Combination Starters—NEMA Rated Class 8538, 8539 / Refer to Catalog 8538CT9701 www.schneider-electric.us selection. For electrical ratings of disconnect and circuit breaker interlocks, see Table 16.107 below. Accessories Interlocks and Control Transformers An electrical interlock may also be factory installed in either a disconnect switch or circuit breaker combination starter. Specify Form Y74 for single pole, or Form Y75 for two pole interlocks. For pricing see factory modifications (Forms). A one or two pole electrical interlock can be added to the disconnect switch or circuit breaker. Thus, if a separate control circuit is used, the magnetic starter can be de-energized when the disconnect is switched to the OFF position. See Table 16.106 for proper interlock Table 16.106: Disconnect Switch and Breaker Interlocks Class SPDT (Y74) Type 8538 a b SBb, SCb, SDb (Series B) SD (Series C) SB, SC (Series C) 8538 SE, SF (Series A) & SE (Series B & C) 8738 SF (Series B & C) SG 8539, 8739 SB, SC, SD, SE, SF, SGa 8538 SBA, SCA, SBG, SCG (Series D) 8538 SBAS8, SCAS8, SBGS8, SCGS8 (Series D) 8738 SBAS8, SCAS8, SBGS8, SCGS8 (Series E) 8738 SBA, SCA, SBG, SCG (Series E) 8538 SDA, SDAb, SDG, SDGb (Series D) 8738 SDA, SDG (Series E) 8538, 8738 SEA, SEG (Series D) No interlocks available for the GJL circuit breaker. The internally mounted auxiliary switch (catalog number AAC) must be used. Class 8538 type numbers ending in suffix “S8”. DPDT (Y75) Class 9999 Type R6 R43 R45 R8 R41 R39 R35 R26 TC11 TC10 TC10 TC11 TC10 TC10 TC10 $ Price 116.00 116.00 107.00 131.00 131.00 135.00 435.00 131.00 120.00 120.00 120.00 120.00 120.00 120.00 120.00 Class 9999 Type R7 R44 R46 R9 R42 R40 R36 R27 TC21 TC20 TC20 TC21 TC20 TC20 TC20 $ Price 221.00 221.00 207.00 243.00 243.00 243.00 521.00 243.00 239.00 239.00 239.00 239.00 239.00 239.00 239.00 Table 16.107: Disconnect Switch and Breaker Interlock Electrical Ratings Class 9999 Type R6, 8, 26, 35, 39, 41, 43, 45, TC10, & TC11 Class 9999 Type R7, 9, 27, 36, 40, 42, 44, 46 & TC 20, 21 AC—50 or 60 Hz AC—50 or 60 Hz Maximum Current Volts 120 240 480 600 Make Break Amps Amps 40 20 10 8 15 10 8 6 Maximum Current Continuous Carrying Current Amps 15 15 15 15 Amps 120 240 480 600 These 100 VA kits are designed specifically to allow for field modification of NEMA Size 0, 1 and 2 combination starters that require a control power transformer. The kit includes a 9070TF100 fused transformer on a special mounting plate for ease of placement and installation on the combo starter back pan. A wire harness (with wiring diagrams) is included to complete the kit. Table 16.108: Control Transformer Field Modification Kits Catalog Number 9999CPT1D1 9999CPT1D3 Primary Voltage 240 x 480 208 Secondary Voltage 120 120 $ Price 447.00 447.00 Table 16.109: Control Transformer Selection NEMA Size Starter Type Standarde Capacity (Form F4T) 50 VAe Additional Capacity (Form F4T10) 100 VAe Additional Capacity (Form F4T11) 200 VAe Additional Capacity (Form F4T12) 16 NEMA DEFINITE PURPOSE TYPE CONTACTORS AND STARTERS Class 9070 Class 9070 Class 9070 Class 9070 Type Type Type Type 0&1 SB & SC T100 T150 T200 T300c 2 SD T100 T150 T300d T300d 3 SE T150 T150 T300 T500 4 SF T300 T300 T500 T500 T50 and T100 and T150 and T300 and 5 SG 8501XO20 8501XO20 8501XO20 8501XO20 EO3S2 is EO3S2 and EO3S2 and EO3S2 and 6 SH standard T50 T100 T200 EO19S2 is EO19S2 and EO19S2 and EO3S2 and 7 SJ standard T50 T100 T200 c Requires oversized enclosure. (Size 2 reversing enclosure.) d Available in standard enclosure with Mag-Gard® circuit breaker and non-fusible disconnect switch. Requires oversized enclosure with thermal-magnetic circuit breakers and fusible disconnect switches. (Size 2 reversing enclosure.) e Complete the contactor or starter Class and Type with Voltage Code, see page 16-110. 16-40 Make Volts CP1 30 15 7.5 6 Break VA 3450 3450 3450 3450 Amps VA 3 1.5 .75 .6 345 345 345 345 Continuous Carrying Current Amps 10 10 10 10 Internal Auxiliary Switch—Circuit breakers can be supplied with a factory installed auxiliary switch for remote indication of an open and/or tripped or a closed breaker. One (specify Form Y741) or two (specify Form Y751) auxiliary switches can be supplied. The switches are supplied with normally open and normally closed circuits with a common connection. Contacts must be used on the same polarity and are rated 15 Amps at 240 Vac. The auxiliary switches are located internally and are furnished with 19-20 inch long leads. Alarm Switch—The alarm switch only operates when the breaker is tripped. It is used to actuate bell alarms and warning lights. The alarm switch is factory installed only (specify Form Y742) and consists of a single pole single throw switch which is normally open except when the breaker is tripped. The contacts are rated 4 Amps at 240 Vac. This switch is located in the breaker and is supplied with 19-20 inch long leads. Transformer Selection—Space and drilling are provided in all disconnect switch and circuit breaker combination starters in NEMA 1, 4 & 4X stainless and polyester, 12 and 7 & 9 bolted enclosures for the field addition (or factory installation) of a Class 9070 control circuit transformer and Class 9999 Type SFR4 fuse holder. This kit can be either panel mounted or side mounted on the Type S starter. For standard control transformer selection in combination starters, see Table 16.109. Consult field office for transformer additions to NEMA 7 & 9 SPIN TOP® enclosures. For secondary fuse holder order 9080PF1. Fuse Block Mounting Brackets—The standard capacity transformer, Class 9070 Type T100, for the Size 0 and 1 starters mounts to the right of the magnetic starter. Standards—Most combination starters and forms are UL Listed in file E152395, Category NKJH, and CSA File CR 584. Discount Schedule © 2009 Schneider Electric All Rights Reserved