat output because no heating elements are used. Notes: Cat No. Add control voltage to Cat No. when ordering. (240 volt or 415 volt AC) For reset only versions, starter is provided with blanking plugs and instructions. 1 ) If required a class 20 overload can be provided. 2 ) For motor full load amps below 6.4 A a lower scale setting is available. 3 ) Version with larger enclosure and extra wiring room. 240/415 V rated coils are suitable for use on 230/400 V in accordance with AS 60068 : 2000