UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida SECTION 16331 PART 1 Pre-Purchase January 2006 PAD-MOUNTED LIQUID COOLED TRANSFORMERS GENERAL 1.01 It is the intent of this specification to secure a pad-mounted liquid cooled transformer that has been prototype tested, factory built, production tested, of the latest commercial design, together with all accessories necessary for a complete installation as described in these specifications herein. The equipment supplied and installed shall meet the requirements of the National Electric Code and all applicable local codes and regulations. All equipment shall be new, of current production by a U. S. firm which manufactures the equipment and assembles the unit so that there is one-source responsibility for warranty, parts, and service through a local representative with factory-trained service personnel. 1.02 A. REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only. 1. 2. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) ANSI C2 (2002) National Electrical Safety Code ANSI C37.47 (1981; Supp. 1983, Correction 1984, R 1992) Distribution Fuse Disconnecting Switches, Fuse Supports, and Current-Limiting Fuses ANSI C57.12.22 (1989) Transformers – Pad-Mounted, Compartmental-Type, SelfCooled, Three-Phase Distribution Transformers with HighVoltage Bushings, 2500 kVA and Smaller: High Voltage, 34 500 GrdY /19 920 Volts and Below; Low Voltage, 480 Volts and Below ANSI C57.12.26 (1993) Transformers – Pad-Mounted Compartmental-Type, SelfCooled, Three-Phase Distribution Transformers for Use with Separable Insulated High-Voltage Connectors, High-Voltage, 34 500 GrdY/19 920 Volts and Below; 2500 kVA and Smaller ANSI C57.12.28 (1999) Switchgear and Transformers – Pad-Mounted Equipment - Enclosure Integrity AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) ASTM A 167 (1994; Rev. A) Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip ASTM D 92 (1990) Flash and Fire Points by Cleveland Open Cup ASTM D 117 (1989) Electrical Insulating Oils of Petroleum Origin ASTM D 877 (1987) Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes ASTM D 1535 (1989) Specifying Color by the Munsell System SECTION 16331 PADMOUNT TRANSFORMER Page 1 of 6 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida 3. ASTM D 3455 (1989) Compatibility of Construction Material with Electrical Insulating Oil of Petroleum Origin ASTM D 3487 (1988; R 1993) Mineral Insulating Oil Used in Electrical Apparatus FACTORY MUTUAL ENGINEERING AND RESEARCH CORPORATION (FM) FM P7825 4. 5. (1994) Approval Guide INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS, INC. (IEEE) IEEE 386 (1995) Separable Insulated Connector Systems for Power Distribution Systems Above 600 V ANSI/IEEE C37.71 (1984; R 1990) Three-Phase, Manually Operated Subsurface Load-Interrupting Switches for Alternating-Current Systems ANSI/IEEE C57.12.00 (2000) Liquid-Immersed Distribution, Power, and Regulating Transformers ANSI/IEEE C57.12.80 (1978; R 1992) Power and Distribution Transformers ANSI/IEEE C57.12.90 (1993) Liquid-Immersed Distribution, Power, and Regulating Transformers and Guide for Short-Circuit Testing of Distribution and Power Transformers ANSI/IEEE C57.98 (1994) Transformer Impulse Tests ANSI/IEEE C62.11 (1999) Metal-Oxide Surge Arresters for Alternating Current Power Circuits INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA) NETA ATS 6. (1991) Electrical Power Distribution Equipment and Systems NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) NEMA LI 1 7. (1989) Industrial Laminated Thermosetting Products NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) NFPA 70 8. (2002) National Electrical Code UNDERWRITERS LABORATORIES INC. (UL) UL 467 1.03 A. B. (1993; Rev thru Feb 2001) Grounding and Bonding Equipment SUBMITTALS Data 1. 2. 3. Pre-Purchase January 2006 Transformer guaranteed losses Transformer loss calculations Tested transformer losses Manufacturer's Catalog Data SECTION 16331 PADMOUNT TRANSFORMER Page 2 of 6 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida 1. Pre-Purchase January 2006 Pad-mounted transformers, dead-front Submittal shall include manufacturer's information for each component, device, and accessory provided with the transformer. C. Drawings 1. Pad-mounted transformer drawings Drawings shall indicate, but not be limited to the following: a. b. c. d. D. E. Overall dimensions, front view, and sectional views. ANSI nameplate data, including manufacturer's name, catalog number, and ratings of fuses. One-line diagram, including switch and fuses. Manufacturer's published time-current curves (on full size logarithmic paper) of the transformer high side fuse. Reports 1. Pad-mounted transformer design tests 2. Pad-mounted transformer routine and other tests 3. Submit certified copies of the following ANSI/IEEE C57.12.00 and ANSI/IEEE C57.12.90 transformer tests. Design Tests ANSI/IEEE C57.12.80, Section 5.1.2 states that "design tests are made only on representative apparatus of basically the same design." Submit design test reports (complete with test data, explanations, formulas, and results), in the same submittal package as the catalog data and drawings for the specified transformer. 1. Temperature rise: "Basically the same design" for the temperature rise test means a pad-mounted transformer with the same coil construction (such as wire wound primary and sheet wound secondary), the same kVA, the same cooling type (OA), the same temperature rise rating, and the same insulating liquid as the transformer specified. 2. Lightning impulse: "Basically the same design" for the lightning impulse dielectric test means a pad-mounted transformer with the same BIL, the same coil construction (such as wire wound primary and sheet wound secondary), and a tap changer, if specified. Design lightning impulse tests shall include both the primary and secondary windings of that transformer. a. b. c. ANSI/IEEE C57.12.90 paragraph 10.3 and ANSI/IEEE C57.98. State test voltage levels. Provide oscillograms with test report. 3. Lifting and moving devices: "Basically the same design" for the lifting and moving devices test means a transformer in the same weight range as the transformer specified. 4. Pressure: "Basically the same design" for the pressure test means a pad-mounted transformer with a tank volume within 30 percent of the tank volume of the transformer specified. SECTION 16331 PADMOUNT TRANSFORMER Page 3 of 6 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida F. Pre-Purchase January 2006 Routine and Other Tests Routine and other tests shall be performed by the manufacturer on the actual transformer prepared for this project to ensure that the design performance is maintained in production. Submit test reports, by serial number and receive approval before delivery of equipment to the project site. Required tests and testing sequence shall be as follows: 1. Resistance measurements 2. Polarity and phase relation 3. Ratio 4. No-load losses (NLL) and excitation current 5. Load losses (LL) and impedance voltage 6. Lightning impulse: a. b. 7. Low frequency dielectric a. b. Applied voltage Induced voltage 8. Leak 9. Dielectric Tests: a. b. G. ANSI/IEEE C57.12.90 and ANSI/IEEE C57.98 State test voltage levels Applied voltage Impulse Certificates PCB Content: Submit manufacturer's certificate that each transformer contains less than one ppm of PCB at shipment for this contract. H. Operation and Maintenance Manuals Pad-mounted transformers, dead-front PART 2 PRODUCTS 2.1 Acceptable Producers: Cooper Power Systems, ABB, and General Electric. 2.2 PRODUCT COORDINATION Products and materials not considered to be pad-mounted transformers and related accessories are specified in Section 16380, "Underground Distribution Primary Cable and Accessories". 2.3 THREE-PHASE PAD-MOUNTED TRANSFORMERS, DEAD-FRONT ANSI C57.12.26 and ANSI C57.12.28 with separate high- and low-voltage compartments. Padmount transformer shall be FM Approved for Outdoor Use. 2.3.1 Compartments SECTION 16331 PADMOUNT TRANSFORMER Page 4 of 6 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida Pre-Purchase January 2006 Divide high- and low-voltage compartments into sections with steel isolating barriers extending the full height and depth of the compartment. Compartment doors: hinged lift-off type with stop in open position and three-point latching. 2.3.1.1 High Voltage High-voltage compartment shall contain the incoming line, insulated high-voltage load-break connectors, bushing well inserts, six high-voltage bushing wells configured for loop feed application, switches, dead-front surge arresters, tap changer handle, connector parking stands with insulated standoff bushings, protective caps, and ground pad. a. Insulated high-voltage load-break connectors: IEEE 386, rated 15 kV, 95 kV BIL. Current rating: 200 amperes rms continuous. Short time rating: 10,000 amperes rms symmetrical for time duration of 0.17 seconds. Connectors and inserts shall be the product of a single manufacturer. Connector shall have a steel reinforced hook-stick eye, grounding eye, test point, and arc-quenching contact material. b. Bushing well inserts and feed-thru inserts: IEEE 386, 200 amperes, 15 kV Class. Provide a bushing well insert for each bushing well unless indicated otherwise. Provide feed-thru inserts as indicated. c. Three, two-position, oil immersed switches shall be mounted inside transformer tank with switch operating handle located in high-voltage compartment and equipped with metal loop for hoop stick operation. Fuses shall be interlocked with switches so that fuses can be removed only when the associated switch is in the “OPEN” position. The high-voltage overcurrent protection scheme provided with the transformer shall be a loadbreak BAYO-Net assembly with a flapper valve to minimize oil spillage. Overcurrent protection shall be provided by a Bay-O-Net expulsion fuse mounted in series with partial range under-oil ELSP current-limiting fuses with an interrupt rating of 30,000 A. d. Surge arresters: ANSI/IEEE C62.11, rated 9 kV, fully shielded, dead-front, elbow type suitable for plugging into bushing well inserts. Provide three arresters for loop feed circuits. e. Parking stands: Provide three (3) insulated standoff bushings for parking of energized load-break connectors on parking stands. 2.3.1.2 Low Voltage 2.3.3 a. Low-voltage compartment shall contain low-voltage bushings with NEMA spade terminals, accessories, stainless steel diagrammatic transformer nameplate, and ground pad. b. Accessories shall include drain valve with sampler device, fill plug, pressure relief device, liquid level gage, pressure-vacuum gage, and dial type thermometer with maximum temperature indicator. Transformer a. Liquid-insulated, two winding, 60 hertz, 65 degrees C rise above a 30 degrees C average ambient, self-cooled type. b. Insulating Liquid: Less flammable, edible-seed-oil based, and UL classified as complying with NFPA 70 requirements for fire point of not less than 300 deg C when tested according to ASTM D 92. Liquid shall be biodegradable and nontoxic. Insulating liquid shall be Cooper Power Systems Envirotemp FR3. SECTION 16331 PADMOUNT TRANSFORMER Page 5 of 6 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida c. Transformer shall be rated 500 kVA, 95 kV BIL. d. Transformer voltage ratings: 12,470 V Delta - 480Y/277 V. e. Tap changer shall be externally operated, manual type for changing tap setting when the transformer is de-energized. Provide four 2.5 percent full capacity taps, two above and two below rated primary voltage. f. Minimum tested impedance shall not be less than 4.5 percent. g. Audible sound levels shall comply with the following: kVA 500 2.3.4 Pre-Purchase January 2006 DECIBELS (MAX) 56 h. Transformer shall include lifting lugs and provisions for jacking under base. The transformer base construction shall be of the fabricated type and suitable for using rollers or skidding in any direction. Provide transformer top with an access handhole. The transformer shall have an insulated low-voltage neutral bushing with lugs for ground cable, and with removable ground strap. i. Provide dial-type thermometer, liquid-level gauge, pressure-vacuum gauge, and drain valve with built-in sampling device. Corrosion Protection Bases and cabinets of transformers shall be corrosion resistant and shall be fabricated of stainless steel conforming to ASTM A 167, Type 304 or 304L. Base shall include any part of padmounted transformer that is within 3 inches of concrete pad. Form cabinets of stainless steel sheets no less than No. 13 U.S. gage. Paint bases, cabinets, and tanks Munsell 7GY3.29/1.5 green. Paint coating system shall comply with ANSI C57.12.28 regardless of base, cabinet, and tank material. The Munsell color notation is specified in ASTM D 1535. PART 3 3.01 A. EXECUTION Delivery Deliver to Owner as specified in Invitation to Bid. END OF SECTION 16331 SECTION 16331 PADMOUNT TRANSFORMER Page 6 of 6 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida SECTION 16420 PART 1 Pre-Purchase January 2006 PANELBOARDS GENERAL 1.01 It is the intent of this specification to secure panelboards that have been factory built, production tested, of the latest commercial design, together with all accessories necessary for a complete installation as described in these specifications herein. The equipment supplied and installed shall meet the requirements of the National Electric Code and all applicable local codes and regulations. All equipment shall be new, of current production by a U. S. firm which manufactures the equipment and assembles the unit so that there is one-source responsibility for warranty, and parts through a local representative with factory-trained service personnel. 1.02 UWF Building 36 Mechanical and Electrical Renovation Electrical Pre-Purchase Items Drawing PP-E1 and PP-E2 shall apply to equipment of this Section. 1.03 A. SUBMITTALS Submit the producer's standard descriptive data sheets for each type of product being provided. Mark the data sheet for the product being provided with an identifying mark or arrow. Any deviation from the submittal requirements may be justification for total rejection. Submit the following: B. A detailed layout and description of each panelboard. C. A statement that the Division 16 contractor has coordinated the circuit breaker requirements with the other divisions supplying equipment. Any change shall be noted. This statement shall also indicate that the wire and conduit sizes have been adjusted accordingly. D. Descriptive manufacturer’s information on all TVSS equipment being supplied installed within the panelboard. PART 2 PRODUCTS 2.01 A. ACCEPTABLE PRODUCERS Cutler-Hammer, General Electric Co., and Square D. Products shall be furnished by one producer. 2.02 A. GENERAL UL 67 and UL 50. Panelboards shall be circuit breaker type. See panel schedules on Drawings for electrical characteristics. All panelboards shall be rated for the intended voltage and shall incorporate switching and protective devices of the number, rating, and type noted on the drawing or specified herein. Where panelboards are to bused as service entrance equipment, they shall be so labeled. Panelboards shall be listed and labeled by Underwriters' Laboratories, Inc. in accordance with UL Standard 67, and shall comply with the requirements of the National Electrical Code and NEMA. Panelboards for use as service disconnecting means shall additionally conform to UL 869. The design shall be such that individual breakers can be removed without disturbing adjacent units or without loosening or removing supplemental insulation supplied as means of obtaining clearances as required by UL. Where "space" is indicated, make provisions for future installation of breaker sized as indicated. Panelboard locks shall be keyed same. Directories shall indicate load served by each circuit of panelboard. Directories shall also indicate source of service (upstream panel, etc.) to panelboard. Type directories and mount in metal holder behind transparent protector covering. 2.03 A. BUS ASSEMBLY AND TEMPERATURE RISE Panelboard bus structure and main lugs or main breaker shall have current ratings as shown on the panelboard schedule. Bus bars shall be sized in accordance with UL standards to limit SECTION 16420 PANELBOARDS Page 1 of 3 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida Pre-Purchase January 2006 temperature rise on any current carrying part to a maximum of 65 degrees C above an ambient of 40 degrees C maximum. Bus bars shall be rigidly supported to prevent damage when subjected to stress, vibration, or short circuit current. Ratings shall be established by heat rise tests in accordance with Underwriters Laboratories Standard UL 67. Provide copper bus assembly and copper only lugs for copper conductors. Bus bars shall be copper. 2.04 A. CIRCUIT BREAKERS Circuit breakers shall be molded case with thermal magnetic or solid state trip units of size, type, and quantity shown on the drawings. The circuit breakers shall be bolt-on type, equipped with individually insulated, braced, and protected connectors. The front faces of all circuit breakers shall be flush with each other. Large permanent, individual circuit numbers shall be affixed to each breaker in a uniform position. Paper stickers are not acceptable for individual circuit numbers. Individual circuit numbers shall be phenolic. Trip indication shall be clearly shown by the breaker handle. Provisions for additional breakers shall be such that no additional connectors will be required to add circuit breakers. Breaker terminals shall be UL listed as suitable for type and size of conductor provided for. 2.05 A. MULTIPOLE BREAKERS Provide common trip-type with single operating handle. Breaker design shall be such that overload in one pole automatically causes all poles to open. Maintain phase sequence throughout each panel so that any three adjacent breaker poles are connected to Phases A, B, and C, respectively. 2.06 A. INTEGRATED EQUIPMENT SHORT CIRCUIT RATING Each panelboard, as a complete unit, shall have a UL short circuit current label equal to or greater than the equipment rating shown on the panelboard schedule on the Drawings. Method of testing shall be per Underwriters Laboratories Standard UL 67. Panelboards shall be marked with their maximum short-circuit current rating at the supply voltage and shall be UL listed. Panelboards rated 240 volts or less shall have short circuit current ratings not less than 10,000 amperes RMS symmetrical or as shown on the Drawings. Panelboards rated 480 volts of less shall have short circuit current ratings not less than 14,000 amperes RMS symmetrical or as shown on the Drawings. 2.07 A. GROUNDING TERMINALS Provide ground bus with lugs for equipment ground wires in each panelboard identified as equipment grounding bus per UL 67 for connecting grounding conductors; bond to steel cabinet. Ampacity shall be at least 50% capacity of the main bus. Ground bar or lugs shall be copper. 2.08 A. NEUTRAL TERMINALS Provide isolated neutral bus terminal in each panelboard for connection of circuit neutral conductors. Ampacity of neutral bar shall be the same as the full capacity of the main bus bars. Neutral bushing shall give a suitable lug for each outgoing feeder requiring a neutral connection. Neutral bar shall be copper. 2.09 A. CABINET Panelboard assembly shall be enclosed in a galvanized steel cabinet. Multi-section panelboards shall have same size enclosures. The rigidity and gauge of steel shall be as specified in UL Standard 50 for cabinets. The size of wiring gutters shall be in accordance with UL Standard 67. Cabinets shall be equipped with latch and tumbler lock on door. Doors over 48" high shall be equipped with three point latch and vault lock. All locks shall be keyed alike. Minimum depth of cabinets shall be 5-3/4" and minimum width shall be 20". Cabinet shall not have ventilating openings. All cabinets shall have door-in-door construction. 2.10 A. SAFETY BARRIERS The panelboard interior assembly shall be dead front with panelboard front removed. Main lugs SECTION 16420 PANELBOARDS Page 2 of 3 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida Pre-Purchase January 2006 or main breakers shall be barriered. 2.11 A. UL LISTING Panelboards shall be listed by Underwriters Laboratories and shall bear the UL label. When indicated, panelboards shall be suitable for use as service equipment. 2.12 A. NAMEPLATES Provide an engraved laminated phenolic or micarta nameplate 1" high by 3" wide with minimum 1/4" letters indicating the panelboard identification. The panelboard shall also have a nameplate affixed to the panelboard with the following information stamped therein: Manufacturer, Voltage, Ampacity, Type of Panelboard, Manufacturer's Order No. and Date, Interrupting Rating - RMS Sym. 2.13 A. GROUND FAULT PROTECTION Provide ground fault protection as indicated on the Drawings. Ground fault protection provisions shall comply with NEC Article 230-95 and UL 943. Provide with "push-to-test" button, visible indication of tripped condition, and ability to detect and trip on current imbalance of 6 milliamperes or greater per requirements of UL 943 for Class A GFCI devices. 2.14 A. PANELBOARD DIRECTORY The directory shall be protected by a transparent protective covering inside of a metal frame attached to the inside the panelboard door. An adhesive plastic sleeve is not acceptable. 2.15 A. TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) Provide in panelboards as indicated otherwise on the drawings. The TVSS shall be bus mounted and be a UL assembly with the panelboard. See TVSS specification for additional requirements. PART 3 EXECUTION 3.01 A. Delivery Deliver to Owner as specified in Invitation to Bid. END OF SECTION 16420 SECTION 16420 PANELBOARDS Page 3 of 3 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida SECTION 16620 PART 1 Pre-Purchase January 2006 TRANSIENT VOLTAGE SURGE SUPPRESSION GENERAL 1.01 It is the intent of this specification to secure transient voltage surge suppression equipment that has been prototype tested, factory built, production tested, of the latest commercial design, together with all accessories necessary for a complete installation as described in these specifications herein. The equipment supplied and installed shall meet the requirements of the National Electric Code and all applicable local codes and regulations. All equipment shall be new, of current production by a U. S. firm which manufactures the equipment and assembles the unit so that there is one-source responsibility for warranty, parts, and service through a local representative with factory-trained service personnel. 1.02 UWF Building 36 Mechanical and Electrical Renovation Electrical Pre-Purchase Items Drawing PP-E1 shall apply to equipment of this Section. 1.03 A. SUMMARY These specifications describe the electrical and mechanical requirements for an electrical transient surge suppression filter systems integrating both transient voltage surge suppression (TVSS) and electrical high frequency noise filtering for a variety of exposure locations as defined in ANSI/IEEE C62.41-1991. B. The unit shall be designed for parallel connection to the facility's wiring system. The suppression filter system shall be designed and manufactured in the USA by a qualified manufacturer of suppression filter system equipment. The qualified manufacturer shall have been engaged in the commercial design and manufacture of such products for a minimum of five (5) years. C. These specifications are based on Current Technology's SF suppression filter systems. Other manufacturers shall provide detailed compliance or exception statements to all provisions of this specification fourteen (14) days prior to bid. 1.04 A. STANDARDS The specified unit shall be designed, manufactured, tested and installed in compliance with the following standards: ANSI/IEEE C62.41-1991 and C62.45-1992; ANSI/IEEE C62.1 and C62.11; Canadian Standards; (CUL); Federal Information Processing Standards Publication 94 (FIPS PUB 94); National Electrical Manufacturers Association (NEMA LS1-1992 Guidelines); National Fire Protection Association (NFPA 70 [NEC], 75, and 78); Underwriters Laboratories (UL 1449 and 1283); Underwriters Laboratories (UL 489 and UL 198). MIL Standard (220A Filter Attenuation). B. 1.05 A. The unit shall be UL 1449 Listed and CUL Approved as a Transient Voltage Surge Suppressor and UL 1283 Listed as an Electromagnetic Interference Filter. ENVIRONMENTAL REQUIREMENTS Storage Temperature. Storage temperature range: -40° to +85° C (-40° to +185° F). B. Operating Temperature. Operating temperature range: -40° to +60° C (-40° to +140° F). C. Relative Humidity. Reliable operation with 5% to 95% non-condensing relative humidity. SECTION 16620 TRANSIENT VOLTAGE SURGE SUPPRESSION Page 1 of 8 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida Pre-Purchase January 2006 D. Operating Altitude. Capable operation up to 13,000 feet above sea level. E. Audible Noise. The unit shall not generate any audible noise. F. Magnetic Fields. No appreciable magnetic fields shall be generated. Unit shall be capable of use in computer rooms without danger to data storage systems or devices. 1.06 A. DESCRIPTION This section describes the materials and installation requirements for high energy transient voltage surge suppressors (abbreviated as TVSS throughout) for the protection of all AC electrical circuits from the effects of lightning induced currents, substation switching transients and internally generated transients resulting from inductive and/or capacitive load switching. The specified system shall provide effective high energy surge current diversion and be suitable for application in ANSI/IEEE C62.41 Category A, B, and C3 environments, as tested by ANSI/IEEE C62.11, C62.45. 1.07 A. SUBMITTALS Submit shop drawings, product data and manufacturer's installation instructions for each type of product being provided. Mark the data sheet for the product being provided with an identifying mark or arrow. The surge suppression submittals shall also include: 1. Electrical and mechanical drawings shall be provided by the manufacturer that shows unit dimensions, weights, component and connection locations, mounting provisions, connection details, and wiring diagram. 2. Category C3 (20KV, 10KA) test results. 3. UL 1449 clamp voltage documentation. 4. IEEE Cat. B3 Ringwave (6kV, 500A @ 100 kHz) 5. Certified Life Expectancy Testing 6. Any required documentation in section 2.0 - Products 7. Required documentation in Section 1.9 - Safety-Overcurrent Protection (Fusing). 8. Provide evaluation forms provided herein filled out with manufacturer's data. Failure to provide forms shall be the basis for rejection of the submittal. 9. The manufacturer shall furnish an installation manual with installation, start-up, spare parts lists, and operating instructions for the specified system. 10. Provide test report(s) from a nationally recognized independent testing laboratory verifying that the suppressor(s) can survive the published surge current rating on a per mode and per phase basis. The test wave shall be the IEEE C62.41, 8x20 microsecond current wave. Note that test data on individual modules are not acceptable. 1.08 A. PRIOR APPROVAL REQUIRED Manufacturer’s shall submit for a 10-day prior approval, a completed TVSS manufacturer’s evaluation questionnaire (provide herein) and provide detailed compliance or exception statements to all provisions of this specification to allow consideration. 1.09 A. ELECTRICAL REQUIREMENTS: Nominal System Operating Voltage shall be either: 480 VAC, wye, three phase, four wire plus SECTION 16620 TRANSIENT VOLTAGE SURGE SUPPRESSION Page 2 of 8 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida Pre-Purchase January 2006 ground or 208 VAC wye, three phase, four wire plus ground as indicated on the Drawings. B. Maximum Continuous Operating Voltage (MCOV): The TVSS and all components in the suppression path (including all MOVs SADs, and selenium cells) maximum continuous operating voltage shall be greater than 115% of the nominal system operating voltage to ensure the ability of the system to withstand temporary RMS overvoltage (swell conditions). C. Operating Frequency: The operating frequency of the system shall be at least 47-63 Hertz. 1.10 A. SAFETY - OVERCURRENT PROTECTION (FUSING) The manufacturer shall supply test data from a nationally recognized laboratory insuring that when the TVSS suppression component(s) is installed commensurate with the installation location for this project, it shall be proven to fail without protected load interruption, in a safe non-violent manner (no smoke, fire, flame, case or module distortion, emission of molten particles or other physical damage). Failure is defined and inclusive of bolted short and high impedance (ground faulted) conditions within the suppressor. If Overcurrent Protection Devices (OPD) are utilized to obtain a fail-safe condition, then a certified test from a nationally recognized testing laboratory shall be submitted to indicate that: The OPD and suppression component(s) I2T capacity is capable of conducting the specified transient current one-time and ten-times without operation. The OPD shall be capable of clearing both high and low impedance fault conditions (in all specified suppression modes) while protecting the TVSS against violent failure as defined above. OPD(s) supplied shall be monitored and provide internal and remote indication of suppression failure/operability. KAIC ratings of commercially available OPD(s) alone or UL 1449 products listing shall not constitute validity without the nationally recognized laboratory test as outlined above. Submittal documentation of compliance shall be provided for approval. 1.11 A. PROTECTION MODES The TVSS shall provide protection as follows: All modes, L-N or L-L (where system does not contain a neutral), L-G, and N-G (where applicable). Note: L=Line, G=Ground, N=Neutral. 1.12 A. UL 1449 RATINGS The maximum UL 1449 listed surge ratings for each and/or all of the specified protection modes shall not exceed the following in any mode of protection: System Voltage 120/208V 208, 277, 277/480 V Without Disconnect 400 V 800 V With Disconnect 500 V 1000 V 1.13 A. NOISE ATTENUATION The unit shall be UL 1283 Listed as an electromagnetic interference filter. The filter shall provide insertion loss with a minimum of 50 dB at 100 kHz per IEEE Cat. B3 Ringwave (6kV, 500A @ 100 kHz). The system shall provide up to 120-dB insertion loss at 100 kHz when used in a coordinated facility system. 1.14 A. QUALITY ASSURANCE The specified system shall be tested at the component and fully assembled level, under surge conditions with AC power applied for a minimum of 1 hour. Testing shall include but not limited to quality control checks, dielectric voltage withstand test per UL and CSA requirements, UL ground continuity test, and operational and calibration test. 1.15 A. WARRANTY The manufacturer shall provide a full five year parts warranty from date of final acceptance of the Owner against any part failure when installed in compliance with manufacturer’s written instructions, UL Listing requirements, and any applicable national, state or local electrical code. The contractor shall be responsible to honor the five-year warranty for parts and labor. SECTION 16620 TRANSIENT VOLTAGE SURGE SUPPRESSION Page 3 of 8 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida PART 2 2.01 A. Pre-Purchase January 2006 PRODUCTS: Approved manufactures, Liebert, Current Technology, Cutler-Hammer/Tycor or approved equal. SERVICE ENTRANCE Suppressors shall be listed in accordance with UL 1449, Standard for Safety, Transient Voltage Surge Suppressors. B. LIFE CYCLE TESTING: The TVSS system shall be duty life cycle tested to survive a minimum of 2,500 surges per phase of 20kV, 10 kA, IEEE C62.41 Category C3 surge current with less than 5% degradation of clamping voltage. C. For 3 phase, 4 wire configurations, suppressors shall provide suppression elements between each phase conductor and the system neutral, each phase conductor and system ground, and between neutral conductor and ground. D. UNIT STATUS INDICATORS: Solid state indicators with printed labels shall be provided on the hinged front cover to redundantly indicate on-line status. Real time monitoring of all suppression components that include all MOVs, Fuses, and Thermal Runaway of MOVs. A problem with any of these features shall trigger a fault indicator light, form C contacts and audible alarm. An alarm silence switch shall be provided with the suppressor. E. Suppressors shall meet or exceed the following criteria: 1. Minimum surge current capacity, per NEMA LS-1 1992 shall be: 100,000 amperes per mode, 200,000 amperes per phase (L-N + L-G). 2. Pulse life ratings: ANSI/IEEE Cat. C3 (8/20sec. waveform): 2500 occurrences without failing or degrading the UL 1449 surge suppression rating more than 10%. 3. UL 1449 RATINGS: The maximum UL 1449 listed surge ratings for each and/or all the specified protection modes shall not exceed the following in any mode of protection: 120/208V - 400 V, 277/480V - 800 V. F. Suppressors shall be of the solid-state componetry and shall operate bidirectionally. G. Suppressors shall be as manufactured by Current Technology, Liebert, EFI, and CutlerHammer/Tycor. H. The suppressor will have a warranty guarantee for a period of five years, incorporating a free replacement if the suppressor is destroyed by lightning within the warranty period including all parts and labor. I. Connection of surge suppression equipment shall be bus mounted to the service entrance equipment. Provide internal overcurrent protection. The overcurrent protection shall be fuses. Provide disconnect. In lieu of disconnect/fuses, a circuit breaker may be supplied for overcurrent protection. J. When supplied internal to the service entrance equipment, it shall be UL listed as an assembly with the service entrance equipment. 2.02 A. B. SURGE SUPPRESSION FOR DISTRIBUTION PANELS GENERAL SUMMARY. These specifications describe the electrical and mechanical requirements for a hybrid high-energy 50,000 amp (per mode, 100,000 amps for multiple modes) class SECTION 16620 TRANSIENT VOLTAGE SURGE SUPPRESSION Page 4 of 8 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida Pre-Purchase January 2006 suppression filter system that integrates transient voltage surge suppression (TVSS) with highfrequency electrical line noise filtering for medium to low exposure applications. The unit shall be connected in parallel with the facility's wiring system per electrical drawings. The unit shall be manufactured in the USA by a qualified manufacturer of suppression filter system equipment who has been engaged in the commercial design and manufacture of such products for a minimum of five (5) years. C. STANDARDS. The specified unit shall be designed, manufactured, tested, and installed in compliance with the following standards: American National Standards Institute and Institute of Electrical and Electronic Engineers (ANSI/IEEE) C62.41-1991 and C62.45-1987); Canadian Standards Association (CSA); Federal Information Processing Standards Publication 94 (FIPS PUB 94); National Electrical Manufacturers Association (NEMA); National Fire Protection Association (NFPA 70 [NEC], 75, and 78); Underwriters Laboratories (UL 1449 and 1283). MIL Standard (220A Filter Attenuation). D. PRODUCT REQUIREMENTS. E. UNIT OPERATING VOLTAGE. The nominal unit operating voltage and configuration shall be as indicated on the drawings. F. MAXIMUM CONTINUOUS OPERATING VOLTAGE (MCOV). The maximum continuous operating voltage (MCOV) of all suppression components utilized in the unit shall not be less than 115% of the facility's nominal operating voltage. G. TESTED SINGLE-PULSE SURGE CURRENT CAPACITY. Based on ANSI/IEEE C62.411991's standard 8 x 20 microsecond current waveform, and in accordance with NEMA Publication No. LS 1-1992, the tested single-pulse surge current capacity, in amps, of the unit shall be no less than as follows: Protection Mode Tested Single Pulse Surge Current L-L L-N L-G N-G 50,000 50,000 50,000 50,000 H. UNIT STATUS INDICATORS. The unit shall include solid-state, long-life, externally mounted LED visual status indicators that monitor the on-line status of each phase of the unit. I. UL 1449 PERFORMANCE RATINGS. The unit's published performance ratings shall be the UL 1449 Listed suppression ratings. The UL 1449 suppression rating shall be, for each mode of protection, as follows: Nominal System Voltage L-N L-G N-G 120/208 277/480 400 800 400 800 400 800 J. LIFE CYCLE TESTING: The TVSS system shall be duty life cycle tested to survive a minimum of 2,500 surges per phase of 20kV, 10 kA, IEEE C62.41 Category C3 surge current with less than 5% degradation of clamping voltage. K. INTERNAL IMPEDANCE. The unit shall provide a path of extremely low impedance and shall not utilize printed circuit boards, quick type disconnects or small gauge wire in the surge current SECTION 16620 TRANSIENT VOLTAGE SURGE SUPPRESSION Page 5 of 8 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida Pre-Purchase January 2006 diversion path. All internal paths shall be low impedance # 8 AWG Copper conductor or Copper or Aluminum bus bar. L. NOISE ATTENUATION: The unit shall be UL 1283 Listed as an electromagnetic interference filter. The filter shall provide insertion loss with a minimum of 50 dB at 100 kHz per IEEE Cat. B3 Ringwave (6kV, 500A @ 100 kHz). The system shall provide up to 120-dB insertion loss at 100 kHz when used in a coordinated facility system. M. FIELD CONNECTIONS. Unless indicated otherwise, provide unit mounted to the panelboard bus. The unit shall be UL listed as an assembly. Where indicated on the Drawings to be remote mounted, the unit shall include mechanical lugs for each phase, neutral and ground, if applicable. The lugs shall accommodate up to # 6 AWG copper conductor. N. ENCLOSURE. Units shall be provided in a NEMA 1 type enclosure of 14 gauge steel. O. Suppressors shall be as manufactured by Current Technology, Liebert, EFI, and CutlerHammer/Tycor. P. The suppressor will have a warranty guarantee for a period of five years, incorporating a free replacement if the suppressor is destroyed by lightning within the warranty period including all parts and labor. PART 3 3.01 A. EXECUTION SERVICE ENTRANCE Install one primary suppressor at each utility service entrance to the facility, according to manufacturer's recommendations. B. Suppressor shall be installed on the service panel, per the manufacturer's installation instructions. When bus mounted, provide disconnect switch. C. Conductors between suppressor and point of attachment to the panelboard shall be kept as short and straight as possible when the suppressor is installed remote from the panelboard. The TVSS shall be close-coupled to the panelboard. The conductors shall not exceed 24”. D. Suppressor's ground shall be bonded to the service entrance ground. E. The contractor shall twist the TVSS input conductors together to reduce input conductor inductance. F. The contractor shall follow the TVSS manufacturer’s recommended installation practices as found in the installation, operation and maintenance manual and comply with all applicable codes. 3.02 A. DISTRIBUTION PANELS Install one secondary suppressor at each panelboard location indicated on the Drawings. Verify proper voltage of panel/suppressor prior to installation. B. Conductors between suppressor and point of attachment to the panelboard shall be kept as short and straight as possible. Provide a 60/3 circuit breaker in panelboard being protected for connection to suppressor. 3.03 A. WIRING REQUIREMENTS Where the TVSS is provided with terminals, provide #6 AWG conductors for the phase, neutral and ground connections. If the TVSS is provided with its own leads of #10 AWG, reduce the panelboard circuit breaker to 30 amperes and make final connection. SECTION 16620 TRANSIENT VOLTAGE SURGE SUPPRESSION Page 6 of 8 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida Pre-Purchase January 2006 SURGE SUPPRESSOR - SERVICE ENTRANCE Specification Section Requirements 2.1.1 UL 1449 listed 2.1.2 ANSI C62.41-1991 C3 test results: 2.1.3 UL Listed Suppression modes: L-N, LG, N-G 2.1.4 Diagnostics (Type) 2.1.5.a 200,000 surge current rating (L-N + LG)/phase 2.1.5.b Pulse Life Testing - 2500 Surges 2.1.5.c UL 1449 Clamping Voltage per mode 2.1.6 Solid State and Bidirectional 2.1.7 Manufacturer and Model Number 2.1.8 5 year Warranty Performance of Product being Submitted SECTION 16620 TRANSIENT VOLTAGE SURGE SUPPRESSION Page 7 of 8 UWF Building 36 Mechanical and Electrical Renovations Pensacola, Florida Pre-Purchase January 2006 SURGE SUPPRESSOR - DISTRIBUTION PANELBOARDS Specification Section Requirements 2.2.2 Filtering and Sine Wave Tracking 2.2.3 Built and tested to Standards: ANSI, IEEE, CSA, FIPS 94, NEMA, NFPA, UL 2.2.4 No Requirements 2.2.5 Applied Voltage Limit 2.2.6 MCOV greater than 115% 2.2.7 50,000 Amp Surge Current L-N, L-G, N-G 2.2.8 Diagnostics (Type) 2.2.9 UL 1449 Clamping Voltage per mode 2.2.10 2500 Category C Surges 2.2.11 No Requirements 2.2.12 EMI/RFI up to 50 dB @ 100Mhz 2.2.13 Lugs to accommodate up to #6 Copper Conductors 2.2.14 NEMA 1 enclosure Surface or Flush Mountable 2.2.15 Manufacturer and Model Number 2.2.16 5 year Warranty Performance of Product being Submitted END OF SECTION 16620 SECTION 16620 TRANSIENT VOLTAGE SURGE SUPPRESSION Page 8 of 8