KUH PDS KUH Horizontal Unit Heater • 2.6 kW to 45 kW • 208, 240, 277 480, 600 Volts • Single or 3-Phase • 8,900 to 153,600 BTU/Hour • Wall or Ceiling Mounting • Meets UL and CSA Requirements (600V CSA Certified Only) Description Applications The KUH horizontal unit heater provides quiet, reliable fan-forced heating in all types of commercial and industrial structures. Each heater houses a bank of Chromalox patented metal sheath Fintube® radiating heating elements with furnace brazed steel fins for long life and superior heat transfer. KUH heaters are versatile, flexible, high performance units that are easily installed in various mounting configurations for primary, supplementary or spot heating applications. Each unit is selfcontained in a rugged construction for long life and require little maintenance. Complementary to modern structure, these heaters have a good, clean appearance. For assured safety, all units meet the requirements of UL (File No. E7061) and CSA (File No. LR40859). The clean design and quality construction of the KUH heater, plus meeting UL and CSA requirements, make it a safe, appropriate heating choice for: Construction • Shipping Rooms • Pump Houses • Power Generating Stations • Aircraft Hangers • Factories • Warehouses • Garages Because it has individually adjustable discharge louvers to direct air flow, and can be wall or ceiling (plus swivel) mounted, the KUH heater may be used in a variety of heating applications: • Primary Heating • Supplementary Heating • Dual System Heating • Spot Heating • Entryway Air Curtain Heating The cabinet is constructed of heavy 18-gauge steel, phosphate undercoated for corrosion resistance, and finished in gray powdercoat. Quiet, vibration-free operation is enabled through the combination fan guard and motor mount attached to the heating housing with rubber vibration isolators. Quality heating element construction assures years of maintenance-free operation. Phone: 1-888-996-9258 • Fax: 615-793-3563 www.chromalox.com ©2005 Chromalox, Inc. KUH Horizontal Unit Heater Features Mount with threaded rods or optional wall or ceiling swivel mounting brackets. Seismic rated. Totally enclosed fan motor. Continuous duty with built-in thermal cutouts operates on same voltage as the heating circuit. Individually adjustable louvers to direct air flow as needed. Field installed disconnect switch (optional) Field installed summer fan switch (optional). Die-formed heavy gauge steel housing with attractive gray powder coat finish. Field installed thermostat with adjustment switch (optional). Magnetic Contactors Standard Electrical & Control Components The self-contained electrical and control features of the KUH simplify installation and ensure safe, long term operation. Heavy duty magnetic control contactors are standard on all models except single-phase 2.6 thru 5 kW models, which are standard without contactors for control by external line voltage thermostat. Optional contactors are also available for these models. • All heaters with a total current draw of 48 Amps or greater have electrically balanced, subdivided circuits with individual fuse protection. The fuse compartment is conveniently located for easy access. • An internal 24 volt control transformer, standard on 480V models, eliminates a need for an external control source. 2 Horizontal type heaters mount on wall or ceiling. Recessed welded fasteners on top of housing are internally threaded for suspension of unit with threaded rods. Also there are optional ceiling and wall swivel mounting brackets. The ceiling bracket lets you mount the Horizontal Unit Heater direct to the ceiling or overhead member, simply and easily. The wall swivel mounting bracket makes for easy wall mounting. Swivel type mounting lets you readily adjust direction of warm air flow for optimum comfort, 180 degrees if need be. • The Electric Heat Bank — Chromalox patented metal sheath Fintube® heating elements. Heat radiating fins are steel, furnace brazed to the tubular heating elements for good heat transfer. They don’t come loose! Wide spacing minimizes clogging. • Thermal overload cutouts open the control circuit and disconnect power to the heating elements if overheating occurs. Automatic reset allows the control circuit to reclose and restore power when the temperature falls to normal levels. • Dynamically balanced fan for smooth, quiet running. Blade pitch is carefully selected so that the volume of air moved results in the optimum discharge air temperature. • 103 Gamma Drive Ext. • Pittsburgh, PA 15238 • PH: 1-800-443-2640 • www.chromalox.com KUH Horizontal Unit Heater Specifications And Ordering Information To order please specify kW, volts, phase, catalog number, PCN and quantity. See back page for control, thermostat and fan options. Electrical Data (60 Hz) Fan Motor Mounting Data Phase Amps BTU/H Volts Phase RPM HP Air Fan Dia. 2,667 2,000/2,667 2,667 1 1 1 12.8 11.1*** 9.6 8,850 8,850 8,850 208 240 277 1 1 1 1650 1650 1550 1/40 1/40 1/30 9” 9” 9” 410 410 360 21° 21° 24° 8’ 8’ 8’ 12’ 12’ 12’ KUH-02-81-00 KUH-02-21-00 KUH-02-71-00 S S S 304004 304012 304020 35 208 208 208/240 208/240 277 480 4,000 4,000 3,000/4,000 3,000/4,000 4,000 4,000 1 3 1 3 1 3 19.2 11.2 16.7*** 9.6*** 14.5 4.8 13,661 13,661 13,661 13,661 13,661 13,661 208 208 240 240 277 480 1 1 1 1 1 1 1650 1650 1650 1650 1550 1550 1/40 1/40 1/40 1/40 1/30 1/35 9” 9” 9” 9” 9” 9” 410 410 410 410 360 380 31° 31° 31° 31° 35° 33° 8’ 8’ 8’ 8’ 8’ 8’ 12’ 12’ 12’ 12’ 12’ 12’ KUH-04-81-00 KUH-04-83-34 KUH-04-21-00 KUH-04-23-34 KUH-04-71-00 KUH-04-43-30 S S S S S S 304039 304047 304055 304063 304071 304080 35 5 5 3.75/5 3.75/5 5 5 208 208 208/240 208/240 277 480 5,000 5,000 3,750/5,000 3,750/5,000 5,000 5,000 1 3 1 3 1 3 24.0 13.8 20.8*** 12.1*** 18.2 6.0 17,076 17,076 17,076 17,076 17,076 17,076 208 208 240 240 277 480 1 1 1 1 1 1 1650 1650 1650 1650 1550 1550 1/40 1/40 1/40 1/40 1/30 1/35 9” 9” 9” 9” 9” 9” 410 410 410 410 360 380 39° 39° 39° 39° 44° 42° 8’ 8’ 8’ 8’ 8’ 8’ 12’ 12 12 12 12 12 KUH-05-81-00 KUH-05-83-34 KUH-05-21-00 KUH-05-23-34 KUH-05-71-00 KUH-05-43-30 S S S S S S 304098 304100 304119 304127 304135 304143 35 7.5 7.5 5.6/7.5 5.6/7.5 7.5 7.5 7.5 208 208 208/240 208/240 277 480 600 7,500 7,500 5,625/7,500 5,625/7,500 7,500 7,500 7,500 1 3 1 3 1 3 3 36.1 20.9 31.1*** 18.1*** 27.2 9.0 7.0 25,598 25,598 25,598 25,598 25,598 25,598 25,598 208 208 240 240 277 480 575 1 1 1 1 1 3 3 1725 1725 1725 1725 1550 1725 1725 1/15 1/15 1/15 1/15 1/15 1/15 1/3 12” 12” 12” 12” 12” 12” 12” 850 850 850 850 750 850 850 28° 28° 28° 28° 32° 28° 28° 8’ 8’ 8’ 8’ 8’ 8’ 8’ 27’ 27’ 27’ 27’ 27’ 27’ 27’ KUH-07-81-34 KUH-07-83-34 KUH-07-21-34 KUH-07-23-34 KUH-07-71-30 KUH-07-43-30 KUH-07-63-32 S S S S S S NS 304151 304160 304178 304186 304194 304207 000000 55 9.7 9.7 7.5/10 7.5/10 10 10 208 208 208/240 208/240 480 600 10,000 10,000 7,500/10,000 7,500/10,000 10,000 10,000 1 3 1 3 3 3 48.0 27.8 41.7*** 24.0*** 12.0 10.0 34,130 34,130 34,130 34,130 34,130 34,130 208 208 240 240 480 575 1 1 1 1 3 3 1725 1725 1725 1725 1725 1725 1/15 1/15 1/15 1/15 1/15 1/3 12” 12” 12” 12” 12” 12” 850 850 850 850 850 850 37° 37° 37° 37° 37° 37° 9’ 9’ 9’ 9’ 9’ 9’ 27’ 27’ 27’ 27’ 27’ 27’ KUH-10-81-34 KUH-10-83-34 KUH-10-21-34 KUH-10-23-34 KUH-10-43-30 KUH-10-63-32 S S S S S NS 304215 304223 304231 304240 304258 000000 55 12.5 9.3/12.5 12.5 12.5 208 208/240 480 600 12,500 9,375/12,500 12,500 12,500 3 3 3 3 34.8 30.1*** 15.1 12.0 42,663 42,663 42,663 42,663 208 240 480 575 1 1 3 3 1725 1725 1725 1725 1/15 1/15 1/15 1/3 12” 12” 12” 12” 850 850 850 850 47° 47° 47° 47° 9’ 9’ 9’ 9’ 27’ 27’ 27’ 27’ KUH-12-83-34 KUH-12-23-34 KUH-12-43-30 KUH-12-63-32 S S S NS 394266 304274 304282 000000 55 15 11.25/15 15 15 208 15,000 208/240 11,250/15,000 480 15,000 600 15,000 3 3 3 3 41.8 36.2*** 18.1 15.0 51,195 51,195 51,195 51,195 208 240 480 575 1 1 3 3 1725 1725 1725 1725 1/15 1/15 1/15 1/3 12” 12” 12” 12” 850 850 850 850 56° 56° 56° 56° 10’ 10’ 10’ 10’ 27’ 27’ 27’ 27’ KUH-15-83-34 KUH-15-23-34 KUH-15-43-30 KUH-15-63-32 S S S NS 304290 304303 304311 000000 55 20 20 20 208/240 15,000/20,000 480 20,000 600 20,000 3 3 3 48.0*** 24.0 19.0 68,460 68,460 68,460 240 480 ** 3 3 3 1725 1725 1725 1/3 1/3 1/3 14” 14” 14” 1240 1240 1240 53° 53° 53° 11’ 11’ 11’ 31’ 31’ 31’ KUH-20-23-34 KUH-20-43-30 KUH-20-63-32 S S NS 304320 304338 000000 75 3 3 30.0 24.0 85,525 85,525 480 ** 3 3 1725 1725 1/3 1/3 14” 14” 1350 1350 60° 60° 12’ 12’ 31’ 31’ KUH-25-43-30 KUH-25-63-32 S NS 304346 000000 75 kW Volts Watts 2.6 2.0/2.6 2.6 208 208/240 277 4 4 3/4 3/4 4 4 25 25 480 600 25,000 25,000 Temp. Velo. Rise CFM °F Max. Ht. Hor. Catalog Throw No. Status* PCN Wt. lbs. 30 30 30 30 208 30,000 208/240 22,500/30,000 480 30,000 600 30,000 3 3 3 3 83.4 72.2*** 36.1 29.0 102,390 102,390 102,390 102,390 240 240 480 ** 3 3 3 3 1725 1725 1725 1725 1/3 1/3 1/3 1/3 14” 14” 14” 14” 1555 1555 1555 1555 64° 64° 64° 64° 13’ 13’ 13’ 13’ 46’ 46’ 46’ 46’ KUH-30-83-34 KUH-30-23-34 KUH-30-43-30 KUH-30-63-32 S S S NS 304354 110 304362 304370 000000 35 35 35 208/240 26,250/35,000 480 35,000 600 35,000 3 3 3 84.3*** 42.1 34.0 119,455 119,455 119,455 240 480 ** 3 3 3 1725 1725 1725 1/3 1/3 1/3 14” 14” 14” 1555 1555 1555 71° 71° 71° 14’ 14’ 14’ 45’ 45’ 45’ KUH-35-23-34 KUH-35-43-30 KUH-35-63-32 S S NS 304389 110 304397 000000 40 40 40 208/240 30,000/40,000 480 40,000 600 40,000 3 3 3 96.0*** 48.0 39.0 136,520 136,520 136,520 240 480 ** 3 3 3 1725 1725 1725 1/3 1/3 1/3 14” 14” 14” 1555 1555 1555 84° 84° 84° 15’ 15’ 15’ 44’ 44’ 44’ KUH-40-23-34 KUH-40-43-30 KUH-40-63-32 S S NS 304400 110 304418 000000 3 3 54.1 43.0 153,585 153,585 480 ** 3 3 1725 1725 1/3 1/3 14” 14” 1555 1555 94° 94° 17’ 17’ 42’ 42’ KUH-45-43-30 KUH-45-63-32 S NS 304426 110 000000 45 45 480 600 45,000 45,000 * S = Stock; NS = Non-Stock ** Check factory for motor data *** 208V amperage is 86% of 240V value Notes: 1.All heaters have built-in contactors except 2.6 thru 5 kW Single Phase Models, and stock 480 volt models have built-in control transformers and contactor with 24 volt holding coils. All stock 208 and 240 volt models have 208/240 volt holding coils. All stock 277 volt models have 277 volt holding coils. 2.Optional contactors are available with 24 volt holding coils on made to order models. When total heater capacity exceeds 48 amps, built-in fusing is provided behind a hinged and latched door in the side which allows easy access. • 103 Gamma Drive Ext. • Pittsburgh, PA 15238 • PH: 1-800-443-2640 • www.chromalox.com 3 KUH Horizontal Unit Heater Application Tips Small rooms can be heated by a one (1) unit heater. Where two (2) walls are exposed, heater should be mounted as shown. Large rooms require multi-unit installations. Number and capacity of units will be determined by volume of building and square feet of floor area to be heated. Arrange units to provide perimeter air circulation. To prevent air stratification, total CFM capacity of all units should circulate the room air volume at least 3 times per hour. Units should be located so their air streams wipe exposed walls without blowing directly at them. In multiple unit heater installations, locate units so each unit supports the air stream from another, thus setting up circulatory air movement. In warehouse type applications, for maintaining minimum temperature, one or more large heaters can be used to reduce initial installation expense. For individual spaces total heating capacity is calculated in the conventional way, using formulas in the ASHRAE “Guide” or those found in the NEMA handbook. For pedestrian entryways when heating capacity is not known, a “rule of thumb” is 3000-5000 watts per door. Use 3000 watts per door for a low traffic single-door entry. For a large multiple-door entry, or a high traffic single-door entry, use 5000 watts per door. Loading Docks. Unit heaters are used to combat cold air inrush when loading dock doors are opened. For such applications, one or more units should be arranged to blow warm air across the opening, not toward it. Mounting Recommendations Hazardous Atmosphere - KUH Horizontal Unit heaters should not be used in potentially explosive atmospheres. Corrosive Atmosphere - The finish is not intended for direct salt spray exposure in marine applications or the highly corrosive atmosphere of greenhouses, swimming pools, chemical storage bins, etc. Mounting Height - Do not install heaters above recommended maximum mounting height. Obstructions - Must not block heater air inlet or discharge. Warning - This heater is not intended for use in hazardous atmospheres where flammable vapors, gases, liquids or other combustible atmospheres are present as defined in the National Electric Code. Failure to comply can result in explosion or fire. Suggested Engineering Specifications Furnish and install Chromalox type KUH Horizontal Unit Heaters with heating and air delivery capacities as shown on the heating schedule. Mounting brackets designed for either ceiling or wall swivel mounting shall be furnished as shown on the heating schedule. The cabinet shall be of 18 gauge die formed furniture grade steel. Individual adjustable louvers shall be furnished to provide desired control of discharge air. All metal surfaces of the casing shall be phosphate coated to resist corrosion, and finished in gray powder coated paint. The electric heating bank shall consist of our metal sheath Fintube® heating elements. Automatic reset 4 thermal overheat protection shall be wired for instantaneous pilot operation of built-in control contactor holding coil. Single phase units 2.6 thru 5kW shall have cutout wired in series with the motor and element. All heaters drawing more than 48 amperes shall have built-in branch circuit fusing for protection. Motors shall be of the totally enclosed continuous fan-duty sleeve bearing type equipped with built-in thermal overload protection. Each unit shall be equipped with a combination fan guard/motor support resiliently mounted at four points to absorb any motor vibration. Fans shall be aluminum, directly connected to fan motor, dynamically balanced and designed specifically for unit heater application. Optional control transformers shall be available to internally develop safer low voltage for pilot-duty control circuits. Fan switching devices shall be available to independently operate the fan motor for summer circulation and winter heat recovery. Individual optional built-in comfort control thermostat is integral or remote fan only switch and disconnect switch shall be available, for all models. All heaters should be UL Listed and CSA Certified and meet the requirements of the National Electrical Code. • 103 Gamma Drive Ext. • Pittsburgh, PA 15238 • PH: 1-800-443-2640 • www.chromalox.com KUH Horizontal Unit Heater Dimensions Welded fasteners (4) for threaded rod** Mounting to overhead steel. Note: Heater must be mounted at least 7’ above floor. Minimum distance to wall * Fasteners for mounting bracket to ceiling or wall not supplied. ** Threaded rod not supplied. Wall line Minimum distance to wall with ceiling mount. Dimensions — Inches Catalog Number A B C D Welded Fasteners E F G H I J K KUH-02 thru -05 16 131/8 87/8 111/16 5 101/4 93/4 51/2 41/16 41/2 41/2 65/8 3 /8-16 13 /8 13 1 8 /4 1 4 /2 1 6 /4 1 6 /4 85/8 3 /8-16 161/4 16 81/4 6 81/4 61/4 10 16 1 6 3 3 10 1 1 1 KUH-07, 10, 12, 15 20 /2 17 /4 11 /2 15 KUH-20, 25 24 201/8 111/2 173/4 KUH-30, 35, 40, 45 1 20 /8 24 17 7 23 /8 W N V M Wall One /16” mounting hole for swivel mounting to ceiling. U 7 1 /8-16 16 /4 8 /4 11 /4 11 /4 Wall Mounted Universal Bracket Ceiling Mounted 11 3 /16-18 413/32” diameter mounting holes for fastening to wall.* Stop for limiting rotation. Swivel bolt permits heater to be rotated to face desired direction. Four bolts are provided for field attachment of swivel bracket to welded fasteners on top of unit. A Mounting Limitations Swivel Mounting Bracket* Finished ceiling Four bolts are provided for field attachment of swivel bracket to welded fasteners on top of unit. Ceiling must be smooth wood, plaster or metal surface with adequate strength to support heater. Not adaptable to acoustic tile or suspended ceilings. Hazardous Atmosphere — Unit heaters should not be used in potentially explosive atmospheres. Corrosive Atmosphere — The finish is not intended for direct salt spray exposure in marine applications or the highly corrosive atmospheres of greenhouses, swimming pools, chemical storage bins, etc. Mounting Height — Do not install Unit Heaters above recommended maximum mounting height. Obstructions must not blockunit heater air inlet or discharge. Clearance Requirements Mounting Limitations Side To Wall 6 inches Back To Wall 6 inches Ceiling Mounted Heaters Wall Mounted Heaters Dimensions — Inches Heater Model # A KUH-02 thru -05 16 KUH-07, 10, 12, 15 KUH-20, 25 M 6 201/2 8 24 8 N 47/16 43/4 61/4 U 4 6 6 V 43/4 71/4 71/4 Dimensions — Inches W 101/2 16 171/2 Ceiling Bracket Cat. Heater Model P Q R S T KUH-02 thru -05 11/2 211/2 63/4 55/8 141/2 24 133/4 95/16 6 71/4 21 Wall Bracket Cat. # 1 3 BUH-01A BUH-04A KUH-07, 10, 12, 15 3 19 5 2 /32 28 /32 9 /2 8 /8 19 /8 BUH-02A KUH-20, 25 23/32 2819/32 91/2 83/8 195/8 BUH-02A BUH-05A BUH-05A KUH-30, 35, 40, 45 KUH-30, 35, 40, 45 Top To Wall 6 inches 1 5 /2 3 30 /4 5 1 3 /2 9 32 /16 BUH-03A BUH-06A • 103 Gamma Drive Ext. • Pittsburgh, PA 15238 • PH: 1-800-443-2640 • www.chromalox.com 5 KUH Horizontal Unit Heater Optional Control Accessories and Remote Thermostats Fan Only Operation Kits Thermostat Kits Catalog Number KUH-TK3 (SPST) KUH-TK4 (DPST) PCN 302519 302527 Summer Fan Switch Power Disconnect Kits Thermostat Kit A fan only operation (optional) is available by means of a built-in switch or by external control. (2-15 kW) (20-45 kW) Catalog Number 3 Pole, 600V Rating Catalog Number KDS-1 KDS-2 KDS-3 6 Rating 40 Amp 80 Amp 100 Amp PCN 304434 304442 304450 Description ISFS-02 Internal Summer Fan Switch 208 through 277Volts ESFS-40 External* Summer Fan Switch With Relay (24 Volt control) ESFS-42 External* Summer Fan Switch With Relay (240 Volt control) ESFS-47 External* Summer Fan Switch With Relay (277 Volt control) PCN PCN 305007 ISFS-02 305007 305015 ESFS-40A 305058 305031 ESFS-42A 305074 305040 — — *Kit includes wall plate (discard plate if switch is to be installed on the heater.) • 103 Gamma Drive Ext. • Pittsburgh, PA 15238 • PH: 1-800-443-2640 • www.chromalox.com KUH Horizontal Unit Heater Recommended Remote Wall Thermostats Industrial Rated NOT A FAIL-SAFE DEVICE Maximum Rating (Amps/Watts) AC 120V 240V 277V 480V DC† 115V 25/3000 25/3000 22/5280 22/5280 18/5000 18/5000 125VA* 125VA* 125VA** 125VA** DC† Catalog Sta230V Number tus 125VA** 125VA** WR-80 WR-90 S S PCN 263177 263185 WR-80 SPST 40°F - 80°F UL Listed WR-90 SPST 20°F - 90°F UL Listed *Pilot Duty (Use With AC Contactor) **Pilot Duty (Use With DC Contactor) †DC Ratings Not UL Listed Light Duty NOT A FAIL-SAFE DEVICE Maximum Rating (Amps/Watts) AC Pilot duty Catalog Sta(VA) Number tus 120V 208V 240V 277V 22/2640 22/2640 22/4575 22/4575 22/5280 22/5280 18/5000 18/5000 125 125 WT-121 WT-122 S S Line Voltage PCN 309999 310009 WT-122 WT-121 DPST SPST 45°F - 75°F 45°F - 75°F Low Voltage WTL-121 SPST 40°F - 80°F 30 VAC 1 Amp Thermostat and Fan Switch NOT A FAIL-SAFE DEVICE Catalog Number Status PCN RTC-90 Surface Mounting Box S S 227360 227379 Electrical Rating VAC FLA Inductive LRA 125 250 277 5.8 2.9 2.4 34.8 17.4 14.4 Pilot Duty (VA) Resistive (Amps) 125 125 125 10 5.0 4.2 RTC-90 50°F - 90°F UL Listed • 103 Gamma Drive Ext. • Pittsburgh, PA 15238 • PH: 1-800-443-2640 • www.chromalox.com 7 KUH Horizontal Unit Heater Model Numbers When ordering KUH heaters, specify the model number and corresponding PCN (Product Code Number). If controls or thermostat/fan options are required, designate these options in the model number when ordering, as shown below. Always specify voltage, phase and kW by listing them on the purchase order product specifications. KUH 05 21 34 41 1 Disconnect Switch 1 40 Amp 2 80 Amp 3 100 Amp Control 0 4 4 4 4 4 4 0 0 1 2 3 4 5 No Thermostat, No Summer Fan Switch Internal Thermostat Only Internal Therm. and Internal Sum. Fan Sw. External Sum. Fan Sw. Only (Not 480V) External Sum. Fan Sw. and Fan Relay (All Volts) Rem. Fan Sw. and Internal Therm. (Not 480V) Rem. Fan Sw., Fan Relay and Int. Therm. (All Volts) Control 0 3 3 3 3 0 0 1 4 5 No Contactor(s) 24V Control Internal Transformer 24V Control Externally Supplied 208/240V Control Internally Supplied, No Transformer 277V Control Internally Supplied Heater Voltage and Phase 81 = 208V, 1 Phase 83 = 208V, 3 Phase 21 = 240V, 1 Phase 23 = 240V, 3 Phase 71 = 277V, 1 Phase 43 = 480V, 3 Phase 63 = 600V, 3 Phase Heating Elements 02 = 2.6 kW 04 = 4.0 kW 05 = 5.0 kW 07 = 7.5 kW 10 = 10.0 kW 12 = 12.5 kW 15 = 15.0 kW 20 = 20.0 kW 25 = 25.0 kW 30 = 30.0 kW 35 = 35.0 kW 40 = 40.0 kW 45 = 45.0 kW Chromalox Horizontal Unit Heater PF310-2 PDS KUH FEB05 8 • 103 Gamma Drive Ext. • Pittsburgh, PA 15238 • PH: 1-800-443-2640 • www.chromalox.com