3VA molded case circuit breaker
Starter and motor protection
3VA1 MCCB
3VA2 MCCB
Applications
Starter protection
Starter and motor protection
Frame sizes
60 A
160 A
Rated currents
32 A – 200 A
25 A - 500 A
Trip Unit
AM
I / LSI; LSIG
IEC breaking capacity Icu 415 V 50/60 Hz
55kA , 70kA
55kA, 110kA
Communication
Not available
Available
Metering
Not available
Available
Unrestricted / © Siemens AG 2015. All Rights Reserved.
250 A
250 A
400 A
630 A
3VA molded case circuit breaker
Starter protection vs. motor protection
Starter protection
Motor protection
MCCB (3VA)
Instantaneous
protection
MCCB (3VA)
Instantaneous
protection
Overload protection
… and more
Contactor
Functional
switching
Contactor
Functional
switching
MCCB (3VA)
Instantaneous
protection
Overload protection
Functional switching
… and more
Overload relay
(3RB; 3UF7)
Overload
protection
Motor
Unrestricted / © Siemens AG 2015. All Rights Reserved.
Motor
Motor
3VA molded case circuit breaker
Starter protection and motor protection
3VA1
3VA2
3VA2
3VA2
TM120M
ETU310M
ETU350M
ETU860M
Starter
protection
Starter
protection
Motor
protection
Motor
protection
L overload (long time) Ir


Thermal memory


S short time delay short circuit Isd




Protection
I instantaneous short circuit Ii



G ground fault Ig
Additional features
Prepared for higher inrush currents from IE3 motors




Phase unbalance protection available
*
*


Blocking protection
*
*

Idle running protection

Power metering integrated

Communication as option

* Function can be achieved with the overload relay (3RB; 3UF7)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
IE3 standard (1/2)
The IE3 standard
is mandatory in
Europe since
January 1st 2015
It applies to
• Newly installed motors
• Motors in continuous operation
In the power range
0.75
7.5
from 2017 on
Unrestricted / © Siemens AG 2015. All Rights Reserved.
375 kW
from 2015 on
3VA molded case circuit breaker
IE3 standard (2/2)
Before
Nominal
current
Motors according
to IE3 standard
IE3 Premium Efficiency
motors
• Higher efficiency factor
because of less ohmic loss
• Reduced nominal current
Starting
current
Less ohmic loss
• Lower resistance
• Increase of starting
current
Inrush
current
A fact that you won‘t find in
data sheets - but what we
have analyzed for you:
The inrush current rises
enormously!
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Inrush current and instantaneous short circuit
3VA1
3VA2
3VA2
3VA2
TM120M
ETU310M
ETU350M
ETU860M
Starter protection
Starter protection
Motor protection
Motor protection
7 … 16 x In2)
3 … 15 x In1)
15 x In1)
3 …15 x In1)
Minimum rotary
switch setting
Minimum rotary
switch setting
Protection
Ii
Ii Default setting
Minimum rotary
switch setting
Minimum setting
All our 3VA molded case
circuit breakers are
prepared for increased
inrush current generated
by IE3 motors.
1) Some frames sizes and current ratings have limited adjustment setting. For more information, please refer to the device manual/FAQ@ SIOS.
2) Up to 125 A, In: 200 A Ii = 7….14 x In
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Overload parameter settings
3VA2
3VA2
ETU350M
ETU860M
Motor protection
Motor protection
Ir
0,4 … 1 x In
0,4 … 1 x In
Setting time delay
@ overload
Trip class TC
Trip class Tc or
Tripping time TP
Trip class TC
10A, 10 / 10E
20 / 20E
10A, 10 / 10E,
20 / 20E, 30 / 30E
Protection
Tripping time TP
3 … 30 s 1)
Using the mode „Trip class TC“ to set the time delay @ overload means always to select a time range
for overload protection.
Example: TC = 20  6s < TP ≤ 20s according to IEC 60947-4-1
A more precise way to set the tripping time is to directly edit the TP with the ETU860M.
1) Some frames sizes and current ratings have limited adjustment setting. For more information, please refer to the device manual/FAQ@ SIOS.
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Tripping time, trip class acc. to IEC 60947-4-1
Tripping classes of overload protection devices in acc. with IEC 60947-41
CLASS
Tripping time
10 A
2 s < tA < 10 s
t 120
100
50
20
10 and 10E
4 and 5 s < tA < 10 s
20 and 20E
6 and 10 s < tA < 20 s
5
30 and 30E
9 and 20 s < tA < 30 s
2
1
50
The tripping classes are based on the tripping time
(tA) at 7.2-times the set current Ie from cold state.
Suffix “E” in class means narrower tolerance
available in solid-state OLR
The overload protection device has to
trip within these times!
Unrestricted / © Siemens AG 2015. All Rights Reserved.
10
CLASS 30
CLASS 25
CLASS 20
CLASS 15
CLASS 10
CLASS 5
20
10
5
Tripping characteristic curve
2
for 3-pole sym. load
1
0,7
1
2
x Ie 5
8
3VA molded case circuit breaker
Phase unbalance protection
If one of the 3 phases fail, a three-phase motor continues to run like a single-phase motor with an
enormous decrease of load torque. There is a high risk that the motor stops rotating.
With the feature „phase unbalance protection“ the 3VA molded case circuit breaker trips by exceeding
the phase unbalance values for the time tunbalance.
3VA2
3VA2
ETU350M
ETU860M
Motor protection
Motor protection
40% fix
5 … 50% (default 40%)
ON
ON / OFF (default ON)
0,7s during start up
4s during normal operation
0,7s during start up
4s during normal operation
Protection
Unbalance Ratio
Phase unbalance protection availability
Delay time tunbalance
The average current and the unbalance ratio are calculated based on:
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Blocking protection
Application examples for blocking protection
• Stone crusher (stone too hard / large)
• Conveyer belt (transport goods wedged)
Motor blocking (or falling back behind breakdown torque) generates high motor
current (close to starting current). But it‘s still not as high as a short circuit
current!
Without the blocking protection feature it might take up to 30s or more
(depending on current and TP setting) until the breaker trips
 unnecessary thermal stress
3VA2
ETU860M
Motor protection
Protection
Ib
Delay time tb
Blocking protection availability
1,2 … 10 x In in A (default 10)
1 … 10s (default 1s)
ON / OFF (default ON)
During the start up phase (ramp up), blocking protection is automatically disabled
until the motor reaches the operating speed (tstart). tstart equals tb.
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Idle running protection
Application examples for idle running protection
• Load transmission between motor and application was lost
(belt rupture, broken chain …)
• Pump, compressor
With the accessory for idle running protection the motor can be switched off by
tripping the circuit breaker.
3VA2
ETU860M
Motor protection
Protection
I<<
Delay time t<<
Idle running protection availability
Unrestricted / © Siemens AG 2015. All Rights Reserved.
0,3 … 0,9 x Ir (default 0,9)
1 … 200s (default 1s)
ON / OFF (default OFF)
3VA1 molded case circuit breaker
Starter protection – TM120M (3VA11/12)
Front view
Characteristic curve
Ii
Size
In
160 A
(3VA11)
Class
M, H
250 A
(3VA12)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
Ii
32 A
40 A
50 A
63 A
80 A
100 A
125 A
160 A
200 A
220 … 510 A
280 … 640 A
350 … 800 A
440 … 1010 A
560 ... 1280 A
700 ... 1600 A
875 … 2000 A
1120 ... 2560 A
1400 … 2800 A
3VA2 molded case circuit breaker
Starter protection – ETU310M I
Front view
Characteristic curve
Ii
Size
In
160 A
(3VA21)
Class
C, L
250 A
(3VA22)
400 A
(3VA23)
630 A
(3VA24)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
Ii
25 A
40 A
63 A
100 A
160 A
200 A
75 … 375 A
120 … 600 A
189 … 945 A
300 … 1.500 A
480 … 2.400 A
600 … 3.000 A
250 A
750 … 3.750 A
400 A
500 A
1.200 … 6.000 A
1.500 … 7.500 A
3VA2 molded case circuit breaker
Motor protection – ETU350M LSI
Front view
Size
In
Ir
Tc
10 / 10E
10A
20 / 20E
17
17
17
17
17
15
Isd
tsd
Ii
25 A
40 A
63 A
100 A
160 A
200 A
10 … 25 A
16 … 40 A
25 … 63 A
40 … 100 A
63 … 160 A
100 … 200 A
400 A
(3VA23)
250 A
100 … 250 A
17
3.750A
630 A
(3VA24)
400 A
500 A
160 … 400 A
250 … 500 A
17
15
6.000 A
7.500 A
160 A
(3VA21)
Class
M, C
Characteristic curve
250 A
(3VA22)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
4
8
3 …15 Ir
30 ms
375 A
600 A
945 A
1.500 A
2.400 A
3.000 A
3VA2 molded case circuit breaker
Motor protection – ETU860M LSIG (1/2)
Front view
Size
160 A
(3VA21)
Class
M, C
250 A
(3VA22)
400 A
(3VA23)
630 A
(3VA24)
Characteristic curve
In
Ir
Isd
25 A
40 A
10 … 25 A
16 … 40 A
63 A
25 … 63 A
100 A
40 … 100 A
160 A
63 … 160 A
200 A
80 … 200 A
250 A
100 … 250 A
400 A
160 … 400 A
500 A
250 … 500 A
1,2 … 15 x In
Unrestricted / © Siemens AG 2015. All Rights Reserved.
tsd
Ii
30 ms
Ig
tg
75 … 375 A 5 … 25 A, OFF
120 … 600 A 8 … 40 A, OFF
13 … 63 A,
189 … 945 A
OFF
20 … 100 A,
300 … 1.500 A
OFF
32 … 160 A,
480 … 2.400 A
OFF 50 … 800 ms
50 … 250 A,
600… 3.000 A
OFF
50 … 250 A,
750… 3.750 A
OFF
80 … 400 A,
1.200 … 6.000 A
OFF
100 … 500 A,
1.500 … 7.500 A
OFF
3VA2 molded case circuit breaker
Motor protection – ETU860M LSIG (2/2)
Front view
Size
Class
M, C
Characteristic curve
In
160 A
(3VA21)
25 A
40 A
63 A
100 A
250 A
(3VA22)
160 A
200 A
250 A
400 A
(3VA23)
630 A
(3VA24)
Tc: Tripping Class
Tp: Tripping Time
400 A
500 A
TC
10A
4
10 / 10E 20 / 20E
8
Tp
I
Ib
tb
I<<
t<<
30
30E
17
17
17
17
24
24
24
24
24
24
24
24
3 … 30 s
3 … 30 s
3 … 30 s
3 … 25 s
17
12
17
20
15
24
–
–
24
3 … 20 s OFF, 5 … 50% 162 … 1600 A, OFF 1 … 10s 0,3 … 0,9 x Ir 1 … 200s
3 … 15 s
240 … 2000 A, OFF
3 … 30 s
300 … 2500 A, OFF
17
12
24
15
24
–
3 … 25 s
3 … 15 s
I: unsymmetrie of the current
I<<: pick up current idle protection
t<<: delay time idle protection
Unrestricted / © Siemens AG 2015. All Rights Reserved.
30 … 250 A, OFF
48 … 400 A, OFF
76 … 630 A, OFF
120 … 1000 A, OFF
480 … 4000 A, OFF
600 … 5000 A, OFF
Ib: pick up time blocking protection
tb: pick up current blocking protection
3VA tables with IE3 motors – motor protection
breaker
SENTRON 3VA circuit breaker for motor protection
In this case, the 3VA circuit breaker for motor protection is also doing the functional
switching
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Starter protection/motor protection – tested combinations
Starter protection
Motor protection
MCCB (3VA)
Instantaneous
protection
MCCB (3VA)
Instantaneous
protection
Overload protection
… and more
Contactor
Functional
switching
Contactor
Functional
switching
Overload relay
Overload
protection
Motor
Unrestricted / © Siemens AG 2015. All Rights Reserved.
Motor
Coordination tests
Tested combinations can be
found in the shape of an FAQ in
SIOS.
The corresponding factory
certificate can also be found in
SIOS.
Please note for these
combinations:
 Functional switching is done
by the contactor
 Mounting rules have to be
heeded
 Unless otherwise indicated,
the combinations are IE3ready
3VA tables with IE3 motors – motor protection
breaker-contactor-combination
SENTRON 3VA motor protection breaker – device combinations
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA tables with IE3 motors – starter protection
breaker-contactor-overload relay-combination
SENTRON 3VA1 starter protection breakers – device combinations
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA tables with IE3 motors – starter protection
breaker-contactor-overload relay-combination
SENTRON 3VA starter protection breakers – device combinations with overload relay 3RB20/21
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA tables with IE3 motors – starter protection
breaker-contactor-overload relay-combination
SENTRON 3VA starter protection breakers – device combinations with overload relay 3RB22/23
and SIMOCODE pro 3UF7
Unrestricted / © Siemens AG 2015. All Rights Reserved.