Installation Instructions for: Briteblade This luminaire complies with BS EN 60598-2-22 and is suitable for normal interior locations including defined escape routes. Normal ambient temperature 0°C to +25°C. Caution DO NOT MEGGA after installation. In accordance with IEE regulation 613-7 and ECA/LIF recommendations, disconnect live and neutral wires from the luminaire to check insulation resistance. Installation 1. Cut an aperture 342 mm x 103 mm in the ceiling. A template, part no.BBT, is available, sold separately. 2. Remove the front bezel and secure the luminaire in the ceiling aperture by winding down all the integral side arms. If installing adjacent to a wall ensure the LED charge indicator is on the room side of the luminaire. 3. Connect an unswitched mains supply to terminals Lch and N. If a switched facility is required for maintained operation connect an additional switched mains supply to terminal Lsw, if the lamp is to be continuously alight terminal Lsw may be linked to terminal Lch. 4. If a test facility is required it should be connected as shown. If the test switch is manually operated it must be self-resetting or key operated. 5. Fit the legend panel (sold separately) into the front bezel and retain with the split pins supplied with the luminaire, splay the split pin ends to secure. 6. Close the gear cover. 7. Re-fit lamp. When fitting the 3W LED lamp ensure that the green label is the same end as LED charge indicator and when installed the green label is facing downwards. 8. Align the charge indicator in the housing with the hole in the bezel and fit the bezel/legend assembly to the luminaire using the wishbone springs fitted. Under no circumstances cover this luminaire with insulating matting or similar material. L Mains lighting fuse To mains lighting N Battery Replacement Performance of the luminaire is dependent on the use of the correct type of high temperature nickel-cadmium battery. Battery life may be impaired if the luminaire is mounted in an ambient temperature greater than 25°C. Store the luminaire or battery between 0°C and 25°C. Replace with high temperature nickel-cadmium battery to the manufacturer's recommended part number. Connect the red lead to positive (+), the black lead to negative (-). Take care not to damage the sleeving. The battery should be replaced when the rated duration is no longer achieved. Warning: When disposing of the battery do not pierce, incinerate or short circuit. The battery contains cadmium and should therefore be disposed of in accordance with recognized disposal methods. Additional Notes On Installation For Electromagnetic Compatibility The intended use of this product is to supply rated illumination for its specified duration in the event of a failure of the mains supply. During normal mains healthy conditions its batteries are charged and in the case of maintained units the lamp may be operated from the 'Lsw’ mains supply. When used as intended this product complies with EMC Directive (89/336/EEC) and the UK EMC regulations 1992 (SI 2372/1992) by meeting the limits set by the standards BS5406:1988 Parts 2 & 3, EN61547:1996 and EN55015:1992. The following installation guidelines must be followed: 1: External cables must be connected using the cable entries or knockouts provided. 2: When routing external cables inside the product they must be: a) kept as short as possible. b) routed close to the housing. c) kept as far as possible from the electronics. Any modifications other than those in the main installation leaflet, or any other use of the product may cause interference and is the responsibility of the user, who should ensure compliance with the EMC and Low Voltage Directives. Safe Installation and Operation Fluorescent emergency luminaire Use solid wires only Tamper-proof test switch To additional emergency luminaires Lch Lsw ONLY USED ON ( MAINTAINED UNITS ( N Lsw Maintained lighting control switch Testing: 1. Check the rating label for voltage and frequency before connecting to the electrical supply. 2. Ensure the mains supply is switched off and the battery disconnected when working on this luminaire, whether installing, re-lamping or carrying out any other servicing. 3. Use only the correct lamp and battery as indicated on the luminaire label. 4. Ensure the fixing is adequate for the luminaire weight. Servicing This luminaire must be Earthed 1. The luminaire must be connected to an unswitched live supply fed by the normal lighting sub-circuit in that location. 2. Check the green LED indicator illuminates to indicate the battery is charging. 3. Maintained luminaires only - check the lamp illuminates when the switched supply is turned on. 4. Briefly interrupt the unswitched supply when the lamp must illuminate at reduced brightness and the LED indicator extinguish. Date of Commissioning Date to be entered in the space provided on the battery label by either the installer or commissioning engineer. Rated lumen output Rated minimum luminaire output in emergency mode in accordance with EN 60598-2-22: 1 lumen. This value is provided to permit checking of correct operation, determination of the lighting level on an escape route can only be made with full photometric data. 1. Ensure this instruction leaflet and recommendations for periodic inspection and test are presented to the authority responsible for the operation and maintenance of this luminaire. 2. Servicing, e.g. cleaning and lamp replacement, must only be carried out after the electricity supply has been switched off. Do not assume a luminaire with no lamps alight is switched off, always check before servicing. Do not touch the lamp pins or any terminals without first disconnecting the battery. 3. Cleaning should be carried out at regular intervals to ensure dirt does not accumulate to an extent that will impair the thermal safety of the luminaire. Regular cleaning will help to maintain the optical performance of the luminaire. 4. Failed lamps, starter switches and batteries must be replaced as soon as practicable by components of the same type. Replace the battery when the luminaire fails to achieve the rated duration marked on the luminaire. Cooper Lighting and Safety Ltd Wheatley Hall Road, Doncaster, South Yorkshire, DN2 4NB Sales General T: +44 (0)1302 303303 +44 (0)1302 321541 F: +44 (0)1302 367155 +44 (0)1302 303220 E: sales@cooper-ls.com technical@cooper-ls.com K745V2 Major Projects London International Sales +44 (0)1992 787999 +44(0)1992 787222 london@cooper-ls.com +44 (0)1302 303250 +44 (0)1302 303251 export@cooper-ls.com Lighting EMERGENCY LUMINAIRE TEST RECORD All emergency lighting installations should be regularly tested and a record kept of the results. Tests carried out to the schedule listed below conform to the requirements of BS EN50172 and BS5266 Part 8 Emergency escape lighting systems. Tests should be conducted at times of minimum risk and buildings not re-occupied until the battery has recharged. Where a large number of emergency luminaires are involved do not test all the luminaires at the same time. Daily Check the charge indicator is illuminated. Monthly Simulate a mains supply failure and check the emergency lamp illuminates. The period of simulated mains failure should be sufficient to check the operation of the luminaire but should not exceed one quarter of the rated duration. When the mains supply is restored check the charge indicator is illuminated Annual Simulate a mains supply failure and check the emergency lamp is illuminated for the rated duration. When the mains supply is restored check the charge indicator isilluminated. Luminaire location Installation Engineer: Ref. No. Telephone No. Luminaire Cat. No. INSTALLATION ENGINEER’S TEST REPORT Charge Indicator: Luminaire type Rated duration Hrs Year 1 Test Signed Date: Signed: Year 2 Date Charge/discharge test: Signed Year 3 Date Signed Year 4 Date Signed Year 5 Date Signed Date Month 1 Month 2 Month 3 Month 4 Month 5 Month 6 Month 7 Month 8 Month 9 Month 10 Month 11 Annual Year 6 Test Month 1 Month 2 Month 3 Month 4 Month 5 Month 6 Month 7 Month 8 Month 9 Month 10 Month 11 Annual Signed Year 7 Date Signed Year 8 Date Signed Year 9 Date Signed Year 10 Date Signed Date