Combination Starters—NEMA Rated Accessories Interlocks

Combination Starters—NEMA Rated
Class 8538, 8539 / Refer to Catalog 8538CT9701
www.schneider-electric.us
selection. For electrical ratings of disconnect
and circuit breaker interlocks, see
Table 16.107 below.
Accessories
Interlocks and Control Transformers
An electrical interlock may also be factory
installed in either a disconnect switch or
circuit breaker combination starter. Specify
Form Y74 for single pole, or Form Y75 for
two pole interlocks. For pricing see factory
modifications (Forms).
A one or two pole electrical interlock can be
added to the disconnect switch or circuit
breaker. Thus, if a separate control circuit is
used, the magnetic starter can be
de-energized when the disconnect is
switched to the OFF position.
See Table 16.106 for proper interlock
Table 16.106: Disconnect Switch and Breaker Interlocks
Class
SPDT (Y74)
Type
8538
a
b
SBb, SCb, SDb (Series B)
SD (Series C)
SB, SC (Series C)
8538
SE, SF (Series A)
&
SE (Series B & C)
8738
SF (Series B & C)
SG
8539, 8739
SB, SC, SD, SE, SF, SGa
8538
SBA, SCA, SBG, SCG (Series D)
8538
SBAS8, SCAS8, SBGS8, SCGS8 (Series D)
8738
SBAS8, SCAS8, SBGS8, SCGS8 (Series E)
8738
SBA, SCA, SBG, SCG (Series E)
8538
SDA, SDAb, SDG, SDGb (Series D)
8738
SDA, SDG (Series E)
8538, 8738
SEA, SEG (Series D)
No interlocks available for the GJL circuit breaker. The internally mounted auxiliary switch
(catalog number AAC) must be used.
Class 8538 type numbers ending in suffix “S8”.
DPDT (Y75)
Class 9999 Type
R6
R43
R45
R8
R41
R39
R35
R26
TC11
TC10
TC10
TC11
TC10
TC10
TC10
$ Price
116.00
116.00
107.00
131.00
131.00
135.00
435.00
131.00
120.00
120.00
120.00
120.00
120.00
120.00
120.00
Class 9999 Type
R7
R44
R46
R9
R42
R40
R36
R27
TC21
TC20
TC20
TC21
TC20
TC20
TC20
$ Price
221.00
221.00
207.00
243.00
243.00
243.00
521.00
243.00
239.00
239.00
239.00
239.00
239.00
239.00
239.00
Table 16.107: Disconnect Switch and Breaker Interlock Electrical Ratings
Class 9999 Type R6, 8, 26, 35, 39, 41, 43, 45, TC10, & TC11
Class 9999 Type R7, 9, 27, 36, 40, 42, 44, 46 & TC 20, 21
AC—50 or 60 Hz
AC—50 or 60 Hz
Maximum Current
Volts
120
240
480
600
Make
Break
Amps
Amps
40
20
10
8
15
10
8
6
Maximum Current
Continuous
Carrying
Current
Amps
15
15
15
15
Amps
120
240
480
600
These 100 VA kits are designed specifically to allow for field modification
of NEMA Size 0, 1 and 2 combination starters that require a control
power transformer. The kit includes a 9070TF100 fused transformer on
a special mounting plate for ease of placement and installation on the
combo starter back pan. A wire harness (with wiring diagrams) is
included to complete the kit.
Table 16.108: Control Transformer Field Modification Kits
Catalog Number
9999CPT1D1
9999CPT1D3
Primary Voltage
240 x 480
208
Secondary Voltage
120
120
$ Price
447.00
447.00
Table 16.109: Control Transformer Selection
NEMA Size
Starter Type
Standarde
Capacity
(Form F4T)
50 VAe
Additional
Capacity
(Form F4T10)
100 VAe
Additional
Capacity
(Form F4T11)
200 VAe
Additional
Capacity
(Form F4T12)
16
NEMA DEFINITE PURPOSE TYPE
CONTACTORS AND STARTERS
Class 9070
Class 9070
Class 9070
Class 9070
Type
Type
Type
Type
0&1
SB & SC
T100
T150
T200
T300c
2
SD
T100
T150
T300d
T300d
3
SE
T150
T150
T300
T500
4
SF
T300
T300
T500
T500
T50 and
T100 and
T150 and
T300 and
5
SG
8501XO20
8501XO20
8501XO20
8501XO20
EO3S2 is
EO3S2 and
EO3S2 and
EO3S2 and
6
SH
standard
T50
T100
T200
EO19S2 is
EO19S2 and
EO19S2 and
EO3S2 and
7
SJ
standard
T50
T100
T200
c
Requires oversized enclosure. (Size 2 reversing enclosure.)
d
Available in standard enclosure with Mag-Gard® circuit breaker and non-fusible
disconnect switch. Requires oversized enclosure with thermal-magnetic circuit breakers
and fusible disconnect switches. (Size 2 reversing enclosure.)
e
Complete the contactor or starter Class and Type with Voltage Code, see page 16-110.
16-40
Make
Volts
CP1
30
15
7.5
6
Break
VA
3450
3450
3450
3450
Amps
VA
3
1.5
.75
.6
345
345
345
345
Continuous
Carrying
Current
Amps
10
10
10
10
Internal Auxiliary Switch—Circuit breakers can be supplied with a
factory installed auxiliary switch for remote indication of an open and/or
tripped or a closed breaker. One (specify Form Y741) or two (specify
Form Y751) auxiliary switches can be supplied. The switches are
supplied with normally open and normally closed circuits with a common
connection. Contacts must be used on the same polarity and are rated
15 Amps at 240 Vac. The auxiliary switches are located internally and
are furnished with 19-20 inch long leads.
Alarm Switch—The alarm switch only operates when the breaker is
tripped. It is used to actuate bell alarms and warning lights. The alarm
switch is factory installed only (specify Form Y742) and consists of a
single pole single throw switch which is normally open except when the
breaker is tripped. The contacts are rated 4 Amps at 240 Vac. This
switch is located in the breaker and is supplied with 19-20 inch long
leads.
Transformer Selection—Space and drilling are provided in all
disconnect switch and circuit breaker combination starters in NEMA 1, 4
& 4X stainless and polyester, 12 and 7 & 9 bolted enclosures for the field
addition (or factory installation) of a Class 9070 control circuit
transformer and Class 9999 Type SFR4 fuse holder. This kit can be
either panel mounted or side mounted on the Type S starter. For
standard control transformer selection in combination starters, see
Table 16.109. Consult field office for transformer additions to NEMA 7 &
9 SPIN TOP® enclosures. For secondary fuse holder order 9080PF1.
Fuse Block Mounting Brackets—The standard capacity transformer,
Class 9070 Type T100, for the Size 0 and 1 starters mounts to the right
of the magnetic starter.
Standards—Most combination starters and forms are UL Listed in file
E152395, Category NKJH, and CSA File CR 584.
Discount
Schedule
© 2009 Schneider Electric