77 CHAPTER 4 TESTING AND CORRELATION 4.1. INTRODUCTION The testing of a machine both at the work and at site is very important for a smooth operation of the machine. Tests are carried out at the work to determine whether the machine has been manufactured according to specifications of the customer and are in conformity with the design of the electrical and mechanical designers. Hence testing is essential at manufacturing works. This chapter, therefore, describes preliminary tests that have to be performed before assembling the machine in the test beds. Here, tests performed in the test beds and the site tests i.e., tests on machines before commissioning are also discussed. 4.2 OPEN CIRCUIT CHARACTERISTICS (MAGNETIZATION CURVE) The fundamental electric properties of an alternator can be well presented by its magnetization (no load) and short circuit characteristics. All the parameters characterizing the operation of the generator can be deduced from the above mentioned curves provided stator winding leakage reactance is known. i.e, basic vector diagram of the machine for every load may be constructed. The graphical relationship which exists between the exciting current and the terminal voltage of armature is called magnetization curve. It can be obtained experimentally by taking various values of exciting current 78 and observing the corresponding armature voltages the machine being operated on open circuit. Usually, it is necessary to insert a considerable resistance in series with the field winding in addition to the ordinary shunt regulator in order to bring down the exciting currents so as to obtain points on the lower portion of the curve. The resulting graph follows the general shape of the B-H curve. 4.2.1 OPEN CIRCUIT TEST on SRA: 1) Connections are made as per the circuit diagram as shown in figure 4.1. 2) The M-G Set is brought to synchronous speed by varying DC motor field. 3) By gradually varying the excitation, the corresponding open circuit voltages are noted and tabulated as shown in table 4.1. Graph is drawn between OC voltage and excitation as shown in fig 4.2. 79 Fig 4.1: Circuit diagram for OCC test 80 Table 4.1 Observations of open circuit test S.No. Field current Induced voltage (If) in Amp. (V1) in Volts. 1 0 9 2 1.0 54 3 1.5 90 4 2.0 120 5 2.5 150 6 3.0 180 7 3.5 204 8 4.0 219 9 4.5 234 10 5.0 240 Open circuit voltage in Volts 250 200 150 100 50 0 0 1 2 3 4 Field Current in Amp Fig. 4.2: open circuit characteristics 5 6 81 4.3 SHORT CIRCUIT CHARACTERISTICS Under short circuit conditions the armature terminals of a synchronous machine which is being driven by a prime mover at synchronous speed are short circuited directly or through ammeter. It has become a conventional that unless and until otherwise mentioned, a short circuited synchronous machine is understood to be a machine, where all the three terminals of which are short circuited. The other short circuited conditions are those of two phase and single phase short circuits as shown in figure , 4.3 , 4.4 and 4.5 respectively. Fig.4.3: Three-phase short circuited synchronous machines Fig.4.4: Two-phase short circuited synchronous machines 82 Fig.4.5: One-phase short circuited synchronous machines A short circuit on a synchronous machine has the internal effect as an inductive load since in comparison to the armature leakage reactance, the armature resistance in almost all synchronous machines has a negligible value. The armature mmf acts directly opposed to the field mmf in such a case. The resultant ampere-turns inducing the armature emf are, therefore the numerical difference between the field and armature mmfs. Since the terminals of the machine are short circuited, the emf induced in the armature winding by the resultant ampere-turns is equal to the voltage drop in the winding itself. If Me, Ma be the field and armature mmf’s, the difference Me-Ma, representing the resultant mmf Mr, induces an emf in the armature winding. This induced voltage impedance drop IZa in the armature winding. The balances occ and the scc characteristics are shown in figure 4.6 In a short circuited synchronous machine the field current is gradually increased, the current flowing in the armature winding 83 increases proportionally. ionally. From the results so recorded, data to determine short circuit ratio (SCR) could be obtained. Fig.4.6: OCC and SCC characteristics 4.3.1. SHORT CIRCUIT TEST on SRA: 1) Connections are made as per requirement as shown in fig 4.7. 2) The M-G G Set is brought to synchronous speed. 3) A three phase short circuit is applied to the output of the alternator through contactor. 4) By varying the field excitation the corresponding short circuit current readings are noted and tabulated in table 4.2. 5) A graph is drawn between short circuit current and excitation current as shown in Fig. 4.8. 84 Fig.4.7: Circuit diagram for short circuit test 85 Table 4.2: observations of short circuit test Field current S.No. Short Circuit (If) in Amp. current (Isc) in A mp. 1 0 0 2 1.0 1.4 3 1.5 2.3 4 2.0 3.0 5 2.5 3.8 6 3.0 4.5 7 3.5 5.4 8 4.0 6.0 9 4.5 6.6 10 5.0 7.5 8 Short circuit current in Amp 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 Field current in Amp Fig. 4.8: SC characteristics 4.4 SHORT CIRCUIT RATIO: The short circuit ratio of a synchronous machine is defined as the ratio of the field current required to produce rated voltage at rated 86 speed and no load to the field current required to produce rated armature current under a sustained three phase short circuit. If there were no saturation, the short circuit ratio would be equal to the reciprocal of the synchronous reactance. Saturation has the effect of increasing the short circuit ratio .The short circuit ratio has significance with respect to both the performance of the machine and its cost. The lower the short circuit ratio, the greater is the change in field current required to maintain constant terminal voltage for a given change in load and lower is the steady state limit. If there is no saturation the short circuit ratio would be constant at all voltage or to be exact at all excitation currents or fields. Hence the maximum power available in steady state is directly proportional to the short circuit ratio and can be increased by increasing the short circuit ratio .The short circuit ratio can be increased by increasing the air gap of the machine. An increase in air gap would mean a bigger model and hence contain more material. The electrical and magnetic parts of the machine need more copper and iron respectively and hence the cost of the machine increases. An increase in short circuit ratio further results in increase in the steady state or sustained short circuit current and hence the designer has to find a compromise. The maximum power in steady state condition is also dependent upon excitation, therefore as a result of improvements in excitation systems 87 there has been a trend towards the use of lower short circuit ratio and consequently lower cost. Steam turbine driven generator i.e. turbo alternator are built with S.C.R anywhere in the range from 0.5 to 1.1 .Most modern generator of this type have a ratios range from 0.8 to 1.1but it appears that 0.7 is more likely used. Water wheel generators have been designed with short circuit ratio up to 2.How ever modern waterwheel generators are universally designed with S.C.R from 0.9 to 1.10.Synchronous condensers have the value of S.C.R as low as 0.5. 4.4.1 Short circuit ratio of SRA The field current required to produce an induced emf equal to rated voltage of 230V is 4.3A ( as derived from the Fig. 4.2). The field current required to circulate a short circuit current equal to rated current of 7A is 4.7A (as derived from the Fig.4.8). SCR of SRA = 4.3/4.7 = 0.91 As this designed SRA is of low rating, it does not fall into saturation while it is shorted. Hence synchronous reactance (Xs) of this SRA is reciprocal of SCR. Xs = 1/ (0.91) = 1.098 88 4.5. HEAT RUN TEST ON SRA Heat run test of a synchronous machine determines the temperature rise which is measured by using IR THERMOMETER as shown in figure 4.10. This of the various parts of the machine under rated load conditions. Depending on the class of insulation used the temperature in any part of the machine should not increase beyond permissible limits. In the case of large machines, it is not possible to load them for rated conditions for test bed, as loading in such cases requires large prime movers and loading capacities. Generally, in test beds the full load heat run test is split into two heat run tests namely the open circuit and short Circuit heat run tests. The final temperature rise on full load is then determined by a superimposition of the two heat run tests. It is inferred that the temperature rise follows very nearly an exponential function and that the thermal-time-constant of synchronous machines vary between 60 to 240 minutes. The temperature rise in the field winding can be watched continuously by measuring the resistance of the winding by recording the voltage and current in the field winding. The core temperature should in no way be above 100°C as under such conditions the teeth which have much higher flux densities are definitely about 20°C higher than the core. The resistance is measured by using the micro ohmmeter shown in figure 4.9. All the observations are tabulated in table 4.3 89 and the measured cold resistance and heat resistance are tabulated in table 4.4. Table4.3: Observations of heat run test conducted on 06-04-2010 Voltages in V V1 V2 S.No Time 1 10:30 AM 390.1 389.5 389.2 6.94 6.93 6.91 1504 2 11:00 AM 387.8 387.5 387.6 6.83 6.82 6.80 1505 3 11:30 AM 385.6 385.3 385.8 6.87 6.81 6.84 1504 4 12:00 384.3 384.5 384.8 6.78 6.75 6.79 NOON 1508 5 12:30 PM 383 384.4 385.2 6.76 6.74 6.73 1508 6 1:00 PM 382 382.8 6.75 6.74 6.78 1508 7 2:00 PM 384.2 382.6 383.2 6.78 6.77 6.80 1508 8 3:00 PM 386.5 383.8 382.6 6.82 6.81 6.83 1508 9 4:00 PM 384.7 385.4 384.2 6.78 6.78 6.77 1508 10 4:30 PM 383.9 1509 384 V3 Currents in A 383 I1 I2 I3 383.5 6.70 6.77 6.76 N(rpm) … (to be continued) 90 Table 4.3: Observations of heat run test Armature Field S.No Time D.C (Iarm) D.C (Varm) D.C (If) D.C (Vf) Power meter (Kw) 1 10:30 AM 3.1 198 3.59 141 4.64 2 11:00 AM 3.0 202 3.72 152 4.57 3 11:30 AM 3.0 202 3.68 151 4.54 4 12:00 PM 2.9 200 3.71 152 4.48 5 12:30 NOON 2.9 201 3.71 153 4.46 6 1:00 PM 2.9 207 3.71 144 4.49 7 2:00 PM 2.9 197 3.71 134 4.49 8 3:00 PM 3.0 195 3.71 134 4.49 9 4:00 PM 3.0 193 3.71 134 4.49 10 4:30 PM 3.0 191 3.71 134 4.45 … (to be continued) 91 Table 4.3: Observations of heat run test Temperatures in degree centigrade Body Driving end Nondriving end S.No Time Room 1 10:30 AM 34.4 34.4 -- 37 2 11:00 AM 34.9 47.2 -- 39 3 11:30 AM 34.9 51.1 38 41 4 12:00 AM 34.9 55.3 40 42 5 12:30 NOON 34.9 56 42 44 6 1:00 PM 36.3 61 43 44 7 2:00 PM 36.9 64 45 45 8 3:00 PM 36.9 65 45 45 9 4:00 PM 36.9 66 46 46 10 4:30PM 37.7 66 46.5 46.5 92 Fig.4.9: Resistance is measured by Micro ohm meter LR-2045 Fig.4.10: Temperature measured by FLUKE IR THERMOMETER 93 Table 4.4: Cold resistance and heat resistance Beginning ( 10 : 30 AM) Ending ( 4 : 30 PM) Line Resistance Line Resistance RY = 96.6mΩ YB = 96.9.mΩ BR = 96.4mΩ RY = 105.3mΩ YB = 105.4mΩ BR = 105.1mΩ Phase resistances Phase resistances RN = 47.6mΩ YN = 47.9mΩ BN = 47.7mΩ . RN = 51.7mΩ YN = 51.1mΩ BN = 51.4mΩ Field Resistance Field Resistance 0.017 kΩ 0.018 kΩ It is inferred from the table 4.3 that the thermal time constant of this SRA is approximately 90 minutes. 4.6. LOAD CHARACTERISTICS: The load characteristic of an alternator is obtained by determining the relationship between the terminal voltage and the load current, while the exciting current and the speed is kept constant. As the armature current is increased, the terminal voltage drops due to many reasons, but when The power factor is leading the load characteristic curve may raise at first. Each curve is nearly straight at the beginning but tends to droop because, with the increase in load 94 current, the angle of lag between current and emf, owing to the original field increases. In modern alternators the steady short circuit current is not much greater than full load rated current .This is purposely arranged to prevent excessive current in the event of short circuit. 4.6.1 Load Test on SRA: In order to obtain the relation between terminal voltage and load current and also to determine the efficiency, load test [25] is conducted. The MG set is made to run at synchronous speed, the resistive load bank is gradually applied on the machine and the corresponding readings are tabulated as shown in the table 4.5 and graph is drawn as shown in Fig. 4.11. 95 Table 4.5: Observations of load test Power meter readings Terminal voltage (VL) in V Load Current (IL) in A Field Current (If) in A 0.8 392 1.2 3.8 1.22 392 1.8 3.8 1.6 385 2.4 3.8 1.8 384 2.8 3.8 2.18 382 3.3 3.8 2.4 382 3.7 3.8 2.82 378 4.3 3.8 3.2 378 4.9 3.8 3.5 378 5.4 3.8 3.7 376 5.8 3.8 4.2 375 6.6 3.8 4.6 374 7.2 3.8 In Kw 96 Terminal Voltage in Volts 400 350 300 250 200 150 100 50 0 0 1 2 3 4 5 6 7 8 Load current in Amp Fig. 4.11: Load characteristics 4.6.2 Efficiency The input of the alternator is the mechanical torque of the D.C motor which is measured by the TORQUE SENSOR as shown in figure 4.12. and its corresponding block diagram is shown in figure 4.13 Fig.4.12 Torque Sensor 97 D.C MOTOR TORQUE SENSOR S.R.A Fig. 4.13 Block diagram to find torque Efficiency of the SRA = Output of SRA/ Input of SRA Output of SRA is nothing but electrical power = Pout = 3×VI l l cosφ = 3×378×5.4×1 Pout = 3535.46W Input to SRA is nothing but output of DC motor which is mechanical power Generally power is defined as torque (T) × angular velocity ( ω )= 2π N Pin = ×T 60 2π × 1500 Pin = × 26.275 60 Pin = 4127.25W Shaft torque 26.275 is read by torque sensor Efficiency of the SRA is 98 η= Pout 3535.46 × 100 = × 100 Pin 4127.25 η = 85.66% Taking the efficiency of the prime mover i.e., DC motor as 86.5% Efficiency of the MG-set = Efficiency of DC motor × Efficiency of SRA = 0.865×0.8566 =0.7409 =74.09% 4.7 CONCEPT OF BALANCED AND UNBALANCED LOAD CONDITIONS A synchronous machine operating under balanced and unbalanced conditions can be analyzed on the basis of two basic concepts viz. The method of symmetrical components and Blondel’s two reaction theory. The set of three equal stator currents which produce a flux wave rotating at synchronous speed with the rotor forms positive phase sequence currents and they are designated as Ia1,Ib1 and Ic1. The set of three equal stator currents which produce a flux wave rotating at synchronous speed against the rotor forms negative phase sequence currents and they are designated as Ia2,Ic2 and Ib2. The set of three equal stator currents which produce no net fundamental air gap flux (because the three currents are in time phase under displaced by 120 elec degrees apart) identified as zero sequence currents and they are designated as Ia0,Ib0 and Ic0. 99 Positive, negative and zero sequence currents may exist not only as fundamental frequency currents but also as harmonics. For example, under balanced conditions all triple harmonic currents are zero sequence. Blondel’s two reaction theory deals mainly with positive sequence currents [26]. Unbalanced loading of a generator effects heating of solid iron and damping circuits which is due to rotor currents induced at twice the supply frequency. This abnormal heating of solid iron limits the negative sequence capability of machine [27]. The additional losses due to negative phase sequence stator currents will exist on the surface of the rotor for solid rotor turbo generators [28]. The study of unbalanced currents reveals significance of rotor design features and practices. 4.7.1 BALANCED LOAD TEST In order to observe the variations in the voltage and currents while the SRA is subjected to phase loading, balanced load test is conducted. Rheostat load has been connected to the SRA and the load setting across each branch is done by selector switches. The corresponding readings captured by power meter are tabulated in table 4.6 and 0ne of the reading is shown in the fig: 4.14. 100 Table 4.6: Observations of balanced load test DC MOTOR SIDE S.No Input Input voltage current ALTERNATOR SIDE V1 V2 V3 I1 I2 I3 Power (kW) 1 195.2 2.12 102.5 102.0 103.0 0.56 0.56 0.56 0.17 2 193.2 2.52 180.1 180.3 180.1 4.3 4.3 4.3 2.32 3 192.7 2.95 232.2 231.1 232.2 5.9 5.9 5.9 4.11 Fig: 4.14 power meter reading depicting balanced loads 101 4.7.2 UNBALANCED LOAD TEST In order to observe the variations in the voltage and currents while the SRA is subjected to asymmetrical loads [29], unbalanced load test is conducted. Rheostat load has been connected to the SRA and the load setting across each branch is done by selector switches. The corresponding readings captured by power meter are tabulated in table 4.7 and 0ne of the reading is shown in the fig: 4.15. Table 4.7: Observations of unbalanced load test DC MOTOR SIDE ALTERNATOR SIDE Input voltage Input current 1 195.4 2.13 102.3 2 194.4 2.32 58.2 3 192.2 2.51 S.No V1 81.5 V2 V3 103.1 104.6 P (Kw) I1 I2 I3 0.55 0.57 0.56 0.17 50.9 40.8 1.45 1.56 2.74 0.27 67.3 64.2 0.98 1.61 2.72 0.35 102 Fig.4.15: Readings captured by power meter CW-140 The inverse currents [30] caused by unbalanced load in the rotor pulsate with twice the grid frequency. Therefore, the associated eddy currents in the solid rotor iron flow in a thin layer under the iron surface specified by the penetration depth. Besides the skin effect forcing them to flow in a thin layer under the iron surfaces the eddy currents are subjected to a second skin effect. It becomes obvious when encircling both the currents in the damper and the slot walls. Together they built up a resultant ampere turn value which drives a common leakage flux across the slot. It is well known that the damper is subjected to a skin effect that displaces this currents towards the slot openings. Without any additional reasoning it can be stated that the same applies to the eddy currents in the slot walls. Thus, the currents in the iron are not only limited by the impedances built up by the iron but also by the common leakage reactance attributed to the damper and iron currents. 103 The additional losses of the SRA due to negative sequence currents [31] is calculated based on the readings recorded in the above table 4.6 & 4.7. In other words, the additional losses [32] due to negative sequence currents is nothing but the difference in power input to the DC motor while the MG set subjected to both the balanced and unbalanced loads. The input power drawn by the DC motor while the MG set is connected to the balanced load = 195.2*2.12 = 413.824 W The input power drawn by the DC motor while the MG set is connected to unbalanced load = 195.4*2.13 = 416.202 W Additional loss of the SRA is nothing but the difference of above two inputs i.e., 416.202 - 413.824 = 2.378 W ∴ Additional losses due to Negative-seq. currents = 2.378 W Total losses of SRA =output – input = 3876.14-3320.3 = 555.84W The percentage of additional losses = 2.378/555.8 = 0.43% 104 As this designed SRA is of low rating and the wedges are made of Glass laminates, the additional losses due to negative sequence currents are very small. In large machines the wedges are metallic and the rotor is made of solid iron forging. Hence the negative sequence capability is limited to 10 % in order to limit negative sequence losses and rotor heating. 4.8 THREE PHASE SHORT CIRCUIT FAULT ON A SYNCHRONOUS GENERATOR: A sudden short circuit [34] in a synchronous machine takes place if the machine is running at synchronous speed and having been excited is suddenly short circuited on its terminals. This may take place either when the machine is running on no-load or when it is loaded. The loading may either be direct-loading at the terminals of the machine or the machine may be synchronized to a grid supplying power to the grid therewith. Modern synchronous machines are starconnected. Synchronous machines with isolated neutrals and as such conditions of a 3-phase or a 2-phase sudden short-circuit are the only ones, which are of importance from a practical point of view. As a result of sudden short-circuits, large currents flow in the machines. Knowledge of these currents is essential in order to design the support of the winding-head and the foundation of the machines. In no-load operation of the synchronous machine, the total flux linking the rotor windings consists of the useful flux Φ and field leakage flux Фel. 105 Φ p o.c. = Φ + Φel In steady state 3-phase short circuit operation of the machine, the total flux linking the rotor windings consists of the effective useful flux Φeff and the field leakage flux. Φ p s.c. = Φeff + Φel The effective useful flux depends upon the effective field current and can be determined with the help of the equivalent circuit diagram of the synchronous machine in three-phase steady state short-circuit condition. Since both the field and the armature reaction m.m.f have their axes in the direct-axis, only the direct-axis equivalent circuit diagram is considered. Since the steady state 3-phase short-circuit corresponds to a purely inductive loading, the effect of the field current is partly neutralized by the armature reaction. For a given field current the induced e.m.f in the armature is ie .xad The armature current I = E i .x = e ad xal + xad xal + xad Hence the effective field current = ie − I = ie − ieeff = ie . Therefore xal xd ie .xad xal + xad 106 Φ eff = Φ. xal xd and hence Φ ps.c. = Φ. xal + Φel xd The total flux linking the rotor under short-circuit conditions Φ ps.c. is smaller than Φ po.c. which is the total flux linking the rotor under opencircuit conditions. In case a three-phase sudden short-circuit occurs on the terminals of an unloaded synchronous machine, the flux Φ po.c. cannot suddenly change its value to Φ ps.c. due to the magnetic inertia. The only difference between a sudden and a steady state short-circuit is called for by the transients which come into play because of magnetic inertia. Due to magnetic inertia, not only the rotor links total flux but also the flux values linked with the three stator phases at the instant of the sudden short circuit, have tendencies to retain their values. It is needless to say that a sudden short-circuits of the three terminals of an excited synchronous machine causes large shortcircuit currents to flow in the armature of the synchronous machine. These sudden short-circuit currents decay down to the steady state value within a few seconds. The sudden short-circuit test is carried out in order to determine the various constants mentioned and also to 107 see whether the machine is capable to withstand the mechanical stresses developed by the sudden short circuit currents. Before performing the test the machine should be carefully inspected to see that the bracing of the stator coil ends is satisfactory and that the foundation is in good condition and the holding down bolts are tight. The rotor should also be inspected to see that all keys and bolts are in place and properly tightened. Generally oscilloscope readings are taken to determine reactances. It is, therefore, necessary to short-circuit the machine by a circuit-breaker which closes all three circuits at almost exactly the same instant to avoid errors due to single phase action at the beginning of the short-circuit. Precision shunts are used for recording the currents on an oscilloscope. It must not be forgotten that the shunts have to be earthed. The major effects of short circuit are increase in armature current which in term result in large electro dynamic forces. These forces may either be between the winding head and iron are the between the winding heads are different phases. The large electro dynamo forces can result in a displacement of the end portions of the stator coils against one another. These displacements can result in an injury to the insulation of the winding and hence shut down of the machine. The end portions of the coils must, therefore, be specially braced. Besides the forces in the end portions of the coils, sudden short circuits by a synchronous machine result in torque pulsation. 108 As a result of these torques of high magnitude the casing, the shaft and the foundation must be designed to withstand the stresses. The very high values of armature currents cause I2R losses in the machine which in turn result increased heating of the machine. since the sudden short circuits are switched off with in a very short time, the heating in the machines due to them is generally not appreciable. 109 4.8.1 Three phase Short circuit Fault on SRA: TRANSIENT RECORDER Fig 4.16: Experimental setup for 3-phase 3 phase short circuit fault After assimilating the procedure of a three phase short circuit and its effects as mentioned in the section 4.8, a three three phase short circuit experiment is performed on the SRA as shown in Fig.4.16 and the corresponding circuit diagram in Fig. 4.17 110 Fig: 4.17 Circuit diagram of SRA under three phase SC fault 1) The connections are made as per the circuit diagram shown in Fig 4.17 2) The MG setup is made to run at synchronous speed 3) By varying excitation the output of the SRA is brought to the 50% of rated voltage. 4) The output terminals of SRA are short circuited through contactor and the supply to the prime mover is disconnected instantaneously. 5) The contactor is open immediately and the transient currents are captured by Transcoder DL –750 as shown in Fig.4.17 111 Fig. 4.18 Voltage and current of SRA during 3phase short circuit As the damper windings are absent in the designed SRA and the height of wedges has been machined during redesigning process. The sub transient current is not noticeable which is evident from figure 4.18. The behavior of the voltage before, during and after circuit can be well understood from Fig. 4.19. short 112 Fig 4.19 Voltage: Before, during and after three phase SC fault Fig 4.20 The currents in all three phases during three phase SHORT CIRCUIT As the three phase short circuit is a symmetrical fault, the currents in all the three phases will be equal in magnitude which is depicted in Fig. 4.20. 113 4.8.2 Determination of Reactances from 3phase sudden short circuit test The direct-axis sub-transient and transient reactances are determined from the current waves of a three-phase short-circuit suddenly applied to the machine operating at no-load and rated speed.The current peaks in one of the three phases are plotted on a graph paper. In plotting the current values from the oscillogram, the first peak should be plotted at abscissa 1 and subsequent peaks numbered consequently. The positive peaks are therefore given odd numbers and the negative even numbers. The current values from the oscillograms should be plotted first and then the median line and the a.c. component. The curves are usually plotted on standard rectangular co-ordinates and most conveniently analyzed if the currents are expressed in p.u. values, with the unit value equal to the peak value of the rated current wave. The a.c. component of the current is then replotted on the semilog scales with the current on the logarithmic scale. Since the first peak is plotted at abscissa 1, the abscissa for the time of application of the short-circuit is usually not at zero, but at a time which can be readily determined from the oscillogram. The zero time line should be drawn on the semi-log plot and extrapolations of the current curves are extended to this line. Since the plot of the current on a semi-log paper is represented by a straight line together with a curve of several 114 cycles at the beginning of the short-circuit, it is important to choose such time and current scales that will avoid a steep slope during the first three or four cycles. The straight line in the current-time plot on a semi-log paper is extrapolated to zero time and X'd = E I 'd Where E = the open circuit voltage of the machine immediately before the sudden short-circuit expressed in p.u I'd = per unit current from the current in the transient state X"d = E I "d I"d is the per unit current from the a.c. component curve at t=0 and E has already been defined. NOTE: It is not essential that the sudden short-circuit should be performed to determine the values of X"d , X'd . The method for the determination of X"d in standstill has already been described. The difficulty, however, arises in the determination of X'd . The modern practice is to determine X"d and X'd with the help of suddenly 115 switching off the three-phase sustained short-circuit. A record of the recovery voltage with time helps us to determine X"d and X'd . The following machine parameters [35] have been determined from the Fig4.17 and 4.19. Base KVA =5 Base KVLL =O.400 Base Current,A = 5/(√3 * 0.400) = 6.95 Base Impedance = (Base KVLL )2* 1000/ Base KVA = 32 Ω Actual Impedance(Za) = Rated Voltage/Rated current = 400/(√3 * 7.5) =30.33 Per unit Impedance =[(Za)* (KVA)B]/[ (KV)2B * 1000] = (30.33 * 5 )/ [(0.415)*1000] = 0.881 Sub-transient Current(Id′′) = 10 p.u Sub-transient Reactance( Xd′′) =1.0/10= 0.1 Transient Current( Id′) = 4.5 p.u Transient Reactance( Xd′) = 1/4.5 = 0.22 Steady state Current(Id) =0.9 p.u 116 Steady state reactance(Xd) = 1/0.9 = 1.1 Sub transient reactance, Xd″ = 0.1 Transient Reactance, Xd′ = 0.22 Steady state reactance Xd = 1.1 4.9 L – L FAULT ON SYNCHRONOUS GENERATOR An experiment to illustrate a three phase L-L fault is performed on the SRA as shown in Fig.4.21. 1. The MG setup is made to run at synchronous speed. 2. By varying excitation the output of the SRA is brought to the 50% of rated voltage. 3. The two phases of output terminals of SRA are short circuited through contactor and the supply to the prime mover is disconnected instantaneously [36]. 4. The contactor is opened immediately and the transient voltages and currents are captured by Transcoder DL-750 as shown in Fig.4.22and its enlarged form is shown in Fig.4.23 117 Fig 4.21 Circuit diagram for LL- Fault Experiment Fig 4.22 Voltage and current at the instant of LL-fault 118 Fig 4.23 Enlarged wave form of V and I during L-L fault 4.9.1 Determination of Reactances from L-L fault on SRA The direct-axis sub-transient and transient reactances are determined from the current waves of a L-L fault suddenly applied to the machine operating at no-load and rated speed. The procedure to calculate the various reactances for L-L fault condition is same as mentioned in section 4.8.2. The machine parameters for L-L fault condition [37] have been determined from the Fig 4.22 & Fig 4.23 Sub-transient Current(Id″) = 6.4 p.u Sub-transient Reactance( Xd″) =1.0/6.4= 0.156 Transient Current( Id′) = 4.2 p.u Transient Reactance( Xd′) = 1/4.2 = 0.238 Steady state Current(Id) = 0.8 p.u 119 Steady state reactance(Xd) = 1/0.8 = 1.25 Sub transient reactance, Xd″ = 0.156 Transient Reactance, Xd′ = 0.238 Steady state reactance Xd = 1.25 4.10 CONCLUSIONS 1. The short circuit ratio of SRA is calculated from OC and SC tests and found as 0.91. 2. The synchronous reactance of SRA is determined as 1.098. 3. The percentage change in resistance for a rise in temperature of 32°C is found as 10% approximately. 4. The thermal time constant of SRA is observed as 90min 5. The value of efficiency of SRA is calculated as 85.66% 6. The additional losses of the SRA due to negative sequence currents is found 2.378W which is 0.43% of total losses 7. The machine reactances for three phase short circuit and L-L fault are calculated from the respective graphs. CHAPTER 5 HARMONIC COMPENSATION