Totally Integrated Power - SENTRON 3VA molded case circuit breaker Starter and motor protection Unrestricted / © Siemens AG 2015. All Rights Reserved. siemens.com/3VA 3VA molded case circuit breaker Starter and motor protection 3VA1 MCCB 3VA2 MCCB Applications Starter protection Starter and motor protection Frame sizes 60 A 160 A Rated currents 32 A – 200 A 25 A - 500 A Trip Unit AM I / LSI; LSIG IEC breaking capacity Icu 415 V 50/60 Hz 55kA , 70kA 55kA, 110kA Communication Not available Available Metering Not available Available Unrestricted / © Siemens AG 2015. All Rights Reserved. 250 A 250 A 400 A 630 A 3VA molded case circuit breaker Starter protection vs. motor protection Starter protection Motor protection MCCB (3VA) Instantaneous protection MCCB (3VA) Instantaneous protection Overload protection … and more Contactor Functional switching Contactor Functional switching MCCB (3VA) Instantaneous protection Overload protection Functional switching … and more Overload relay (3RB; 3UF7) Overload protection Motor Unrestricted / © Siemens AG 2015. All Rights Reserved. Motor Motor 3VA molded case circuit breaker Starter protection and motor protection 3VA1 3VA2 3VA2 3VA2 TM120M ETU310M ETU350M ETU860M Starter protection Starter protection Motor protection Motor protection L overload (long time) Ir Thermal memory S short time delay short circuit Isd Protection I instantaneous short circuit Ii G ground fault Ig Additional features Prepared for higher inrush currents from IE3 motors Phase unbalance protection available * * Blocking protection * * Idle running protection Power metering integrated Communication as option * Function can be achieved with the overload relay (3RB; 3UF7) Unrestricted / © Siemens AG 2015. All Rights Reserved. 3VA molded case circuit breaker IE3 standard (1/2) The IE3 standard is mandatory in Europe since January 1st 2015 It applies to • Newly installed motors • Motors in continuous operation In the power range 0.75 7.5 from 2017 on Unrestricted / © Siemens AG 2015. All Rights Reserved. 375 kW from 2015 on 3VA molded case circuit breaker IE3 standard (2/2) Before Nominal current Motors according to IE3 standard IE3 Premium Efficiency motors • Higher efficiency factor because of less ohmic loss • Reduced nominal current Starting current Less ohmic loss • Lower resistance • Increase of starting current Inrush current A fact that you won‘t find in data sheets - but what we have analyzed for you: The inrush current rises enormously! Unrestricted / © Siemens AG 2015. All Rights Reserved. 3VA molded case circuit breaker Inrush current and instantaneous short circuit 3VA1 3VA2 3VA2 3VA2 TM120M ETU310M ETU350M ETU860M Starter protection Starter protection Motor protection Motor protection 7 … 16 x In2) 3 … 15 x In1) 15 x In1) 3 …15 x In1) Minimum rotary switch setting Minimum rotary switch setting Protection Ii Ii Default setting Minimum rotary switch setting Minimum setting All our 3VA molded case circuit breakers are prepared for increased inrush current generated by IE3 motors. 1) Some frames sizes and current ratings have limited adjustment setting. For more information, please refer to the device manual/FAQ@ SIOS. 2) Up to 125 A, In: 200 A Ii = 7….14 x In Unrestricted / © Siemens AG 2015. All Rights Reserved. 3VA molded case circuit breaker Overload parameter settings 3VA2 3VA2 ETU350M ETU860M Motor protection Motor protection Ir 0,4 … 1 x In 0,4 … 1 x In Setting time delay @ overload Trip class TC Trip class Tc or Tripping time TP Trip class TC 10A, 10 / 10E 20 / 20E 10A, 10 / 10E, 20 / 20E, 30 / 30E Protection Tripping time TP 3 … 30 s 1) Using the mode „Trip class TC“ to set the time delay @ overload means always to select a time range for overload protection. Example: TC = 20 6s < TP ≤ 20s according to IEC 60947-4-1 A more precise way to set the tripping time is to directly edit the TP with the ETU860M. 1) Some frames sizes and current ratings have limited adjustment setting. For more information, please refer to the device manual/FAQ@ SIOS. Unrestricted / © Siemens AG 2015. All Rights Reserved. 3VA molded case circuit breaker Tripping time, trip class acc. to IEC 60947-4-1 Tripping classes of overload protection devices in acc. with IEC 60947-41 CLASS Tripping time 10 A 2 s < tA < 10 s t 120 100 50 20 10 and 10E 4 and 5 s < tA < 10 s 20 and 20E 6 and 10 s < tA < 20 s 5 30 and 30E 9 and 20 s < tA < 30 s 2 1 50 The tripping classes are based on the tripping time (tA) at 7.2-times the set current Ie from cold state. Suffix “E” in class means narrower tolerance available in solid-state OLR The overload protection device has to trip within these times! Unrestricted / © Siemens AG 2015. All Rights Reserved. 10 CLASS 30 CLASS 25 CLASS 20 CLASS 15 CLASS 10 CLASS 5 20 10 5 Tripping characteristic curve 2 for 3-pole sym. load 1 0,7 1 2 x Ie 5 8 3VA molded case circuit breaker Phase unbalance protection If one of the 3 phases fail, a three-phase motor continues to run like a single-phase motor with an enormous decrease of load torque. There is a high risk that the motor stops rotating. With the feature „phase unbalance protection“ the 3VA molded case circuit breaker trips by exceeding the phase unbalance values for the time tunbalance. 3VA2 3VA2 ETU350M ETU860M Motor protection Motor protection 40% fix 5 … 50% (default 40%) ON ON / OFF (default ON) 0,7s during start up 4s during normal operation 0,7s during start up 4s during normal operation Protection Unbalance Ratio Phase unbalance protection availability Delay time tunbalance The average current and the unbalance ratio are calculated based on: Unrestricted / © Siemens AG 2015. All Rights Reserved. 3VA molded case circuit breaker Blocking protection Application examples for blocking protection • Stone crusher (stone too hard / large) • Conveyer belt (transport goods wedged) Motor blocking (or falling back behind breakdown torque) generates high motor current (close to starting current). But it‘s still not as high as a short circuit current! Without the blocking protection feature it might take up to 30s or more (depending on current and TP setting) until the breaker trips unnecessary thermal stress 3VA2 ETU860M Motor protection Protection Ib Delay time tb Blocking protection availability 1,2 … 10 x In in A (default 10) 1 … 10s (default 1s) ON / OFF (default ON) During the start up phase (ramp up), blocking protection is automatically disabled until the motor reaches the operating speed (tstart). tstart equals tb. Unrestricted / © Siemens AG 2015. All Rights Reserved. 3VA molded case circuit breaker Idle running protection Application examples for idle running protection • Load transmission between motor and application was lost (belt rupture, broken chain …) • Pump, compressor With the accessory for idle running protection the motor can be switched off by tripping the circuit breaker. 3VA2 ETU860M Motor protection Protection I<< Delay time t<< Idle running protection availability Unrestricted / © Siemens AG 2015. All Rights Reserved. 0,3 … 0,9 x Ir (default 0,9) 1 … 200s (default 1s) ON / OFF (default OFF) 3VA1 molded case circuit breaker Starter protection – TM120M (3VA11/12) Front view Characteristic curve Ii Size In 160 A (3VA11) Class M, H 250 A (3VA12) Unrestricted / © Siemens AG 2015. All Rights Reserved. Ii 32 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 220 … 510 A 280 … 640 A 350 … 800 A 440 … 1010 A 560 ... 1280 A 700 ... 1600 A 875 … 2000 A 1120 ... 2560 A 1400 … 2800 A 3VA2 molded case circuit breaker Starter protection – ETU310M I Front view Characteristic curve Ii Size In 160 A (3VA21) Class C, L 250 A (3VA22) 400 A (3VA23) 630 A (3VA24) Unrestricted / © Siemens AG 2015. All Rights Reserved. Ii 25 A 40 A 63 A 100 A 160 A 200 A 75 … 375 A 120 … 600 A 189 … 945 A 300 … 1.500 A 480 … 2.400 A 600 … 3.000 A 250 A 750 … 3.750 A 400 A 500 A 1.200 … 6.000 A 1.500 … 7.500 A 3VA2 molded case circuit breaker Motor protection – ETU350M LSI Front view Size In Ir Tc 10 / 10E 10A 20 / 20E 17 17 17 17 17 15 Isd tsd Ii 25 A 40 A 63 A 100 A 160 A 200 A 10 … 25 A 16 … 40 A 25 … 63 A 40 … 100 A 63 … 160 A 100 … 200 A 400 A (3VA23) 250 A 100 … 250 A 17 3.750A 630 A (3VA24) 400 A 500 A 160 … 400 A 250 … 500 A 17 15 6.000 A 7.500 A 160 A (3VA21) Class M, C Characteristic curve 250 A (3VA22) Unrestricted / © Siemens AG 2015. All Rights Reserved. 4 8 3 …15 Ir 30 ms 375 A 600 A 945 A 1.500 A 2.400 A 3.000 A 3VA2 molded case circuit breaker Motor protection – ETU860M LSIG (1/2) Front view Size 160 A (3VA21) Class M, C 250 A (3VA22) 400 A (3VA23) 630 A (3VA24) Characteristic curve In Ir Isd 25 A 40 A 10 … 25 A 16 … 40 A 63 A 25 … 63 A 100 A 40 … 100 A 160 A 63 … 160 A 200 A 80 … 200 A 250 A 100 … 250 A 400 A 160 … 400 A 500 A 250 … 500 A 1,2 … 15 x In Unrestricted / © Siemens AG 2015. All Rights Reserved. tsd Ii 30 ms Ig tg 75 … 375 A 5 … 25 A, OFF 120 … 600 A 8 … 40 A, OFF 13 … 63 A, 189 … 945 A OFF 20 … 100 A, 300 … 1.500 A OFF 32 … 160 A, 480 … 2.400 A OFF 50 … 800 ms 50 … 250 A, 600… 3.000 A OFF 50 … 250 A, 750… 3.750 A OFF 80 … 400 A, 1.200 … 6.000 A OFF 100 … 500 A, 1.500 … 7.500 A OFF 3VA2 molded case circuit breaker Motor protection – ETU860M LSIG (2/2) Front view Size Class M, C Characteristic curve In 160 A (3VA21) 25 A 40 A 63 A 100 A 250 A (3VA22) 160 A 200 A 250 A 400 A (3VA23) 630 A (3VA24) Tc: Tripping Class Tp: Tripping Time 400 A 500 A TC 10A 4 10 / 10E 20 / 20E 8 Tp I Ib tb I<< t<< 30 30E 17 17 17 17 24 24 24 24 24 24 24 24 3 … 30 s 3 … 30 s 3 … 30 s 3 … 25 s 17 12 17 20 15 24 – – 24 3 … 20 s OFF, 5 … 50% 162 … 1600 A, OFF 1 … 10s 0,3 … 0,9 x Ir 1 … 200s 3 … 15 s 240 … 2000 A, OFF 3 … 30 s 300 … 2500 A, OFF 17 12 24 15 24 – 3 … 25 s 3 … 15 s I: unsymmetrie of the current I<<: pick up current idle protection t<<: delay time idle protection Unrestricted / © Siemens AG 2015. All Rights Reserved. 30 … 250 A, OFF 48 … 400 A, OFF 76 … 630 A, OFF 120 … 1000 A, OFF 480 … 4000 A, OFF 600 … 5000 A, OFF Ib: pick up time blocking protection tb: pick up current blocking protection 3VA tables with IE3 motors – motor protection breaker SENTRON 3VA circuit breaker for motor protection In this case, the 3VA circuit breaker for motor protection is also doing the functional switching Unrestricted / © Siemens AG 2015. All Rights Reserved. 3VA molded case circuit breaker Starter protection/motor protection – tested combinations Starter protection Motor protection MCCB (3VA) Instantaneous protection MCCB (3VA) Instantaneous protection Overload protection … and more Contactor Functional switching Contactor Functional switching Overload relay Overload protection Motor Unrestricted / © Siemens AG 2015. All Rights Reserved. Motor Coordination tests Tested combinations can be found in the shape of an FAQ in SIOS. The corresponding factory certificate can also be found in SIOS. Please note for these combinations: Functional switching is done by the contactor Mounting rules have to be heeded Unless otherwise indicated, the combinations are IE3ready 3VA tables with IE3 motors – motor protection breaker-contactor-combination SENTRON 3VA motor protection breaker – device combinations Unrestricted / © Siemens AG 2015. All Rights Reserved. 3VA tables with IE3 motors – starter protection breaker-contactor-overload relay-combination SENTRON 3VA1 starter protection breakers – device combinations Unrestricted / © Siemens AG 2015. All Rights Reserved. 3VA tables with IE3 motors – starter protection breaker-contactor-overload relay-combination SENTRON 3VA starter protection breakers – device combinations with overload relay 3RB20/21 Unrestricted / © Siemens AG 2015. All Rights Reserved. 3VA tables with IE3 motors – starter protection breaker-contactor-overload relay-combination SENTRON 3VA starter protection breakers – device combinations with overload relay 3RB22/23 and SIMOCODE pro 3UF7 Unrestricted / © Siemens AG 2015. All Rights Reserved. Thank you for your attention! siemens.com/3VA Unrestricted / © Siemens AG 2015. All Rights Reserved.