3UA Thermally Delayed Overload Relays CLASS 10 Technical data according to IEC 60 947-4-1 General data Type 3UA60 01- . ./ 3UA61 01-.. 3UA62 01-.. 3UA66 3UA68 Trip class 10 10 10 A 10 A Phase failure sensitivity by differential shutter yes Adjustable to automatic reset yes RESET button with trip-free feature yes STOP button yes Test function yes no integrated Accessories Permissible ambient temperature °C –20 to +60 –25 to +55 Shock resistance g/ms 8/10 Rated insulation voltage Ui (pollution degree 3) V 1000 Rated impulse withstand voltage kV 8 Sealable cover Main circuit DC, AC up to 400 Hz Type of current, frequency range AC 50 to 400 Hz Current setting range (≤ 200 A / > 200 A ) Conductor cross-sections Terminal screw mm2 Solid or stranded Finely stranded with end sleeve mm2 Flat bars mm Tightening torque Nm lb. in M6 2 x 25 to 70 M8 2 x 50 to 120 M 8/M 10 185/240 M 10 2x240 25 to 50 – 25 to 95 20 x 3 – 20x3/2x30x5 – 2x30x5 6 to 8 52 to 60 10 to 14 89 to 124 10 to 14 89 to 124/ 14 to 24 124 to 210 14 to 24 124 to 210 Nm lb. in Power losses per conducting path (max.) • at lowest value of setting range W 5 5 4 (5) 6 (9) • at highest value of setting range W 7 8 10 (12) 15 (22) Typical tripping characteristics 1 2 0 1 0 0 A N S 2 -5 6 8 0 b 5 0 2 0 m in Tripping curve 3 is applicable to 3-pole loads and curve 2 to 2pole loads. For single-pole loads, the tripping curves lie between curves 2 and 3. For normal operation, all 3 bimetallic strips of the overload relay must be heated. The 3UA overload relays are suitable for protecting motors with phase control. For protecting single-phase or DC-loads, therefore, all three main conducting paths must be connected in series. Tripping curve 3 is then applicable. The release current with a 3-pole symmetrical load is between 105 % and 120 % of the set current. T r ip p in g tim e Tripping characteristics The current-time curves show the relationship between the tripping time from cold state and multiples of the set current IE. When the relay is at operating temperature and carrying 1.0 × IE, the tripping times are reduced to approximately 25 %. s T 1 0 5 2 5 0 3 1 2 0 2 1 0 5 2 5 1 2 1 0 x IE T r ip p in g c u r r e n t ( a v e r a g e ) 3UA Thermally Delayed Overload Relays CLASS 10 Technical data according to IEC 60 947-4-1 Auxiliary circuit Type 3UA60 01- . ./ Auxiliary contacts 1 NO + 1 NC Conductor cross-sections Terminal screw Solid or stranded Finely stranded with end sleeve Tightening torque Rated insulation voltage Ui (pollution degree 3) NS1-5329 • NC • NO and NC connected as changeover contact NS1-5331 NS1-5330 • NO and NC with unequal potential Rated impulse withstand voltage Uimp 3UA61 01-.. 3UA62 01-.. 3UA66 3UA68 mm2 mm2 Nm lb. in M3 2 x (0.5 to 1.5); 2 x (0.75 to 2.5) 2 x (0.5 to 1.5); 2 x (0.75 to 2.5) 0.8 to 1.2 7 to 10.3 M 3.5 2 x (0.5 to 1); 2 x (1 to 2.5) 2 x (0.5 to 1); 2 x (0.75 to 2.5) 0.8 to 1.4 7 to 12 V 690 - V - 690 V - 400 V - 690 kV 6 A A A A A A A 4 3 1.5 0.6 - 2 1.5 1.25 1.15 1.1 1 0.8 A A A A A A A 2.2 1.5 0.8 0.6 - 2 1.5 1.25 1.15 1.1 1 0.8 A A A A 1 0.15 0.1 2 0.5 0.3 0.2 A 6 yes A A A 6 10 6 3 AC V - 400 Switching capacity NC at AC. AC-14/AC-15 NO at AC. AC-14/AC-15 NC/NO at DC, DC-13 Conventional thermal current Ith Contact reliability Short-circuit protection Fuse links Miniature circuit-breaker • Rated operational current Ie at Ue: - 24 V - 60 V - 125 V - 230 V - 400 V - 500 V - 600 V - 690 V Rated operational current Ie at Ue: - 24 V - 60 V - 125 V - 230 V - 400 V - 500 V - 600 V - 690 V Rated operational current Ie at Ue: - 24 V - 60 V - 110 V - 220 V Suitable for PLC; 17 V, 5 mA Utilization category gL/gG fast C-characteristics s-, u-, U-ratings Rated voltage B 600, R 300 Switching capacity Box terminal block for installing as a single unit Type 3UX1 424 For overload relays 3UA60 Conductor cross-sections Terminal screw Solid or stranded Finely stranded with end sleeve mm2 mm2 Trip classes of thermal, delayed magnetic or solid-state overload relays – excerpt from IEC 60947-4-1 Trip class 10A 10 20 30 Tripping time tA in seconds at 7.2 x Ie from cold state 2 < tA ≤ 10 4 < tA ≤ 10 6 < tA ≤ 20 9 < tA ≤ 30 M6 2x25 to 70 2x25 to 50 630 3UA Thermally Delayed Overload Relays CLASS 10 Technical data according to IEC 60 947-4-1 and DIN VDE 0660 Part 102 Short-circuit protection with fuses for motor feeders with short-circuit currents up to 50 kA at 690 V1), 50/60 Hz Overload relays Type Setting range A Permissible short-circuit fuses for motor starters consisting of overload relay and contactor, contactor assembly Fuse links NH Type 3NA NH DIAZED Type 5SB Type 3ND NEOZED Type 5SE Utilization category Utilization category gL/gG aM Type of coordination 2) “1” A “2” A Type of coordination 2) “2” A u-listed fuses CLASS R K5 British standards fuses BS 88 Type T Type of coordination 2) “1” A “2” A A 3UA60, 3UA61, 3UA62 thermal overload relays 55 to 80 63 to 90 80 to 110 90 to 120 110 to 135 120 to 150 135 to 160 150 to 180 170 to 205 400 400 400 400 400 400 400 400 400 160 160 200 224 224 250 250 250 250 100 100 125 125 160 160 160 200 200 315 315 315 315 315 315 355 355 355 160 160 160 200 200 250 250 250 315 125 200 250 315 400 630 630 355 355 500 500 800 800 1000 224 224 355 400 450 500 500 300 350 400 450 500 600 600 700 800 3UA66, 3UA68 thermal overload relays 80 to 125 125 to 200 160 to 250 200 to 320 250 to 400 320 to 500 400 to 630 355 355 500 500 800 800 1000 224 224 400 400 500 500 500 (630) 3) 1) Voltage tolerance +5%. 2) Coordination of short-circuit equipment according to IEC 60947-4-1/DIN VDE 0660 Part 102: Type of coordination “1”: The contactor or starter must not endanger persons or the installation in the event of a short-circuit. They do not need to be suitable for further operation without repair and the renewal of parts. Type of coordination “2”: The contactor or starter must not endanger persons or the installation in the event of a short-circuit and must be suitable for further use. There is a danger of contact welding. 3) Applies to 3TB contactors. 300 300 300 300 400 400 1200 CLASS L