Pipe Hangers
Supports
Seismic Bracing
UL Listed
for Fire Sprinkler
Installations
TOLCO™ is a brand of
TOLCO™ Fire Protection Support Systems
Supporting
the Flow.
www.tolco.com
Revision 5/24/2001
a brand of
Catalog Forward
Warning
This catalog has been created with an acute awareness of the field problems of the piping contractor.
We have sought and received input from engineers,
installers, field inspectors and others closely involved
with the installation of piping systems. This is where
needs are discovered, and where products and services are genuinely tested.
Pipe hanger products included in this catalog are
intended for installation and service only as described
herein.
TOLCO™ is proud to present a complete and versatile line of pipe hangers and related products. The
TOLCO line has been methodically developed to
effectively address support problems in the commercial and industrial piping fields.
A thorough knowledge of our customers’ needs and
problems was no less important than the development
of our manufacturing skills in the emergency of
TOLCO as a leader in the pipe hanger industry. Our
people are equipped to respond quickly to your product and service needs on both standard items and
specialized metal fabrication.
We are aware that these products have been used
(often without incident) for purposes and in ways other
than those for which they were designed and manufactured. Examples of which are: use of products as
erection tools; use of beam clamps on a beam not
specified for them; use of concrete inserts as an
anchor for pulling pipe to proper elevation; suspension
of one clevis hanger under another resulting in cumulative load greater than specified capability. In such
cases of misapplication or improper use, we cannot
be held responsible for injuries or property damage.
TOLCO pipe hanger products are carefully designed
and manufactured to industry standards. Care should
be exercised by installers and end users to install, use
and maintain these products properly to avoid any
possible on-the-job accidents.
Custom Fabrication
Designs
We have expanded our manufacturing capacity in
response to the growing demand for customized
metal fabrication and special hangers. When some
detail of construction or piping arrangement makes it
necessary to deviate from standard types of hangers,
TOLCO is equipped to furnish hangers and supports
of any required type. These products combine proven
designs and standards with new innovations that
enhance their utility.
Product design and specifications are subject to
change without notice.
Approvals and Specifications
TOLCO, as a member of the American Pipe Fittings
Association, is cooperating with engineers and architects in the preparation of specifications covering
hanger requirements and the interpretation of applicable piping safety codes.
All TOLCO products are carefully manufactured to
meed the highest standards in the industry. All products, as a minimum conform to Manufacturers
Standardization Society MSS-SP-58, and to the allowable stresses specified in the ANSI B31.1 code for
pressure piping.
Finishes
Most hangers are available in: stainless steel, electro-galvanized or hot-dipped galvanized. Other
special finishes are available upon request. Items
ordered hot-dip galvanized may be supplied with electro-galvanized threaded components unless otherwise
specified. If you require a finish not listed in the
product data of a specific hanger, please consult
our factory.
Index
Figure numbers in this catalog are in numerical order.
Terms and Conditions of Sale
For conditions and terms of sale, please consult our
current price guide.
Many TOLCO Products are also listed, approved or
conform to:
Underwriter’s Laboratories UL-203
Factory Mutual Engineering
National Fire Protection Association NFPA-13,
NFPA-13R, NFPA-13D and NFPA-24
Federal Specification WW-H-171EE
Main Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92870 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266
www.tolco.com
www.tolco.com
Revision 4/26/2005
Index —
Pipe Hangers and Straps
Fig. 1
Fig. 1F
Standard Clevis Hanger Standard Clevis Hanger
MSS-SP-69, Type 1
with Felt Lining
WW-H-171E, Type 1
Page 7
Page 5
Fig. 1PVC
PVC Coated
Clevis Hanger
MSS-SP-69, Type 1
WW-H-171E, Type 1
Page 7
Fig. 2FWON
Fig. 2F
Fig. 2WON
Adjustable Band Hanger
Adjustable Band Hanger Adjustable Band Hanger
w/o Swivel Nut
with Felt Lining
w/o Swivel Nut
with Felt Lining
MSS-SP-69, Type 10
MSS-SP-69, Type 7
MSS-SP-69, Type 10
WW-H-171E, Type 10
WW-H-171E, Type 7
WW-H-171E, Type 10
Page 9
Page 10
Page 10
Fig. 200WON
Trimline Band Hanger
w/o Swivel Nut
MSS-SP-69, Type 7
WW-H-171E, Type 7
Page 42
Fig. 1CBS
Cross Bolt Spacer
Page 6
Fig. 2
Adjustable Band Hanger
MSS-SP-69, Type 10
WW-H-171E, Type 10
Page 8
Fig. 2NFPA
Trimline Band Hanger
with Reducer Rod Size
MSS-SP-69, Type 10
WW-H-171E, Type 10
Page 8
Fig. 24
Hanger for
CPVC Plastic Pipe,
Double Fastener Strap
Type Side Mount
Page 20
Fig. 200
Trimline Band Hanger
MSS-SP-69, Type 10
WW-H-171E, Type 10
Page 40
Fig. 3
J-Hanger for
Pipe or Conduit
MSS-SP-69, Type 5
Page 11
Fig. 23
Hanger for CPVC
Plastic Pipe, Double
Fastener Strap Type
Page 19
Fig. 22
Hanger for CPVC
Plastic Pipe
Single Fastener Type
Page 17
Fig. 22C
Combination Hanger
Restrainer Application
for CPVC Plastic Pipe
Page 18
Fig. 120RWA (B)
Retrofit Wrap Around
U-Hanger Clamp
MSS-SP-69, Type 4
WW-H-171E, Type 4
Page 38
Fig. 120RWA (A)
Retrofit Wrap Around
U-Hanger Clamp
Page 38
Fig. 28
Fig. 26
Nail Plate
Page 22
Fig. 3PVC
J-Hanger
with PVC Coating
MSS-SP-69, Type 5
Page 11
Fig. 3F
J-Hanger with Felt Lining
MSS-SP-69, Type 5
Page 11
Standoff Hanger and
Restrainer for CPVC
Plastic Pipe
Page 23
Fig. 120
U-Hanger
Page 37
Fig. 324
Pipe Roller Hanger
MSS-SP-69, Type 43
WW-H-171E, Type 44
Page 43
NOTE: For more information on TOLCO products, please see TOLCO™ Pipe Hangers and Support Systems Catalog.
2
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 4/26/2005
Index —
Pipe Clamps
Fig. 4B
Seismic
Pipe Clamp
Page 14
Fig. 4
Standard Pipe Clamp
MSS-SP-69, Type 4
WW-H-171E, Type 4
Page 12
Fig. 4A
Pipe Clamp for
Sway Bracing
Page 13
Fig. 4F
Standard Pipe Clamp
with Felt Lining
MSS-SP-69, Type 4
WW-H-171E, Type 4
Page 12
Fig. 4PVC
PVC Coated
Pipe Clamp
Page 12
Fig. 6
Riser Clamp
MSS-SP-69, Type 8
WW-H-171E, Type 8
Page 16
Fig. 6F
Riser Clamp
with Felt Lining
MSS-SP-69, Type 8
Ww-H-171E, Type 8
Page 16
Fig. 6PVC
PVC Coated
Riser Clamp
MSS-SP-69, Type 8
WW-H-171E, Type 8
Page 16
Beam Clamps and Accessories
Fig. 61T
Threaded Top Hook
Page 27
Fig. 65
Steel Reversible
"C" Type Beam Clamp
with Lock Nut
3/4" Opening
MSS-SP-69,
Type 19 & 23
WW-H-171E, Type 23
Page 28
Fig. 66
Steel Reversible
"C" Type Beam Clamp
with Lock Nut
11/4" Opening
MSS-SP-69,
Type 19 & 23
WW-H-171E, Type 23
Page 28
Fig. 69
Beam Clamp
Retaining Strap
Page 31
Fig. 69R
Retrofit Capable
Beam Clamp
Retaining Strap
Page 32
Fig. 130
Beam Clamp with
Bolt and Nut
Page 39
Upper Attachments
Fig. 42
Angle Bracket
Page 24
Fig. 50
Side Beam Bracket
Page 24
Fig. 51
Side Beam Bracket
for NFPA Pipe Sizing
Page 25
Fig. 58
Threaded Side
Beam Bracket
Page 26
Fig. 78
All Steel
Ceiling Plate
Page33
NOTE: For more information on TOLCO products, please see TOLCO™ Pipe Hangers and Support Systems Catalog.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
3
www.tolco.com
Revision 5/24/2001
Index —
Concrete Inserts
Fig. 109A
Concrete Deck Insert
Page 35
Fig. 109F
Concrete Insert
Page 36
Threaded Products & Accessories
Fig. 98
Rod Stiffener
Page 34
Seismic Brace Attachments
Fig. 4L
Longitudinal “In-Line”
Sway Brace Attachment
Page 15
Fig. 907
4-Way Longitudinal
Sway Brace Attachment
Page 48
Fig. 981
Retrofit Universal Sway
Brace Attachment
Page 53
Fig. 25
Surge Restrainer
Page 21
Fig. 800
Adjustable Sway Brace
Attachment to Steel
Page 44
Fig. 909
No-Thread Swivel
Sway Brace Attachment
Page 49
Fig. 990
Cable Sway Brace
Attachment
Page 54
Fig. 910
Swivel
Sway Brace Fitting
Page 50
Fig. 991
Cable Sway Brace
Attachment
Page 55
Fig. 825
Bar Joist Sway
Brace Attachment
Page 45
Fig. 825A
Bar Joist Sway
Brace Attachment
Page 46
Fig. 975
Straight
Sway Brace Fitting
Page 51
Fig. 906
Sway Brace
Multi-Fastener Adapter
Page 47
Fig. 980
Universal Swivel
Sway Brace Attachment
Page 52
Fig. 1000
Fig. 1001
"Fast Clamp"
Sway Brace Attachment
Sway Brace Attachment
Page 57
Page 56
Fig. 2002
Sway Brace Attachment
Page 58
NOTE: For more information on TOLCO products, please see TOLCO™ Pipe Hangers and Support Systems Catalog.
4
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 8/15/2005
Component of State of
California OSHPD Approved
Seismic Restraints System
Fig. 1 - Standard Clevis Hanger
Size Range — Size 1/2" thru 36" pipe.
Material — Carbon Steel
Function — Recommended for the suspension of
non-insulated pipe or insulated pipe with Fig. 220 shield.
Note — When an oversized clevis is used, a pipe spacer
should be placed over the cross bolt to assure that the
lower U-strap will not move in on the bolt. When attaching seismic bracing to clevis hangers, a Fig. 1 CBS (cross
bolt spacer) must be installed. See TOLCO™ Seismic
Restraint Approval Guidelines.
APPROVALS — Underwriters’ Laboratories Listed in the
USA (UL), Canada (cUL) 3/4" thru 8". FM Approved
3/4" - 11/2", 6" - 8".Conforms to Federal Specification
WW-H-171E, Type 1, and Manufacturers Standardization
Society SP-58, Type 1. Also available to accommodate rod
schedule per National Fire Protection Association (NFPA)
Pamphlet 13. Included in our Seismic Restraints Catalog
approved by the State of California Office of Statewide
Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic
Restraint Systems Guidelines.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish
or Stainless Steel.
Dimensions • Weights
Pipe
Size
Rod Size A
STD
NFPA
B
C
D
Max. Rec.
Load Lbs.
Approx.
Wt./100
1/2
3/4
1
3/8
3/8
3/8
3/8
3/8
3/8
21⁄16
27⁄8
31⁄4
13⁄16
17⁄8
21⁄16
1
1
1
610
610
610
36
38
42
11⁄4
11⁄2
2
3/8
3/8
3/8
3/8
3/8
3/8
39⁄16
37⁄8
47⁄16
21⁄4
23⁄8
23⁄4
1
1
1
610
610
610
46
49
55
21⁄2
3
31⁄2
1/2
1/2
1/2
3/8
3/8
3/8
55⁄16
515⁄16
67⁄16
31⁄4
31⁄2
33⁄4
1
11⁄4
11⁄4
1130
1130
1130
124
140
152
4
5
6
8
10
12
5/8
5/8
3/4
3/4
7/8
7/8
3/8
1/2
1/2
1/2
5/8
5/8
73⁄8
815⁄16
913⁄16
129⁄16
161⁄4
191⁄4
41⁄4
51⁄4
51⁄2
71⁄8
95⁄8
115⁄8
11⁄2
11⁄2
11⁄2
2
31⁄4
31⁄2
1430
1430
1940
2000
3600
3800
190
235
317
428
918
1143
14
16
18
1
1
1
—
—
—
2013⁄16
2115⁄16
247⁄16
125⁄16
127⁄16
1315⁄16
313⁄16
35⁄8
37⁄8
4200
4600
4800
1543
1925
2243
20
*24
*30
*36
11⁄4
11⁄4
11⁄4
11⁄2
—
—
—
—
265⁄16
313⁄8
387⁄8
48
147⁄16
171⁄2
217⁄8
273⁄4
4
41⁄4
5
53⁄4
4800
4800
6000
9500
4161
4835
6940
18103
*Furnished with pipe spacer to support maximum load rating
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
5
www.tolco.com
Revision 5/24/2001
Fig. 1CBS - Clevis Bolt Spacer
Component of State of
California OSHPD Approved
Seismic Restraints System
Size Range — Size 1" thru 20" clevis hanger
Material — Carbon Steel
Function — Used as a spacer at a seismic brace location to
keep clevis hanger from collapsing during seismic event.
Approvals — Underwriters Laboratories Listed in the USA
(UL) and Canada (cUL). Included in our Seismic Restraints
Catalog approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic
Restraint Systems Guidelines.
Installation Note — Fig. 1CBS fits easily over the cross bolt
and attaches by pinching tabs down.
Finish — Mil Galvanized
Note — Available in HDG finish or Stainless Steel materials.
6
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 5/24/2001
Fig. 1F — Felt Lined Standard Clevis Hanger
Fig. 1PVC — PVC Coated Standard Clevis Hanger
Size Range — Size 1/2" thru 8" pipe.
Material — Carbon Steel
Insulation Material — 3/16" felt
Function — The Fig. 1F is designed for the suspension of copper
tube so as to prevent electrolysis between tube and hanger. The
Fig. 1PVC is designed for steel or other pipe types of same O.D.
Both Fig. 1F and Fig. 1PVC act to reduce noise and vibration in pipe
or tube system.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) and
Canada (cUL).
Maximum Temperature — 650°F
Finish — Plain
Note —When Fig. 1F is used for steel or other pipe types, consult
factory for proper size hanger. Available in Electro-Galvanized and
HDG finish or Stainless Steel.
Order By — Figure number, nominal tube size and finish
Fig. 1F
Fig. 1PVC
Dimensions • Weights
Pipe
Size
Rod Size A
STD
NFPA
B
C
D
Max. Rec.
Load Lbs.
Approx.
Wt./100
1/2
3/4
1
3/8
3/8
3/8
3/8
3/8
3/8
27⁄8
31⁄16
33⁄8
1
111⁄16
17⁄8
1
1
1
610
610
610
36
38
43
11⁄4
11⁄2
2
3/8
3/8
3/8
3/8
3/8
3/8
33⁄4
41⁄16
41⁄2
21⁄16
23⁄16
29⁄16
1
1
1
610
610
610
47
50
56
21⁄2
3
31⁄2
1/2
1/2
1/2
3/8
3/8
3/8
51⁄2
61⁄8
63⁄4
31⁄16
35⁄16
39⁄16
1
11⁄4
11⁄4
1130
1130
1130
125
141
153
4
5
6
8
5/8
5/8
3/4
3/4
3/8
1/2
1/2
1/2
75⁄8
87⁄8
10
123⁄4
41⁄16
51⁄16
55⁄16
615⁄16
11⁄2
11⁄2
11⁄2
2
1430
1430
1940
2000
191
236
318
429
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
7
www.tolco.com
Revision 3/31/2003
Fig. 2 — Adjustable Band Hanger
Fig. 2NFPA — Adjustable Band Hanger with Reduced Rod
Size Range — Size 21/2" thru 4" pipe.
Material — Carbon Steel, Pre-Galvanized
Function — Recommended for the suspension of non-insulated pipe or insulated pipe with Fig. 220 shield. Fig. 2NFPA
accommodates the reduced rod schedule of the National Fire Protection
Association Pamphlet 13.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) and
Canada (cUL). Factory Mutual Engineering approved. Conforms to Federal
Specification WW-H-171E, Type 10 and Manufacturers Standardization
Society SP-69, Type 10. Included in our Seismic Restraints Catalog
approved by the State of California Office of Statewide Health Planning and
Development (OSHPD).
Finish — Pre-Galvanized
Note — Available in Stainless Steel materials.
Order By — Figure number, pipe size and material
Component of State of
California OSHPD Approved
Seismic Restraints System
Dimensions • Weights
*
**
8
Pipe
Size
Rod Size
A
B
C
Max. Rec.
Load Lbs.
21⁄2
3
31⁄2
4
5
6
1/2*
1/2*
1/2*
5/8*
5/8**
3/4**
53⁄4
6
73⁄8
73⁄8
9
93⁄8
41⁄4
41⁄8
51⁄4
5
61⁄8
61⁄2
15⁄8
11⁄4
21⁄8
15⁄8
21⁄4
17⁄8
600
600
600
1000
1250
1250
Approx Wt./100
Fig. 2
Fig. 2NFPA
41
45
52
59
97
139
3/8" nut is used when NFPA rod sizing is requested.
1/2" nut is used when NFPA rod sizing is requested.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
40
43
50
56
95
105
www.tolco.com
Revision 3/31/2003
Fig. 2F - Adjustable Band Hanger with Felt Lining
Size Range — 1/2" thru 6" copper tubing
Material — Carbon Steel, Pre-Galvanized
Function — Recommended for the suspension of copper tube so
as to prevent electrolysis. The felt lining also acts to reduce noise in
copper or other pipe types.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) and
Canada (cUL). Conforms to Federal
Specification WW-H-171E, Type 10 and Manufacturers
Standardization Society SP-69, Type 10.
Finish — Pre-Galvanized
Note — When used for steel or other pipe types, consult factory
for proper size. Available in Stainless Steel materials.
Order By — Figure number and copper tube size
Dimensions • Weights
Copper Tube
Size
Rod Size
A
B
C
Max. Rec.
Load Lbs.
Approx.
Wt./100
1/2
3/4
1
3/8
3/8
3/8
31/8
31/8
33/8
25/8
21⁄2
25/8
13/8
11/8
11/8
400
400
400
12
12
13
11⁄4
11⁄2
2
3/8
3/8
3/8
33/4
37/8
41⁄4
27/8
27/8
3
11⁄4
11/8
1
400
400
400
14
15
16
21⁄2*
3*
31⁄2*
1/2
1/2
1/2
53/4
6
73/8
41/8
4
51⁄4
13/4
11⁄2
13/8
600
600
600
41
46
53
4*
5**
6**
5/8
5/8
3/4
73/8
9
93/8
5
61/8
61⁄2
17/8
21⁄2
21⁄4
1000
1250
1250
60
98
140
* 3/8" nut is used when requested.
** 1/2" nut is used when requested.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
9
www.tolco.com
Revision 5/24/2001
Fig. 2WON - Adjustable Band Hanger w/o Swivel Nut
Fig. 2FWON - Felt Lined Band Hanger w/o Swivel Nut
Size Range — (Fig. 2WON) Size 1/2" thru 8" pipe.
(Fig. 2F WON) 1/2" thru 8" copper tube
Material — Pre-Galvanized Steel
Function — Recommended for the suspension of
non-insulated pipe or insulated pipe with Fig. 220 shield.
Approvals — Underwriters’ Laboratories Listed in the
USA (UL) and Canada (cUL). Conforms to Federal
Specification WW-H-171E, Type 7, and Manufacturers
Standardization Society SP-69, Type 7, 3/4" thru 6".
Finish — Pre-Galvanized
Note — Available in Stainless Steel materials.
Order By — Figure number and pipe size
Fig. 2WON
Fig. 2F WON
Dimensions • Weights
Pipe
Size
Rod Size
A
B
C
D
Max. Rec.
Load Lbs.
Approx.
Wt./100
1/2
3/4
1
3/8
3/8
3/8
25⁄8
25⁄8
27⁄8
21⁄8
2
21⁄8
11⁄4
1
1
400
400
400
14
14
16
11⁄4
11⁄2
2
3/8
3/8
3/8
33⁄8
31⁄2
33⁄4
21⁄2
21⁄2
21⁄2
11⁄4
1
7/8
400
400
400
17
18
20
21⁄2
3
31⁄2
1/2*
1/2*
1/2*
5
51⁄2
63⁄4
31⁄2
35⁄8
45⁄8
11⁄2
11⁄4
2
600
600
600
27
40
48
4
5
6
8
5/8*
5/8**
3/4**
3/4**
63⁄4
81⁄2
91⁄4
121⁄4
43⁄8
55⁄8
57⁄8
77⁄8
11⁄2
21⁄8
15⁄8
25⁄8
1000
1250
1250
1250
53
91
99
120
* 3/8" nut is used when NFPA rod sizing is requested.
** 1/2" nut is used when NFPA rod sizing is requested.
10
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 8/15/2005
Component of State of
Fig. 3 - J-Hanger for Pipe or Conduit
California OSHPD Approved
Seismic Restraints System
Fig. 3F - Felt Lined J-Hanger for Copper Tubing
Fig. 3PVC - PVC Coated J-Hanger for Pipe or Conduit
Size Range — 1/2" thru 12" pipe
Material — Carbon Steel
Function — Recommended for the suspension of non-insulated pipe, or
insulated pipe with Fig. 220 shield. Side hole allows for wall mounting.
Fig. 3F and Fig. 3PVC are designed to reduce noise and vibration and/or
prevent electrolysis between pipe and hanger.
Approvals — Conforms to Manufacturers Standardization Society SP-69,
Type 5. Underwriters Laboratories Listed in the USA (UL) and Canada
(cUL). Included in our Seismic Restraints Catalog approved by the
State of California Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement information relating
to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems
Guidelines.
Finish — Electro-Galvanized
Note — Available in HDG finish or Stainless Steel materials.
Order By — Figure number, pipe size and finish
Fig. 3
Fig. 3PVC
Fig. 3F
Dimensions • Weights
Copper Tube
Size
Rod Size
A
B
C
D
E
F
Max. Rec.
Load Lbs.
Approx.
Wt./100
1/2
3/4
1
3/8
3/8
3/8
25⁄8
27⁄8
215⁄16
13⁄4
17⁄8
115⁄16
7/16
7/16
7/16
11⁄2
111⁄16
113⁄16
115⁄166
21⁄8
25⁄16
400
400
400
18
21
22
11⁄4
11⁄2
2
3/8
3/8
3/8
31⁄4
39⁄16
311⁄16
2
23⁄16
21⁄8
7/16
7/16
7/16
21⁄16
27⁄16
29⁄16
25⁄8
27⁄8
31⁄16
400
400
400
25
27
29
21⁄2
3
31⁄2
1/2
1/2
1/2
47⁄16
413⁄16
51⁄8
27⁄16
29⁄16
25⁄8
9/16
9/16
9/16
33⁄16
31⁄2
33⁄4
35⁄8
41⁄16
43⁄8
500
500
500
64
72
84
4
5
6
5/8
5/8
3/4
61⁄8
63⁄4
73⁄4
33⁄16
31⁄4
39⁄16
9/16
9/16
9/16
45⁄8
51⁄16
513⁄16
53⁄16
53⁄4
65⁄8
550
550
600
138
162
249
8
10
7/8
7/8
93⁄16
103⁄4
315⁄16
37⁄8
9/16
9/16
615⁄16
75⁄8
8
91⁄8
760
760
291
315
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
11
www.tolco.com
Revision 5/31/2005
Component of State of
California OSHPD Approved
Seismic Restraints System
Fig. 4 - Standard Pipe Clamp
Fig. 4F - Standard Pipe Clamp Felt Lined
Fig. 4PVC - Standard Pipe Clamp PVC Coated
Size Range — (Fig. 4) Size 1/2" thru 30" pipe.
Size Range — (Fig. 4F) Size 1/2" thru 21/2" copper tubing
Material — Carbon Steel
Function — Recommended for the suspension of non-insulated pipe or insulated pipe with
Fig. 220 shields. (Use Fig. 330 Weldless Eye Nut, Fig. 102 Eye Rod or Fig. 101 Welded
Eye Rod.) Also recommended for attachment of sway bracing up to 31/2" pipe size, for
larger pipe sizes use Fig. 4A. Fig. 4F and Fig. 4PVC are designed to reduce noise and
vibration and/or prevent electrolysis.
Approvals — Underwriters’ Laboratories Listed in the USA (UL), Canada (cUL) 3/4" - 8",
and approved by Factory Mutual Engineering, 3/4" - 8". Federal Specification WW-H-171E,
Type 4, 11/2" thru 24" and Manufacturers Standardization Society SP-69, Type 4. Included
in our Seismic Restraints Catalog approved by the State of California Office of Statewide
Health Planning and Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to the TOLCO Seismic
Restraint Systems Guidelines.
Note — When the Fig. 4 is used as a sway brace, to ensure performance,
the UL Listing requires that it must be used with other TOLCO™ brace
products.
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number, pipe size and finish.
Fig. 4F
Order Note — When ordering Fig. 4F allow for 3/16" felt on each half of clamp.
Fig. 4
Fig. 4PVC
Dimensions • Weights
Max. Design Load Lbs.
For Service Temp.
650°
750°F
Pipe
Size
A
B
C
D
Bolt Size
1/2
3/4
1
37⁄16
39⁄16
39⁄16
1/4
1/4
1/4
11⁄8
11⁄4
11⁄4
11⁄8
11⁄4
15⁄16
5/16
5/16
5/16
500
500
500
445
445
445
29
31
35
11⁄4
11⁄2
2*
43⁄16
49⁄16
59⁄16
1/2
5/16
1/2
13⁄8
15⁄8
2
111⁄16
17⁄8
21⁄4
5/16
5/16
3/8
500
800
1040
445
715
930
40
42
93
21⁄2*
3*
31⁄2*
67⁄16
7
711⁄16
9/16
5/8
3/8
21⁄2
23⁄4
31⁄8
23⁄4
31⁄16
33⁄8
1/2
1/2
1/2
1040
1040
1040
930
930
930
126
141
154
4
5
6
81⁄2
93⁄4
115⁄8
5/8
3/4
3/4
35⁄16
37⁄8
47⁄8
311⁄16
43⁄8
51⁄8
5/8
5/8
3/4
1040
1040
1615
930
930
1440
229
261
537
8
10
12
135⁄16
161⁄2
181⁄2
1
1
1
55⁄8
71⁄4
81⁄4
6
71⁄4
81⁄4
3/4
7/8
7/8
1615
2490
2490
1440
2220
2220
625
1378
1574
14
16
18
20
23
257⁄8
11⁄8
11⁄8
11⁄4
9
101⁄4
111⁄2
9
101⁄4
111⁄2
7/8
7/8
1
2490
2490
3060
2220
2220
2730
2103
2314
3276
Approx.
Wt./100
121⁄2
121⁄2
11⁄8
3060
2730
3863
20
28
13⁄8
24
331⁄2
15⁄8
151⁄4
151⁄4
11⁄4
3060
2730
5222
30
417⁄8
2
19
19
13⁄4
3500
3360
10511
*Meets UL 203A requirements for attachment of sway bracing. Horizontal design load for 1/2"-2" - 380#, 21⁄2" - 395#, 3" - 435#, 31⁄2" - 540#
12
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 5/5/2006
Component of State of
California OSHPD Approved
Seismic Restraints System
Fig. 4A - Pipe Clamp for Sway Bracing
Size Range — 4" thru 8" pipe. For sizes smaller than 4" use TOLCO™ Fig. 4.
Material — Carbon Steel
Function — For bracing pipe against sway and seismic disturbance.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) and Canada
(cUL) 4" thru 8". Included in our Seismic Restraints Catalog approved by
the State of California Office of Statewide Health Planning and Development
(OSHPD).
Installation Instructions — The Fig. 4A is the "braced pipe" attachment
component of a longitudinal, lateral or riser brace assembly. It is intended to
be combined with the "bracing pipe" and TOLCO transitional and structural
attachment component(s) to form a complete bracing assembly. NFPA 13
and/or OSHPD guidelines should be followed.
To Install — Place the Fig. 4A over the pipe to be braced. Attach TOLCO
transitional fitting, either Fig. 980, 910 or 909, to the clamp ears. Tighten bolts
and nuts; torque requirement is a minimum of 50 ft. lbs. Transitional fitting
attachment can pivot for adjustment to proper brace angle.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number, pipe size and finish
Fig. 4A - Longitudinal Brace
Dimensions • Weights
Pipe
Sizes
A
B
C
D
Bolt Size
Max. Horizontal
Design Load
Approx.
Wt./100
4
5
6
8
81⁄2
93⁄4
111⁄2
131⁄4
9/16
9/16
5/8
3/4
33⁄8
37⁄8
5
611⁄16
311⁄16
43⁄8
51⁄8
61⁄8
1/2
1/2
1/2
1/2
2015
2015
2015
2015
221
253
513
601
TOLCO® brand bracing components are desgined to be compatible ONLY with other TOLCO® brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO® brand bracing components, in the instance that
such TOLCO® brand bracing components are used in
combination with products, parts or systems which are not manufactured or sold under
the TOLCO® brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind,
including but not limited to loss of business or profit, where non-TOLCO brand bracing components have been, or are used.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
13
www.tolco.com
Revision 5/5/2006
Fig. 4B - Pipe Clamp for Sway Bracing
Component of State of
California OSHPD Approved
Seismic Restraints System
Size Range — 3/4" thru 8" pipe.
Material — Carbon Steel
Function — For bracing pipe against sway and seismic disturbance.
Features — This product's design incorporates concentric loading of the "brace pipe",
connection components and fasteners which is critical to the performance of seismic
bracing assemblies.
Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
Included in our Seismic Restrains Catalog approved by the State of California Office of
Statewide Health Planning and Development (OSHPD).
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials.
Order By — Figure number, pipe size and finish.
Installation Instructions — The Fig. 4B is the "braced
pipe" attachment component of a longitudinal or lateral
sway brace assembly. It is intended to be combined with
the "bracing pipe" and TOLCO transitional and structural
attachment component(s) to form a complete bracing
assembly. NFPA 13 and/or OSHPD guidelines should be
Shown with two TOLCO™
followed.
Fig. 980’s and Schedule 40
brace pipe.
To Install — Place the Fig. 4B over the pipe to be braced.
Attach other TOLCO transitional fitting, Fig. 909, 910
or 980. Tighten bolts and nuts. Transitional fitting attachment can pivot for adjustment to proper brace angle.
Fig. 4B - Hanger/Longitudinal Brace
Dimensions • Weights
Pipe
Sizes
Rod Size
A
B
C
D
Bolt Size
Max. Design
Load Lbs.
Approx.
Wt./100
3/4
1
11⁄4
3/8
3/8
3/8
1
1
1
27⁄8
31⁄4
39⁄16
25⁄8
215⁄16
31⁄4
5/16
5/16
5/16
330
330
330
56
60
74
11⁄2
2
21⁄2
3/8
3/8
1/2
1
11⁄2
13⁄4
313⁄16
51⁄8
55⁄8
37⁄16
45⁄8
53⁄8
5/16
5/16
3/8
330
440
440
79
156
176
3
31⁄2
4
1/2
1/2
5/8
17⁄8
2
2
63⁄4
71⁄4
85⁄8
61⁄8
63⁄4
71⁄4
3/8
3/8
1/2
660
660
800
198
219
288
5
6
8
5/8
3/4
7/8
2
21⁄8
21⁄8
97⁄8
1015⁄16
137⁄16
85⁄16
91⁄2
111⁄2
5/8
5/8
3/4
980
980
1200
390
448
691
TOLCO® brand bracing components are desgined to be compatible ONLY with other TOLCO® brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO® brand bracing components, in the instance that
such TOLCO® brand bracing components are used in
combination with products, parts or systems which are not manufactured or sold under
the TOLCO® brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind,
including but not limited to loss of business or profit, where non-TOLCO brand bracing components have been, or are used.
14
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 5/5/2006
Fig. 4L
Longitudinal “In-Line” Sway Brace Attachment
Size Range — 2½" through 8" IPS.
Material — Carbon Steel
Function — For bracing pipe against sway and seismic disturbance.
Approvals — Underwriter's Laboratories Listed in the USA (UL) and
Canada (cUL) 2½" through 8".
Installation Instructions — The Fig. 4L is the "braced pipe" attachment
component of a longitudinal sway brace assembly. It is intended to be
combined with the "bracing pipe" and TOLCO structural attachment
component to form a complete bracing assembly. NFPA 13 and/or
OSHPD guidelines should be followed.
To Install — Place the Fig. 4L over the pipe to be braced and tighten
bolts. Then engage "bracing pipe" into jaw opening and tighten set bolt
until hex head snaps off. Jaw attachment can pivot for adjustment to
proper brace angle.
Finish — Plain
Note — Available in electro-galvanized and HDG finish.
Order By — Figure number, pipe size and finish.
Dimensions • Weights
Sizes
A
C
D
Bolt
Size
Max. Rec.
Load Lbs.
Approx.
Wt./100
21⁄2
3
4
5
6
8
67⁄16
7
81⁄2
93⁄4
111⁄2
131⁄4
21⁄2
23⁄4
33⁄8
37⁄8
5
611⁄16
23⁄4
31⁄16
311⁄16
43⁄8
51⁄8
61⁄8
1/2
1/2
1/2
1/2
1/2
1/2
2015
2015
2015
2015
2015
2015
253
268
348
380
640
728
Longitudinal Brace
4-Way Riser Brace
(Plan view)
TOLCO® brand bracing components are desgined to be compatible ONLY with other TOLCO® brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO® brand bracing components, in the instance that
such TOLCO® brand bracing components are used in
combination with products, parts or systems which are not manufactured or sold under
the TOLCO® brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind,
including but not limited to loss of business or profit, where non-TOLCO brand bracing components have been, or are used.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
15
www.tolco.com
Revision 5/24/2001
Fig. 6 - Riser Clamp
Fig. 6F - Felt Lined Riser Clamp
Fig. 6PVC - PVC Coated Riser Clamp
Size Range — (Fig. 6) 1/2" thru 20" pipe
(Fig. 6F) 1/2" thru 21/2" copper tubing
(Fig. 6PVC) 1/2" thru 6" pipe
Material — Carbon Steel
Insulation Material — (Fig. 6F) 3/16" felt.
Function — Used for supporting vertical piping.
Approvals — Underwriters’ Laboratories Listed in the USA (UL), Canada
(cUL) 1/2" - 8". Factory Mutual Engineering Approved, 3/4" thru 8".
Conforms to Federal Specification WW-H-171E, Type 8, 3/4" thru 20" and
Manufacturers Standardization Society SP-69, Type 8.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless Steel
materials.
Order By — (Fig. 6 and Fig. 6PVC) pipe size and finish. (Fig. 6F) copper
tube size and finish. (Fig. 6F is available for Iron Pipe Size, consult factory.
Fig. 6
Fig. 6PVC
Fig. 6F
Dimensions • Weights
16
Pipe
Size
A
B
C
Bolt Size
Max. Rec.
Load Lbs.
Approx.
Wt./100
1/2
3/4
1
91⁄4
91⁄4
99⁄16
1/2
1/2
1/2
11⁄8
11⁄8
11⁄4
3/8
3/8
3/8
255
255
255
144
144
147
11⁄4
11⁄2
2
911⁄16
103⁄8
103⁄4
1/2
1/2
1/2
13⁄8
11⁄2
2
3/8
3/8
3/8
255
255
255
150
153
165
21⁄2
3
31⁄2
11
12
13
5/8
5/8
5/8
21⁄4
3
31⁄4
3/8
3/8
1/2
390
530
670
228
246
264
4
5
6
131⁄2
141⁄2
151⁄8
3/4
3/4
7/8
33⁄8
43⁄8
47⁄8
1/2
1/2
1/2
810
1160
1570
347
385
564
8
10
12
14
16
18
20
181⁄2
201⁄4
223⁄4
24
26
28
30
1
1
1
11⁄8
11⁄8
11⁄4
13⁄8
53⁄4
71⁄4
81⁄4
9
101⁄4
111⁄2
121⁄2
5/8
5/8
5/8
5/8
3/4
3/4
3/4
2500
2500
2700
2700
2900
2900
2900
1017
1138
1759
1922
3245
3372
3499
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 3/31/2003
Fig. 22 - Hanger for CPVC Plastic Pipe Single Fastener Strap Type
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre-Galvanized
Function — Intended to perform as a hanger to support only CPVC piping used in automatic fire sprinkler systems. The product acts as a hanger
when tab is upward and the fastener screw is in the horizontal position.
Figure 22 can be installed on the top of a beam, but in this situation acts as
a guide to the piping which is supported by the beam itself. It is not intended
to support CPVC pipe from under a flat horizontal surface, such as a ceiling.
For this type of installation, use the TOLCO™ Fig. 23, Double Fastener Strap
for CPVC Piping. Fig. 22, when inverted, with the hanger tab downward,
can function as a restrainer to prevent the upward movement of the sprinkler
head during activation.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) and
Canada (cUL) to support fire sprinkler piping. Meets and exceeds the
requirements of NFPA 13, 13R and 13D.
Features — Fig. 22 incorporates features which protect the pipe and ease
installation. The flared edge design*
protects CPVC pipe from any rough surface. It is easily attached to the building structure using the special UL Listed
hex head self threading screw furnished with the product, this is the minimum size fastener acceptable. It is
recommended that rechargeable electric drills fitted with a hex socket attachment to be used as installation tools. No
impact tools (such as a hammer) or impact fasteners (such as drive screws or nails) are allowed. Damage has been
know to result from installations using impact type tools. No pre-drilling of a pilot hole in wood is required.
Finish — Pre-Galvanized
Note — Fastener into light gauge metal may be ordered separately. Minimum acceptable: #10 x 1" Hardened Self
Threading Screw with 5/16" hex washer head.
Order By — Figure number and CPVC pipe size.
* Patent Pending
Dimensions • Weights
CPVC
Pipe Size
A
B
C
Max. Hanger
Spacing (Ft.)
Fastener Hex
Head Size
Approx.
Wt./100
3/4
1
11⁄4
11⁄2
2
27⁄16
211⁄16
31⁄16
35⁄16
33⁄4
15⁄16
17⁄16
15⁄8
13⁄4
21⁄8
13⁄16
13⁄16
13⁄16
13⁄16
13⁄16
51⁄2
6
61⁄2
7
8
5/16
5/16
5/16
5/16
5/16
9
9
11
12
15
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
17
www.tolco.com
Revision 3/31/2003
Fig. 22C - Combination Hanger & Restrainer Application
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre-Galvanized
Function — Designed to support a CPVC pipe away
from the corner of a beam. This position allows for easy
installation of drops or risers without adding additional
wood blocks.
Approvals — Underwriters’ Laboratories Listed in the USA
(UL) and Canada (cUL) for use as a combination hanger and
restrainer.
Finish — Pre-Galvanized
Note — Approved UL Listed fastener into wood is furnished
with the product. A fastener into light gauge metal may be
ordered separately. Minimum acceptable #10 x 1" hardened
self threading screw with 5/16" hex washer head.
Order By — Fig. 22C application is composed of two
standard Fig. 22 models — order two singles for each hanger
and restrainer application required.
18
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 5/24/2001
Fig. 23 - Hanger for CPVC Plastic Pipe Double Fastener Strap Type
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre-Galvanized
Function — Intended to perform as a hanger/restrainer to support
only CPVC piping used in automatic fire sprinkler systems. Can be
installed on the top or on the bottom of a beam. The Fig. 23 can also
be installed on the side of a beam. The Fig. 23 can also function as
a restrainer to prevent the upward movement of the sprinkler head
during activation.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) and
Canada (cUL) to support fire sprinkler piping. Meets and exceeds
the requirements of NFPA 13, 13R and 13D.
Features — Fig. 23 incorporates features which protect the pipe
and ease installation. The flared edge design* protects the CPVC
pipe from any rough surface. It also incorporates snap restrainers
allowing easier and faster installation. Easily attaches to the building
structure using the two UL Listed hex head self threading screws**
furnished with the product. It is recommended that rechargeable
electric drills fitted with a hex socket attachment be used as
installation tools. No impact tools (such as a hammer) or impact
fasteners (such as drive screws or nails) are allowed. Damage has
been known to result from installations using impact type tools.
No pre-drilling of a pilot hole in wood is required.
Finish — Pre-Galvanized
Order By — Figure number and pipe size
* Patent Pending
** Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
Dimensions • Weights
CPVC
Pipe Size
A
B
C
Max. Hanger
Spacing (Ft.)
Fastener Hex
Head Size
Approx.
Wt./100
3/4
1
11⁄4
31⁄8
33⁄8
43⁄16
19⁄16
111⁄16
23⁄32
13⁄16
13⁄16
13⁄16
51⁄2
6
61⁄2
5/16
5/16
5/16
9
9
11
11⁄2
2
47⁄16
47⁄8
27⁄32
27⁄16
13⁄16
13⁄16
7
8
5/16
5/16
12
15
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
19
www.tolco.com
Revision 5/24/2001
Fig. 24 - Hanger for CPVC Plastic Pipe Double Fastener
Strap Type - Side Mount
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre-Galvanized
Function — Intended to perform as a hanger/restrainer to support only
CPVC piping used in automatic fire sprinkler systems. Can be installed
on the top or on the bottom of a beam. The Fig. 24 can also function
as a restrainer to prevent the upward movement of the sprinkler head
during activation.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) and
Canada (cUL) to support fire sprinkler piping. Meets and exceeds the
requirements of NFPA 13, 13R and 13D.
Features — Fig. 24 incorporates features which protect the pipe and
ease installation. The flared edge design* protects the CPVC pipe from
any rough surface. Easily attaches to the building structure using the two
UL Listed hex head self threading screws** furnished with the product. It
is recommended that rechargeable electric drills fitted with a hex socket attachment
be used as installation tools. No impact tools (such as a hammer) or impact fasteners
(such as drive screws or nails) are allowed. Damage has been known to result from
installations using impact type tools. No pre-drilling of a pilot hole in wood is required.
Finish — Pre-Galvanized
Order By — Figure number and pipe size
* Patent Pending
** Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
Dimensions • Weights
CPVC
Pipe Size
A
B
C
Max. Hanger
Spacing (Ft.)
Fastener Hex
Head Size
Approx.
Wt./100
3/4
1
11⁄4
25⁄16
25⁄8
3
15⁄32
15⁄16
11⁄2
13⁄16
13⁄16
13⁄16
51⁄2
6
61⁄2
5/16
5/16
5/16
9
9
11
11⁄2
2
31⁄4
311⁄16
15⁄8
127⁄32
13⁄16
13⁄16
7
8
5/16
5/16
12
15
20
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 3/24/2003
Fig. 25 - Surge Restrainer
Size Range — One size fits 3/4" thru 2" pipe.
Material — Steel
Function — Designed to be used in conjunction with TOLCO™ Band Hangers to
restrict the upward movement of piping as it occurs during sprinkler head activation or earthquake type activity. The surge restrainer
is easily and efficiently installed by snapping into a locking position on
the bank hanger. This product is intended to satisfy the requirements as indicated
in the National Fire Protection Association (NFPA 13, 1999 Edition), 6-2.3.3, 62.3.4 and A-6i-2.3.3 Can be used to restrain either
steel pipe or CPVC plastic Pipe.
Approvals — Underwriters’ Laboratories Listed only when used with TOLCO
band hangers Fig. 2, 2NFPA and 200, in the USA (UL) and
Canada (cUL).
Finish — Pre-Galvanized
Order By — Figure number and TOLCO band hanger, size from
3/4" thru 2".
Patent #5,344,108
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
21
www.tolco.com
Revision 6/12/2006
Fig. 26 - Nail Plate
Sizes - Small – 11/2" x 23/4"
Large – 3" x 23/4"
Material – Carbon Steel
Finish – Plain
Function – To prevent damage to plastic pipe or conduit from
installation of fasteners after pipe has been installed, such as drywall screws, nails etc. The Small size is designed to be installed
on the side of a 2x4, while the Large size is designed for either a
4x4 or two stacked 2 x4’s such as at the base and at the top of
framing walls.
Installation – Designed to be installed into wood structural member adjacent to the pipe. No fasteners required.
Order By - Figure Number and size (small or large)
Small
Large
22
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
www.tolco.
Revision 5/24/2001
Fig. 28 - "Stand-Off" Hanger & Restrainer for CPVC Plastic Pipe
Size Range — 3/4" through 2"
Material — Carbon Steel, Pre-Galvanized
Function — Designed to be used as a hanger and restrainer for CPVC piping where
the "stand-off" design will ease installation by eliminating the need for wood blocking.
Features:
• Flared edge design protects CPVC pipe from any rough or abrasive surfaces.
• Unique twist and lock design holds pipe firmly in place and allows retrofit type
of installation.
• The "Stand-Off" design eliminates the need for wood block extension.
• Can be installed on horizontal or vertical piping regardless of mounting
surface orientation.
• Attached easily to wood structure with two hex head self-threading screws
furnished with product.
• Installs easily using rechargeable electrical driver with 5/16" extension socket
eliminating impact tool damage to pipe.
• U.L. Listed as a hanger and a restrainer for fire sprinkler piping.
Approvals — Underwriters' Laboratory Listed in the USA (UL) and Canada (cUL) to
support automatic fire sprinkler systems. Meets and exceeds the requirements of
NFPA 13, 13R and 13D. Fig. 28 satisfies the UL vertical restraint requirement where
needed. UL Listed as a hanger and vertical restraint when installed on 3/8" composite
wood material. Use two Fig. 27B Speed Nuts when used as a hanger and restraint.
Use one Fig. 27B Speed Nut on the upper installed screw when used as a hanger only.
Order by — Figure number and pipe size.
US AND INTERNATIONAL PATENT APPLICATION IN PROCESS.
Dimensions • Weights
23
Pipe
Size
A
3/4
1
11⁄4
11⁄2
2
31⁄32
35⁄16
35⁄8
4
41⁄2
B
C
Approx.
Wt.
2
23⁄16
23⁄8
21⁄2
211⁄16
31⁄2
31⁄2
31⁄2
31⁄2
35⁄8
.180
.210
.225
.310
.340
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
23
™
www.tolco.com
®
Revision 5/24/2001
a brand of
Fig. 42 - Angle Bracket
Material — Carbon Steel
Function — Recommended for supporting pipe at various
distances from wall or column.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, size and finish
Dimensions • Weights
Pipe
Size
A
B
Hole
Size
Max. Rec.
Load Lbs.
1
2
3
4
3
4
3
4
2
3
2
3
7/16
7/16
9/16
9/16
180
180
390
390
Approx.
Wt./100
46
65
85
115
Fig. 50 - Side Beam Bracket
Size Range — 3/8" thru 7/8" rod
Material — Carbon Steel
Function — Recommended for attaching hanger rod to side
of beams or walls.
Approvals — 3/8", Underwriters’ Laboratories Listed in
the USA (UL) and Canada (cUL), and Factory Mutual
Engineering approved.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size and finish
Dimensions • Weights
Pipe
Size
A
B
C
Hole
Size
Max. Rec.
Load Lbs.
3/8
1/2
5/8
2
2
2
3/4
3/4
3/4
2
2
2
7/16
9/16
11/16
700
700
700
35
35
32
3/4
7/8
21⁄2
21⁄2
3/4
3/4
21⁄2
21⁄2
13/16
15/16
1250
1250
110
100
24
Approx.
Wt./100
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
24
™
www.tolco.com
®
Revision 5/24/2001
a brand of
Fig. 51 - Side Beam Bracket for NFPA Rod and Fastener Sizing
Size Range — 3/8" and 1/2" rod, 1/2" thru 8" pipe
Material — Carbon Steel
Function — Recommended for attaching hanger rod to side of
beams or walls. Designed to accommodate current rod schedule and fastener requirements per National Fire Protection
Association (NFPA) Pamphlet 13.
Approvals — Underwriters’ Laboratories Listed in the USA (UL)
and Canada (cUL), and Factory Mutual Engineering approved.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size and finish
Dimensions • Weights
Pipe
Rod
Size
Size
1/2 - 2
21⁄2 - 4
5-6
8
25
3/8
3/8
1/2
1/2
Hole Size
A
B
C
H-1
H-2
Max. Rec.
Load Lbs.
2
2
21⁄2
21⁄2
3/4
3/4
3/4
3/4
2
2
21⁄2
21⁄2
7/16
9/16
9/16
11/16
7/16
7/16
9/16
9/16
700
700
1250
1250
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Approx.
Wt./100
35
34
71
70
25
www.tolco.com
Revision 5/24/2001
Fig. 58 - Threaded Side Beam Bracket
Size Range — 3/8" rod, pipe sizes 1/2" thru 4"
Material — Carbon Steel
Function — Practical and economical bracket used to support
piping from wood, concrete or steel beams.
Features — Unique design allows rod to be easily threaded into
bracket. Offset design permits unlimited rod adjustment. Center
mounting hole will accept 3/8" and 1/2" fastener bolts. Per NFPA
13: 1/2" thru 2" pipe requires 3/8" fastener, 21/2" thru 4" pipe
requires 1/2" fastener.*
Approvals — Underwriters’ Laboratories Listed in the USA (UL)
and Canada (cUL), and Factory Mutual Engineering approved thru
4" pipe.
*Note — Additionally UL has listed the Fig. 58 with fasteners as
shown in table below.
Finish — Plain
Note — Available in Electro-Galvanized finish.
Order By — Figure number and finish
Dimensions • Weights
Pipe Size
Qty.
2
2
21⁄2 - 4
31⁄2
4
4
4
2
1
1
2
2
2
2
Fastener Type
Material
#16 x 2 Drive Screws
Wood
3/8 Lag Bolt
Wood
1/2 Lag Bolt
Wood
1/4 x 11⁄2 Lag Bolt
Wood
1/4 x 2 Lag Bolts*
Wood
1/4 x 1 tek screws
14 gauge
1/4 x 1 tek screws
16 gauge
* No pre-drilling required
Dimensions • Weights
Pipe
Size
Rod
Size
A
B
C
Max. Rec.
Load Lbs.
1/2 thru 4
3/8
23⁄4
11⁄2
11⁄8
300
26
Approx.
Wt./100
14
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
26
www.tolco.com
Revision 5/24/2001
Fig. 61T - Bar Joist Hanger
Size Range — 3/8" thru 1/2" rod sizes
Material — Carbon Steel
Function — Designed to hook on top chord of metal bar joist.
Hanger rod is threaded into product and secured with a washer
and nut.
Approvals — Underwriters’ Laboratories Listed in the USA
(UL) and Canada (cUL) for up to 4" pipe with 3/8" rod, up to 6"
pipe with 1/2" rod.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size, and thickness of
bar joist.
Dimensions • Weights
Pipe
Size
Rod
Size
Max. Rec.
Load Lbs.
Up to 4
6
3/8
1/2
300
600
27
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
27
www.tolco.com
Revision 5/24/2001
Fig. 65 and Fig. 66 - Reversible C-Type Beam Clamps
3/4" and 11⁄4" Throat Openings
Size Range — (Fig. 65 and Fig. 66) 3/8", 1/2" and 5/8" rod
Material — Carbon Steel with hardened cup point set screw
and jam nut
Function — Recommended for hanging from steel beam where
flange thickness does not exceed 3/4" (Fig. 65) or 11/4" (Fig. 66).
Features — All steel construction eliminates structural
deficiencies associated with casting type beam clamps. May
be used on top or bottom flange of the beam. (Beveled lip
allows hanging from top flange where clearance is limited.)
May be installed with set screw in up or down position. Offset
design permits unlimited rod adjustment by allowing the rod to
be threaded completely through the clamp. Open design permits
inspection of thread engagement.
Approvals — Underwriters’ Laboratories Listed in the USA
(UL) and Canada (cUL). Factory Mutual Engineering approved.
Conforms to Federal Specification WW-H-171E, Type 23 and
Manufacturers Standardization Society SP-69, Type 19. Exceeds
requirements of the National Fire Protection Association (NFPA),
Pamphlet 13, 3/8" rod will support 1/2" thru 4" pipe, 1/2" rod will
support 1/2" thru 8" pipe. Included in our Seismic Restraints
Catalog approved by the State of California Office of Statewide
Health Planning and Development (OSHPD). For additional load,
spacing and placement information relating to OSHPD projects,
please refer to the TOLCO Seismic Restraint Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, rod size and finish
Fig. 65 Patent #4,570,885
Fig. 65
Dimensions • Weights
Rod Size
A
B
C
D
E
F
3/8
1/2
5/8
13⁄16
11⁄2
11⁄2
3/4
3/4
3/4
1
1
1
7/16
9/16
9/16
1
11⁄4
11⁄4
Max. Rec. Approx.
Load Lbs.* Wt./100
610
1130
1130
28
55
55
* Max. loads for clamp with set screw in up or down position.
Fig. 66
Dimensions • Weights
Rod Size
A
B
C
D
E
F
3/8
1/2
5/8
13⁄16
11⁄2
11⁄2
11⁄4
11⁄4
11⁄4
1
1
1
7/16
9/16
9/16
1
11⁄4
11⁄4
Max. Rec. Approx.
Load Lbs.* Wt./100
610
1130
1130
28
55
55
* Max. loads for clamp with set screw in up or down position.
28
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Component of State of
California OSHPD Approved
Seismic Restraints System
www.tolco.com
Revision 5/31/2005
Fig. 67SS - Stainless Steel Reversible C-Type Beam Clamps
3/4" and 11⁄4" Throat Openings
Size Range — 3/8" and 1/2" rod sizes
Material — All Stainless Steel (T-316 or T-304)
Function — Recommended for hanging from steel beams where
flange thickness does not exceed 3/4".
Features — All steel construction eliminates structural deficiencies
associated with casting type beam clamps. May be used on top
or bottom flange of the beam. May be installed with the set screw in
up or down position. Offset design permits unlimited rod adjustment
by allowing the rod to be threaded completely through the clamp.
Approvals — Underwriters’ Laboratories LIsted in the USA (UL) and
Canada (cUL). Factory Mutual Engineering approved. Conforms
to Manufacturers’ Standardization Society SP-69, Type 19. Meets
or exceeds requirements of the National Fire Protection Association
(NFPA), pamphlet 13, 3/8" rod will support 1/2" through 4" pipe,
1/2" rod will support 1/2" through 8" pipe.
Order By — Figure number and rod size
Fig. 67SS
Dimensions • Weights
Pipe
Size
A
B
C
D
E
F
G
1/2 - 4
5, 6, 8
3/8
1/2
17⁄8
17⁄8
11⁄2
13⁄4
3/4
13/16
3/4
3/4
7/8
7/8
11⁄8
11⁄8
Stock
Size
Test
Load
Approx.
Wt./100
5/16 x 1
3/8 x 11⁄2
1500 lbs.
4050 lbs.
47
84
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
29
www.tolco.com
Revision 5/31/2005
Fig. 68SS - Stainless Steel Reversible C-Type Beam Clamps
3/4" and 11⁄4" Throat Openings
Size Range — 3/8" and 1/2" rod sizes
Material — All Stainless Steel (T-316 or T-304)
Function — Recommended for hanging from steel beams where
flange thickness does not exceed 11⁄4" (Fig. 68SS).
Features — All steel construction eliminates structural deficiencies
associated with casting type beam clamps. May be used on top
or bottom flange of the beam. May be installed with the set screw
in up or down position. Offset design permits unlimited rod
adjustment by allowing the rod to be threaded completely through
the clamp.
Approvals — Underwriters’ Laboratories LIsted in the USA
(UL) and Canada (cUL). Factory Mutual Engineering approved.
Conforms to Manufacturers’ Standardization Society SP-69, Type
19. Meets or exceeds requirements of the National Fire Protection
Association (NFPA), pamphlet 13, 3/8" rod will support 1/2" through
4" pipe, 1/2" rod will support 1/2" through 8" pipe.
Order By — Figure number and rod size
Fig. 68SS
Dimensions • Weights
Pipe
30
Size
A
B
C
D
E
F
Stock
Size
Test
Load
Approx.
Wt./100
1/2 - 4
5, 6, 8
3/8
1/2
21⁄16
21⁄4
2
21⁄4
3/4
13/16
11⁄4
11⁄4
11⁄8
11⁄4
3/8 x 11⁄2
1/2 x 2
1500 lbs.
4050 lbs.
84
170
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 8/13/2005
Fig. 69 - Beam Clamp Retaining Strap
Size Range — 3/8" thru 7/8" rod by 4" thru 16" length.*
Function — To offer more secure fastening of various types
of beam clamps to beam where danger of movement might
be expected. NFPA 13 requires the use of retaining straps
with all beam clamps installed in earthquake areas. Satisfies
requirements of NFPA 13 (1999) 6-4.7.1.
Important Note — Good installation practice of a retaining
strap requires that the strap be held tightly and securely to
all component parts of the assembly. Therefore a locking
mechanism of some kind such as a hex nut or the beveled
locking slot on the TOLCO™ Fig. 69R will provide a more
secure reliable installation.
Approvals — Underwriters’ Laboratories listed in the
USA (UL) and Canada (cUL). Approved for use with any
listed beam clamp. Included in our Seismic Restraints
Catalog approved by the State of California Office of
Statewide Health Planning and Development (OSHPD).
For additional load, spacing and placement information
relating to OSHPD projects, please refer to the TOLCO
Seismic Restraint Systems Guidelines.
Component of State of
California OSHPD Approved
Seismic Restraints System
B
Finish — Pre-Galvanized
Order By — Figure number, type, length “B” and rod size
being used with beam clamp
Note — Minimum return on Strap: 1".
Dimensions • Weights
Type
Rod Size A
Hole Size
B
1
3/8
1/2
5/8
3/4
3/8 - 7/8
7/16
9/16
11/16
13/16
Specify
Specify
Specify
Specify
Specify
Specify
2
3
* Longer lengths are available, consult factory.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
31
www.tolco.com
Revision 8/31/2001
Fig. 69R - Retrofit Capable Beam Clamp Retaining Strap
Size Range — 3/8" and 1/2" rod; 4" thru 16" length.**
Material — Pre-Galvanized Steel
Function — To offer more secure fastening of various types
of beam clamps to beam where danger of movement might be
expected. NFPA 13 requires the use of retaining straps with all
beam clamps installed in earthquake areas. Satisfies requirements of NFPA 13 (1999) 6-4.7.1.
Features — Beveled locking slot* is precisely formed to align
with the threaded section of a hanger rod or set screw and
engage the unit securely. May be used as shown in section
“A-A” or inverted. Allows easy installation for new construction
or retrofit applications.
Important Note — Good installation practice of a retaining strap
requires that the strap be held tightly and securely to all component parts
of the assembly. Therefore a locking mechanism of some kind, such as
the beveled locking slot of the Fig. 69R or a hex nut tightened against
other types of retaining straps will provide a more secure and reliable
installation.
Approvals — Underwriters’ Laboratories listed in the USA (UL) and
Canada (cUL). Approved for use with any listed beam clamp. Included in
our Seismic Restraints Catalog approved by the State of California Office
of Statewide Health Planning and Development (OSHPD). For additional
load, spacing and placement information relating to OSHPD projects,
please refer to the TOLCO Seismic Restraint Systems Guidelines.
Finish — Pre-Galvanized
Order By — Figure number, rod or set screw size and length
Note — Minimum return on Strap: 1".
* Patent #5,947,424
Dimensions • Weights
Rod Size A
3/8"
1/2"
32
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Length
Specify
Specify
www.tolco.com
Revision 3/31/2003
Fig. 78 - All Steel Ceiling Plate
Size Range — 3/8" rod
Material — Carbon Steel
Features — Attachment to wood beams, ceilings, metal decks or
walls. Can also be welded to steel beams.
Approvals — Underwriters’ Laboratories Listed in the USA
(UL) and Canada (cUL). Factory Mutual Engineering approved.
Additionally, (UL) has listed the Fig. 78 with fasteners as shown in
the table below.
Finish — Plain and Electro-Galvanized
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, rod size and finish
A
C
B
E
D(2)
Patent #5,702,077
UL Listed Fastener Table
Pipe Size
Qty
Fastener Type
11⁄4
Material
1/2 - 2
21⁄2 - 4
1/2 - 2
2
2
2
#14 x
A-point hex-washer-head sheet metal screw
1/4 x 11⁄2 wood screws*
1/4 x 1 tek screws
1/2 - 2
1/2 - 2
2
2
#14 x 11⁄4 A-point hex-washer-head sheet metal screw
#14 x 2 A-point-hex-washer-head sheet metal screw
Wood
Wood
Metal (18 gauge)
Wood
Wood thru 5/8" gyp board
* No pre-drilling
Dimensions • Weights
Pipe Size
A
B
C
1/2 - 2
5-6
3
21⁄8
11⁄8
D
E
5/16
3/8
Consult factory for data
Max. Rec.
Load Lbs.*
Approx.
Wt./100
150
15
* Minimum safety factor of 5
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
33
™
www.tolco.com
www.tolco.com
®
Revision 5/24/2001
a brand of
Fig. 98 - Rod Stiffener
Component of State of
California OSHPD Approved
Seismic Restraints System
Size Range — Secures 3/8" thru 7/8" hanger rod
Material — Carbon Steel
Function — Secures channel to hanger rod for vertical seismic
bracing.
Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Included
in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health
Planning and Development (OSHPD). For additional load, spacing and placement information
relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines
Finish — Electro Galvanized
Note — Available in HDG finish or Stainless Steel materials.
Order By — Figure number
34
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 8/15/2005
Component of State of
California OSHPD Approved
Seismic Restraints System
Fig. 109A - Concrete Deck Insert
Size Range — 3/8" thru 7/8" rod
Material — Carbon Steel
Function — For use in metal deck formed concrete to attach hanger
rods. Allows for pre-positioning of hanger rods in poured concrete decks.
Approvals — Underwriters’ Laboratories listed in the
USA (UL) and Canada (cUL). Included in our Seismic Restraints
Catalog approved by the State of California Office of Statewide Health
Planning and Development (OSHPD). For additional load, spacing and
placement information relating to OSHPD projects, please refer to the
TOLCO Seismic Restraints Systems Guidelines. Hangers certified by
a registered professional engineer to conform to Section 6-1.1 of NFPA
#13 (1999) and Section 9.1.1.2 of NFPA #13 (2002).
Finish — Plate: Plain Steel. Rod: Electro-Galvanized
Note — Available in HDG finish or Stainless Steel materials.
Order By — Figure number, rod size and finish. Custom rod lengths are
available. Consult factory.
Spacing/Load Chart for 3000 PSI
Light Weight Concrete over 20 GA Steel Deck
Rod
Size
Max.
Pipe Size
Max. Hanger
Spacing
Max. Rec
Loads
3/8
1/2
5/8
4"
15'-0"
8"
15'-0"
Consult Factory Consult Factory
1144
1158
1430
3/4
7/8
Consult Factory Consult Factory
Consult Factory Consult Factory
2000
2000
NOTES:
1. Mounting holes are standard. If the plate is not
mechanically secured to the deck ribs, a jam nut is
required to prevent the anchor bolt from laying over
when concrete is poured.
2. Minimum spacing between inserts shall be not less
than 41⁄2" for 3/8" and 6" for 1/2"
Max. Rec. Loads shown include safety factory of 5.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
35
™
www.tolco.com
www.tolco.com
Revision
8/13/2001
Revision
5/24/2001
®
a brand of
Component of State of
California OSHPD Approved
Seismic Restraints System
Fig. 109F - Concrete Insert
Size Range — 3/8" thru 7/8" rod
Material — Carbon Steel
Function — Designed to be embedded in concrete to provide a point
of support.
Approvals — Underwriters’ Laboratories listed in the USA (UL) and
Canada (cUL) for 3/8" and 1/2". Included in our Seismic Restraints
Catalog approved by the State of California Office of Statewide Health
Planning and Development (OSHPD). For additional load, spacing and
placement information relating to OSHPD projects, please refer to the
TOLCO Seismic Restraint Systems Guidelines.
Finish — Plain anchor bolt with Electro-Galvanized hardware and plate.
Note — For rod sizes 5/8" - 11⁄2" refer to Fig. 107F. Available in Stainless
Steel or HDG finish on request.
Order By — Figure number, rod size and finish.
Note — The Hex or Jam Nut has NO value in determining the loads. Their
function is to assist in locking the Coupling snug to the bottom of the deck
form preventing the concrete from leaking into the coupling threads. Any
other suitable locking device may be substituted if desired.
Dimensions • Weights
Design Load Vertical
Design Load Shear
Hard Rock
Lt. Wt.
Hard Rock
Lt. Wt.
Hard Rock
Lt. Wt.
Depth
De
min. (in.)
3/8
1/2
5/8
1255
2321
780
735
1392
468
978
978
1278
733
733
958
777
980
688
525
679
445
31⁄2
31⁄2
4
2
2
2
3/4
7/8
1346
2321
806
1392
1278
1278
958
958
927
1166
619
803
4
4
21⁄2
6
Rod
Size
36
Design Load 45°
“E” Embedment
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 8/15/2005
Component of State of
California OSHPD Approved
Seismic Restraints System
Fig. 120 - “U” Hanger
Size Range — Size 3/4" thru 8" pipe
Material — Carbon Steel
Function — Used to support piping from wood beams where no
contraction is expected. Used extensively in automatic fire sprinkler systems.
Approvals — Meets or exceeds the requirements of National
Fire Protection Association (NFPA), Pamphlet 13. Underwriters
Laboratories Listed in the USA (UL) and Canada (cUL). Included
in our Seismic Restraints Catalog approved by the State of
California Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement information
relating to OSHPD projects, please refer to the TOLCO Seismic
Restraint Systems Guidelines.
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, pipe size, length and finish
Dimensions • Weights
Pipe
Size
A
Fastener
Size
Max Rec.
Load Lbs.***
3/4
1
11⁄4
5/16
5/16
5/16
16 x 2*
16 x 2*
16 x 2*
250
250
250
11⁄2
2
21⁄2
5/16
5/16
3/8
16 x 2*
16 x 2*
3/8 x 21⁄2**
250
250
320
3
31⁄2
4
5
6
8
3/8
3/8
3/8
1/2
1/2
1/2
3/8
3/8
1/2
1/2
1/2
5/8
21⁄2**
21⁄2**
3**
3**
3**
3**
320
560
560
560
760
x
x
x
x
x
x
*
Drive screw
** Lag bolt
*** With minimum safety factor of 5
Fastener schedule per NFPA
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
37
www.tolco.com
www.tolco.com
Revision 5/24/2001
Fig. 120RWA (Models A&B)
Retrofit Wrap Around U-Hanger Clamp
Component of State of
California OSHPD Approved
Seismic Restraints System
Size Range — Model A 1" thru 2" pipe
Model B 1" thru 8" pipe
Material — Carbon Steel
Function — Clamp Models “A” and “B” are designed to
restrain movement of the pipe within standard U-hangers as
is required by NFPA 13. Where retrofit capability is crucial,
the Fig. 120RWA is a labor efficient alternative to the standard
TOLCO™ Fig. 120W Wrap Around U-Hanger.
Features — Model “A” is installed fast and easily by hand. No
tools are necessary. Model “B” installs easily by tightening two
hex nuts. Both Models feature a unique bracing slot that locks
onto a standard U-hanger to become a solid unit that will stabilize the pipe during seismic activity or sprinkler head activation.
Models “A” and “B” are designed to be used in retrofit or new
construction applications. Both Models will clamp to existing
U-Hangers without restriction to leg angle
Approvals — Underwriters’ Laboratories listed in the USA
(UL) and Canada (cUL). Included in our Seismic Restraints
Catalog approved by the State of California Office of Statewide
Health Planning and Development (OSHPD). For additional
load, spacing and placement information relating to OSHPD
projects, please refer to the TOLCO Seismic Restraint Systems
Guidelines. NFPA 13 (1999) A-6-2.3.3.
Finish — Model “A”, Galvanized. Model “B”, Plain and
Galvanized. Consult factory for Stainless Steel material.
Order By — Figure number, model, type numbers and
pipe size
Ordering Note — Order Model “A” by pipe size (1" thru 2").
Order Model “B” by the following type and pipe size:
Type 1 — (1" and 11⁄4" pipe size)
Type 2 — (11⁄2" and 2" pipe size)
Type 3 — (21⁄2" and 3" pipe size)
Type 4 — (4" pipe size)
Type 6 — (5" and 6" pipe size)
Type 8 — (8" pipe size)
Important Note — The bracing slot feature is sized to fit the
U-Hanger rod schedule as required by NFPA 13 as follows:
5/16" rod for up to 2" pipe
3/8" rod for 21⁄2" - 6" pipe
1/2" rod for 8" pipe
For other rod size requirements consult factory.
38
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Model A
Model B
www.tolco.com
Revision 1/13/2004
Fig. 130 - Beam Clamp with Bolt and Nut
Size Range — Fig. 130-1 = TJI 35
Fig. 130-2 = —
Fig. 130-3 = TJI 25
Fig. 130-4 = TJI 55 & 65
Fig. 130-5 = TJI 75
Fig. 130-6 = TJI 96
Material — Carbon Steel
Function — Effective and economical method of hanging from
“Trus Joist” type beams. Use with Fig. 102 Eye Rod.
Approvals — Sizes 1, 2, 3 and 4 Underwriters’ Laboratories
listed in the USA (UL) and Canada (cUL) listed through 4" pipe.
All Fig. 130 Beam Clamps meet requirements of Factory Mutual
Engineering and NFPA 13, through 4" pipe.
Finish — Electro-Galvanized
Note — Available in HDG finish or Stainless Steel materials.
Order By — Figure number with dash designation and finish or
by H&W of beam and finish.
Dimensions • Weights
Size
Beam Dimensions
Approx.
130-
A
H
W
Wt./100
1
2
3
31⁄4
31⁄2
31⁄4
11⁄2
13⁄4
11⁄2
25⁄16
21⁄2
13⁄4
65
70
58
4
5†
6†
31⁄2
35⁄8
41⁄2
11⁄2
13⁄4
21⁄2
31⁄2
31⁄2
37⁄8
83
86
101
* Max. Rec. Load 500 lbs.
**Safety Factor of 5
† Larger bolts and I-rods are required for 5" and 6" pipe sizes
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
39
™
www.tolco.com
www.tolco.com
®
Revision
5/24/2001
Revision
5/24/2001
a brand of
Fig. 200 - “Trimline” Adjustable Band Hanger
Size Range — 1/2" thru 8" pipe
Material — Carbon Steel, Mil. Galvanized to G90
specifications
Function — For fire sprinkler and other general piping
purposes. Knurled swivel nut design permits hanger
adjustment after installation.
Features —
• (1/2" thru 2") Flared edges ease installation for
all pipe types and protect CPVC plastic pipe from
abrasion. Captured design keeps adjusting nut
from separating with hanger. Hanger is easily
installed around pipe.
• (21⁄2" thru 8" Spring tension on nut holds it
securely in hanger before installation. Adjusting
nut is easily removed.
Approvals — Underwriters’ Laboratories listed (1/2"
thru 8") in the USA (UL) and Canada (cUL) for steel
and CPVC plastic pipe and Factory Mutual Engineering
Approved (3/4" thru 8"). Conforms to Federal
Specifications WW-H-171E, Type 10 and Manufacturers
Standardization Society SP-69, Type 10.
Maximum Temperature — 650°F
Finish — Mil. Galvanized. For Stainless Steel materials,
order TOLCO™ Fig. 200WON.
Order By — Figure number and pipe size
Dimensions • Weights
Pipe
Size
40
Rod Size
Inch
Metric
A
B
Max. Rec.
Load Lbs.
Approx.
Length
1/2
3/4
1
3/8
3/8
3/8
8mm or 10mm
8mm or 10mm
8mm or 10mm
31⁄8
31⁄8
33⁄8
25⁄8
21⁄2
25⁄8
400
400
400
11
11
12
11⁄4
11⁄2
2
3/8
3/8
3/8
8mm or 10mm
8mm or 10mm
8mm or 10mm
33⁄4
37⁄8
41⁄2
27⁄8
27⁄8
3
400
400
400
13
14
15
21⁄2
3
31⁄2
3/8
3/8
3/8
10mm
10mm
10mm
55⁄8
57⁄8
73⁄8
41⁄8
4
51⁄4
600
600
600
27
29
34
4
5
6
8
3/8
1/2
1/2
1/2
10mm
12mm
12mm
12mm
73⁄8
91⁄8
101⁄8
131⁄8
5
61⁄4
63⁄4
83⁄4
1000
1250
1250
1250
35
66
73
136
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 8/31/2001
Fig. 200H - Heavy Duty Band Hanger (for Trapeze)
Size Range — 1/2" thru 4" trapeze pipe size.
Used to support up to 8" pipe.
Material — Carbon Steel — Pre-Galvanized to
G40 Spec
Function —Designed primarily to support substantially heavier loads than is normally intended
for the nominal hanger size. Used extensively to
support trapeze installations and the increased
loads from both above and below the trapeze
assembly.
Features — Furnished with 3/8" or 1/2" adjusting threaded ring nut.
Approvals — Underwriters’ Laboratories listed
in the USA (UL) and Canada (cUL). Conforms
to Federal Specification WW-H-171E, Type 10
and Manufacturers Standardization Society
SP-69, Type 10.
Maximum Temperature — 650°F
Finish — Pre-Galvanized
Order By — Figure number, pipe size and rod
size.
Important Design Note — Because of the
increased loads applied to the trapeze assembly,
both the upper trapeze supports as well as the
lower hanging unit must be able to hold the
maximum loads intended.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
41
www.tolco.com
www.tolco.com
Revision 5/24/2001
Fig. 200WON - “Trimline” Adjustable Band Hanger w/o Swivel Nut
Size Range — 1/2" thru 8" pipe
Material — Carbon Steel
Function — Recommended for the suspension of fire
sprinkler and non-insulated pipe or insulated pipe with
Fig. 220 shield. Generally installed with two hex nuts.
Features — Flared edges on sizes 1/2" thru 2". Eases
installation and protects CPVC pipe from any abrasion.
Approvals — Underwriters’ Laboratories listed
(1/2" thru 8") in the USA (UL) and Canada (cUL)
for steel and CPVC plastic pipe and Factory Mutual
Engineering approved. Conforms to Federal
Specifications WW-171E, Type 7 and Manufacturers
Standardization Society SP-69, Type 7
Maximum Temperature — 650°F
Finish — Mil. Galvanized to G-90
Note — Available in Stainless Steel materials
Order By — Figure number and pipe size
Dimensions • Weights
Pipe
42
Size
Rod Size
A
B
C
Max. Rec.
Load Lbs.
Approx.
Length
1/2
3/4
1
3/8
3/8
3/8
21⁄2
21⁄2
27⁄8
2
2
21⁄8
400
400
400
8
8
9
11⁄4
11⁄2
2
3/8
3/8
3/8
33⁄8
31⁄2
33⁄4
21⁄2
21⁄2
21⁄2
400
400
400
10
11
12
21⁄2
3
31⁄2
3/8
3/8
3/8
51⁄8
53⁄8
63⁄4
35⁄8
31⁄2
45⁄8
600
600
600
24
27
32
4
5
6
8
3/8
1/2
1/2
1/2
63⁄4
83⁄8
93⁄8
123⁄8
41⁄2
51⁄2
6
8
1000
1250
1250
1250
33
60
68
130
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 8/15/2005
Component of State of
California OSHPD Approved
Seismic Restraints System
Fig. 324 - Pipe Roll Hanger
Size Range — 21⁄2" thru 24" pipe
Material — Cast iron and carbon steel
Function — For supporting pipe where movement may
occur due to thermal expansion.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 44, 1" thru 20", and Manufacturers
Standardization Society SP-69, Type 43. Underwriters
Laboratories Listed in the USA (UL) and Canada (cUL).
Included in our Seismic Restraints Catalog approved by the
State of California Office of Statewide Health Planning and
Development (OSHPD). For additional load, spacing and
placement information relating to OSHPD projects, please
refer to the TOLCO Seismic Restraint Systems Guidelines.
Note — When pipe line is insulated, total outside diameter
f pipe and covering should be used to determine size of
anger; also see Figs. 260-1 to 265-4.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Dimensions • Weights
Pipe Size
Rod Size
A
B*
C
Max. Rec.
Load Lbs.
Approx.
Wt./100
21⁄2
3
31⁄2
1/2
1/2
1/2
515⁄16
65⁄8
71⁄4
35⁄16
315⁄16
43⁄8
17⁄8
23⁄16
29⁄16
225
310
390
171
224
250
4
5
6
5/8
5/8
3/4
77⁄8
91⁄8
103⁄16
51⁄16
61⁄8
71⁄16
27⁄8
37⁄16
41⁄16
475
685
780
372
649
869
8
10
12
7/8
7/8
7/8
121⁄2
155⁄16
179⁄16
93⁄16
113⁄8
131⁄2
51⁄16
65⁄16
77⁄16
780
965
1200
1368
1909
3001
14
16
18
1
1
1
201⁄4
223⁄8
241⁄2
145⁄8
165⁄8
185⁄8
87⁄16
95⁄16
103⁄8
1200
1200
1400
3578
4150
5382
20
24
11⁄4
11⁄2
263⁄4
319⁄16
205⁄8
245⁄8
2611⁄16
1313⁄16
1600
1600
7317
12600
D
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
43
™
www.tolco.com
www.tolco.com
®
Revision
5/24/2001
Revision
8/30/2002
a brand of
Fig. 800 - Adjustable Sway Brace Attachment to Steel
Size Range — 4" thru 18" beam width
Material — Carbon Steel
Function — Seismic brace attachment to steel.
Features — This product’s design incorporates a concentric
attachment point which is critical to the performance of structural
seismic connections. NFPA 13 indicates the importance of concentric
loading of connections and fasteners. Permits secure connection to
steel where drilling and/or welding of brace connection could present
structural issues. Comes completely assembled ready for installation.
The Fig. 800 must be used with one of the TOLCO™ Fig. 900 series
brace fittings (ordered separately).
Installation Instructions — Tighten set bolts against flange until bolt
head breaks off. Tighten hex head bolts into clamp body until lock
washers are fully flat.
Application Note — Allows bracing in either lateral or longitudinal
direction.
Approvals — Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL). Included in our Seismic Restraints Catalog approved
by the State of California Office of Statewide Health Planning and
Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to the TOLCO
Seismic Restraint Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, type number and size number.
Important Structural Note:
TOLCO Steel Fig. 65/66 components were used during structural
testing and are required to achieve the listed results. Malleable iron
components must never be substituted because of their serious
potential for fracture and failure.
Dimensions • Weights
*Max. Design Loads/Lbs.
Type
1
2
Flange Thickness Along
Max. (In.)
Beam
3/4
11⁄4
1265
1265
Across
Beam
2015
2015
Dimensions • Weights
*Max. Design Loads/Lbs.
Size
1
2
3
4
5
6
7
44
Fits Beam
Range (In.)
4
6
8
10
12
14
16
-
6
8
10
12
14
16
18
Along
Beam
Across
Beam
1265
1265
1265
1265
1265
1265
1265
2015
2015
2015
2015
2015
2015
2015
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Component of State of
California OSHPD Approved
Seismic Restraints System
www.tolco.com
Revision 5/24/2001
Fig. 825 - Bar Joist Sway Brace Attachment
Size Range — One size accommodates all TOLCO Fig. 900 Series sway
brace attachments. Maximum Horizontal Design Load 2015 lbs.
Material — Carbon Steel
Function — *To attach sway and hanger assemblies bracing to steel bar
joist structural members.
Features — This product’s design incorporates a concentric attachment
point which is critical to the performance of structural seismic connections.
NFPA 13 indicates the importance of concentric loading of connections and
fasteners. Permits secure non-friction connection without drilling or welding.
Unique design reinforces point of connection to joist. Break off head bolt
design assures verification of proper installation.
Approvals — Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL). Included in our Seismic Restraints Catalog approved by the
State of California Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement information relating
to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems
Guidelines.
Important Structural Note:
The TOLCO Fig. 825 has significant UL established design loads, however,
structural issues related to the steel joist member require restricted location
installation for all bracing. Steel Joist Manufacturers require that all earthquake bracing connections be within 6" of the cord panel point. Installation
of the Fig. 825 must be limited to the outer third sections of the joist span.
For installations within the center third section of the joist span, use UL
Listed TOLCO Fig. 825A.
Finish — Plain, Electro-Galvanized and HDG
Order By — Figure number and finish
*Important Note — The Fig. 825 is precision manufactured to perform its
function as a critical component of a complete bracing assembly.
To ensure performance, the UL Listing requires that the Fig. 825 must
be used only with other TOLCO bracing products.
US Patent #6,098,942, Canada Patent #2,286,659
Component of State of
California OSHPD Approved
Seismic Restraints System
Maximum Design Load 2015 Lbs.
Weight/100 237.5 Lbs.
UL Listed as Hanger Attachment
6" Pipe Max.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
45
www.tolco.com
www.tolco.com
Revision 5/24/2001
Fig. 825A - Bar Joist Sway Brace Attachment
Size Range — One size accommodates all TOLCO Fig. 900 Series sway
brace attachments. Maximum Horizontal Design Load 1265 lbs.
Material — Carbon Steel
Function — *To attach sway bracing to steel bar joist structural members.
Features — This product’s design incorporates a concentric attachment
point which is critical to the performance of structural seismic connections.
NFPA 13 indicates the importance of concentric loading of connections and
fasteners. Permits secure non-friction connection without drilling or welding.
Unique design reinforces point of connection to joist. Break off head bolt
design assures verification of proper installation.
Approvals — Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL). Included in our Seismic Restraints Catalog approved by the
State of California Office of Statewide Health Planning and Development
(OHSPD). For additional load, spacing and placement information relating
to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems
Guidelines.
Important Structural Note:
The TOLCO Fig. 825A has significant UL established design loads, however,
structural issues related to the steel joist member require restricted location
installation for all bracing. Steel Joist Manufacturers require that all earthquake bracing connections be within 6" of the cord panel point. Installation
of the Fig. 825A is not restricted to the two outer third sections of the joist.
For greater design loads, refer to TOLCO Fig. 825.
Finish — Plain
Order By — Figure number and finish
*Important Note — The Fig. 825A is precision manufactured to perform its
function as a critical component of a complete bracing assembly.
To ensure performance, the UL Listing requires that the Fig. 825A must
be used only with other TOLCO bracing products.
Patent #6,098,942
46
Maximum Design Load 1265 Lbs.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 8/15/2005
Fig. 906 - Sway Brace Multi-Fastener Adapter
Size Range — Use with 1" and 11⁄4" TOLCO UL listed 900 Series
Earthquake Brace Attachments.
Material — Carbon Steel
Application — Allows sway brace fittings to develop greater load
carrying ability by providing multiple fastener attachments. The
National Fire Protection (NFPA) provides information on fastener
loads to various structures. Refer to NFPA Pamphlet 13 (1996)
Edition, Table 4-14.4.3.5.6.
Approvals — Underwriters Laboratories Listed in the USA
(UL) and Canada (cUL) only when used with TOLCO 900
Series Earthquake Brace Attachments. Included in our Seismic
Restraints Catalog approved by the State of California Office
of Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to
OSHPD projects, please refer to the TOLCO Seismic Restraint
Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number and specify dimensions H1 and H2.
Component of State of
California OSHPD Approved
Seismic Restraints System
Dimensions • Weights
A
B
C
D
H1
H2
Approx.
Wt./100
12
9
2
1/4
Specify
Specify
Varies
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
47
™
www.tolco.com
www.tolco.com
®
Revision
5/24/2001
Revision
05/05/2005
a brand of
Fig. 907 - 4-Way Longitudinal Sway Brace Attachment
Size Range — 1" x 1", 1" x 11⁄4" and 11⁄4" x 11⁄4" bracing pipe.
Material — Carbon Steel, hardened cone (or cup) point engaging screw
Function — For bracing pipe against sway and seismic disturbances,
Functions as as longitudinal brace connection when attached to a lateral brace
pipe. Bracing connection must be positioned as close as physically possible
to the braced pipe (No more than 3" away). Must be used only with TOLCO
bracing components. When used in conjunction with TOLCO Fig. 1000, this
combination bracing restricts piping movement in tension and compression both
laterally and longitudinally.
Features — Universal swivel design allows the Fig. 907 to achieve any angle
of attachment required. Pipe end requires no threads — simply slide bracing
pipes through fittings and tighten each set screw until lock washer is fully
compressed, or extends 20 ft.-lbs.
Application Note — Length of bracing pipe per NFPA 13, Table 6-4.5.8 (L/
R=200); 1" schedule 40 pipe maximum 7’0": 11/4" schedule 40 pipe
maximum 9’0". Alternative pipe materials are currently under review. Please
consult factory.
Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada
(cUL). Included in our Seismic Restraints Catalog approved by the State of
California Office of Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to OSHPD projects,
please refer to the TOLCO Seismic Restraint Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, bracing pipe sizes and finish.
Important Note — The Fig. 907 is precision manufactured to perform its
function as a critical component of a complete bracing assembly. To ensure
performance, the UL Listing requires that the Fig. 907 must be used only
with other TOLCO bracing products. The Fig. 907 is not intended for use
with the Fig. 1001 Sway Brace Attachment.
NATIONAL AND INTERNATIONAL PATENT APPLICATION IN PROCESS.
Dimensions • Weights
Pipe Size
A
B
Max. Design
Load Lbs.*
Approx.
Wt./100
1x1
1 x 11⁄4
11⁄4 x 11⁄4
43⁄4
51⁄16
53⁄8
43⁄4
413⁄16
51⁄4
655*
655*
655*
103
107
109
* Load will accommodate up to 4" pipe at maximum spacing.
48
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Component of State of
California OSHPD Approved
Seismic Restraints System
www.tolco.com
Revision 5/24/2001
Fig. 909 - No-Thread Swivel Sway Brace Attachment
Component of State of
California OSHPD Approved
Seismic Restraints System
Size Range — 1" bracing pipe. For brace pipe sizes larger than 1",
use TOLCO Fig. 980.
Material — Carbon Steel, hardened cone point engaging screw
Function — The structural component of a sway and seismic bracing
system.
Features — This product’s design incorporates a concentric attachment opening which is critical to the performance of structural seismic
connections. NFPA 13 (1999 Edition) Table 6-4.5.9 indicates clearly
that fastener table load values are based only on concentric loading.
No threading of the bracing pipe is required. Open design allows for
easy inspection of pipe engagement. All steel construction eliminates
deficiencies associated with malleable type attachments. Fastener can
be mounted to all surface angles.
Application Note — The Fig. 909 is used in conjunction with the
TOLCO Fig. 1000, Fig. 1001, or Fig. 4 (A) pipe clamp, and joined
together with bracing pipe. Install per NFPA 13 and/or TOLCO State of
California OSHPD Approved Seismic Restraint Manual. The required
type, number and size of fasteners used for the structure attachment
fitting shall be in accordance with NFPA 13 and/or OSHPD.
Installation — Extend bracing pipe through opening. Tighten cone
point engaging screw until head bottoms out or minimum torque 23 ft./lbs.
Approvals — Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL). Included in our Seismic Restraints Catalog approved
by the State of California Office of Statewide Health Planning and
Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to the TOLCO
Seismic Restraint Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, pipe size and finish.
Important Note — The Fig. 909 is precision manufactured to perform
its function as a critical component of a complete bracing assembly.
Sway brace assemblies are intended to be installed in accordance with
NFPA 13 and the manufacturer’s installation instructions. To ensure
performance, the UL Listing requires that the Fig. 909 must be
used only with other TOLCO bracing products.
NATIONAL AND INTERNATIONAL PATENT APPLICATION IN
PROCESS.
Dimensions • Weights
Pipe Size
A
B
H*
Max. Design.
Load Lbs.
Max. Design Load
Lbs. w/Washer
Approx.
Wt./100
1
6
15⁄8
17/32
2015
2765
91
* Available with hole sizes to accommodate up to 3/4" fastener. Consult Factory.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
49
www.tolco.com
Revision 5/24/2001
Fig. 910 - Swivel Sway Brace Fitting
Size Range — 1" and 11⁄4" bracing pipe. For brace pipe sizes larger than
11⁄4", use TOLCO Fig. 980.
Material — Carbon Steel
Function — For bracing pipe against sway and seismic disturbances. The
building attachment component of a sway brace system; the
Fig. 910 is used in conjunction with the Fig. 1001, Fig. 1000 or with a Fig. 4A
Pipe Clamp and joined together with a brace pipe per NFPA 13.
Features — This product’s design incorporates a concentric attachment
opening which is critical to the performance of structural seismic connections. NFPA 13 (1999 Edition) Table 6-4.5.9 indicates clearly that fastener
table load values are based only on concentric loading. Universal swivel
design allows Fig. 910 to be attached at any surface angle. All steel construction. NFPA 13 (1999 Edition) Table 6-4.5.8: 1" Schedule 40 bracing
pipe maximum 7’0". 11⁄4" Schedule 40
bracing pipe maximum 9’0".
Approvals — Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL). Included in our Seismic Restraints Catalog approved
by the State of California Office of Statewide Health Planning and
Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic
Restraint Systems Guidelines.
Note — The Fig. 910 Swivel Attachment and the Fig. 1001, Fig. 1000, or
Fig. 4A Pipe Clamp make up a sway brace system of (UL) Listed attachments and bracing materials which satisfies the requirements of
Underwriters’ Laboratories and the National Fire Protection
Association (NFPA).
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish
or Stainless Steel materials.
Order By — Figure number, pipe size and finish.
Note — Specific weight load conditions may require
more than one fastener to the building surface.
Sway brace attachments may be ordered with multiple and/or larger fastener mounting holes. Consult
the factory. The Fig. 910 is precision manufactured
to perform its function as a critical component of a
complete bracing assembly.
To ensure performance, the UL Listing requires
that the Fig. 910 must be used only with other
TOLCO bracing products.
Component of State of
California OSHPD Approved
Seismic Restraints System
Dimensions • Weights
50
Pipe Size
A
B
C
D Hole
Size
E
F
Max. Design
Load Lbs.
Approx.
Wt./100
1
11⁄4
2
13⁄16
11⁄2
15⁄16
3
3
9/16
9/16
25⁄16
25⁄16
2
25⁄16
2015
2015
88
99
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
™
www.tolco.com
®
Revision 5/24/2001
a brand of
Fig. 975 - Straight Sway Brace Fitting
Size Range — 1" bracing pipe. For brace pipe sizes larger than 1",
use TOLCO Fig. 980.
Material — Carbon Steel
Function — For bracing pipe against sway and seismic disturbances.
The building attachment component of a sway brace system; the
Fig. 975 is used in conjunction with the Fig. 1000, Fig. 1001 or with a
Fig. 4A Pipe Clamp and joined together with a brace pipe per NFPA
13.
Features — Open design allows for easy checking of thread engagement. All steel construction eliminates deficiencies associated with
malleable type attachments.
Application Note — Length of bracing pipe per National Fire
Protection Association Pamphlet NFPA 13, Table 4-5.4.3.5.1(B):
1" Schedule 40 bracing pipe maximum 7’0".
Approvals — Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL).
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number and finish.
Note — Specific weight load conditions may require more than one
fastener to the building surface. Sway brace attachments may be
ordered with multiple and/or larger fastener mounting holes. Consult
the factory. Use Fig. 975 in straight position only. Bending of this
fitting alters the material strength. Use Fig. 909 or Fig. 910 when
angle fitting is required.
Important Note — The Fig. 975 is precision manufactured to perform
its function as a critical component of a complete bracing assembly.
To ensure performance, the UL Listing requires that the Fig. 975
must be used only with other TOLCO bracing products.
Dimensions • Weights
Pipe Size
A
B
C
Hole
Size
Max. Design
Load Lbs.
Approx.
Wt./100
1
4
31⁄2
11⁄2
9/16
2015
88
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
51
www.tolco.com
Revision 3/28/2003
Fig. 980 - Universal Swivel Sway Brace Attachment
Component of State of
Size Range — One size fits bracing pipe 1" thru 2", TOLCO 12 gauge channel, and all structural
California OSHPD Approved
steel up to 1/4" thick.
Seismic Restraints System
Material — Carbon Steel
Function — Multi-functional attachment to structure or braced pipe
fitting. Features — This product’s design incorporates a concentric
attachment opening which is critical to the performance of structural
seismic connections. NFPA 13 (1999 Edition) Table 6-4.5.9
H
indicates clearly that fastener table load values are based
only on concentric loading. Fits multiple sizes of bracing pipe, strut or structural steel. Mounts to any surface
angle. Break off bolt head assures verification of proper
installation.
Application Note — Install per NFPA 13 and/or TOLCO
A
State of California (OSHPD) Approved Seismic Restraint
Manual.
B
Installation — Place bracing component into jaw fully and tighten bolt until head
breaks off.
Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning
and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects,
please refer to the TOLCO Seismic Restraint Systems Guidelines.
Note — The Fig. 980 Swivel Attachment and the Fig. 1001, Fig. 1000 , Fig. 2001 or Fig. 4A Pipe Clamp make up a
sway brace system of UL Listed attachments and bracing materials which satisfies the requirements of Underwriters’
Laboratories and the National Fire Protection Association (NFPA)
Finish — Plain
Note — Available in Electro-Galvanized finish.
Order By — Figure number and finish.
Important Note — The Fig. 980 is precision manufactured to perform its function as a critical component of a complete bracing assembly. To ensure performance, the UL Listing requires that the Fig. 980 must be used only
with other TOLCO bracing products.
NATIONAL AND INTERNATIONAL PATENT APPLICATION IN PROCESS.
Dimensions • Weights
*
52
A
B
H*
Max. Design
Load Lbs.
Approx.
Wt./100
51⁄4
17⁄8
17/32
2765
132
Available with hole sizes to accommodate up to 3/4" fastener. Consult factory.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 5/5/2006
Fig. 981 - Fast Attach — Universal Swivel Sway Brace Attachment
Component of State of
Size Range — One size fits bracing pipe 1" thru 2", TOLCO 12 gauge channel,
California OSHPD Approved
Seismic Restraints System
and all structural steel up to 1/4" thick.
Material — Carbon Steel
Function — Multi-functional attachment to hanger rod, trapeze rod, structure or
braced pipe fitting.
Features — Fits multiple sizes of bracing pipe, strut or structural steel. Swivel allows adjustment to various surface angles. Break-away bolt head assures verification of proper installation torque. Unique “fast attach” yoke design allows Fig. 981 to be installed using hanger
rods 3/8" through 3/4" in size. “Stackable” design allows installation of both lateral and longitudinal braces, as well as opposing braces, to be easily installed on a single hanger rod,
with no disassembly. The retrofit yoke has a visual verification of proper installation torque.
Tighten existing hex nut down until the slight gap in the yoke assembly closes completely.
Installation — The Fig. 981 is the “braced pipe” attachment component of a
lateral or longitudinal brace assembly. It is intended to be combined with the
pipe hanger, all-thread rod, “bracing pipe” and TOLCO transitional and structural
attachment component(s) to form a complete bracing assembly. NFPA 13 and or
OSHPD guidelines should be followed.
To Install — Spin nut on top of hanger counterclockwise to loosen the nut and
raise it above the top of the hanger. Attach Fig. 981 by slipping the open side of
the 981 yoke onto the all thread rod above the top of the hanger. Be sure that
the concave indented side of the Fig. 981 yoke is facing upward away from the
top of the hanger toward the loosened hex net. Spin the hex nut clockwise and
tighten securely. Insert brace pipe into the jaw of the 981 and tighten the cone point set bolt until the hex head breaks
off ensuring proper installation torque. Pivot brace pipe to proper angle and attach to structure using a TOLCO swivel
structural attachment
Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Included in our Seismic Restraint
Systems Guidelines, approved by the California Office of Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic
Restraint Systems Guidelines.
Finish — Electro-Galvanized
Note — Available in Electro-Galvanized finish.
Order By — Figure number, rod size 3/8" thru 3/4" and finish.
US AND INTERNATIONAL PATENT APPLICATION IN PROCESS.
Dimensions • Weights
A
B
C
D
Max. Design
Load Lbs.
Approx.
Wt./100
51⁄8
41⁄8
11⁄4
21⁄4
2015
88
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
53
www.tolco.com
www.tolco.com
Revision 5/24/2001
Component of State of
California OSHPD Approved
Seismic Restraints System
Fig. 990 - Cable Sway Brace Attachment
Size Range — 1/8", 3/16" and 1/4" pre-stretched cable. 3/8" thru 11⁄4"
hanger rod bolt or fastener.
Material — Carbon Steel
Function — Cable attachment for sway bracing. Attaches sway brace to
structure or to hanger. To be used with 7 x 19 strand core pre-stretched
galvanized aircraft cable.
Features — Cable easily slides into oversized front arch opening.
Breakaway hex nuts assure verification of proper installation. Will mount
to any surface angle.
Approvals — Included in our Seismic Restraints Catalog approved by the
State of California Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement information relating
to OSHPD projects, please refer to the TOLCO Seismic Restraint System
Guidelines.
Finish — Electro-Galvanized
Order By — Figure number, cable size and mounting hole size.
Note — Order 990H for hanger rod, bolt or fastener hole size 1" thru 11⁄4".
Dimensions • Weights
Cable
Diameter
A
B
1/8"
3/16"
1/4"
45⁄16"
5"
5"
2"
21⁄4"
25⁄8"
Maximum Design
Load Lbs.
975*
2050*
3150*
* Maximum load rating controlled by cable breaking strength.
54
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 8/15/2005
Fig. 991 - Fast Attach — Cable Sway Brace Attachment
Size Range — 1/8", 3/16" and 1/4" pre-stretched cable. Fits rod size 3/8" thru 3/4".
Material — Carbon Steel
Function — Cable attachment for sway bracing. Attaches sway brace to hanger
rod. To be used with 7 x 19 strand core pre-stretched galvanized aircraft cable.
Features — Fits multiple sizes of cable. Cable easily slides into
oversized front arch opening. Swivel allows adjustment to various
surface angles. Break-away hex nuts assure verification of proper
installation torque. Unique “Fast-Attach” yoke design allows Fig. 991 to be installed
using hanger rods 3/8" through 3/4" in size. “Stackable” design allows installation
of both lateral and longitudinal braces, as well as opposing braces, to be easily
installed on a single hanger rod, with no disassembly. The retrofit yoke has a visual
verification of proper installation torque. Tighten existing hex nut down until the
slight gap in the yoke assembly closes completely.
Approvals — Included in our Seismic Restraints Catalog approved by the State
of California Office of Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to OSHPD projects,
please refer to the TOLCO Seismic Restraint System Guidelines.
Finish — Electro-Galvanized
Order By — Figure number, rod size 3/8" through 3/4"
US AND INTERNATIONAL PATENT APPLICATION IN PROCESS.
Component of State of
California OSHPD Approved
Seismic Restraints System
Dimensions • Weights
Cable
Diameter
A
B
1/8"
3/16"
1/4"
53⁄4"
63⁄4"
63⁄4"
21⁄8"
21⁄2"
21⁄2"
Maximum Design
Load Lbs.
975*
2050*
3150*
* Maximum load rating controlled by cable breaking strength.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
55
www.tolco.com
www.tolco.com
Revision 5/24/2001
Fig. 1000 - “Fast Clamp” Sway Brace Attachment
Size Range — Pipe size to be braced: 1" thru 6" Schedule 10
thru 40.* Pipe size used for bracing: 1" and 11⁄4" Schedule 40
IPS.
* Additionally (UL) approved for use to brace Schedule 7
sprinkler pipe up to 4" (maximum horizontal design load
655 lbs.) Torque requirement 6 — 8 ft. lbs.
Material — Carbon Steel
Function — For bracing pipe against sway and seismic
disturbance. The pipe attachment component of a sway brace
system: Fig. 1000 is used in conjunction with a TOLCO™ Fig.
900 Series Fitting and joined together with bracing pipe per
NFPA 13* or TOLCO OSHPD Approved Seismic Manual,
forming a complete sway brace assembly.
Features — Can be used to brace Schedules 7 thru 40 IPS.
Field adjustable, making critical pre-engineering of bracing pipe
unnecessary. Unique design requires no threading of bracing
pipe. Can be used as 4-way riser brace. Can be used as
longitudinal brace with Fig. 907. All steel construction eliminates
structural deficiencies associated with casting type sway brace
fittings. Comes assembled and individually packaged with
illustrated installation instructions — sizes are clearly marked.
Steel leaf spring insert provided to assure installer and inspector
necessary minimum torque has been achieved.
Application Note — Position Fast Clamp and tighten two hex
nuts until leaf spring flattens. A minimum of 1" pipe extension
beyond the Fig. 1000 is recommended.
Approvals — Underwriters Laboratories Listed in the USA (UL)
and Canada (cUL). Included in our Seismic Restraints Catalog
approved by the State of California Office of Statewide Health
Planning and Development (OSHPD). For additional load,
spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems
Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Order first by pipe size to be braced, followed by
pipe size used for bracing, figure number and finish.
Important Note — The Fig. 1000 is precision manufactured to
perform its function as a critical component of a complete
bracing assembly. To ensure performance, the UL Listing
requires that the Fig. 1000 must be used only with other
TOLCO bracing products.
Component of State of
California OSHPD Approved
Seismic Restraints System
Maximum Design Load
1" thru 4" pipe size — 2015 lbs.
6" size — 1265 lbs.
TOLCO® brand bracing components are desgined to be compatible ONLY with other TOLCO® brand bracing components, resulting in a Listed
seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO® brand bracing components, in the instance
that such TOLCO® brand bracing components are used in combination with products, parts or systems which are not manufactured or sold under
the TOLCO® brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any
kind, including but not limited to loss of business or profit, where non-TOLCO brand bracing components have been, or are used.
56
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 8/01/2003
Fig. 1001 - Sway Brace Attachment
Component of State of
Size Range — Pipe size to be braced: 21⁄2" thru 8" IPS.* Pipe size used
California OSHPD Approved
1
for bracing: 1" and 1 ⁄4" Schedule 40 IPS.
Seismic Restraints System
Material — Carbon Steel
Function — For bracing pipe against sway and seismic disturbance.
The pipe attachment component of a sway brace system: The Fig. 1001
is used in conjunction with a TOLCO™ 900 Series fitting and joined
together with bracing pipe per NFPA 13, forming a complete sway brace
assembly.
Features — *Can be used to brace schedules 7 through 40 IPS.
Field adjustable, making critical pre-engineering of bracing pipe length
unnecessary. Unique design requires no threading of bracing pipe. Can
be used as a component of a four-way riser brace. Comes assembled
and ready for installation. Fig. 1001 has built-in visual verification of
correct installation. See installation note below.
Installation Note — Position Fig. 1001 over the pipe to be braced
Maximum Design Load
and tighten two hex head cone point set bolts until heads bottom
Sch 7 - 1600 lbs.
out. A minimum of 1" pipe extension is recommended.
Sch 10 & 40 w/1" Brace Pipe - 2015 lbs.
Approvals — Underwriters Laboratories Listed in the USA (UL)
Sch 10 & 40 w/11⁄4" Brace Pipe - 2765 lbs.
and Canada (cUL). Included in our Seismic Restraints Catalog
approved by the State of California Office of Statewide Health
Planning and Development (OSHPD). For additional load, spacing and
placement information relating to OSHPD projects, please refer to the
TOLCO Seismic Restraint Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Indicate pipe size to be braced followed by pipe size used
for bracing, figure number and finish.
Important Note — The Fig. 1001 is precision manufactured to perform
its function as a critical component of a complete bracing assembly. To
ensure performance, the UL Listing requires that the Fig. 1001 must
be used only with other TOLCO bracing products. The Fig 1001
is not intended for use with the Fig. 907 4-Way Longitudinal Brace
Attachment.
NATIONAL AND INTERNATIONAL PATENT APPLICATION IN PROCESS
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
57
www.tolco.
Revision 8/30/2002
Fig. 2002 - Sway Brace Attachment
Size Range — Pipe size to be braced: 21⁄2" thru 8" all steel
schedules, copper, plastic, FRP, cast iron and ductile iron.
Consult factory when bracing other than steel. The Fig. 2002
accepts brace pipes sizes 11⁄2" and 2" steel schedule 10
through schedule 40.
Material — Carbon Steel
Function — For bracing pipe against sway and seismic
disturbance. The pipe attachment component of a sway brace
system: The Fig. 2002 is used in conjunction with a TOLCO™
900 Series sway brace attachments and joined together with
bracing pipe. Install per NFPA 13 and/or TOLCO State of
California OSHPD Approved Seismic Restrain Manual.
Features — Unique design will not damage thin wall, plastic,
copper or ductile iron pipe. Easy verification of proper
installation by tightening bolts until ears touch.
Installation — Place Fig. 2002 over pipe to be braced.
Slide bracing pipe through attachment and tighten hex nuts
until ears touch.
Approvals — Underwriters Laboratories Listed in the USA
(UL) and Canada (cUL). Included in our Seismic Restraints
Catalog approved by the State of California Office of Statewide
Health Planning and Development (OSHPD). For additional
load, spacing and placement information relating to OSHPD
projects, please refer to the TOLCO Seismic Restraint
Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, pipe size to be braced, pipe size
used for bracing (11⁄2" or 2") and finish.
Important Note — The Fig. 2002 is precision manufactured
to perform its function as a critical component of a complete
bracing assembly. To ensure performance, the UL Listing
requires that the Fig. 2002 must be used only with other
TOLCO bracing products.
58
Component of State of
California OSHPD Approved
Seismic Restraints System
Maximum Design Load 2015 Lbs.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 5/24/2001
Reference
Material
Included in our Seismic Restraints Catalog
approved by the State of California Office of
Statewide Health Planning and Development
(OSHPD). For additional load, spacing and
placement information relating to OSHPD
projects, please refer to the TOLCO Seismic
Restraint Systems Guidelines.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
59
www.tolco.com
Revision 5/24/2001
TOLCO Cross Reference Chart
60
TOLCO
GRINNELL
B-LINE
MCO
PHD
SUPER STRUT
CARPENTER
& PATERSON
EMPIRE
INDUSTRIES
1
1A
1CBS
1C.I.
1F
1LD
1LDF
1PVC
1LDPVC
1V
2
2F
2FWON
2WON
3
3F
4
4A
4B
4C.I.
4F
4H
4L
4PVC
5
6
6F
6PVC
7
8
9
9X
14
14X
20
20S
21
21F
22
23
24
25
27A
28
30
30L
30M
30H
31-M
31-O
32
33
34
35
40
41
42
260
300
—
590
—
65
—
—
—
—
—
—
—
—
67
—
212
212FP
—
—
—
216
—
—
295
261
—
—
103
100
600
599
595
594
262
—
—
—
—
—
—
—
—
—
194
—
195
199
—
—
—
47
49
52
—
—
—
B3100
B3108
—
B3102
B3100F
B3104
B3104F
B3100C
B3104C
B3106
B3170
B3170NFF
B3172F
B3172
B3690
B3690F
B3140
—
—
—
—
B3142
—
—
B3144
B3373
—
B3373C
B3148
B3149
B3132
B3132W
B3134
B3134W
B3180
B3256
—
—
—
—
—
—
—
—
B3068
—
B3066
B3067
—
—
B3147
B3084
B3086
B3085
B3190
B3191
—
400
415
—
405
400FL
410
410FL
420
—
—
100
100FL
—
105
418
418FL
450
—
—
—
—
451
—
—
452
510
—
520
700
705
517
516
—
—
—
—
8EG
—
107
108
109
—
—
—
348
351
352
353
—
—
712
373
374
374A
457
458
319
450
430
—
420
450F
440
440F
453
—
450V
151
151F
180F
180
970
97-F
520
—
—
—
—
522
—
—
525
550
—
553
535
545
580
585
590
595
825
830
—
—
—
—
—
—
—
—
—
850
855
860
—
—
840
—
904
903
820
810
910
C710
CX710
—
CI1710
C710F
CL710
—
C710P
—
—
C727
C727F
C725
C727
C711
C711F
C725
—
—
—
—
—
—
—
C726
C720
—
C720P
C720L
CX725
C724
W724
—
—
164
—
—
—
—
—
—
—
—
—
C736
—
C739M
C739H
—
—
RCS
—
—
—
C704A
C704
—
100
100EL
—
100C.I.
—
200
—
100PVC
—
200VT
800
—
—
—
—
—
175
—
—
—
—
298
—
—
304
126
—
126PVC
179
267
159
258
158DB
260
114
—
—
—
—
—
—
—
—
—
69
—
84
139
—
—
127
—
—
—
227
227S
152
11
11X
—
11CI
—
110
—
110PC
—
11V
31
—
—
—
—
—
212
—
—
—
—
216
—
—
189
50
—
49PC
95
97
97
599
595
75
231
180
—
—
—
—
—
—
—
—
820
—
801
802
—
—
—
—
67
68
146
145
53
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 5/24/2001
TOLCO Cross Reference Chart
TOLCO
GRINNELL
B-LINE
MCO
PHD
SUPER STRUT
CARPENTER
& PATERSON
EMPIRE
INDUSTRIES
50
51
52
58
60
61
61T
62
64
65
66
68
69
69R
70
70R
70S
71
78
81
81PVC
82
82PVC
83
84
99
100
101
101L
102
102L
103
104
105
106
107
107F
108
109
109F
110
111
113
114
115
116
117
118
119
120
120MJ
120RWAA
120RWAB
120W
122
123
124
202
206
—
—
227
—
—
133-134
95
92
93
93
89, 87
—
135
136R
—
135
128R
CT65
—
CT121
—
—
—
—
146
278
278X
248
248X
140
—
142
—
—
—
—
—
—
137
120
—
—
—
—
—
60
—
—
—
—
—
—
—
—
—
B3060
—
B3070
—
—
B3042
—
B3050
B351L
—
B3033
B3033
B3367
—
B655
B656
—
B3220
B3199
B3104CT
B3104CTC
B3373CT
B3373CTC
B3195CT
B3195CT
—
—
B3211
B3211X
B3210
B3210X
B3205
B3212
B3213
—
—
—
—
B3019
B2501
B3188
B3501
—
—
—
B3234
—
B3248
—
—
—
—
—
—
—
—
—
325
—
326
—
—
359
—
361
200
300
310
—
255C
—
25
25R
26S
—
—
402
—
511
—
—
—
51
50
40W
—
40
—
—
—
—
46
—
—
—
370A
—
150
—
10
10H
11
—
13
340
12
—
—
—
—
—
—
—
—
—
—
925
—
—
—
—
610, 620
250
350
—
360
359
—
100
105
104
—
940
442
—
552
554
982
980
10
20
55
—
50
—
15
60
40
—
70
—
—
885
—
90
95, 110
110
110H
130
135
134
960
136
80
—
—
—
—
—
—
—
540
AB201
542
—
—
—
—
C755T-C757T
C775L
C777
C778
M778
U568
—
H119
H119R
—
—
M742R
CTL710
—
CT720
—
C716
—
—
H104
E157
—
E156
—
—
—
E151
—
—
—
—
C745
—
H115
HL115
E145
—
E147
—
E148
C781
EF147
—
—
—
—
—
—
—
—
303
—
—
—
45
6
—
15
238
192
—
—
18
—
123
123R
—
123W
95
100CT
100PVC
126CT
—
—
—
94
—
93
341
22
306
133
31
28
—
177
—
—
—
—
283
222
165
103
103
706
176
102
—
44
—
—
—
—
—
59
—
202
—
—
—
159
158
—
218
21L
62
61
—
22R
—
51
51R
—
—
—
110CT
110PC
50CT
50CTI or 59PC
—
—
54
—
26W
—
26
—
57
—
55
—
77
—
81
—
—
137
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
56
52
52
72
52L
75
52F
—
—
—
—
—
—
83
84
61
™
www.tolco.com
www.tolco.com
®
Revision
5/24/2001
Revision
5/24/2001
a brand of
TOLCO™ Cross Reference Chart
62
TOLCO
GRINNELL
B-LINE
MCO
PHD
SUPER STRUT
CARPENTER
& PATERSON
EMPIRE
INDUSTRIES
125
126
130
200
200WON
202
203
207
209
210
219
220
244H
244HR
244C
244CR
260-1
261-11/2
262-2
263-21/2
264-3
265-4
301CT
302
303
304
305
306
307
309
309N
310
310N
312
313
315
316
316T
317
317/319
318/319
318
322
323
324
325
326
327
328
329
330
331
332
333
335
336
337
—
—
—
69
—
CT69
—
—
—
—
168
167
—
—
—
—
160
161
162
163
164
165
CT138R
138R
108
66
66
114
110R
181
—
282
285N
102
191
—
—
—
—
264
—
259
171
—
181
175
177
271
274
218, 229
290
230
299
157
217
14
—
DS16
B3228
—
B3170NF
105
B3170CT
B3170CTC
—
—
—
—
B3151
—
—
—
—
B3160
B3161
B3162
B3163
B3164
B3165
B3198HCT
B3198H
B3173
B3083WO
B3083WO
B3224
B3222
B3014
B3014N
B2500
N2500
B3096
B3092
B3093
B3088
B3088T
B3095
B3093
B3092
B3090
B3114R
B3121
B3110
B3120
B3122
B3117SL
B3118SL
B3054
B3200
B3202
B3201
B3203
B3045
B3040
B3082
43
42
356
130
—
101
102
—
—
—
—
125
126
—
127
—
630
631
632
633
634
635
456
455
—
320L
320W
—
47
282
282N
355
355N
—
724
722
—
—
720
—
—
721
605
621
610
615
620
617
619
360
35
30
31
26
369
363
321
48
45
—
—
—
E151D
E150S
—
—
—
CT727
CT727P
—
—
—
—
C790
—
—
—
—
C789
C789A
C789B
C789C
C789D
C789E
MT718
M718
—
C789W/O
C780W/HW
—
E120
—
—
452
AB102
—
—
C786
—
—
—
C786
—
C785
—
C729-2½
C729-2
CR729A
RC729
C730C
C730D
M732
E120A
F112
F111
M129
C769
—
C747
166
—
—
800
1A
800CT
800PVC
—
—
—
—
265P
—
—
—
—
351
352
353
354
355
356
81CT
—
—
—
—
38
12
—
650-266-75
—
—
137
—
137
—
—
—
—
—
125
—
110
140
39
109
—
53
293
—
132
276
—
92
14
—
59
—
—
31
310
C10CTI
—
—
—
—
—
167
—
—
—
—
1900
1901
1902
1903
1904
1905
41HCT
41H
—
—
—
114
47
—
—
—
—
422
—
425 or 427
—
—
420
426
427
427
277
271
272
275
274
279S
280S
229
131
320
909
157
156
155
—
153
—
47W
47D
160
170
165
—
165
—
651
653
654
655
656
658
512H
508
500
900-1
900
44
32
950
950N
—
—
875
880
882
—
871
880
875
876
882
490
—
470
460
480
486
487
630
35
960
38
25
—
635
—
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 5/24/2001
TOLCO™ Cross Reference Chart
TOLCO
GRINNELL
B-LINE
MCO
PHD
SUPER STRUT
CARPENTER
& PATERSON
EMPIRE
INDUSTRIES
343
405
406
420
421
421C
422
425
426
427
428
429
430
431
432
500
505
506
568
580
581
582
598
650
800
825
825A
906
907
909
910
975
980
981
990
991
1000
1001
2002
55
—
—
—
256
—
255
—
280
436
437
438-1
438-2
438-3
—
178
247
—
B268
80-V
81H
82A-G
98A-G
296
—
—
—
—
—
—
112
—
—
—
—
—
—
—
—
B3080
B3256
B3257
—
B3281
—
—
—
B3891
—
—
B3891
B3892
B3893
371
—
—
650
651
—
—
—
640
—
—
640-1
640-2
640-3
—
625
—
—
—
—
—
—
—
—
—
—
—
—
—
—
335AB
335A
—
—
—
—
—
—
—
936
—
—
—
670-678
—
—
—
690
—
—
690-1
690-2
690-3
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
890 —
—
—
—
—
—
—
—
—
—
—
—
PG794
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
220
—
—
—
—
—
—
—
—
—
—
—
—
—
—
478
—
—
568
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
69
—
—
—
—
—
—
—
4000 Series
—
—
4100 Series
—
—
—
—
—
35
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
B3264
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
63
™
www.tolco.com
®
Revision 5/24/2001
a brand of
Cross Reference Chart - Grinnell to TOLCO™
64
GRINNELL
TOLCO
GRINNELL
TOLCO
GRINNELL
TOLCO
GRINNELL
TOLCO
14
47
49
52
55
60
65
CT65
66
67
69
CT69
80-V
81H
82A-G
89, 87
92
93
95
98A-G
100
103
108
110R
112
114
120
CT121
CT138R
128R
133-134
135
136R
137
138R
140
142
146
157
160
161
162
163
164
336
33
34
35
343
118
1LD
81
305
3
200
202
580
581
582
69
65
66
64
598
8
7
303
307
910
306
111
82
301CT
78
62
70, 71
70R
110
302
103
105
100
333
260-1
261-11/2
262-2
263-21/2
264-3
178
181
191
192
194
195
199
202
206
212
212FP
216
217
227
230
247
248
248X
255
256
257
259
260
261
262
264
B268
271
274
278
278X
280
282
285N
290
295
296
299
300
436
437
438-1
438-2
438-3
500
324
313
312
30
30M
30H
50
51
4
4A
4H
335
60
331
505
102
102L
422
421
426
318
1
6
20
317/319
568
327
328
101
101L
426
309, 309N
310N
330
5
650
332
1A
427
428
429
430
431
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1CBS
1F
1LDF
2
2F
2FWON
2WON
3F
4B
4C.I.
4F
6F
20S
21
21F
22
23
24
25
30L
31M
31O
32
40
41
42
52
58
61
69R
70S
83
84
99
104
106
107
107F
108
109
109F
113
114
115
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
120W
122
123
124
125
126
130
200WON
203
207
209
210
244H
244HR
244C
244CR
315
316
317
316T
318/319
323
337
405
406
420
421
425
432
506
800
825
825A
906
907
909
975
980
981
990
991
1000
1001
2002
165
167
168
171
175
177
265-4
220
219
322
325
326
590
594
595
599
600
218, 229
1C.I.
14X
14
9X
9
329
—
—
—
—
—
—
116
117
119
120
120MJ
120RWA
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
www.tolco.
Revision 5/24/2001
Cross Reference Chart - B-Line to TOLCO™
B-LINE
TOLCO
B-LINE
TOLCO
B-LINE
TOLCO
B-LINE
TOLCO
DS16
B351L
B655
B656
B2500
N2500
B2501
B3014
B3014N
B3019
B3033
B3040
B3042
B3045
B3050
B3054
B3060
B3066
B3067
B3068
B3070
B3080
B3082
B3083WO
B3083
B3084
B3085
B3086
B3088
B3088T
B3090
B3092
B3093
B3095
B3096
B3100
B3100C
B3100F
B3102
B3104
B3104C
B3104CT
B3104CTC
B3104F
B3106
B3108
B3110
B3114
B3117SL
B3118SL
125
64
70
70R
310
310N
109F
309
309N
109
68
336
61
335
62
329
50
30M
30H
30
52
343
337
304
305
33
35
34
316
316T
318
318/319
317/319
317
312
1
1PVC
1F
1C.I.
1LD
1LDPVC
81
81PVC
1LDF
1V
1A
324
322
327
328
B3121
B3122
B3132
B3132W
B3134
B3134W
B3140
B3142
B3144
B3147
B3148
B3149
B3151
B3160
B3161
B3162
B3163
B3164
B3165
B3170
B3170CT
B3170CTC
B3170NFF
B3172
B3172F
B3173
B3180
B3188
B3190
B3191
B3195CT
B3198H
B3198HCT
B3199
B3200
B3201
B3202
B3203
B3205
B3210
B3210X
B3211
B3211X
B3212
B3213
B3220
B3224
B3228
B3234
B3248
323
326
9
9X
14
14X
4
4H
5
32
7
8
220
260-1
216-11/2
262-2
263-21/2
264-3
265-4
2
202
203
2F
2WON
2FWON
303
20
110
40
41
83
302
301CT
78
330
332
331
333
103
102
102L
101
101L
104
105
71
306
126
116
118
B3256
B3257
B3264
B3281
B3367
B3373
B3373C
B3373CT
B3373CTC
B3501
B3690
B3690F
B3891
B3892
B3893
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
405
406
500
421
69
6
6PVC
82
82PVC
111
3
3F
426
430
431
1CBS
4A
4B
4C.I.
4F
6F
20S
21
21F
22
23
24
25
30L
31M
31O
42
51
58
60
65
66
69R
70S
84
99
100
106
107
107F
108
113
114
115
117
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
120
120MJ
120RWA
120W
122
123
124
130
200
200WON
207
209
210
219
244H
244HR
244C
244CR
420
421C
422
425
427
428
432
505
506
568
580
581
582
598
650
800
825
825A
906
907
909
910
975
980
981
990
991
1000
1001
2002
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
65
™
www.tolco.com
®
Revision 5/24/2001
a brand of
Cross Reference Chart - MCO to TOLCO™
66
MCO
TOLCO
MCO
TOLCO
MCO
TOLCO
MCO
TOLCO
8EG
10
10H
11
12
13
25
25R
25S
26
30
31
35
40
40W
42
43
46
47
50
51
100
100FL
102
105
125
126
127
130
150
200
255C
282
282N
300
310
319
320L
320W
321
325
326
335A
335AB
340
348
351
352
353
355
355N
21
113
114
115
119
117
70
70R
70S
333
331
332
330
102
101
126
125
106
307
100
99
2
2F
203
200WON
220
244H
244C
200
110
64
69
309
309N
64
66
42
304
305
337
50
52
975
910
118
30
30L
30M
30H
310
310N
356
359
360
361
363
367
370A
371
373
374
374A
400
400FL
402
40
410
410FL
41
418
418FL
450
451
452
455
456
457
458
470
510
511
516
517
605
610
615
617
619
620
621
625
630
631
632
633
634
635
640
640-1
640-2
640-3
651
130
61
329
62
336
335
109
343
33
34
35
1
1F
81
1C.I.
1LD
1LDF
1A
3
3F
4
4H
5
302
301CT
40
41
20
6
82
9X
9
322
324
325
327
328
326
323
500
260-1
261-11/2
262-2
263-21/2
264-3
265-4
426
429
430
431
421
651
700
705
712
720
721
722
724
—
420
—
—
—
—
—
—
—
—
520
—
—
—
—
107
108
109
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
421
7
8
32
317
318
315
313
1CBS
1PVC
1LDPVC
1V
2FWON
4A
4B
4C.I.
4F
6F
6PVC
14
14X
20S
21F
22
23
24
25
31M
31O
51
58
60
68
69R
71
78
81PVC
82PVC
83
84
101l
102L
103
104
107
107F
108
109F
111
116
120
—
—
—
—
—
—
—
101
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
120MJ
120RWAA
120RWAB
120W
122
123
124
202
207
209
210
219
244HR
244CR
303
306
312
316
316T
317/319
318/319
405
406
421C
422
425
427
428
432
505
506
568
580
581
582
598
650
800
825A
906
907
909
980
981
990
991
1000
1001
2001
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
™
www.tolco.com
®
Revision 5/24/2001
a brand of
Cross Reference Chart - PHD to TOLCO™
PHD
TOLCO
PHD
TOLCO
PHD
TOLCO
PHD
TOLCO
10
15
20
25
32
35
38
40
44
45
47D
47W
48
50
55
60
70
80
90
95, 110
100
104
105
110
110H
130
134
135
136
151
151F
153
160
165
170
180
180F
250
350
359
360
420
430
440
440F
450
450F
450V
453
460
470
99
103
100
333
307
330
332
105
306
126
210
209
125
102
101
104
107
120
110
111
70
70S
70R
113
114
115
117
116
119
2
2F
203
219
244H/244C
220
2WON
2FWON
64
65
69
69
1C.I.
1A
1LD
1LDF
1
1F
1V
1PVC
325
324
480
486
487
490
500
508
512H
520
522
525
535
545
550
552
553
554
580
585
590
595
610, 620
630
635
651
653
654
655
656
658
670-678
690
810
820
825
830
840
850
855
860
871
875
876
880
882
885
890
900
900-1
903
904
910
326
327
328
322
303
302
301CT
4
4H
5
7
8
6
82
6PVC
82PVC
9
9X
14
14X
62
329
336
260-1
261-11/2
262-2
263-21/2
264-3
265-4
421
426
41
40
20
20S
32
30L
30M
30H
316T
317/319
318/319
317
318
109
975
305
304
35
34
42
925
930
936
940
950
950N
960
970
970F
980
982
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
52
118
343
78
309
309N
331
3
3F
84
83
1CBS
1LDPVC
4A
4B
4PVC
4C.I.
4F
4L
6F
21
21F
22
23
24
25
28
30
31M
31O
33
50
51
58
60
61
61T
66
69R
71
81PVC
101L
102L
106
107F
108
109F
120MJ
120RWAA
120RWAB
120W
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
690-1
690-2
690-3
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
122
124
130
200
200WON
202
207
244HB
244CR
310
310N
316
323
335
337
405
406
420
421C
422
425
427
428
429
430
431
432
500
505
506
568
580
581
582
598
650
800
825
825A
906
907
909
910
980
981
990
1000
1001
2002
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
67
www.tolco.com
Revision 5/24/2001
Cross Reference Chart - Super Strut to TOLCO™
68
SUPER
STRUT
TOLCO
SUPER
STRUT
TOLCO
SUPER
STRUT
TOLCO
AB102
F111
F112
H104
H115
H119
H119R
HL115
E120
E120A
M129
E145
E147
EF147
E148
E150S
E151
E151D
E156
E157
164
AB201
C475
452
540
542
U568
C704
C704A
C710
C710F
C710P
CI710
CL710
CTL710
CX710
C711
C711F
C716
M718
C720
C720L
C720P
CT720
C724
W724
C725
C725
C726
C727
C727
310N
332
331
100
110
70
70R
111
307
330
333
113
115
119
117
126
105
125
102
101
20
51
109
310
50
52
69
41
40
1
1F
1PVC
1C.I.
1LD
81
1A
3
3F
83
302
6
7
6PVC
82
9
9X
2FWON
4
5
2
2WON
C727F
CT727
CT727P
C729-2
C729-2½
CF729A
RC729
C730C
C730D
M732
C736
C739H
C739M
M742R
C747
C755T-C757T
C777
C769
C775L
C778
M778
C780W/HW
C780W/O
C781
C785
C786
C789
C789A
C789B
C789C
C789D
C789E
C790
PG794
RCS
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2F
202
203
324
323
325
326
327
328
329
30
30H
30M
78
337
62
65
335
64
66
68
305
304
118
318
317/319
260-1
260-11/2
262-2
263-21/2
264-3
265-4
220
421
32
1CBS
1LDF
1LDPVC
1V
4B
4C.I.
4F
4H
4L
4PVC
6F
14
20S
21
21F
22
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
23
24
25
28
30L
31M
31O
33
34
35
42
58
60
61
61T
69R
70S
71
81PVC
82PVC
84
89
101L
102L
103
104
106
107
107F
108
109F
114
116
120
120MJ
120RWA
120W
122
123
124
130
200
200WON
207
209
210
219
244HR
244C
244CR
303
SUPER
STRUT
TOLCO
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
306
309
309N
312
313
316
316T
317
318/319
322
336
343
405
406
420
421C
422
425
426
427
428
429
430
431
432
500
505
506
568
580
581
582
598
650
800
825
825A
906
907
909
910
975
980
981
990
991
1000
1001
2002
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
™
www.tolco.com
®
Revision 5/24/2001
a brand of
Cross Reference Chart - Carpenter & Paterson to
TOLCO™
CARPENTER &
CARPENTER &
CARPENTER &
CARPENTER &
TOLCO
TOLCO
TOLCO
PATERSON
PATERSON
PATERSON
PATERSON
6
12
14
15
18
28
31
33
38
39
44
45
53
59
69
84
85
92
93
94
100
102
103
109
110
114
123
125
126
127
132
133
137
137
139
140
152
158
165
166
175
176
177
179
192
200
220
222
227
258
260
61
307
336
62
69
105
104
102
306
325
120
60
328
123
30
30M
78
335
101
99
1
118
115
326
323
20
70
318
6
32
331
103
312
315
30H
324
42
9
113
125
4
117
107
7
65
1LD
343
111
40
9X
14X
267
276
283
293
298
303
304
306
341
351
352
353
354
355
356
399
478
706
800
800
100C.I.
100CT
100EL
100PVC
100PVC
123R
123W
126CT
126PVC
158DB
1A
200VT
227S
265P
650-266-75
800CT
800PVC
81CT
—
—
—
—
—
—
—
—
—
—
—
—
—
8
332
110
329
4H
50
5
102L
101L
260-1
260-11/2
262-2
263-21/2
264-3
265-4
568
500
116
2
200
1C.I.
81
1A
1PVC
81PVC
70R
71
82
6PVC
14
200WON
1V
41
220
309N
202
203
301CT
1CBS
1F
1LDF
1LDPVC
2F
2FWON
3
3F
4A
4B
4C.I.
4F
4L
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
4PVC
6F
20S
21
21F
22
23
24
25
27
27A
28
30L
31-M
31-O
33
34
35
51
52
58
61T
66
68
69R
70S
82PVC
83
84
100
106
107F
108
109
114
119
120MJ
120RWAA
120W
122
124
126
130
207
209
210
219
244H
244HR
244C
244CR
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
TOLCO
302
303
304
305
309
310
310N
313
316
316T
317
317/319
318/319
322
327
330
333
337
405
406
421
421C
422
425
426
427
428
429
430
431
432
505
506
580
581
582
598
650
800
825A
906
907
910
975
980
981
990
991
1000
1001
2002
69
www.tolco.com
Revision 5/24/2001
Cross Reference Chart - Empire Industries to TOLCO™
70
EMPIRE
INDUSTRIES
TOLCO
EMPIRE
INDUSTRIES
TOLCO
EMPIRE
INDUSTRIES
TOLCO
11
26
31
31
35
47
50
51
52
53
54
55
56
57
59
61
62
67
68
69
72
75
75
77
80
81
83
84
95
97
110
114
137
145
146
150
155
156
157
158
159
167
180
189
202
212
216
218
229
231
255
256
1
102
2
200
506
307
6
70
115
42
99
105
113
103
125
66
65
34
35
343
116
14X
118
107
209
108
123
124
7
8
1LD
306
110
41
40
130
336
335
333
61
60
220
20S
5
50
4
4H
62
329
20
421C
421
271
272
273
275
277
310
320
420
422
426
427
427
595
599
600
801
802
320
909
1900
1901
1902
1903
1904
1905
110CT
110PC
110PC
11CI
11V
11X
131
21L
22R
26W
279S
280S
310CTI
4000 Series
4100 Series
41H
41HCT
425 or 427
49PC
50CT
50CTI or 49PC
51R
52F
52L
81N
—
—
323
324
326
325
322
200WON
331
317
312
317/319
318/319
318
14
9X
9
30M
30H
30
332
260-1
260-11/2
262-2
263-21/2
264-3
265-4
81
1PVC
81PVC
1C.I.
1V
1A
330
64
69
101
327
328
202
426
429
302
301CT
313
6PVD
82
82PVC
70R
119
117
309N
1CBS
1F
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1LDF
1LDPVC
2F
2FWON
3
3F
4A
4B
4C.I.
4F
4L
4PVC
6F
21
21F
22
23
24
25
27
27A
28
30L
31-M
31-O
33
51
52
58
61T
68
69R
70S
71
78
83
84
100
101L
102L
104
106
107F
109
109F
111
114
120
120MJ
120RWAA
120W
122
EMPIRE
INDUSTRIES
TOLCO
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
126
203
307
210
219
244H
244HR
244C
244CR
303
304
305
309
310
310N
315
316
316T
337
405
406
422
425
427
428
430
431
432
500
505
568
580
581
582
598
650
800
825A
906
907
909
910
975
980
981
990
991
1000
1001
2002
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
www.tolco.com
Revision 5/24/2001
TOLCO to MSS and Federal Specification Cross Reference
TOLCO
1
1A
1LD
2
2NFPA
2WON
3
4
4 CI
4H
5
6
20
20S
30L
30M
30H
62
64
65
66
68
81
82
110
200
200WON
202
203
220
260-1
261-11⁄2
MSS-SP-69
Federal Spec.
Ww-H-171E
Type 1
Type 1
—
Type 10
Type 10
Type 7
Type 5
Type 4
Type 4
Type 4
Type 3
Type 8
Type 26
Type 26
Type 31
Type 32
Type 33
Type 21
Type 23
Type 19
Type 19
Type 19
—
Type 8
Type 24
Type 10
Type 7
Type 10
Type 10
Type 40
Type 39
Type 39
Type 1
Type 1
Type 12
Type 10
Type 10
Type 7
—
Type 4
Type 4
Type 4
Type 3
Type 8
Type 26
Type 26
Type 32
Type 33
Type34
Type 21
Type 23
Type 23
Type 23
Type 23
Type 12
Type 8
Type 24
Type 10
Type 7
Type 10
Type 10
Type 41
Type 40A & 40B
Type 40A & 40B
TOLCO
MSS-SP-69
Federal Spec.
Ww-H-171E
262-2
263-21⁄2
264-3
265-4
301CT
302
303
304
305
306
307
309
310
317
318
317A
322
324
327
328
329
330
331
332
335
336
343
499
500
568
580
582
598
650
Type 39
Type 39
Type 39
Type 39
Type 12
Type 12
Type 11
Type 22
Type 22
Type 15
Type 16
Type 18
Type 18
Type 36
Type 37
Type 38
Type 41
Type 43
Type 44
Type 46
Type 30
Type 17
Type 13
Type 14
Type 25
Type 27
Type 57
Type 58
Type 49
Type 51
Type 54 & 55
Type 51
Type 51
Type 50
Type 40A & 40B
Type 40A & 40B
Type 40A & 40B
Type 40A & 40B
Type 25
Type 25
Type 11
Type 22
Type 22
Type 15
Type 16
Type 18
Type 19
Type 37
Type 38
Type 39
Type 42
Type 44
Type 45
Type 47
Type 30
Type 17
Type 13
Type 14
Type 53
Type 54
—
—
Type 50
Type 51
Type 52
Type 51
Type 51
—
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
71
™
www.tolco.com
®
Revision 5/24/2001
a brand of
Beam Dimensions
American Standard
Channels — C Shapes
Designation Flange
Depth & Wt. Width
"x" Lbs.
"Y"
C3
C3
C3
C4
C4
C5
C5
C6
C6
C6
C7
C7
C7
C8
C8
C8
C9
C9
C9
C10
C10
C10
C10
C12
C12
C12
C15
C15
C15
C18
C18
C18
C18
72
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
4.1
5.0
6.0
5.4
7.25
6.7
9.0
8.2
10.5
13.0
9.8
12.25
14.75
11.5
13.75
18.75
13.4
15.0
20.0
15.3
20.0
25.0
30.0
20.7
25.0
30.0
33.9
40.0
50.0
42.7
45.8
51.9
58.0
13⁄8
11⁄2
15⁄8
15⁄8
13⁄4
13⁄4
17⁄8
17⁄8
2
21⁄8
21⁄8
21⁄4
21⁄4
21⁄4
23⁄8
21⁄2
21⁄2
21⁄2
25⁄8
25⁄8
23⁄4
27⁄8
3
3
3
31⁄8
33⁄8
31⁄2
33⁄4
4
4
41⁄8
41⁄4
Ave.
Thickness
"Z"
.250
.313
.313
.375
.375
.375
.438
.438
.500
.625
.625
American Standard
I Beams — S Shapes
Designation Flange
Depth & Wt. Width
"x" Lbs.
"Y"
S3
S3
S4
S4
S5
S5
S6
S6
S7
S7
S8
S8
S10
S10
S12
S12
S12
S12
S15
S15
S18
S18
S20
S20
S20.3
S20.3
S24
S24
S24
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
5.7
23⁄8
7.5
21⁄2
7.7
25⁄8
9.5
23⁄4
10.0
3
14.75 31⁄4
12.5
33⁄8
17.25 35⁄8
15.3
35⁄8
20.0
37⁄8
18.4
4
23.0
41⁄8
25.4
45⁄8
35.0
5
31.8
5
35.0
51⁄8
40.8
51⁄4
50.0
51⁄2
42.9
51⁄2
50.0
55⁄8
54.7
6
70.0
61⁄4
66.0
61⁄4
75.0
63⁄8
86.0
7
96.0
71⁄4
80.0
7
90.0
71⁄8
100.0 71⁄4
Ave.
Thickness
"Z"
.250
.313
.313
.375
.375
.438
.500
.563
.688
.625
.688
.813
.938
.875
American Standard Wide Flange — W Shapes
Designation Flange
Depth & Wt. Width
"x" Lbs.
"Y"
W4
W5
W6
W8
W8
W8
W8
W8
W8
W8
W8
W8
W8
W10
W10
W10
W10
W10
W10
W10
W10
W10
W10
W10
W12
W12
W12
W12
W12
W12
W12
W12
W12
W12
W12
W12
W12
W12
W14
W14
W14
W14
W14
W14
W14
W14
W14
W14
W14
x 13
x 19
x 25
x 18
x 21
x 24
x 28
x 31
x 35
x 40
x 48
x 58
x 67
x 22
x 26
x 33
x 39
x 45
x 49
x 54
x 60
x 68
x 77
x 88
x 26
x 30
x 35
x 40
x 45
x 50
x 53
x 58
x 65
x 72
x79
x 87
x 96
x 106
x 30
x 34
x 38
x 43
x 48
x 53
x 61
x 68
x 74
x 82
x 90
4
5
51⁄8
51⁄4
51⁄4
61⁄2
61⁄2
8
8
81⁄8
81⁄8
81⁄4
81⁄4
53⁄4
53⁄4
8
8
8
10
10
101⁄8
101⁄8
101⁄4
101⁄4
61⁄2
61⁄2
61⁄2
8
8
81⁄8
10
10
12
12
121⁄8
121⁄8
121⁄8
121⁄4
63⁄4
63⁄4
63⁄4
8
8
8
10
10
101⁄8
101⁄8
141⁄2
Ave.
Thickness
"Z"
.375
.430
.455
.330
.400
.400
.465
.435
.495
.560
.685
.810
.935
.360
.440
.435
.530
.620
.560
.615
.680
.770
.870
.990
.380
.440
.520
.515
.575
.640
.575
.640
.605
.670
.735
.810
.900
.990
.385
.455
.515
.530
.595
.660
.645
.720
.785
.855
.710
Designation Flange
Depth & Wt. Width
"x" Lbs.
"Y"
W14
W14
W14
W14
W16
W16
W16
W16
W16
W16
W16
W16
W16
W18
W18
W18
W18
W18
W18
W18
W18
W18
W21
W21
W21
W21
W21
W21
W21
W21
W24
W24
W24
W24
W24
W24
W27
W27
W27
W27
W30
W30
W30
W30
W33
W33
W33
W36
W36
W36
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
99
109
120
132
36
40
45
50
57
67
77
89
100
50
55
60
65
71
76
86
97
106
62
68
73
83
93
101
111
122
76
84
94
104
117
131
94
102
114
146
108
116
134
132
118
130
141
135
150
160
145⁄8
145⁄8
145⁄8
143⁄4
7
7
7
71⁄8
71⁄8
101⁄4
101⁄4
103⁄8
103⁄8
71⁄2
71⁄2
71⁄2
75⁄8
75⁄8
11
111⁄8
111⁄8
111⁄4
81⁄4
81⁄4
81⁄4
83⁄8
83⁄8
121⁄4
123⁄8
123⁄8
9
9
91⁄8
123⁄4
123⁄4
127⁄8
10
10
101⁄8
14
101⁄2
101⁄2
101⁄2
101⁄2
111⁄2
111⁄2
111⁄2
12
12
12
Ave.
Thickness
"Z"
.780
.860
.940
1.030
.630
.505
.565
.630
.715
.665
.760
.875
.985
.570
.630
.695
.750
.810
.680
.770
.870
.940
.615
.685
.740
.835
.930
.800
.875
.960
.680
.770
.875
.750
.850
.960
.745
.830
.930
.975
.760
.850
.930
1.000
.740
.855
.960
.790
.940
1.020
™
www.tolco.com
®
Revision 5/24/2001
a brand of
™
Decimals of a Foot
Inch
0"
0
1/16
1/8
3/16
1/4
5/16
3/8
7/16
1/2
9/16
5/8
11/16
3/4
13/16
7/8
15/16
0
.0052
.0104
.0156
.0208
.0260
.0313
.0365
.0417
.0469
.0521
.0573
.0625
.0677
.0729
.0781
1"
2"
3"
4"
5"
6"
7"
8"
9"
10"
11"
.0833
.0085
.0938
.0990
.1042
.1094
.1146
.1198
.1250
.1302
.1354
.1406
.1458
.1510
.1563
.1615
.1667
.1719
.1771
.1823
.1875
.1927
.1979
.2031
.2083
.2135
.2188
.2240
.2292
.2344
.2396
.2448
.2500
.2552
.2604
.2656
.2708
.2760
.2812
.2891
.2917
.2969
.3021
.3073
.3125
.3177
.3229
.3281
.3330
.3385
.3438
.3490
.3542
.3594
.3646
.3724
.3750
.3802
.3854
.3906
.3958
.4010
.4063
.4118
.4167
.4219
.4271
.4323
.4375
.4427
.4479
.4557
.4583
.4635
.4688
.4740
.4792
.4844
.4896
.4948
.5000
.5052
.5104
.5156
.5208
.5260
.5313
.5391
.5417
.5469
.5521
.5573
.5625
.5677
.5729
.5781
.5833
.5885
.5938
.5990
.6042
.6094
.6146
.6224
.6250
.6302
.6354
.6406
.6458
.6510
.6563
.6615
.6667
.6719
.6771
.6823
.6875
.6927
.6979
.7057
.7083
.7135
.7188
.7240
.7292
.7344
.7396
.7448
.7500
.7552
.7604
.7656
.7708
.7760
.7813
.7891
.7917
.7969
.8021
.8073
.8125
.8177
.8229
.8221
.8333
.8385
.8438
.8490
.8542
.8594
.8646
.8724
.8750
.8802
.8854
.8906
.8958
.9010
.9063
.9115
.9167
.9219
.9271
.9323
.9375
.9427
.9479
.9557
.9583
.9635
.9688
.9740
.9792
.9844
.9896
.9948
Decimals of an Inch
Fraction
Decimal
1/32
1/16
3/32
1/8
5/32
3/16
7/32
1/4
9/32
5/16
11/32
3/8
13/32
7/16
15/32
1/2
.0312
.0625
.0937
.1250
.1562
.1875
.2187
.2500
.2812
.3125
.3437
.3750
.4062
.4375
.4687
.500
Fraction
Decimal
17/32
9/16
19/32
5/8
21/32
11/16
23/32
3/4
25/32
13/16
27/32
7/8
29/32
15/16
31/32
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
.5312
.5625
.5937
.6250
.6562
.6875
.7187
.7500
.7812
.8125
.8437
.8750
.9062
.9375
.9687
73
www.tolco.com
Revision 5/24/2001
Steel Pipe Data
Schedule 40 & 80
Pipe
Size
Sched.
No.
3/8
40
80
40
80
40
80
40
80
40
80
40
80
40
80
40
80
40
80
40
80
40
80
1/2
3/4
1
11⁄4
11⁄2
2
21⁄2
3
31⁄2
4
Wall
Wt. Per Water Weight
Thickness Foot
per Ft./Lbs
O.D.
.675
.840
1.050
1.315
1.660
1.900
2.375
2.875
3.500
4.000
4.500
.091
.126
.109
.147
.113
.154
.133
.179
.104
.191
.145
.200
.154
.218
.203
.276
.216
.300
.226
.318
.237
.337
.567
.738
.850
1.087
1.130
1.473
1.678
2.171
2.272
2.996
2.717
3.631
3.652
5.022
5.790
7.660
7.570
10.250
9.110
12.510
10.790
14.980
.083
.061
.132
.101
.230
.186
.374
.311
.647
.555
.882
.765
1.452
1.279
2.072
1.834
3.200
2.860
4.280
3.850
5.510
4.980
Pipe
Size
Sched.
No.
5
40
80
40
80
40
80
40
80
40
80
40
80
40
80
40
80
40
80
40
80
20
API
6
8
10
12
14
16
18
20
24
30
36
O.D.
5.563
6.625
8.625
10.750
12.750
14.000
16.000
18.000
20.000
24.000
30.000
36.000
Wall
Wt. Per Water Weight
Thickness Foot
per Ft. Lbs.
.258
.375
.280
.432
.322
.500
.365
.593
.406
.687
.437
.750
.500
.843
.563
.937
.593
1.031
.687
1.218
.500
.500
14.620
20.780
18.970
28.570
28.550
43.390
40.480
64.400
53.600
88.60
63.00
107.000
83.000
137.000
105.000
171.000
123.000
209.000
171.000
297.000
158.000
190.000
8.660
7.870
12.510
11.290
21.600
19.800
34.100
31.100
48.500
44.000
58.500
51.200
76.500
69.700
97.200
88.500
120.400
109.400
174.200
158.200
286.000
417.000
Copper Tube Data
Type L
Type K
Nom.
Tube
Size
O.D.
Tubing
O.D.
1/4
3/8
1/2
5/8
3/4
1
11⁄4
11⁄2
2
21⁄2
3
31⁄2
4
5
6
3/8
1/3
5/8
3/4
7/8
11⁄8
13⁄8
15⁄8
21⁄8
25⁄8
31⁄8
35⁄8
41⁄8
51⁄8
61⁄8
.375
.500
.625
.750
.875
1.125
1.375
1.625
2.125
2.625
3.125
3.625
4.125
5.125
6.125
74
Wall
Wt. Per Water Weight
Thickness Foot
per Ft./Lbs
.030
.035
.040
.042
.045
.050
.055
.060
.070
.080
.090
.100
.110
.125
.140
.126
.198
.285
.362
.455
.655
.884
1.140
1.75
2.480
3.330
4.290
5.380
7.610
10.200
.034
.062
.100
.151
.209
.357
.546
.767
1.341
2.064
2.949
3.989
5.188
8.081
11.616
Nom.
Tube
Size
O.D.
Tubing
O.D.
1/4
3/8
1/2
5/8
3/4
1
11⁄4
11⁄2
2
21⁄2
3
31⁄2
4
5
6
3/8
1/2
5/8
3/4
7/8
11⁄8
13⁄8
15⁄8
21⁄8
25⁄8
31⁄8
35⁄8
41⁄8
51⁄8
61⁄8
.375
.500
.625
.750
.875
1.125
1.375
1.625
2.125
2.625
3.125
3.625
4.125
5.125
6.125
Wall
Wt. Per Water Weight
Thickness Foot
per Ft. Lbs.
.035
.049
.049
.049
.065
.065
.065
.072
.083
.095
.109
.120
.134
.160
.192
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
.145
.269
.344
.418
.641
.839
1.040
1.360
2.050
2.920
4.000
5.120
6.510
9.670
13.870
.032
.055
.094
.144
.188
.337
.527
.743
1.310
2.000
2.960
3.900
5.060
8.000
11.200
www.tolco.com
Revision 5/24/2001
a brand of
Cast Iron Pipe Data
American Water Works Assn. (AWWA)
Mechanical Joint Pipe Class 150. Approximately same weight for Bell & Spigot. Flanged cast iron pipe add weight of flanges
Pipe Size
3
4
6
8
10
12
14
16
18
20
24
30
36
42
48
O.D.
C.I. Pipe
3.96
4.80
6.90
9.05
11.10
13.20
15.30
17.40
19.50
21.60
25.80
32.00
38.30
44.50
50.80
Wall
Thickness
.32
.35
.38
.41
.44
.48
.51
.54
.58
.62
.73
.85
.94
1.05
1.14
Wt. Per
Foot
12.2
16.4
25.7
36.7
48.7
62.9
78.8
95.0
114.7
135.9
190.4
277.3
368.9
479.1
595.2
Standard No Hub “Soil Pipe”
Pipe Size
2
3
4
5
6
8
10
O.D.
I.D.
2.25
3.25
4.25
5.25
6.25
8.38
10.50
1.89
2.89
3.89
4.87
5.85
7.94
9.98
Wt. of Water
per Ft./Lbs.
3.73
5.72
12.80
23.10
35.50
51.00
69.30
90.30
114.00
141.50
201.00
312.00
449.00
612.00
803.00
Extra Heavy “Soil Pipe”
Pipe Size
2
3
4
5
6
8
10
O.D.
I.D.
2.38
3.50
4.50
5.50
6.50
8.62
10.75
2.00
3.00
4.00
5.00
6.00
8.00
10.00
Load Carrying Capacities of Threaded Steel Rod
Rod
Diameter In.
3/8
1/2
5/8
3/4
7/8
1
11/8
11/4
11/2
13/4
2
21/2
21/2
*
Root Area
Thread Sq. In.
.068
.126
.202
.302
.419
.552
.693
.889
1.293
1.744
2.300
3.023
3.719
Max. Safe Load
in Lbs. @650°F*
610
1130
1810
2710
3770
4960
6230
8000
11630
15700
20700
27200
33500
Max. Rec. Load
in Lbs. @ 750°F*
540
1010
1610
2420
3360
4420
5560
7140
10370
14000
18460
24260
29800
Weight per
Ft./Lbs.
.376
.668
1.040
1.500
2.400
2.670
3.380
4.170
6.010
8.180
10.680
13.520
16.960
Maximum recommended load based on minimum safety factor of 5.
Main Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92870 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266
www.tolco.com
Fittings
Wrot and cast copper pressure fittings • Wrot and cast copper drainage fittings •
Wrot copper PEXlink® fittings • Cast copper alloy flared fittings • Cast copper alloy
flanges • ABS and PVC DWV fittings • Schedule 40 PVC pressure fittings • CPVC
CTS fittings • CPVC CTS-to-metal transition fittings • Schedule 80 PVC and CPVC
systems • CPVC metric piping systems
Valves & Actuation
Pressure-rated bronze, iron and alloy-iron gate, globe and check valves • Pressure-rated
bronze ball valves • Boiler specialty valves • Commercial and industrial butterfly valves •
Circuit balancing valves • Carbon and stainless steel ball valves • ANSI flanged steel ball
valves • Pneumatic and electric actuators and controls • Grooved ball and butterfly valves
• High performance butterfly valves • UL/FM fire protection valves • Low-pressure gate,
globe, check and ball valves • Bronze specialty valves • Frostproof sillcocks • Quarter-turn
supply stops • MSS specification valves • PVC ball valves • CPVC CTS ball valves • Just
Right® recirculating valves
Chemtrol®
Thermoplastic pipe, valves and fittings in PVC, Corzan® CPVC, polypropylene and
PVDF Kynar® • Chem-Aire® thermoplastic compressed air piping systems •
Pneumatic and electric actuation systems
Corzan® is a registered trademark of Noveon, IP Holdings Corp.
Kynar® is a registered trademark of ATOFINA Chemical, Inc.
Supporting
the Flow.
™
eNIBCO®
A suite of services designed to make customers more efficient • More cost-effective •
More informed • EDI—Electronic Data Interchange • VMI—Vendor Managed Inventory •
NIBCO.com • NIBCOpartner.com • eNIBCO will continuously develop new products to
deliver the competitive advantage.
Every solution
begins with
TOLCO .
™
TOLCO™
Office / Manufacturing
1375 Sampson Avenue
Corona, California 92879
USA
Phone:
Fax:
951.737.5599
951.737.0330
We're committed to
supporting all of your flow
Pipe Hangers • Pipe Supports
TOL-Strut Channel • Seismic Bracing
™
Customer Service:
Phone: 800.786.5266
control needs. We can
provide creative solutions for
your most challenging bracing and support applications.
Solutions that make your
installations easier, safer
and more cost-effective.
For solutions that will support
your flow-control applications,
call on us. We're TOLCO, a
product line committed to
quality, service and innovation—
Supporting the Flow.
C-TOLFP-0105
www.tolco.com