AEB Series: Bolted Combination and Non-Combination Full Voltage Motor Starters
Explosionproof, Dust-Ignitionproof, Watertight
Units Provide Disconnecting Means and Undervoltage, Circuit and Motor Running Protection.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Application
• Combination and non-combination motor starters are used in
areas where hazardous materials are handled or stored.
• These units provide disconnecting means, undervoltage
protection, circuit protection, and motor running protection.
Features
•
•
•
•
•
Controls
•
•
•
•
•
Controls: Hazardous Location Motor Starters
•
•
•
•
•
65,000 AIC. Highest interrupt rated enclosure in the industry.
Copperfree cast aluminum.
Precision machined flame path between box and cover.
Bolt on slotted mounting feet.
Stainless steel, captive Quad-Lead® cover bolts (disengage in
1-1/2 turns).
External stainless steel breaker operating handle.
Ground lug package and installation instructions for termination
of ground wire enclosed.
Four point control terminal block, NEMA 1B with wire markers.
Breaker operators can be locked in the ON or OFF position
(combination starters only).
Four plugged 3/4” NPSM outlets drilled and tapped for control
devices.
Standard outlets top and bottom.
Plugged 1/2” outlets top and bottom for optional breather/
drain.
Components are mounted on a galvanized steel removable
pan.
Enclosures are designed to accept Cutler-Hammer ✢, or Square
D  motor starters/circuit breakers. For other manufacturers,
contact your local representative.
O-ring gasket insures watertight integrity.
Standard Materials
• Bodies and covers: copperfree (4/10 of 1%) aluminum
• Block hinges, cover bolts, handle, breaker and operator shafts:
stainless steel
• O-ring: neoprene
Standard Finish
• Corrosion resistant gray powder coat epoxy inside and out
Options
• See modifications page.
Certifications and Compliances
• UL Standards: UL 508, UL 698, UL 1203
• UL Classified: E84577
✢ Cutler-Hammer is a registered trademark of Eaton Corporation.
 Square D is a registered trademark of Schneider Electric.
428
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
AEB Series: Bolted Combination and Non-Combination Full Voltage Motor Starters
Explosionproof, Dust-Ignitionproof, Watertight
Units Provide Disconnecting Means and Undervoltage, Circuit and Motor Running Protection.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Catalog Numbering Guide
Example: The part number below depicts an Appleton, Class I, Division I, Groups B, C and D, NEMA Size 1, Bolted type, Combination Full
Voltage Nonreversing Motor Starter operating at 480 Vac, Cutler-Hammer ✢ starter w/120 Vac control voltage, and a Cutler-Hammer 7A MCP. If a breaker is not required, omit last two characters.
AE
1
B
AE Series
B
4
W
Starter Function:
A - FVNR (ATL)
B - Comb. FVNR
C - FVR
D - Comb. FVR
E - 2S1W
F - Comb. 2S1W
G - 2S2W
H - Comb. 2S2W
J - Contactor (3 pole)
K - Comb. Contactor
(3-pole)
M - Lighting Contactor
(3- thru 12-pole)
N - Comb. Lighting
Contactor (3- thru 12-pole)
Control Voltage (120V coil standard):
1 - 120 Vac
2 - 240 Vac
3 - 380 Vac
4 - 480 Vac
5 - 575 Vac
6 - 600 Vac
7 - 24 Vdc
8 - 48 Vdc
Starter Manufacturer: †
W - Cutler-Hammer
S - Square D
C - Freedom (AN16)
Bi Metal A - Freedom (AN16)
Electronic
2
▲
Suffix for Other
Options/Features:
See Modifications
Controls: Hazardous Location Motor Starters
Operating Voltage:
1 - 120 Vac
2 - 240 Vac
3 - 380 Vac
4 - 480 Vac
5 - 575 Vac
6 - 600 Vac
7 - 24 Vdc
8 - 48 Vdc
Enclosure Type:
B Series
C
Controls
NEMA Size:
0, 1, 2, 3, 4, 5
1
Breaker Manufacturer: †
C - Cutler-Hammer
S - Square D
MCP
1=3Amp
2=7Amp
3=15Amp
4=30Amp
5=50Amp
6=70Amp
7=100Amp
8=150Amp
9=250Amp
0=400Amp
Breaker Trip (Thermal Mag):
A - 15 Amp
B - 20 Amp
C - 25 Amp
D - 30 Amp
E - 35 Amp
F - 40 Amp
G - 50 Amp
H - 60 Amp
J - 70 Amp
K - 80 Amp
M - 90 Amp
N - 100 Amp
P - 125 Amp
Q - 150 Amp
R - 175 Amp
S - 200 Amp
T - 225 Amp
U - 250 Amp
V - 300 Amp
W - 350 Amp
X - 400 Amp
† Contact your local representative for other manufacturers.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
429
AEB Series Motor Starters Modifications
Explosionproof, Dust-Ignitionproof, Watertight
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Description
Suffix
Catalog
Factory Number Field
Installed
Installed
Controls
Description
Catalog Number
Field Installed
Nameplates
Operators 
Start/Stop dual push button
S3X
AEPDGRE
Stop push button
S2X
AEPRC
Start push button
S1X
AEPGA
Engraved nameplate — black letters on
white surface, 2” x 4”/50.8 x 101.6 mm,
NP
0.125”/3.18 mm letters, 3 lines max.
specify legend
Overload Heater – Provide FLA at the time of order.
Stop, lighted PB, red 120 Vac
LP5X
AEPTRE
Start, lighted PB, green 120 Vac
LP4X
AEPTGE
3 position selector switch specify legend
A3X
AESS31MN
40 Watt enclosure
space heaters
n/a
120 Vac
O-120V
AFA4327X11
240 Vac
O-240V
AFA4327X12
480 Vac
O-480V
AFA4327X13
2 position selector switch specify legend
A2X
AESS22ML
Red pilot light, 120 Vac
L5
AEPL1R
Control Terminal Blocks (Above 12 points contact your local
Green pilot light, 120 Vac
L4
AEPL1G
representative)
Red pilot light, 240 Vac
L52
AEPL2R
20 Amp, 600 Vac
8 point
8K
n/a
Green pilot light, 240 Vac
L42
AEPL2G
NEMA 1B w/wire markers
12 point
12K
n/a
Red pilot light, 480 Vac
L54
AEPL4R
Cutler-Hammer ✢ Starter Auxiliary Contacts
Green pilot light, 480 Vac
L44
AEPL4G
NEMA 4X Breather/Drain Fittings
Controls: Hazardous Location Motor Starters
Suffix
Factory
Installed
Drain fitting
Breather fitting
(Drilled and tapped installation included.)
DN
BR
Size 0-4 
DRNB4X
BRTB4X
Control Power Options 
Size 5 
1NO/1NC
X11C
AJ-11
2NO/2NC
X22C
AJ-11 (2 ea.)
1NO/1NC
X511C
A3463D94G18
X522C
A3463D94G18
(2 ea.)
1NO/1NC
X11S
A999SX8
2NO/2NC
X22S
A999SX8
(2 ea.)
2NO/2NC
Square D  Starter Auxiliary Contacts
Fused CPT, 50 Va
T1
AFCPT050
Fused CPT, 100 Va
T2
AFCPT100
Fused CPT, 200 Va
T3
AFCPT200
Fused CPT, 250 Va
T4
AFCPT250
Fused CPT, 50 Va w/interposing relay
T5
AFCPT050R
Fused CPT, 150 Va
T6
AFCPT150
Fused CPT, 300 Va
T7
AFCPT300
Fused CPT, 500 Va
T8
AFCPT500
Fused CPT, 750 Va
T9
AFCPT750
Separate control fused circuit
S-120V n/a
Specify starter coil voltage
S-240V n/a
Size 0-5 
S-480V n/a
NOTE: CPT includes primary and secondary fuses.
 Add —L to part no. for Size 5 starters.
 Size 1 and 2 150 Vac Max. Size 3 and 4 300 Vac Max.
 Contact your local representative for other voltages.
 8 Aux. Contacts Max. includes one seal-in and seven added.
 4 Aux. Contacts Max. includes one seal-in and three added.
 Size 0-1 includes one seal-in and four added. Size 2-5 includes one seal-in and three added.
✢ Cutler-Hammer is a registered trademark of Eaton Corporation.
 Square D is a registered trademark of Schneider Electric.
430
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
AEB Series Motor Starter Enclosures
Explosionproof, Dust-Ignitionproof, Watertight
Nonreversing Bolted Enclosure.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
NEMA
Size
Catalog Number ▲
Approximate Weight in
Pounds/Kilograms
Standard Conduit
(Inches)
Mounting Hardware Set
Catalog Number
Combination Full Voltage Nonreversing Enclosure Only
0
AE0BB
80/36
1
AE1BB
80/36
2
AE2BB
85/39
3
AE3BB
140/64
4
AE4BB
140/64
5
AE5BB
500/227
1-1/2
AMH7
2-1/2
4
AMH8
Full Voltage Nonreversing Enclosure Only
AE0BA
80/36
1
AE1BA
80/36
2
AE2BA
85/39
3
AE3BA
140/64
2
4
AE4BA
140/64
2-1/2
5
AE5BA
500/227
4
Controls
0
1-1/2
AMH7
Controls: Hazardous Location Motor Starters
AMH8
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
431
AEB Series Full Voltage Motor Starters
Explosionproof, Dust-Ignitionproof, Watertight
3-Phase, 60 Hertz, Nonreversing (Across the line), 120V Coil Cutler-Hammer, Bolted Enclosure.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
Controls
240
Controls: Hazardous Location Motor Starters
480
600
NEMA
Size
Maximum
Horsepower
Amp
Trip
Catalog Number ▲
Approximate
Weight in
Pounds/Kilograms
Conduit Size
(Inches)
0
3
NA
AE0BA2W1
80/36
1
7-1/2
NA
AE1BA2W1
80/36
2
15
NA
AE2BA2W1
85/39
3
30
NA
AE3BA2W1
140/64
2
4
50
NA
AE4BA2W1
140/64
2-1/2
4
Mounting Hardware Set
Catalog Number
1-1/2
AMH7
5
100
NA
AE5BA2W1
500
0
5
NA
AE0BA4W1
80/36
1
10
NA
AE1BA4W1
80/36
2
25
NA
AE2BA4W1
85/39
3
50
NA
AE3BA4W1
140/64
2
4
100
NA
AE4BA4W1
140/64
2-1/2
5
200
NA
AE5BA4W1
500/227
4
AMH8
1-1/2
AMH7
0
5
NA
AE0BA6W1
125/57
1
10
NA
AE1BA6W1
125/57
2
25
NA
AE2BA6W1
130/59
3
50
NA
AE3BA6W1
195/88
2
4
100
NA
AE4BA6W1
195/88
2-1/2
5
200
NA
AE5BA6W1
500/227
4
AMH8
1-1/2
AMH7
AMH8
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
432
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
AEB Series Combination Full Voltage Motor Starters
With Thermal Magnetic Circuit Breakers. Explosionproof, Dust-Ignitionproof, Watertight
3-Phase, 60 Hertz, Nonreversing, 120V Coil Cutler-Hammer, Bolted Enclosure.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
NEMA
Size
0
1
2
240
3
5
1
2
480
3
4
5
0
1
2
600
3
4
5
Catalog Number ▲
Approximate
Weight in
Pounds/Kilograms
2
15
AE0BB2W1CA
125/57
3
20
AE0BB2W1CB
125/57
5
40
AE1BB2W1CF
125/57
7-1/2
50
AE1BB2W1CG
125/57
10
50
AE2BB2W1CG
130/59
15
100
AE2BB2W1CL
130/59
20
100
AE3BB2W1CL
195/88
30
125
AE3BB2W1CM
195/88
40
175
AE4BB2W1CR
195/88
50
200
AE4BB2W1CS
195/88
60
250
AE5BB2W1CU
500/227
75
300
AE5BB2W1CV
500/227
100
400
AE5BB2W1CX
500/227
3
15
AE0BB4W1CA
125/57
5
20
AE0BB4W1CB
125/57
7-1/2
30
AE1BB4W1CD
125/57
10
35
AE1BB4W1CE
125/57
20
50
AE2BB4W1CG
130/59
25
70
AE2BB4W1CJ
130/59
50
100
AE3BB4W1CN
195/88
60
125
AE3BB4W1CP
195/88
75
150
AE4BB4W1CQ
195/88
100
200
AE4BB4W1CS
195/88
500/227
125
250
AE5BB4W1CU
150
300
AE5BB4W1CV
500/227
200
400
AE5BB4W1CX
500/227
5
15
AE0BB6W1CA
125/57
7-1/2
20
AE1BB6W1CB
125/57
10
30
AE1BB6W1CD
125/57
15
40
AE2BB6W1CF
130/59
25
50
AE2BB6W1CG
130/59
30
70
AE3BB6W1CJ
195/88
50
100
AE3BB6W1CN
195/88
75
125
AE4BB6W1CP
195/88
100
150
AE4BB6W1CQ
195/88
150
250
AE5BB6W1CU
500/227
200
300
AE5BB6W1CV
500/227
Conduit Size
(Inches)
Mounting Hardware Set
Catalog Number
1-1/2
AMH7
2-1/2
4
AMH8
Controls: Hazardous Location Motor Starters
0
Amp
Trip
Controls
4
Maximum
Horsepower
1-1/2
AMH7
2-1/2
4
AMH8
1-1/2
AMH7
2-1/2
4
AMH8
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
433
AEB Series Combination Full Voltage Motor Starters
With Motor Circuit Protector. Explosionproof, Dust-Ignitionproof, Watertight
3-Phase, 60 Hertz, Nonreversing, 120V Coil Cutler-Hammer, Bolted Enclosure.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
NEMA
Size
7
AE0BB2W1C2
125/57
15
AE0BB2W1C3
125/57
1
7
30
AE1BB2W1C4
125/57
2
15
50
AE2BB2W1C5
130/59
3
30
100
AE3BB2W1C7
195/88
4
50
150
AE4BB2W1C8
195/88
5
100
400
AE5BB2W1C0
500/227
1
3
AE0BB4W1C1
125/57
0
3
7
AE0BB4W1C2
125/57
Controls
Controls: Hazardous Location Motor Starters
2
3
5
15
AE0BB4W1C3
125/57
7
15
AE1BB4W1C3
125/57
10
30
AE1BB4W1C4
130/59
12
30
AE2BB4W1C4
130/59
25
50
AE2BB4W1C5
130/59
30
50
AE3BB4W1C5
195/88
50
100
AE3BB4W1C7
195/88
4
100
150
AE4BB4W1C8
195/88
5
200
400
AE5BB4W1C0
500/227
1
3
AE0BB6W1C1
125/57
0
1
600
Catalog Number ▲
Approximate
Weight in
Pounds/Kilograms
1
1
480
Amp
Trip
3
0
240
Maximum
Horsepower
2
3
4
5
3
7
AE0BB6W1C2
125/57
5
15
AE0BB6W1C3
125/57
7
15
AE1BB6W1C3
125/57
10
30
AE1BB6W1C4
125/57
20
30
AE2BB6W1C4
130/59
25
50
AE2BB6W1C5
130/59
40
50
AE3BB6W1C5
195/88
50
100
AE3BB6W1C7
195/88
60
100
AE4BB6W1C7
195/88
100
150
AE4BB6W1C8
195/88
200
400
AE5BB6W1C0
500/227
Conduit Size
(Inches)
Mounting Hardware Set
Catalog Number
1-1/2
AMH7
2-1/2
4
AMH8
1-1/2
AMH7
2-1/2
4
AMH8
1-1/2
AMH7
2-1/2
4
AMH8
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
434
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
AEB Series Full Voltage Motor Starters
Explosionproof, Dust-Ignitionproof, Watertight
3-Phase, 60 Hertz, Reversing, 120V Coil Cutler-Hammer, Bolted Enclosure.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
240
480
Amp
Trip
Catalog Number ▲
Approximate
Weight in
Pounds/Kilograms
0
3
NA
AE0BC2W1
115/52
1
7-1/2
NA
AE1BC2W1
115/52
2
15
NA
AE2BC2W1
125/57
3
30
NA
AE3BC2W1
300/136
2
4
50
NA
AE4BC2W1
300/136
2-1/2
0
5
NA
AE0BC4W1
115/52
1
10
NA
AE1BC4W1
115/52
2
25
NA
AE2BC4W1
125/57
3
50
NA
AE3BC4W1
300/136
2
4
100
NA
AE4BC4W1
300/136
2-1/2
0
5
NA
AE0BC6W1
115/52
1
10
NA
AE1BC6W1
115/52
2
25
NA
AE2BC6W1
125/57
3
50
NA
AE3BC6W1
300/136
2
4
100
NA
AE4BC6W1
300/136
2-1/2
Conduit Size
(Inches)
Mounting Hardware Set
Catalog Number
1-1/2
AMH7
1-1/2
1-1/2
AMH8
AMH7
Controls
600
Maximum
Horsepower
NEMA
Size
AMH8
AMH7
Controls: Hazardous Location Motor Starters
AMH8
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
435
AEB Series Combination Full Voltage Motor Starters
With Thermal Magnetic Circuit Breaker. Explosionproof Dust-Ignitionproof, Watertight
3-Phase, 60 Hertz, Reversing, 120V Coil Cutler-Hammer Bolted Enclosure.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
NEMA
Size
0
1
240
2
Controls
3
4
0
Controls: Hazardous Location Motor Starters
1
480
2
3
4
0
1
600
2
3
4
Maximum
Horsepower
Amp
Trip
Catalog Number ▲
Approximate
Weight in
Pounds/
Kilograms
2
15
AE0BD2W1CA
120/54
3
20
AE0BD2W1CB
120/54
5
35
AE1BD2W1CE
120/54
7-1/2
50
AE1BD2W1CG
120/54
10
50
AE2BD2W1CG
135/61
15
100
AE2BD2W1CN
135/61
20
100
AE3BD2W1CN
320/145
30
125
AE3BD2W1CP
320/145
50
200
AE4BD2W1CS
320/145
3
15
AE0BD4W1CA
120/54
5
20
AE0BD4W1CB
120/54
7-1/2
30
AE1BD4W1CD
120/54
10
35
AE1BD4W1CE
120/54
20
50
AE2BD4W1CG
135/61
25
70
AE2BD4W1CJ
135/61
50
100
AE3BD4W1CN
320/145
60
125
AE3BD4W1CP
320/145
75
150
AE4BD4W1CQ
320/145
100
200
AE4BD4W1CS
320/145
5
15
AE0BD6W1CA
120/54
7-1/2
20
AE1BD6W1CB
120/54
10
30
AE1BD6W1CD
120/54
15
40
AE2BD6W1CF
135/61
25
50
AE2BD6W1CG
135/61
30
70
AE3BD6W1CJ
320/145
50
100
AE3BD6W1CN
320/145
75
125
AE4BD6W1CP
320/145
100
150
AE4BD6W1CQ
320/145
Conduit Size
(Inches)
Mounting Hardware Set
Catalog Number
1-1/2
AMH7
2-1/2
AMH8
1-1/2
AMH7
2-1/2
AMH8
1-1/2
AMH7
2-1/2
AMH8
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
436
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
AEB Series Combination Full Voltage Motor Starters
With Motor Circuit Protector. Explosionproof, Dust-Ignitionproof, Watertight
3-Phase, 60 Hertz, Reversing, 120V Coil Cutler-Hammer Bolted Enclosure.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
NEMA
Size
Catalog Number ▲
Approximate
Weight in
Pounds/Kilograms
7
AE0BD2W1C2
120/54
15
AE0BD2W1C3
120/54
1
7
30
AE1BD2W1C4
120/54
2
15
50
AE2BD2W1C5
135/61
3
30
100
AE3BD2W1C7
320/145
4
50
150
AE4BD2W1C8
320/145
1
3
AE0BD4W1C1
120/54
3
7
AE0BD4W1C2
120/54
5
15
AE0BD4W1C3
120/54
1
480
2
15
AE1BD4W1C3
120/54
30
AE1BD4W1C4
135/61
15
30
AE2BD4W1C4
135/61
25
50
AE2BD4W1C5
135/61
30
50
AE3BD4W1C5
320/145
50
100
AE3BD4W1C7
320/145
4
100
150
AE4BD4W1C8
320/145
1
3
AE0BD6W1C1
120/54
0
3
7
AE0BD6W1C2
120/54
5
15
AE0BD6W1C3
120/54
1
2
3
4
7
15
AE1BD6W1C3
120/54
10
30
AE1BD6W1C4
120/54
20
30
AE2BD6W1C4
135/61
25
50
AE2BD6W1C5
135/61
40
50
AE3BD6W1C5
320/145
50
100
AE3BD6W1C7
320/145
60
100
AE4BD6W1C7
320/145
100
150
AE4BD6W1C8
320/145
Mounting Hardware Set
Catalog Number
1-1/2
AMH7
2-1/2
AMH8
1-1/2
AMH7
2-1/2
AMH8
1-1/2
AMH7
2-1/2
AMH8
Controls: Hazardous Location Motor Starters
3
7
10
Conduit Size
(Inches)
Controls
1
0
600
Amp
Trip
3
0
240
Maximum
Horsepower
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
Contact your local representative for size of enclosure.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
437
AEB Series Full Voltage Motor Starters
Explosionproof, Dust-Ignitionproof, Watertight
Two Speed Single Winding, 5 Pole-3-Pole, 3-Phase, 60 Hertz, 120V Coil, Cutler-Hammer.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
240
Controls
480
Controls: Hazardous Location Motor Starters
600
Maximum
Horsepower
Amp
Trip
Catalog Number ▲
Approximate
Weight in
Pounds/Kilograms
0
3
NA
AE0BE2W1
85/39
1
7-1/2
NA
AE1BE2W1
85/39
2
15
NA
AE2BE2W1
190/86
3
30
NA
AE3BE2W1
540/245
2
4
50
NA
AE4BE2W1
540/245
2-1/2
0
5
NA
AE0BE4W1
85/39
1
10
NA
AE1BE4W1
85/39
2
25
NA
AE2BE4W1
190/86
3
50
NA
AE3BE4W1
540/245
2
4
100
NA
AE4BE4W1
540/245
2-1/2
0
5
NA
AE0BE6W1
85/39
1
10
NA
AE1BE6W1
85/39
2
25
NA
AE2BE6W1
190/86
3
50
NA
AE3BE6W1
540/245
2
4
100
NA
AE4BE6W1
540/245
2-1/2
NEMA
Size
Conduit Size
(Inches)
Mounting Hardware Set
Catalog Number
1-1/2
AMH7
1-1/2
1-1/2
AMH8
AMH7
AMH8
AMH7
AMH8
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
438
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
AEB Series Combination Full Voltage Motor Starters
With Thermal Magnetic Circuit Breaker. Explosionproof, Dust-Ignitionproof, Watertight
Two Speed Single Winding, 5 Pole - 3-Pole, 3-Phase, 60 Hertz, 120V Coil Cutler-Hammer.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
240
480
Approximate
Weight in
Pounds/Kilograms
Maximum
Horsepower
Amp
Trip
0
3
20
AE0BF2W1CB
130/59
1
7-1/2
50
AE1BF2W1CG
130/59
2
15
100
AE2BF2W1CN
195/88
3
30
125
AE3BF2W1CP
545/247
4
50
200
AE4BF2W1CS
545/247
0
5
20
AE0BF4W1CB
130/59
1
10
40
AE1BF4W1CF
130/59
2
25
70
AE2BF4W1CJ
195/88
3
50
100
AE3BF4W1CN
545/247
4
100
200
AE3BF4W1CS
545/247
0
5
20
AE0BF6W1CB
130/59
1
10
30
AE1BF6W1CD
130/59
Catalog Number ▲
25
50
AE2BF6W1CG
195/88
50
100
AE3BF6W1CN
545/247
4
100
150
AE3BF6W1CQ
545/247
Mounting Hardware Set
Catalog Number
1-1/2
AMH7
2-1/2
AMH8
1-1/2
AMH7
2-1/2
AMH8
1-1/2
AMH7
2-1/2
AMH8
Controls: Hazardous Location Motor Starters
2
3
Conduit Size
(Inches)
Controls
600
NEMA
Size
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
439
AEB Series Combination Full Voltage Motor Starters
With Motor Circuit Protector. Explosionproof, Dust-Ignitionproof, Watertight
Two Speed Single Winding, 5 Pole - 3-Pole, 3-Phase, 60 Hertz, 120V Coil Cutler-Hammer.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
Amp
Trip
Catalog Number ▲
Approximate
Weight in
Pounds/Kilograms
1
7
AE0BF2W1C2
130/59
3
15
AE0BF2W1C3
130/59
1
7-1/2
30
AE1BF2W1C4
130/59
2
15
50
AE2BF2W1C5
195/88
3
30
100
AE3BF2W1C7
545/247
4
50
150
AE4BF2W1C8
545/247
1
3
AE0BF4W1C1
130/59
3
7
AE0BF4W1C2
130/59
5
15
AE0BF4W1C3
125/57
7-1/2
15
AE1BF4W1C3
125/57
10
30
AE1BF4W1C4
130/59
15
30
AE2BF4W1C4
195/88
25
50
AE2BF4W1C5
195/88
30
50
AE3BF4W1C5
545/247
NEMA
Size
0
240
Controls
0
1
480
Controls: Hazardous Location Motor Starters
2
3
4
0
1
600
2
3
4
Maximum
Horsepower
50
100
AE3BF4W1C7
545/247
100
150
AE4BF4W1C8
545/247
1
3
AE0BF6W1C1
130/59
3
7
AE0BF6W1C2
130/59
5
15
AE0BF6W1C3
130/59
7-1/2
15
AE1BF6W1C3
130/59
10
30
AE1BF6W1C4
130/59
20
30
AE2BF6W1C4
195/88
25
50
AE2BF6W1C5
195/88
40
50
AE3BF6W1C5
545/247
50
100
AE3BF6W1C7
545/247
60
100
AE4BF6W1C7
545/247
100
150
AE4BF6W1C8
545/247
Conduit Size
(Inches)
Mounting Hardware Set
Catalog Number
1-1/2
AMH7
2-1/2
AMH8
1-1/2
AMH7
2-1/2
AMH8
1-1/2
AMH7
2-1/2
AMH8
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
440
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
AEB Series Full Voltage Motor Starters
Explosionproof, Dust-Ignitionproof, Watertight
Two Speed Two Winding, 3-Pole-3-Pole, 3-Phase, 60 Hertz, 120V Coil, Cutler-Hammer.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
240
480
Catalog Number ▲
Approximate Weight
in Pounds/Kilograms
Conduit Size
(Inches)
Mounting Hardware Set
Catalog Number
0
3
AE0BG2W1
85/39
1
7-1/2
AE1BG2W1
85/39
2
15
AE2BG2W1
190/86
1-1/2
AMH7
3
30
AE3BG2W1
540/245
2
4
50
AE4BG2W1
540/245
2-1/2
0
5
AE0BG4W1
85/39
1
10
AE1BG4W1
85/39
2
25
AE2BG4W1
190/86
3
50
AE3BG4W1
540/245
2
4
100
AE4BG4W1
540/245
2-1/2
0
5
AE0BG6W1
85/39
1
10
AE1BG6W1
85/39
2
25
AE2BG6W1
190/86
3
50
AE3BG6W1
540/245
2
4
100
AE4BG6W1
540/245
2-1/2
1-1/2
1-1/2
AMH8
AMH7
AMH8
AMH7
AMH8
Controls: Hazardous Location Motor Starters
Maximum
Horsepower
Controls
600
NEMA
Size
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
441
AEB Series Combination Full Voltage Motor Starters
With Thermal Magnetic Circuit Breakers. Explosionproof, Dust-Ignitionproof, Watertight
Two Speed Two Winding, 3-Pole - 3-Pole, 3-Phase, 60 Hertz, 120V Coil Cutler-Hammer.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
240
Controls
480
Controls: Hazardous Location Motor Starters
600
NEMA
Size
Approximate
Weight in
Pounds/Kilograms
Maximum
Horsepower
Amp
Trip
0
3
20
AE0BH2W1CB
130/59
1
7-1/2
50
AE1BH2W1CG
130/59
Catalog Number ▲
2
15
100
AE2BH2W1CN
195/88
3
30
125
AE3BH2W1CP
545/247
4
50
200
AE4BH2W1CS
545/247
0
5
20
AE0BH4W1CB
130/59
1
10
40
AE1BH4W1CF
130/59
2
25
70
AE2BH4W1CJ
195/88
3
50
100
AE3BH4W1CN
545/247
4
100
200
AE3BH4W1CS
545/247
0
5
20
AE0BH6W1CB
130/59
1
10
30
AE1BH6W1CD
130/59
2
25
50
AE2BH6W1CG
195/88
3
50
100
AE3BH6W1CN
545/247
4
100
150
AE3BH6W1CQ
545/247
Conduit Size
(Inches)
Mounting Hardware Set
Catalog Number
1-1/2
AMH7
2-1/2
AMH8
1-1/2
AMH7
2-1/2
AMH8
1-1/2
AMH7
2-1/2
AMH8
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
442
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
AEB Series Combination Full Voltage Motor Starters
With Motor Circuit Protector. Explosionproof, Dust-Ignitionproof, Watertight
Two Speed Two Winding, 3-Pole - 3-Pole, 3-Phase, 60 Hertz, 120V Coil Cutler-Hammer.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
NEMA
Size
0
240
Amp
Trip
Catalog Number ▲
1
7
AE0BH2W1C2
130/59
15
AE0BH2W1C3
130/59
7-1/2
30
AE1BH2W1C4
130/59
2
15
50
AE2BH2W1C5
195/88
3
30
100
AE3BH2W1C7
545/247
4
50
150
AE4BH2W1C8
545/247
1
3
AE0BH4W1C1
130/59
3
7
AE0BH4W1C2
130/59
1
480
2
4
0
1
2
3
4
15
AE0BH4W1C3
125/57
15
AE1BH4W1C3
125/57
10
30
AE1BH4W1C4
130/59
15
30
AE2BH4W1C4
195/88
25
50
AE2BH4W1C5
195/88
30
50
AE3BH4W1C5
545/247
50
100
AE3BH4W1C7
545/247
100
150
AE4BH4W1C8
545/247
1
3
AE0BH6W1C1
130/59
3
7
AE0BH6W1C2
130/59
5
15
AE0BH6W1C3
130/59
7-1/2
15
AE1BH6W1C3
130/59
10
30
AE1BH6W1C4
130/59
20
30
AE2BH6W1C4
195/88
25
50
AE2BH6W1C5
195/88
40
50
AE3BH6W1C5
545/247
50
100
AE3BH6W1C7
545/247
60
100
AE4BH6W1C7
545/247
100
150
AE4BH6W1C8
545/247
Mounting Hardware Set
Catalog Number
1-1/2
AMH7
2-1/2
AMH8
1-1/2
AMH7
2-1/2
AMH8
1-1/2
AMH7
2-1/2
AMH8
Controls: Hazardous Location Motor Starters
3
5
7-1/2
Conduit Size
(Inches)
Controls
3
1
0
600
Maximum
Horsepower
Approximate
Weight in
Pounds/
Kilograms
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
443
AEB Series Combination Lighting Contactor
With Thermal Magnetic Breaker. Explosionproof, Dust-Ignitionproof, Watertight
3-Pole, 60 Hertz, 120V Coil Cutler-Hammer.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
120
Controls
240
Controls: Hazardous Location Motor Starters
480
600
NEMA
Size
Maximum
Horsepower
Amp
Trip
Catalog Number ▲
Approximate
Weight in
Pounds/
Kilograms
1
30
40
AE1BN1W1CF
125/57
2
60
70
AE2BN1W1CJ
130/59
3
100
125
AE3BN1W1CP
195/88
4
200
225
AE4BN1W1CT
195/88
5
400
450
AE5BN1W1CZ
560/254
1
30
40
AE1BN2W1CF
125/57
2
60
70
AE2BN2W1CJ
130/59
3
100
125
AE3BN2W1CP
195/88
4
200
225
AE4BN2W1CT
195/88
5
400
450
AE5BN2W1CZ
560/254
1
30
40
AE1BN4W1CF
125/57
2
60
70
AE2BN4W1CJ
130/59
3
100
125
AE3BN4W1CP
195/88
4
200
225
AE4BN4W1CT
195/88
5
400
450
AE5BN4W1CZ
560/254
1
30
40
AE1BN6W1CF
125/57
2
60
70
AE2BN6W1CJ
130/59
3
100
125
AE3BN6W1CP
195/88
4
200
225
AE4BN6W1CT
195/88
5
400
450
AE5BN6W1CZ
560/254
Conduit Size
(Inches)
Mounting Hardware Set
Catalog Number
1-1/2
AMH7
2-1/2
4
AMH8
1-1/2
AMH7
2-1/2
4
AMH8
1-1/2
AMH7
2-1/2
4
AMH8
1-1/2
AMH7
2-1/2
4
AMH8
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
444
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
AEB Series Lighting Contactor
Explosionproof, Dust-Ignitionproof, Watertight
3-Pole, 60 Hertz, 120V Coil Cutler-Hammer.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Line
Voltage
120
240
Amp
Trip
Approximate
Weight in
Pounds/Kilograms
Conduit Size
(Inches)
1
30
AE1BM1W1
125/57
2
60
AE2BM1W1
130/59
3
100
AE3BM1W1
195/88
2
Mounting Hardware Set
Catalog Number
1-1/2
4
200
AE4BM1W1
195/88
2-1/2
5
400
AE5BM1W1
560/254
4
1
30
AE1BM2W1
125/57
2
60
AE2BM2W1
130/59
3
100
AE3BM2W1
195/88
2
4
200
AE4BM2W1
195/88
2-1/2
5
400
AE5BM2W1
560/254
4
1
30
AE1BM4W1
125/57
2
60
AE2BM4W1
130/59
3
100
AE3BM4W1
195/88
2
4
200
AE4BM4W1
195/88
2-1/2
5
400
AE5BM4W1
560/254
4
1
30
AE1BM6W1
125/57
2
60
AE2BM6W1
130/59
3
100
AE3BM6W1
195/88
2
4
200
AE4BM6W1
195/88
2-1/2
5
400
AE5BM6W1
560/254
4
AMH7
AMH8
1-1/2
AMH7
AMH8
1-1/2
AMH7
Controls: Hazardous Location Motor Starters
600
Maximum
Horsepower
Controls
480
NEMA
Size
AMH8
1-1/2
AMH7
AMH8
▲ To complete the catalog number please add the appropriate suffix for other options/features. Suffixes, see AEB Series Motor Starters Modifications.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
445
AEB Series Motor Starter Enclosure Typical Wiring Diagram
Explosionproof, Dust-Ignitionproof, Watertight
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Typical Wiring Diagram for Size 5 and 6 — Starter Only and Combination
CB
CT
CT
M
M
T1
L1
M
L2
M
M
T2
L2
MOTOR
M
T3
L3
T1
L1
T2
OL
OL
L1
MOTOR
T3
L3
L1
L2
COMBINATION STARTER
L2
NON-COMBINATION STARTER
L1
START
STOP
1
2
R
1
3
2
RUN
F
F
F
H4
OL'S
( SEE LEFT FOR CONTROL OPTIONS )
M
M
G
3
REMOTE
2-WIRE CONTROL ( H-O-A SEL SW)
H3
H1
CPT
F
X2
R
STOP
SPACE HEATER
2
H2
X2
X1
AUTO
1
Controls
CR
M
F
M
OFF
F
CR
(FOR SEPERATE 208V AND OVER ADD FUSE )
3
3-WIRE CONTROL (START & STOP )
HAND
L2
F
120V SEPARATE CONTROL
1
2
CR
3
M
G
FULL VOLTAGE CONTROL
FOR 120V STARTER COIL
CONTROL OPTIONS
M
4
X2
STOP
SPACE HEATER
M
5
8
7
10
M
6
FULL VOLTAGE CONTROL
FOR 480V STARTER COIL
RUN
OL'S
( SEE LEFT FOR CONTROL OPTIONS )
9
M
11
WIRING DIAGRAM
SIZE 5 & 6
CFVNR and FVNR MOTOR STARTER
Controls: Hazardous Location Motor Starters
X11 = 1NO-1NC
X22 = 2NO-2NC
AUX CONTACTS
446
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
AEB Series Motor Starter Enclosure Typical Wiring Diagram
Explosionproof, Dust-Ignitionproof, Watertight
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Typical Wiring Diagram for Size 1 Thru 4 — Starter Only and Combination — Reversing
L1
L1
L1
L2
L2
L3
L3
L2
L3
L1
OL
R
L1
R
OL
R
OL
T1
T2
F
H4 H2 H3 H1
MOTOR
T3
CPT
F
L2
1
F
NON-COMBINATION STARTER
L2
L2
L1
OL'S
F
X2
REVERSE
F
6
F
R
F
G
STOP
SPACE HEATER
X2
TRANSFORMER CONTROL
REVERSE
4
R
OL'S
F
4
3
2
R
R
F
R
3
R
4
5
FORWARD
( SEE LEFT FOR CONTROL OPTIONS )
REVERSE
3
120V SEPARATE CONTROL
F
FORWARD
2
2
(FOR 240V AND OVER ADD FUSE )
L2
1
STOP
FORWARD
A
COMBINATION STARTER
1
X2
F
L3
L3
X1
R
1
L1
F
( SEE LEFT FOR CONTROL OPTIONS )
F
CB
L1
L2
F
A
F
F
Controls
R
6
5
REVERSE
FORWARD
R
5
6
F
R
R
G
STOP
SPACE HEATER
SEPARATE CONTROL
CONTROL OPTIONS
R
F
7
8
11
10
13
12
FULL VOLTAGE REVERSING
14
COMBINATION AND NON-COMBINATION
MOTOR STARTER
R
F
9
SIZE 1 thru 4
AUX CONTACTS
Controls: Hazardous Location Motor Starters
X11 = 1NO-1NC
X22 = 2NO-2NC
Typical Wiring Diagram for Size 1 Thru 4 — Starter Only and Combination — 2 Speed, Single Winding
L1
S
OL
S
OL
S
OL
L1
L2
L2
L2
L3
L3
L3
L2
T1
L1
L1
T2
F
F
T3
H4
H2
H3
H1
S
CPT
L1
L2
S
NON-COMBINATION STARTER
CB
L1
L1
L2
L2
MOTOR
F
OL
F
OL
F
OL
1
T6
F
X1
X2
R
T4
1
3
2
F
A
F
R
3
2
F
SLOW
F
3
S
G
STOP
SPACE HEATER
TRANSFORMER CONTROL
SLOW
4
F
S
X2
F
4
FAST
S
S
OL'S OL'S
S
2
6
F
FAST
( SEE LEFT FOR CONTROL OPTIONS )
1
STOP
X2
SLOW
F
5
(FOR 240V AND OVER ADD FUSE )
L2
COMBINATION STARTER
1
S
F
4
T5
120V SEPARATE CONTROL
L1
F
OL'S OL'S
S
L3
L3
FAST
( SEE LEFT FOR CONTROL OPTIONS )
A
F
F
5
6
SLOW
FAST
S
S
5
6
F
S
S
G
STOP
SPACE HEATER
CONTROL OPTIONS
S
F
7
8
11
10
13
F
9
X11 = 1NO-1NC
X22 = 2NO-2NC
SEPARATE CONTROL
12
S
14
AUX CONTACTS
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
2 SPEED - SINGLE WINDING
COMBINATION AND NON-COMBINATION
MOTOR STARTER
SIZE 1 thru 4
447
AEB Series Motor Starter Enclosure Typical Wiring Diagram
Explosionproof, Dust-Ignitionproof, Watertight
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG
Typical Wiring Diagram for Size 1 Thru 4 — Starter Only and Combination — 2 Speed, 2 Winding
L2
L1
L1
L1
L2
L2
L3
L3
L1
L1
L2
L3
F
OL
F
OL
T2
F
OL
T3
H4 H2 H3 H1
CPT
OL
S
OL
T12
S
OL
T13
MOTOR
T11
F
X1
X2
R
2
1
F
3
F
A
4
120V SEPARATE CONTROL
F
STOP
1
2
OL'S
F
3
F
3
S
G
STOP
SPACE HEATER
TRANSFORMER CONTROL
X2
SLOW
F
A
OL'S
F
SLOW
SPEED
Controls
F
R
S
2
F
FAST
( SEE LEFT FOR CONTROL OPTIONS )
FAST
SPEED
S
5
S
(FOR 240V AND OVER ADD FUSE )
L2
COMBINATION STARTER
1
OL'S
F
L3
L1
X2
SLOW
L2
L2
OL'S
S
L1
L3
FAST
( SEE LEFT FOR CONTROL OPTIONS )
CB
L1
F
F
S
L2
NON-COMBINATION STARTER
T1
4
S
5
4
S
5
S
F
S
G
STOP
SPACE HEATER
CONTROL OPTIONS
SEPARATE CONTROL
F
7
10
9
12
11
F
COMBINATION AND NON-COMBINATION
MOTOR STARTER
S
8
Controls: Hazardous Location Motor Starters
2 SPEED - 2 WINDING
S
6
X11 = 1NO-1NC
X22 = 2NO-2NC
2
13
SIZE 1 thru 4
AUX CONTACTS
Typical Wiring Diagram for Lighting Contactor — 30 Amp thru 400 Amp — Starter Only and Combination
NON-COMBINATION CONTACTOR
COMBINATION LTG. CONTACTOR
CB
C
C
L1
L1
C
L2
C
L2
C
C
L3
L3
L1
L1
L2
L2
L2
L1
120V SEPARATE CONTROL
(FOR 208V AND OVER ADD FUSE )
ON
OFF
F
1
F
F
F
(SEE TAP CHART ON XFMR)
H4
3
2-POSITION SELECTOR SWITCH CONTROL
HAND
OFF
R
ON
F
1
C
3
H3
H1
CPT
AUTO
1
H2
X2
PC
HAND
OFF
X1
X2
ON
R
AUTO
2
1
ON
OFF
1
C
3
X2
PC
PC
2
3
2
C
M
G
SPACE HEATER
PUSHBUTTON CONTROL
OFF
PC
C
G
OFF
SPACE HEATER
FULL VOLTAGE CONTROL
CONTROL OPTIONS
M
4
5
8
7
10
M
6
TRANSFORMER CONTROL
M
9
M
11
LIGHTING CONTACTOR
COMBINATION AND NON-COMBINATION
X11 = 1NO-1NC
X22 = 2NO-2NC
30AMP thru 400AMP
AUX CONTACTS
448
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
AEB Series Combination Full Voltage Motor Starter Enclosure Dimensions
3.125
Explosionproof, Dust-Ignitionproof, Watertight
CL
2.380
8.875
MTG.
3.125
7.00
2.380
1/2" NPT
FOR BREATHER
1 1/2" NPT
CL
TOP VIEW
CL
3.125
Enclosure Layout for Size 0, 1 and 2 — Starter Only
16.625
2.380
RESET
1/2" NPT
FOR BREATHER1/2" NPT
FOR BREATHER
CL
10 x 12
14.125
FRONT VIEW
2.380
RESET
RESET
10 x 12
7.00
1 1/2" NPT
10 x 12
16.625
RESET
Front View
10 x 12
0.750
14.125
FRONT VIEW
11.062
12.19
7.00
BottomCL View
27.620
TOP VIEW
CL
3.13
2.38
19.44
3.13
RESET
19.44
CL
1/2" NPT
FOR DRAIN
14.125
0.75
TOP VIEW
CL
19.25 MTG.
LEFT VIEW
9.69
9.69
11.38
0.75
11.38
LEFT VIEW
Left Side View
LEFT VIEW
0.75
14.125
14.125
FRONT VIEW
FRONT VIEW
Front View
3.75
19.25 MTG.
12.19
CL 12.25 MTG.
2.38
CL
TOP VIEW
2" NPT
31.63
BOTTOM VIEW
2.38
1" NPT
1/2" NPT
FOR BREATHER
2 1/2" NPT
2.38
COVER OPEN 130°
CL
2.38
1/2" NPT
FOR DRAIN
3.75
14.125
FRONT VIEW
2" NPT
BOTTOM VIEW
Bottom View
3.13
3.13
CL
COVER OPEN 90°
0.75
1" NPT
2" NPT
7.19
9.69
11.38
COVER OPEN 130°
19.44
Enclosure Layout for Size 4 — Starter Only
7.69VIEW
LEFT
12.25 MTG.
TopBOTTOM
ViewVIEW
RESET
7.69
12.19
12.25 MTG.
2" NPT
BOTTOM
VIEW
1" NPT
1/2" NPT
FOR DRAIN
2.38
COVER OPEN 90°
2.38
2.38
COVER OPEN 90° COVER OPEN 90°
27.620
12.1912.25 MTG.
12.19
COVER OPEN 130° COVER OPEN 130°
1"
NPT
7.69
7.19
1/2" NPT
FOR DRAIN
FRONT VIEW
7.19
7.19
CL
3.75
11.38
3.13
9.69
3.13
2" NPT
3.13
RESET
RESET
7.00
1/2" NPT
FOR BREATHER
19.44
3.13
19.25 MTG.
TOP VIEW
1/2" NPT
FOR
BREATHER
1 " NPT
1 1/2" NPT
TOP VIEW
27.620
27.620
1/2" NPT
FOR BREATHER
2" NPT
2.380
RESET
2 1/2" NPT
3.75
2 1/2" NPT
7.69
CL
TOP VIEW
23.88
31.63
0.75
10.56
18.13
CL
3.75
12.19
LEFT VIEW
2 1/2" NPT
RESET
RESET
1/2" NPT
FOR BREATHER
FRONT VIEW
3.75
19.25 MTG.
19.25 MTG.
TOP VIEW
2.38
31.63
1/2" NPT
1/2" NPT
FOR BREATHER
FOR BREATHER
1/2" NPT
FOR DRAIN
7.69
COVER OPEN 90°
19.25 MTG.
TOP VIEW
2 1/2" NPT
23.88
23.88
FRONT VIEW
Left Side View
10.56
Front View
0.75
18.13
7.69
7.69
COVER OPEN 90°
COVER OPEN 90°
3.75
CL
CL
FRONT VIEW
12.19
LEFT VIEW
18.13
3.75
RESET
1/2" NPT
FOR DRAIN
COVER OPEN 130°
1" NPT
BOTTOM VIEW
1/2" NPT
FOR DRAIN
Top View
Bottom View
2 1/2" NPT
2 1/2" NPT
23.88
16.25 MTG.
15.06
16.25 MTG.
15.06
COVER OPEN 130°
1/2" NPT
CL BOTTOM VIEW
COVER OPEN 130°
1"BOTTOM
NPT
FOR DRAIN
VIEW
1" NPT
FRONT VIEW
3.75
LEFT VIEW
LEFT VIEW
18.13
3.75
0.75
0.75
3.75
12.19
12.19
3.75
10.56
10.56
16.25 MTG.
15.06
31.63
7.69
COVER OPEN 90°
2 1/2" NPT
16.25 MTG.
15.06
COVER OPEN 130°
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
1" NPT
BOTTOM VIEW
449
Controls: Hazardous Location Motor Starters
19.25 MTG.
19.25 MTG.
2" NPT
2.38
19.44
1 " NPT
1/2" NPT
FOR DRAIN
12.250
MTG.
1/2"
NPT
FOR BREATHER
BOTTOM VIEW
COVER OPEN 130°
2" NPT
1 " NPT
BOTTOM VIEW
1 1/2" NPT
1/2" NPT
FOR DRAIN
2.380
COVER OPEN 90°
7.00
COVER OPEN 130°
19.44
Top View
6.56
2.380
6.56
COVER OPEN 90°
COVER OPEN 90°
12.19
12.250 MTG.
12.19
12.250 MTG.
1 " NPT
COVER OPEN 130°
CLCL
VIEW
CL
COVER OPEN BOTTOM
130°
BOTTOM VIEW
1 1/2" NPT
1 1/2" NPT
2.38
2.38
7.00
6.56
3.13
Enclosure Layout for Size 3 — Starter Only
1/2" NPT
FOR DRAIN
Controls
9.50
LEFT VIEW
19.44
CL
2.380
12.250 MTG.
3.13
Left Side View
CL
3.125
14.125
FRONT VIEW
1/2" NPT
FOR DRAIN
6.56
12.19
3.125
FRONT VIEW
3.125
0.750
11.062
3.13
3.125
9.50
LEFT VIEW
19.44
COVER OPEN 90°
TOP VIEW
14.125
3.125
0.750
3.125
9.50
8.875
11.062
MTG.
LEFT VIEW
1/2" NPT
FOR BREATHER
CL
3.125
LEFT VIEW
16.625
0.750
TOP VIEW
3.125
11.062
16.625
8.875
MTG.
1 1/2" NPT
9.50
TOP VIEW
3.13
8.875
MTG.
7.00
3.125
1 1/2" NPT
7.00
AEB Series Full Voltage Motor Starter Enclosure Dimensions
Explosionproof, Dust-Ignitionproof, Watertight
CL
4.50
Enclosure Layout for Size 5 — Starter Only
3.50
CL
10.60
4.50
CL
4.50
3.50
10.60
10.60
1/2" NPT
FOR BREATHER
1/2" NPT
FOR BREATHER
4" NPT
TOP VIEW
4.50
RESET
34.00
3.50
46.00
4.50
RESET
4" NPT
CL
0.75
4.50
9.56
LEFT VIEW COVER OPEN 90°
9.56
COVER OPEN 90°21.50
26.13
0.75
LEFT VIEW
46.00
26.13
LEFT VIEW
COVER OPEN 130°
21.50
FRONT VIEW
FRONT VIEW
Left Side View
CL 4.50
0.75TOP VIEW
4.50
COVER OPEN 130°
FRONT VIEW
22.50 MTG.3.50
1" NPT
22.50 MTG.
1" NPT
4.50
16.56
0.75
LEFT VIEW
21.50
2.38
FRONT VIEW
12.00
1/2" NPT
FOR BREATHER
1 1/2" NPT
3.13
4" NPT
BOTTOM VIEW
ON
OFF
19.25 MTG.
7.00
ON
OFF
1 1/2" NPT
OFF
TOP VIEW
3.13
7.00
CL
19.25 MTG.
TOP VIEW
1/2" NPT
1/2" NPT
FOR BREATHERFOR BREATHER
ON
TOP VIEW
27.63
2.38
RESET
19.44
27.63
3.13
27.63
12.00
OFF
LEFT VIEW
7.19
11.38 0.75
0.75
Left Side View
TOP VIEW
19.44
CL
14.131/2" NPT
FOR DRAIN
Front View
FRONT VIEW
2.38
FRONT VIEW
COVER OPEN 90°
FRONT VIEW
12.19
COVER OPEN 130°
1" NPT
2.38
2.38
CL
OFF
12.25 MTG.
3.75
19.25 MTG.
14.13
LEFT VIEW
1 1/2" NPT
CL
Bottom View
2.38
1/2" NPT
FOR BREATHER
2.38
3.75
0.75
1 1/2" NPT
BOTTOM VIEW
2 1/2" NPT
7.19
9.69
12.88
7.69
12.25 MTG.
1/2" NPT
FOR DRAIN
3.13
3.13
CL
1/2" NPT
FOR DRAIN
2.38
12.19
COVER OPEN 130°
1" NPT
19.44
Enclosure Layout for Size 3 and 4 — Combination
11.38
7.19
COVER OPEN 90°
Top View
7.69
CL
2.38
12.19
12.19
12.25 MTG.
12.25 MTG. 1 1/2" NPT
COVER OPEN 130°
COVER OPEN 130°
1" NPT
1" NPT
BOTTOM VIEW BOTTOM VIEW
12.88
RESET
12.88
7.69
1/2" NPT
FOR DRAIN
FRONT VIEW
7.19
COVER OPEN 90°
COVER OPEN 90°
14.13
14.13
27.63
LEFT VIEW
CL
3.13
0.75
ON
9.69
11.38
3.13
11.38
3.13
1 1/2" NPT
RESET
9.69
9.69
LEFT VIEW
1/2" NPT
FOR BREATHER
19.44
3.13
RESET
7.00
19.25 MTG.
3.50
22.50 MTG.
1" NPT
7.00
2.38
CL
12.00
1 1/2" NPT
19.25 MTG.
2.38
COVER OPEN 130°
CL
Bottom View
1/2" NPT
FOR DRAIN
4.50
CL
3.13
9.56
12.00
COVER OPEN 90°
26.13
4" NPT
BOTTOM VIEW
34.00
CL
Enclosure Layout
for Size 0, 1 and 2 — Combination
14.94
22.50 MTG.
1" NPT
4" NPT
Top View
RESET
3.50
21.50
BOTTOM VIEW 4" NPT
BOTTOM VIEW
Front View
9.56
COVER OPEN 90°
COVER OPEN 130°
3.50
4.50
3.13
14.94
16.56
1/2" NPT 34.00
FOR BREATHER
1/2" NPT
34.00
FOR DRAIN
1/2" NPT
4.50
FOR DRAIN
26.13
3.75
27.50 MTG.
14.94
16.56
1/2" NPT
FOR DRAIN
CL
14.94
16.56
Controls
46.00
TOP VIEWCL
RESET
Controls: Hazardous Location Motor Starters
TOP VIEW
3.13
27.50 MTG.
27.50 MTG.
27.50 MTG.
4" NPT
46.00
10.60
1/2" NPT
FOR BREATHER
4" NPT
3.50
CL
ON
1 1/2" NPT
TOP VIEW
31.63
BOTTOM VIEW
RESET
2 1/2" NPT
2 1/2" NPT
3.75
12.88
7.69
1/2" NPT
1/2" NPT
FOR BREATHERFOR BREATHER
CL
ON
OFF
TOP VIEW
31.63
31.63
10.56
TOP VIEW
0.75
23.88
18.13
12.19
RESET
19.25 MTG.
OFF
LEFT VIEW
2 1/2" NPT
RESET
1/2" NPT
FOR BREATHER
FRONT VIEW
ON
1/2" NPT
FOR DRAIN
CL
3.75
ON
3.75
19.25 MTG.
19.25 MTG.
2.38
OFF
7.69
COVER OPEN 90°
TOP VIEW
2 1/2" NPT
31.63
16.25 MTG.
15.06
COVER OPEN 130°
23.88
23.88
1" NPT
BOTTOM VIEW
RESET
18.13
CL
FRONT VIEW
10.56
FRONT VIEW
Front View
0.75
18.13
12.19
LEFT VIEW
FRONT VIEW
7.69
7.69
COVER OPEN 90°
COVER OPEN 90°
1/2" NPT
FOR DRAIN
CL
1/2" NPT
FOR DRAIN
Top View
Bottom View
23.88
2 1/2" NPT
2 1/2" NPT
1/2" NPT
16.25 MTG. C 16.25 MTG.
15.06
15.06
L
FOR DRAIN
COVER OPEN 130°
COVER OPEN 130°
BOTTOM VIEW BOTTOM VIEW
1" NPT
1" NPT
3.75
LEFT VIEW
3.75
LEFT VIEW
Left Side View
450
18.13
3.75
0.75
3.75
0.75
12.19
3.75
10.56
12.19
3.75
10.56
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
7.69
COVER OPEN 90°
2 1/2" NPT
15.06
COVER OPEN 130°
16.25 MTG.
AEB Series Full Voltage Motor Starter Enclosure Dimensions
Explosionproof, Dust-Ignitionproof, Watertight
CL
4.50
3.50
17.12
10.60
Enclosure Layout for Size 5 — Combination
CL
CL
17.12
3.50
17.12
1/2" NPT
FOR BREATHER
4" NPT
4.50
4.50
TOP VIEW
3.50
10.60
27.50 MTG.
10.60
OFF
4" NPT
1/2" NPT
1/2" NPT
FOR BREATHER FOR46.00
BREATHER
ON
4" NPT
C
TOP VIEW L
TOP VIEW
RESET
34.00
3.50
17.12
ON
OFF
ON
46.00
46.00
RESET
1/2" NPT
FOR BREATHER
14.94
4" NPT
16.56
RESET
0.75
34.00
FRONT VIEW
27.50 MTG.
4.504.50
LEFT VIEW
Left Side View
ON
26.13
FRONT VIEW
FRONT VIEW
10.19
10.19
COVER OPEN 90°COVER OPEN 90°
21.50
RESET
Front View
21.50
3.50
22.50 MTG.
Top View
CL
4.50
FRONT VIEW
34.00
22.50 MTG.
3.125
TOP VIEW
CL
1/2" NPT
FOR BREATHER
1 1/2" NPT
4" NPT
BOTTOM VIEW
TOP VIEW
1/2" NPT
1/2" NPT
FOR BREATHER FOR BREATHER
1 1/2" NPT
19.250 MTG.
2.38
3.50
1" NPT
27.63
TOP VIEW
RESET
2.38
19.44
3.125
27.63
7.00
1/2" NPT
FOR BREATHER
19.44
19.44
14.13
CL
1/2" NPT
1/2" NPT
FOR DRAIN
FOR DRAIN
3.125
0.75
C
L
3.125
3.125
11.38
3.125
9.69 1 1/2" NPT
RESET
TOP VIEW
LEFT VIEW
11.38 0.75
0.75 14.13
27.63
VIEW
LeftLEFT
Side
ViewLEFT VIEW
6.56
2.38
COVER OPEN 90°COVER OPEN 90°
14.13
12.19
12.19
12.250 MTG.
1 1/2" NPT
BottomCLView
4.50
10.60
27.50 MTG.
CL
4.50
12.250 MTG.
1 1/2" NPT
BOTTOM VIEW
TOP VIEW
1/2" NPT
1/2" NPT
FOR BREATHER FOR BREATHER
4" NPT
4" NPT
1/2" NPT
FOR BREATHER
4" NPT
2.38
3.50
COVER OPEN 130°
1" NPT
FRONT VIEW
3.50
1/2" NPT
FOR DRAIN
3.125
3.125
COVER OPEN 90°
3.50
12.19
14.13
CL
CL
4.50
6.56
9.69
LEFT VIEW
1 1/2" NPT
BOTTOM VIEW
19.44
10.60
10.60
12.250 MTG.
Top View
Enclosure Layout for Size 3 and 4 — Starter Only — Reversing
0.75
2.38
12.19
2.38
12.250 MTG.
1 1/2" NPT
RESET
11.38
1/2" NPT
FOR DRAIN
6.56
COVER OPEN 130°
COVER OPEN 130°
BOTTOM
VIEW BOTTOM VIEW
1" NPT
1" NPT
FRONT VIEW
Front
View
FRONT VIEW
CL
COVER OPEN 90°
COVER OPEN 130°
1" NPT
FRONT VIEW
6.56
9.69
11.38
CL
Bottom View
CL4.50
2.38
21.50
COVER OPEN 130°
27.63
9.69
4" NPT
BOTTOM VIEW
46.00
TOP VIEW CL
TOP VIEW
4.50
27.50 MTG.
27.50 MTG.
RESET
3.50
46.00
10.60
RESET
34.00
46.00
1/2" NPT
FOR BREATHER
4" NPT
14.94
16.56
RESET
0.75
CL
LEFT VIEW
27.50 MTG.
4.50
14.94
16.56
LEFT VIEW
14.94
16.560.75
26.13
26.13
FRONT VIEW
FRONT VIEW
0.75
LEFT VIEW
Left Side View
Front View
46.00
TOP VIEW
26.1334.00
34.00
1/2" NPT
CL
FRONT VIEW FOR DRAIN
4.504.50
9.56
9.56
COVER OPEN 90°COVER OPEN 90°
4" NPT
1/2" NPT
FOR DRAIN
LEFT VIEW
FRONT VIEW
4.50
9.56
COVER OPEN 90°
21.50
COVER OPEN 130°
3.50
22.50 MTG.
1" NPT
BOTTOM VIEW
9.56
COVER OPEN 90°
21.50
COVER OPEN 130°
3.50
22.50 MTG.
1" NPT
4" NPT
Bottom View
34.00
CL
26.13
4.50
3.50
TopBOTTOM
ViewVIEW
4.50
4.50
BOTTOM VIEW
22.50 MTG.
4" NPT
BOTTOM VIEW
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012 14.94
16.56
1/2" NPT
FOR DRAIN
4.50
3.50
21.50
21.50
22.50 MTG.
COVER OPEN 130°
COVER
OPEN 130° 1" NPT
1" NPT
RESET
0.75
1/2" NPT
FOR DRAIN
CL
4" NPT
451
Controls: Hazardous Location Motor Starters
10.19
2.38
COVER OPEN 90°
7.00
19.250 MTG.
1" NPT
1/2" NPT
FOR DRAIN
3.125
26.13
RESET
19.250 MTG.
COVER OPEN 130°
4" NPT
COVER OPEN 130°
COVER OPEN 130°
1" NPT
1" NPT
BOTTOM VIEW BOTTOM VIEW
1 1/2" NPT
19.250 MTG.
22.50 MTG.
3.50
22.50 MTG.
4" NPT
3.125
0.75
LEFT VIEW
3.50
21.50
46.00
26.13
7.00
Enclosure Layout
for Size 0, 1 and 2 — Starter Only — Reversing
14.94
7.00
10.19
COVER OPEN 90°
4.50
CL
16.56
1/2" NPT
FOR DRAIN
4.50
Controls
LEFT VIEW
OFF
0.75
0.75
34.00
1/2" NPT
FOR DRAIN
CL
CL
4.50
14.94
16.56
4.50
26.13
TOP VIEW
LEFT VIEW
14.94
16.56
1/2" NPT
FOR DRAIN
CL
3.125
OFF
10.60
3.125
27.50 MTG.
27.50 MTG.
4.50
AEB Series Full Voltage Motor Starter Enclosure Dimensions
3.13
Explosionproof, Dust-Ignitionproof, Watertight
CL
2.38
2.38
CL
3.13
3.13
12.00
Enclosure Layout for Size 0, 1 and 2 — Combination — Reversing
CL
1/2" NPT
FOR BREATHER
1 1/2" NPT
2.38
7.00
TOP VIEW
12.00
7.00
ON
ON
OFF
TOP VIEW
RESET
19.44
27.63
12.00
1/2" NPT
FOR BREATHER
19.44
1 1/2" NPT
RESET
ON
9.69
9.69
11.38
11.380.75
0.75 14.13
FRONT VIEW
7.19
2.38
FRONT
VIEW
Front
View
Controls: Hazardous Location Motor Starters
CL
17.12
17.12
COVER OPEN 90°
14.13
3.50
FRONT VIEW
27.50 MTG.
LEFT VIEW
OFF
ON
OFF
12.25 MTG.
4" NPT
1 1/2" NPT
BOTTOM VIEW
1 1/2" NPT
Bottom CView
L
4.50
3.50
CL
3.50
12.19
COVER OPEN 130°
1" NPT
10.60
10.60
2.38
12.19
COVER OPEN 130°
1" NPT
1/2" NPT
FOR DRAIN
4.50
4.50
7.19
9.69
CL
3.13
3.13
10.60
Enclosure Layout for Size 3 and 4 — Combination — Reversing
0.75
7.19
19.44
17.12
1/2" NPT
FOR DRAIN
COVER OPEN 90°
Top View
FRONT VIEW
CL
2.38
12.19
12.19 12.25 MTG.
12.25 MTG.
1 1/2" NPT
COVER OPEN 130°
COVER OPEN 130°
1" NPT
1" NPT
BOTTOM VIEW BOTTOM VIEW
RESET
11.38
1/2" NPT
FOR DRAIN
3.13
TOP VIEW
COVER OPEN 90°
COVER OPEN 90°
14.13
27.63
VIEWView
LEFT VIEW
LeftLEFT
Side
3.13
LEFT VIEW
7.19
3.13
0.75 CL
11.38
OFF
19.44
CL14.13
1/2" NPT
FOR DRAIN
9.69
3.13
RESET
19.25 MTG.
27.63
TOP VIEW
3.13
27.63
7.00
Controls
CL
2.38
19.25 MTG.
19.25 MTG.
OFF
3.13
7.00
1/2" NPT
1/2" NPT
FOR BREATHER FOR BREATHER
ON
OFF
1 1/2" NPT
19.25 MTG.
1 1/2" NPT
3.13
12.00
12.25 MTG.
TOP VIEW
1 1/2" NPT
ON
OFF
1/2" NPT
FOR BREATHER
4" NPT
2.38
BOTTOM VIEW
1/2" NPT
1/2" NPT
FOR BREATHER FOR BREATHER
4" NPT
46.00
CL
TOP VIEW
ON
TOP VIEW
4.50
10.60
RESET
OFF
34.00
46.00
46.00
14.94
16.56
RESET
1/2" NPT
FOR BREATHER
4" NPT
0.75
TOP VIEW
CL
ON
LEFT VIEW
27.50 MTG.
14.94
16.560.75
0.75 26.13
LEFT VIEW
LEFT VIEW
FRONT VIEW
Left Side View
46.00
26.13
10.19
21.50
10.19
FRONT VIEW
Front View
21.50
34.00
3.50
21.50
2.38
2 1/2" NPT
22.50 MTG.
CL
ON
OFF
4" NPT
TOP VIEW
BOTTOM VIEW
31.63
2.38
2 1/2" NPT
3.75
12.88
7.69
CL
3.75
1" NPT
3.75
COVER OPEN 130°
1/2" NPT
FOR BREATHER
2 1/2" NPT
3.50
21.50
FRONT VIEW
12.88
7.69
CL
Bottom View
1/2" NPT
FOR DRAIN
COVER OPEN 90°
19.25 MTG.
LEFT VIEW
12.88
7.69
4" NPT
BOTTOM VIEW
4.50
10.19
26.13
1" NPT
2.38
Enclosure Layout
for Size 1 and 2 — Combination — Two Speed, Single Winding — 5 Pole - 3 Pole
14.94
0.75
22.50 MTG.
COVER OPEN 130°
34.00
CL
4.50
16.56
3.50
COVER OPEN 90°
4" NPT
TopBOTTOM
ViewVIEW
COVER OPEN12.88
130°
COVER OPEN 130°
1" NPT
1" NPT
7.69
BOTTOM VIEW
RESET
4.50
3.50
22.50 MTG.
4" NPT
22.50 MTG.
1/2" NPT
FOR DRAIN
4.50
COVER OPEN 90°COVER OPEN 90°
4.50
10.19
26.1334.00
1/2" NPT
CL
FRONT
VIEW FOR DRAIN
4.50
4.50
4.50
14.94
16.56
1/2" NPT
FOR DRAIN
CL
3.75
27.50 MTG.
27.50 MTG.
RESET
3.50
17.12
CL
1/2" NPT
1/2" NPT
FOR BREATHER FOR BREATHER
RESET
RESET
ON
OFF
ON
TOP VIEW
31.63
31.63
TOP VIEW
0.75
10.56
23.88
18.13
CL
3.75
12.19
LEFT VIEW 2 1/2" NPT
1/2" NPT
FOR BREATHER
FRONT VIEW
3.75
OFF
19.25 MTG.
19.25 MTG.
2.38
1/2" NPT
FOR DRAIN
7.69
COVER OPEN 90°
19.25 MTG.
OFF
RESET
ON
RESET
RESET
TOP VIEW
RESET
COVER OPEN 130°
23.88
23.88
18.13
FRONT VIEW
10.56
RESET
0.75
FRONT VIEW
Front View
RESET
18.13
12.19
LEFT VIEW
FRONT VIEW
7.69
7.69
COVER OPEN 90°COVER OPEN 90°
15.06
15.06
1/2" NPT
FOR DRAIN
16.25 MTG.
COVER OPEN 130°
COVER OPEN 130°
BOTTOM VIEW
1" NPT
1" NPT
CL
2 1/2" NPT
16.25 MTG.
Bottom View
23.88
2 1/2" NPT
1/2" NPT
FOR DRAIN
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
BOTTOM VIEW
7.69
COVER OPEN 90°
15.06
COVER OPEN 130°
1" NPT
2 1/2" NPT
BOTTOM VIEW
1/2" NPT
FOR DRAIN
Top View
3.75
LEFT VIEW
CL
3.75
CL
3.75
LEFT VIEW
Left Side View
452
18.13
3.75
0.75
0.75
12.19
3.75
10.56
12.19
3.75
10.56
16.25 MTG.
15.06
31.63
16.25 MTG.
2 1/2" NPT
AEB Series Full Voltage Motor Starter Enclosure Dimensions
Explosionproof, Dust-Ignitionproof, Watertight
CL
4.50
17.12
Enclosure Layout for Size 3 and 4 — Combination — Two
Speed, Single Winding — 5 Pole - 3 Pole
10.60
CL
4.50
3.50
17.12
10.60
OFF
OFF
ON
TOP VIEW
46.00
46.00
CL
TOP VIEW
4.50
3.50
10.60
RESET
RESET
OFF
RESET
14.94
16.56
4.50 4.50
LEFT VIEW
LEFT VIEW
FRONT VIEW
Left Side View
FRONT VIEW
4.50
22.50 MTG.
1" NPT
4" NPT
BOTTOM VIEW
4" NPT
34.00
Top
View
CL
RESET
21.50
COVER OPEN 130°
3.50
22.50 MTG.
22.50 MTG.
21.50
21.50
4" NPT
COVER OPEN 130°
COVER OPEN 130°
1" NPT
1" NPT
BOTTOM VIEW BOTTOM VIEW
Front View
RESET
3.50
3.50
COVER OPEN 90°
FRONT VIEW
COVER OPEN 90°
COVER OPEN 90°
26.13
26.13
10.19
1/2" NPT
FOR DRAIN
4.50
10.19
4.50
Controls
27.50 MTG.
1/2" NPT
26.13FOR DRAIN
CL
CL
0.75 TOP VIEW
10.19
46.00
0.75
0.75
34.00
34.00
RESET
ON
4.50
1/2" NPT
FOR BREATHER
LEFT VIEW
14.94
16.56
1/2" NPT
FOR DRAIN
CL
4.50
14.94
16.56
34.00
RESET
46.00
4" NPT
RESET
TOP VIEW
ON
1/2" NPT
1/2" NPT
FOR BREATHERFOR BREATHER
4" NPT
4" NPT
27.50 MTG.
ON
17.12
27.50 MTG.
27.50 MTG.
4" NPT
10.60
OFF
1/2" NPT
FOR BREATHER
4.50
3.50
C
L
Bottom View
3.125
17.12
3.50
CL
1/2" NPT
FOR DRAIN
4.50
2.38
10.19
26.13
21.50
COVER OPEN2.38
130°
FRONT VIEW
2.38
1" NPT
3.125
0.75
16.56
LEFT VIEW
3.125
CL
CL
7.00
3.50
Enclosure Layout
Speed,
Two
Winding
— 3 Pole - 3 Pole
COVER OPEN
90°
14.94 for Size 0, 1 and 2 — Starter Only — Multi
22.50 MTG.
1/2" NPT
1/2" NPT
FOR BREATHER
FOR BREATHER
27.63
3.125
TOP VIEW TOP VIEW
CL
RESET
RESET
2.38
19.44
27.63
3.125
27.63
7.00
1/2" NPT
FOR BREATHER
19.44
19.44
14.13
1/2" NPT
1/2" NPT
FOR DRAIN FOR DRAIN
3.125
0.75
CL
3.125
11.38
CL
TOP VIEW
LEFT VIEW
6.56
9.69
0.75
11.38
14.13
0.75
27.63
VIEW LEFT VIEW
LeftLEFT
Side
View
6.56
12.19
12.250 MTG.12.250 MTG.
12.19
1" NPT
2.38
Top View
12.88
7.69
RESET
Bottom View
3.125
19.44
CL
CL
2.38
1/2" NPT
FOR DRAIN
Enclosure Layout for Size 3 and 4 — Starter Only — Two Speed, Two Winding — 3 Pole - 3 Pole
12.250
CL MTG.
12.19 CL
COVER OPEN 130°
FRONT VIEW
2.38
2.381"
NPT
31.63
BOTTOM VIEW
RESET
2 1/2" NPT
RESET
1/2" NPT
FOR BREATHER
3.75
31.63
TOP VIEW
0.75
10.56
RESET
RESET
1/2" NPT
FOR DRAIN
CL
1/2" NPT
FRONT VIEW
FOR BREATHER
LEFT
2 1/2" VIEW
NPT
RESET
23.88
18.13
12.19
3.75
31.63
3.75
2.38
TOP VIEW
19.25 MTG.
19.25 MTG.
12.88
7.69
1/2" NPT
FORCLBREATHER
2 1/2" NPT
TOP VIEW
1 1/2" NPT
3.75
12.88
7.69
LEFT VIEW
3.75
12.88
7.69
2.38
COVER OPEN 90°
14.13
0.75
19.25 MTG.
11.38
1/2" NPT
FOR BREATHER
2 1/2" NPT
6.56
9.69
1 1/2" NPT
BOTTOM VIEW
1 1/2" NPT 1 1/2" NPT
COVER OPEN
130° OPEN 130°
COVER
BOTTOM
BOTTOM VIEW
1" NPT
1" NPT VIEW
Front View
FRONT VIEWFRONT VIEW
RESET
2.38
COVER OPEN
90° OPEN 90°
COVER
14.13
COVER OPEN 130°
3.75
11.38
1/2" NPT
FOR DRAIN
2.38
12.250 MTG.
12.19
FRONT VIEW
3.125
9.69
6.56
COVER OPEN 90°
3.125
1 1/2" NPT
9.69
RESET
RESET
3.125
RESET
RESET
CL
3.125
19.250 MTG.
19.250 MTG.
19.250 MTG.
1 1/2" NPT 1 1/2" NPT
RESET
7.69
COVER OPEN 90°
19.25 MTG.
TOP VIEW
Left Side View
Front View
10.56
0.75
18.13
7.69
COVER OPEN 90°
FRONT VIEW
7.69
COVER OPEN 90°
15.06 16.25 MTG.
15.06
COVER OPEN 130°
12.19
LEFT VIEW
CL1/2" NPT
FOR DRAIN
CL
RESET
1" NPT
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012
COVER OPEN 130°
BOTTOM VIEW
1" NPT
1/2" NPT
FOR DRAIN
Top View
2 1/2" NPT
16.25 MTG.
CL
BOTTOM VIEW
Bottom View
23.88
2 1/2" NPT
1/2" NPT
FOR DRAIN
7.69
COVER OPEN 90°
16.25 MTG.
15.06
COVER OPEN 130°
1" NPT
2 1/2" NPT
BOTTOM VIEW
3.75
18.13
RESET
FRONT VIEW
1" NPT
3.75
FRONT VIEW
3.75
18.13
0.75
12.19
3.75
0.75
10.56
LEFT VIEW
3.75
12.19
COVER OPEN 130°
23.88
23.88
3.75
10.56
LEFT VIEW
16.25 MTG.
15.06
31.63
BOTTOM VIEW
2 1/2" NPT
453
Controls: Hazardous Location Motor Starters
TOP VIEW
7.00
7.00
19.250 MTG.
1/2" NPT
FOR BREATHER
1 1/2" NPT
4" NPT
BOTTOM VIEW
AEB Series Full Voltage Motor Starter Enclosure Dimensions
3.13
Explosionproof, Dust-Ignitionproof, Watertight
CL
2.38
2.38
3.13
3.13
CL
CL
Enclosure Layout for Size 0, 1 and 2 — Combination — Two12.00Speed,
Two Winding
— 3 Pole - 3 Pole
1/2" NPT
FOR BREATHER
1 1/2" NPT
2.38
7.00
12.00
1 1/2" NPT
ON
ON
OFF
TOP VIEW
TOP VIEW
CL
RESET
RESET
27.63
3.13
27.63
12.00
1/2" NPT
FOR BREATHER
19.44
19.44
1/2" NPT
1/2" NPT
0.75CL
FOR DRAIN 14.13
FOR DRAIN
7.00
OFF
11.38
11.38
LEFT VIEW
7.19
0.75
0.75
CL
14.13
2.38
COVER OPEN 90°
COVER OPEN 90°
14.13
Left Side View
FRONT VIEW
Front View
17.12
CL
1 1/2" NPT
BOTTOM VIEW
1 1/2" NPT
Top View
RESET
RESET
Bottom View
19.44
1/2" NPT
FOR DRAIN
3.13
FRONT VIEW
12.19
12.19
12.25 MTG.
12.25 MTG.1 1/2" NPT
COVER OPEN 130°
COVER OPEN 130°
1" NPT
1" NPT
BOTTOM VIEW BOTTOM VIEW
3.13
LEFT VIEW
2.38
12.25 MTG.
2.38
27.63
LEFT VIEW
19.44
1/2" NPT
FOR DRAIN
7.19
12.19
COVER OPEN 130°
1" NPT
FRONT VIEW
7.19
CL
COVER OPEN 90°
TOP VIEW
ON
9.69
19.25 MTG.
9.69
3.13
11.38
3.13
9.69
3.13
RESET
RESET
3.13
1 1/2" NPT
RESET
RESET
Controls
27.63
2.38
19.25 MTG.
19.25 MTG.
OFF
19.25 MTG.
7.00
ON
OFF
3.13
7.00
TOP VIEW
1/2" NPT
1/2" NPT
FOR BREATHERFOR BREATHER
1 1/2" NPT
3.13
12.00
CL
4.50
10.60
3.50
7.19
Enclosure Layout9.69for Size 3 and
4 — Combination — Two COVER
Speed,
Two Winding 2.38
— 3 Pole - 3 Pole
0.75
OPEN 90°
14.13
Controls: Hazardous Location Motor Starters
11.38
LEFT VIEW
17.12
12.19
COVER OPEN 130°
1" NPT
FRONT VIEW
17.12
10.60
OFF
27.50 MTG.
OFF
ON
OFF
3.50
TOP VIEW
3.50
46.00
CL
4" NPT
4" NPT
ON
17.12
1/2" NPT
FOR BREATHER
4" NPT
ON
4.50
4.50
10.60
1 1/2" NPT
12.25 MTG.
CLBOTTOM VIEWCL
1/2" NPT
1/2" NPT
FOR BREATHERFOR BREATHER
RESET
RESET
4.50
TOP VIEW
3.50
27.50 MTG.
27.50 MTG.
10.60
OFF
RESET
RESET
0.75
4" NPT
26.13
27.50 MTG.
TOP VIEW
LEFT VIEW
LEFT VIEW
LEFT VIEW
26.13
RESET
RESET
FRONT VIEW
Left Side View
14.94
16.56
4.50 4.50
4.50
0.75
0.75
1/2" NPT
FOR DRAIN
22.50 MTG.
21.50
COVER OPEN 130°
1" NPT
4" NPT
BOTTOM VIEW
4.50
26.13
FRONT VIEW
Front View
0.75
34.00
1/2" NPT
FOR DRAIN
CL
3.50
COVER OPEN 90°
34.00
CL
14.94
16.56
1/2" NPT
FOR DRAIN
4.50
10.19
FRONT VIEW
46.00
14.94
16.56
4.50
1/2" NPT
FOR BREATHER
RESET
LEFT VIEW
10.19
10.19
COVER OPEN 90°
COVER OPEN 90°
21.50
3.50
3.50
Top 22.50
View
MTG.
34.00
22.50 MTG.
21.50
4" NPT
1/2" NPT
FOR DRAIN
4" NPT
C
COVER OPEN 130°
COVER OPEN 130°
1" NPT L
1" NPT
BOTTOM VIEW BOTTOM VIEW
4.50
4.50
Bottom View
26.13
FRONT VIEW
10.19
3.50
COVER OPEN 90°
22.50 MTG.
21.50
COVER OPEN 130°
454
34.00
CL
14.94
16.56
ON
RESET
TOP VIEW
46.00
46.00
1" NPT
4" NPT
BOTTOM VIEW
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2012