ENhanced TEChnology www.entecene.co.kr Pole Top SF6 Gas Insulated Load Break Switch for Power Distribution System thru 15.5kV, 25.8kV & 36kV V. 2.0 Pole Top SF6 Gas Insulated Load Break Switch for Power Distribution System thru 15.5kV, 25.8kV & 36kV Pole Top SF6 Gas Insulated Load Break Switches are designed to meet growing requirements for reliability of power distribution. Switches filled with SF6 gas as the insulating and arc quenching medium with puffer principle in making and breaking ensure the positive breaking of small inductive, mainly active load current, cable charging current, magnetizing current and etc. They are manufactured under a quality system conforming to ISO 9001. Features Manual and motor operation The basic mechanism is operator independent quick close and quick open spring toggle mechanism. The switch can be operated manually or it can be operated with an integrated motor drive for remote and/or local control. The manual operating handle is free to operate regardless of the position of the motor driven mechanism. Stainless steel enclosure and safety devices The switch enclosure is made of stainless steel plate (STS304L) and filled with SF6 gas. The completely sealed enclosure provides maintenance free operation even in severe weather conditions. It is designed to guarantee the safety even at the maximum fault capacity. Polymer or porcelain bushing with silicone rubber boots The switch can be provided with hydrophobic cycloaliphatic epoxy resin(HCEP), epoxy bushing with silicone rubber boots or porcelain bushing. The high voltage terminal is provided with the NEMA (or clamp stud) terminal or the molded cone type lead which has high dielectric strength even under heavily polluted conditions. Microprocessor based controller Microprocessor based control cubicle for feeder automation is designed for outdoor pole mounting on a separate external panel and is normally mounted low on the pole for ease of access. The basic control cubicle is provided with detection of phase and earth faults from current sensing elements and checks the live and dead line status from the voltage sensing element. The details of the fault and event log can be stored and transmitted to the SCADA or remote control unit through modem. Pole Top SF6 Gas Insulated Load Break Switch EARTH CABLE CABLE BAND CONTROL CABLE CONTROL BOX Metering Voltage & current Measures kW and kWh, power factor Demand watts & VARs and frequency Load profile data & ocillogram Monitoring & Recording Setting, metering and data recording Counters Fault waveforms Remote communication(ETMFC101-N1) Ports: RS232, RS485, RJ45 (TCP/IP) Protocols: DNP3.0, MODBUS, IEC60870-5-101/104 Built-in RTU ETSWC101 ETMFC101-N1 Ratings Rated voltage (kV) 15.5kV 25.8kV 36kV Rated current (A) 630 630 630 50 / 60 50 / 60 50 / 60 16 12.5 12.5 41.6 32.5 32.5 Cable charging breaking current (A) 17 25 20 Power frequency withstand voltage(kA) 50 60 70 Lightning impulse withstand voltage(kA) 110 150 170 Frequency (Hz) Short-time withstand current (kA) / 1s Short-circuit making current (kA) Insulation media Operating mechanism Arc extinguishing method Control and operation function SF6 gas Spring toggle Puffer RTU built-in or Separate digital control Rated voltage 110/220V(Option) Power supply DC 24V Permeable voltage range Control 85~110% AC power frequency withstand voltage 2,000V 1min Basic Impulse Level 6kV Enclosure Stainless steel (STS304L) 15.5kV SF6 Gas Insulated Load Break Switch Construction 6)5-84)<- 0)6,4-47+316/ ,M^QKM 0)6/-: 0)6,4- 16,1+)<7: ! ;-)416/ +766-+<7: 4-/ 8ZM[[]ZM 4WKSQVO,M^QKM +7=6<-: 16,1+)<7: ;IN\a,M^QKM ;./I[.QTTQVO,M^QKM 25.8kV SF6 Gas Insulated Load Break Switch 6)5-84)<- 0)6,4-47+316/ ,M^QKM 0)6/-: ;\QKSMZ ფၷ ืଐଐ൦၀ཙ-87@A๓རၫ ၼွጔશှከ།ၷှണੱ ႆၨരಋཙ།႒ၼ൦ ၼွཙဒ 4 SO 0b 0)6,4- 7.. 76 ;./); S> ) -IZ\P<MZUQVIT 16,1+)<7: 4-/ +7=6<-: :MKMX\IKTM 16,1+)<7: 8ZM[[]ZM 4WKSQVO,M^QKM 76 : * ) ; !3> ) 4*; + < ;INM\a,M^QKM ;./I[.QTTQVO,M^QKM 36kV SF6 Gas Insulated Load Break Switch -):<0<-:516)4 0)6,4-47+316/ ,M^QKM .:-- 4 SO 0b 47+3 ;./); 76 S> ) 0)6,487;1<17616,1+)<7: 0)6/-: 7.. 6)5-84)<- 8ZM[[]ZM4WKSQVO,M^QKM +7=6<-: ; + < * ! : ! 76 ) 8ZM[[]ZM :MTQMN,M^QKM /);.QTTQVO>IT^M;. * Note. Product structure and arrangement shall be modified without notice. 201502 225-38 Choirubaekro, Bongdam-Eup, Hwaseong-City, Gyunggi-Do, Republic of Korea Post code : 445-893 TEL: +82-31-299-8400 FAX : +82-31-299-8401/ 2 http://www.entecene.co.kr E-mail : entec@entecene.co.kr