emergency

advertisement
L136
EEQ SERIES • LIGHTING
C O M PA C T F L U O R E S C E N T E M E R G E N C Y L I G H T I N G
Class I, Div. 1 & 2, Groups C,D
Class I, Zones 1 & 2, Groups IIB, IIA
Class II, Div. 1 & 2, Groups E,F,G
Class III
NEMA 3
Compliances: UL 844; UL 1570, UL924 (File E162407)
UL Wet Location Listed (Indoor & Outdoor)
Rated for 40Cº ambient. Minimum start 0º C
Temperature codes:
Class I C,D T6;
Class II E,F,G T4;
Suitable for Class III
F E AT U R E S - S P E C I F I C AT I O N S
Use Push-To-Test station suitable for
area of use for testing purposes. FXCS
series control stations should be used
for hazardous locations.
EMERGENCY
Applications
HOSTILELITE® EEQ Emergency
Lighting fixtures provide continuous
illumination under normal power and
switch to emergency battery backup
during power outages. Emergency
Units ONLY are available that operate
only when normal power fails.
Units contain battery unit that provides
the OSHA required 90 minutes of illumination (same lamp) for egress.
Units are designed for general and task
lighting indoors or outdoors where
flammable gases or vapors or combustible dusts exist and create a hazardous location, as defined by the NEC.
Features
• Quad-Pin long-life triple-tube compact fluorescent lamps included
• Choice of Pendant, Ceiling, Wall or
Stanchion mount
• Factory Sealed - No external seal
required
• Corrosion resistant-Copper-free
aluminum (less than 4/10 of 1%)
die-cast construction w/Baked-on
epoxy/polyester powder finish
• Exposed hardware is 316 grade
stainless steel
• LED charging indicator light visible
through lens
Accessories
Exit sign: Model HEXA-100 (note omit
2nd “G” in catalog number for globeonly fixture) see page L74.
Reflectors: Use standard dome ERSD15
or angle model ERA15 (see page L73).
12-1/8
7
12-1/8
8
E E Q 2 6 , 3 2 & 4 2 WAT T N O R M A L & E M E R G E N C Y M O D E F I X T U R E S
QUAD-PIN FLUOR.
LAMP INCLUDED
LINE VOLTAGE
@ 60 HZ
PENDANT 3/4" CATALOG NUMBER CEILING 3/4" BRACKET 3/4" 2 6 Wa t t
1 2 0 VA C EEQ2626E1A2GG
EEQ2626E1X2GG
EEQ2626E1B2GG
EEQ2626E1D4GG
3 2 Wa t t
1 2 0 VA C EEQ3232E1A2GG
EEQ3232E1X2GG
EEQ3232E1B2GG
EEQ3232E1D4GG
4 2 Wa t t
1 2 0 VA C EEQ4242E1A2GG
EEQ4242E1X2GG
EEQ4242E1B2GG
EEQ4242E1D4GG
STANCHION 1-1/4" E E Q 2 6 , 3 2 & 4 2 W A T T E M E R G E N C Y - O N LY M O D E F I X T U R E S
CATALOG NUMBER CEILING 3/4" BRACKET 3/4" QUAD-PIN FLUOR.
LAMP INCLUDED
LINE VOLTAGE
@ 60 HZ
PENDANT 3/4" 2 6 Wa t t
1 2 0 o r 2 7 7 VA C EEQ0026E10A2GG
EEQ0026E10X2GG
EEQ0026E10B2GG
EEQ0026E10D4GG
3 2 Wa t t
1 2 0 o r 2 7 7 VA C EEQ0032E10A2GG
EEQ0032E10X2GG
EEQ0032E10B2GG
EEQ0032E10D4GG
EEQ0042E10B2GG
EEQ0042E10D4GG
4 2 Wa t t
1 2 0 o r 2 7 7 VA C EEQ0042E10A2GG
EEQ0042E10X2GG
Pendant, Ceiling & Bracket models may be changed to 1" hubs by changing the 11th character from 2
to 3; e.g. EEQ2626E1A3GG (12th character in EMERGENCY-ONLY MODE).
Stanchion fixtures are 1-1/2" with a 1-1/2 to 1-1/4" reducer.
Omit 2nd “G” for globe-only fixture for use with HEXA-100 Exit Accessory.
Normal and Emergency Mode Models are available in 277Volt; change the 1 in the catalog number to 4.
Emergency-Only Models are factory set to 120V and can be changed to 277Volt in field.
Standard color for fixtures is Killark beige. Add -R for RED adder.
EEQ fixtures use a tank extension ring and are 2-1/2" taller than EBF fixtures (see page L76).
Photometric characteristics similar to EBF26 page L85, except adjusted for lumen output.
STANCHION 1-1/4" LUMEN OUTPUT
LAMP SOURCE
NORMAL POWER EMERG. POWER
2 6 Wa t t
1800
450
3 2 Wa t t
2400
575
4 2 Wa t t
3200
750
B A L L A S T D ATA
OPERATING AMPS
INPUT WATTS
BALLAST CIRCUIT
2 6 Wa t t ( 1 x 2 6 )
LAMP WATTS
1 2 0 / 2 7 7 VA C
VOLTAGE
.24@120V /.11 @277V
29
HPF
REGULATION
Electronic
3 2 Wa t t ( 1 X 3 2 )
1 2 0 / 2 7 7 VA C
.31@120V /.13 @277V
36
HPF
Electronic
4 2 Wa t t ( 1 x 4 2 )
1 2 2 / 2 7 7 VA C
.38@120V /.17 @277V
46
HPF
Electronic