E CO SM A RT B OX E R A HU STANDARD CONFIGURATIONS
COMPLETE PACKAGED AIR HANDLING UNITS WITH ALL THE
NECESSARY CONTROLS.
98
029 2085 8200
Nuaire AHU_Layout 1 12/08/2011 10:29 Page 99
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMART B OXER
TEC H NI C A L I NF O R MATI O N
B E NE F I T S
VERY QUIET
PART L AND ENERGY EFFICIENT
COIL OPTIONS
25mm double skinned panels provide better
acoustic and thermal properties over conventional
AHU’s.
Fan impellers are selected for optimum efficiency
and noise characteristics. Motors are IE2 to BS 5000
direct drive and high efficiency belt drive.
DX & chilled water coils are available, call Nuaire
for further details.
Note: Undressed coils are also available.
REDUCE INSTALLATION TIME
IMPROVED LIFE CYCLE/NO SYSTEM
OVERLOADS
WARRANTY
All components are pre-assembled, wired and
tested at the Nuaire manufacturing facility. Units
are delivered conveniently in sections for easy site
assembly.
Ecosmart Boxer has a 5 year warranty.
Ecosmart is pre-programmed to automatically give
a soft start function which prevents electrical
overloading and minimises mechanical wear.
SIMPLE PRECISE COMMISSIONING
LONG LASTING
Minimum and maximum ventilation rates precisely
set and limited at AHU requiring no throttling
dampers.
Each section is manufactured from a highly rigid
pentapost framework with heavy gauge AluzincY,
corrosion resistant steel panels.
ENERGY EFFICIENT
CONSTANT PRESSURE CONTROL
AVAILABLE
All models have Ecosmart controls built in, which
provide the most energy efficient and cost effective
solution.
For further information contact Nuaire.
ANCILLARIES & COMPONENT OPTIONS:
Weather terminals.
Silencers.
Dampers.
Vertical and horizontal heat exchangers.
Base frames.
DX Coils.
Monometrer.
Filter sizes 1 & 2 = G4 panel,
sizes 3 - 7 = G4 bag or G4 bag & F7 bag.
nuaire.co.uk
99
Nuaire AHU_Layout 1 12/08/2011 10:29 Page 100
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMA RT B OXER
TEC H NI C A L I NF O R MATI O N
PERFORMANCE - ECOSMART BOXER SIZES 1 and 2
Casing
Ecosmart Boxer supply unit filter and heating coil
600
Tested in duct
500
ISO 5801 2007
Fan Static Pressure (Pa)
V
400
1H
2H
300
200
2
1
Ecosmart Boxer sizes 1 and 2.
100
0
0
0.5
1.0
1.5
Air volume flow rate (m3/s)
ESBH S - 2 - LC
|
| | |
Ecosmart Boxer supply Unit filter and heating and cooling coil
1
600
Tested in duct
V
Fan Static Pressure (Pa)
500
ISO 5801 2007
400
1H
2H
300
200
2
1
100
0
0
0.5
1.0
1.5
Air volume flow rate (m3/s)
Ecosmart Boxer fan unit only
600
V
Fan Static Pressure (Pa)
ISO 5801 2007
400
1H
2H
300
200
2
1
100
0
0
0.5
1.0
Air volume flow rate (m /s)
3
100
029 2085 8200
2
3
4
1. Ecosmart Boxer range
2. S = Supply
EX = Extract
3. Size 1 - 2
4. L = Low Pressure hot water heater battery
LC = Low Pressure hot water heater
battery and CHCW chilled water
cooling coil
LD = Low Pressure hot water heater
battery and DX cooling coil
ED = Electric heater battery and
DX = Direct expansion (refrigerant type
coil)
Note: If no Ecosmart control is required
example code would be: BHS2NC-LC.
If fan control only is required (undressed
coils) example code would be:
BHS2FC-LC.
Tested in duct
500
Code descriptions
1.5
AIR HANDLING UNITS (AHU’S)
ECOSMART BOXER
TECHNIC AL INFORMATION
PERFORMANCE - ECOSMART BOXER SIZES 1 and 2
ELECTRIC AL & SOUND
Curve
Motor
Rating
(kW)
Electric
Coil Data
(kW)
Fan Input
Power
(watts)
Type
Ducted sound power levels dB re 1pW
Data
125
250
500
1K
2K
RPM
1
1.28
18
1110
1272
1H
1.13
18
1620
2
1.6
24
2H
1.6
24
4K
8K
I inlet
O outlet
73
77
67
75
57
77
59
78
59
78
54
73
45
67
25
1480
I inlet
O outlet
72
77
66
74
62
75
58
76
58
76
52
72
42
64
24
1620
960
I inlet
O outlet
72
77
66
74
62
75
58
76
58
76
52
72
42
64
24
1600
1065
I inlet
O outlet
79
81
74
81
69
76
69
76
65
72
60
69
54
63
33
EXTRACT
Curve
Breakout
dBA@
3m
SUPPLY WITH ELECTRIC HEATER
Code
Phase
FLC
(amps)
SC
(amps)
Curve
Code
Phase
Total FLC
(amps)
Total SC
(amps)
1
ESBHEX1
1
4.84
4.84
1
ESBHS1-E
3
29.9
4.9
1H
ESBHEX1H
1
7.3
7.3
1H
ESBHS1H-E
3
32.2
7.22
2
ESBHEX2
1
6.4
6.4
2
ESBHS2-E
3
40.7
7.32
2H
ESBHEX2H
1
9.4
9.4
2H
ESBHS2H-E
3
42.8
9.4
SUPPLY WITH ELECTRIC HEATER & COOLING COIL
Curve
Code
Phase
FLC
(amps)
SUPPLY WITH ELECTRIC HEATER & DX COOLING COIL
SC
(amps)
Curve
Code
FLC
(amps)
Phase
SC
(amps)
1
ESBHS1-EC
3
29.5
4.8
1
ESBHS1-ED
3
29.5
4.84
1H
ESBHS1H-EC
3
32.2
7.2
1H
ESBHS1H-ED
3
32.2
7.22
2H
ESBHS2H-EC
3
42.4
9.0
2
ESBHS2-ED
3
40.7
7.32
2H
ESBHS2H-ED
3
42.8
9.4
SUPPLY WITH LPHW HEATER
Curve
Code
Phase
Flow valve setting
FLC
(amps)
SC
(amps)
1
ESBHS1-L
1
4.84
4.84
1H
ESBHS1H-L
1
7.2
7.2
2
ESBHS2-L
1
6.4
6.4
2H
ESBHS2H-L
1
9.0
9.0
SUPPLY WITH LPHW HEATER & DX COOLING COIL
Curve
Code
Phase
FLC
(amps)
SC
(amps)
1
ESBHS1-LD
1
0.0
0.0
1H
ESBHS1H-LD
1
5.2
5.2
2
ESBHS2-LD
1
0.0
0.0
2H
ESBHS2H-LD
1
9.4
9.4
SUPPLY WITH LPHW HEATER & COOLING COIL
Curve
Code
Phase
FLC
(amps)
SC
(amps)
1
ESBHS1-LC
3
4.84
4.84
1H
ESBHS1H-LC
3
5.2
5.2
2
ESBHS2-LC
3
6.4
6.4
2H
ESBHS2H-LC
3
9.0
9.0
Download specification from www.nuaire.co.uk/specifications
DX COIL DATA
Unit
Size
Max Air kW
Evap.
Flow
Rating temp
m3/s
R407C deg C
PD
Conn
through size
Coil KPa
1
0.4
8
5
10
2x12&16od
2
0.7
13.5
5
16
2x12&22od
Unit
Size
Frost
Coils In
Out
Cooling
Coils In
Out
Heating
Coils In
Out
1
0.75BSP
0.75BSP
1 BSP
1 BSP
1.25BSP
1.25BSP
2
0.75BSP
0.75BSP
1.25BSP
1.25BSP
1.25BSP
1.25BSP
For wiring diagrams refer to pages 110.
nuaire.co.uk
101
Nuaire AHU_Layout 1 12/08/2011 10:29 Page 102
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMA RT B OXER
TEC H NI C A L I NF O R MATI O N
DIMENSIONS AND CONFIGURATIONS
Length
Ecosmart BOXER sizes 1 and 2
B
DI ME N S I ON S ( m m ) & W E I GH T S ( K G)
ESBHEX*
ESBHS*L/E
Size L
W
L
W
ESBHS* LC/LD, ED/EC
Heating & Cooling
L
W
B
C
1
700
84
1000
132
1600
170
954 530
400
342
2
1000
117
1130
185
1730
264
954 670
500
342
D dia D1
NB: Units are handed left hand side as standard. (L=Length, W=Weight).
Right hand side is available on request.
C
D dia
For component ‘Z’ factors please refer to page 109.
D1
Airflow
Airflow
Model shown: size 1 and 2 (right hand extract).
Model shown: size 1 and 2 (left hand extract).
Model shown: size 1 and 2 (right hand LPHW supply).
Model shown: size 1 and 2 (left hand LPHW supply).
Model shown: size 1 and 2 (right hand electric supply).
Model shown: size 1 and 2 (left hand electric supply).
102
029 2085 8200
Nuaire AHU_Layout 1 12/08/2011 10:29 Page 103
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMART B OXER
TEC H NI C A L I NF O R MATI O N
PERFORMANCE - ECOSMART BOXER SIZES 3 - 7
Casing
Ecosmart Boxer supply unit filter and heating coil
1200
Tested in duct
V
Fan Static Pressure (Pa)
1000
ISO 5801 2007
800
7
600
6
4
400
5
3
Ecosmart Boxer sizes 3 - 7
200
0
0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
Air volume flow rate (m3/s)
ESBH S - 3 - LC
|
| | |
Ecosmart Boxer Supply unit filter and heating and cooling coil
1200
Tested in duct
1000
ISO 5801 2007
Code descriptions
1
2
3
4
Fan Static Pressure (Pa)
V
800
7
600
6
400
5
4
3
200
0
0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
Air volume flow rate (m3/s)
Ecosmart Boxer fan unit only
1200
Note: If no Ecosmart control is required
example code would be: BHS3NC-LC.
If fan control only is required
(undressed coils) example code would
be: BHS3FC-LC.
Tested in duct
V
Fan Static Pressure (Pa)
1000
ISO 5801 2007
800
6
600
5
1. Ecosmart Boxer range
2. S = Supply
EX = Extract
3. Size 3 - 7
4. L = Low Pressure hot water heater
battery
LC = Low Pressure hot water heater
battery and CHCW chilled water
cooling coil
LD = Low Pressure hot water heater
battery and DX cooling coil
ED = Electric heater battery and
DX = Direct expansion (refrigerant type
coil)
Please note: Sizes 3 - 7 do not have
filters included as standard.
7
4
400
3
200
0
0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
Air volume flow rate (m /s)
3
N.B. Unit air volume flowrates are calculated by component velocity.
Download specification from www.nuaire.co.uk/specifications
nuaire.co.uk
103
Nuaire AHU_Layout 1 12/08/2011 10:30 Page 104
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMA RT B OXER
TEC H NI C A L I NF O R MATI O N
PERFORMANCE - ECOSMART BOXER SIZES 3 - 7
E L E C T R I C A L & S OU N D
Curve
Motor
Rating
(kW)
Electric
Coil Data
(kW)
Fan Input
Power
(watts)
RPM
Type
Ducted sound power levels dB re 1pW
Data
125
250
500
1K
2K
Pole
Phase
3
2.2
27
1.584
1920
4
3
4
3
36
2.407
2160
2
5
4
54
3.132
2340
6
4
54
4.035
7
5.5
54
5.177
Breakout
dBA@
3m
4K
8K
I inlet
O outlet
84
87
81
82
82
81
76
75
73
71
67
66
62
62
40
3
I inlet
O outlet
87
90
84
85
85
84
79
78
76
74
70
69
65
65
43
2
3
I inlet
O outlet
89
92
86
87
87
86
81
80
78
76
72
71
67
67
45
1780
4
3
I inlet
O outlet
84
84
86
84
83
84
80
85
77
80
72
74
65
66
43
1630
4
3
I inlet
O outlet
86
87
91
90
85
87
81
86
79
82
74
75
69
70
45
C ODI N G
Supply with
LPHW Heater
& Cooling Coil
Code
Supply with
LPHW Heater &
DX Cooling Coil
Code
FLC
(amps)
SC
(amps)
Curve
Extract
Code
Supply with
LPHW Heater
Code
3
ESBHEX3
ESBHS3-L
ESBHS3-LC
ESBHS3-LD
5
5
4
ESBHEX4
ESBHS4-L
ESBHS4-LC
ESBHS4-LD
7
7
5
ESBHEX5
ESBHS5-L
ESBHS5-LC
ESBHS5-LD
8
8
6
ESBHEX6
ESBHS6-L
ESBHS6-LC
ESBHS6-LD
8.5
8.5
7
ESBHEX7
ESBHS7-L
ESBHS7-LC
ESBHS7-LD
11
11
Flow valve setting.
C ODI N G
DX COIL DATA
Curve
Supply with
Electric Heater &
DX Cooling Coil
Code
Supply with
Electric Heater
Code
Supply with
Electric Heater
& Cooling Coil FLC
Code
(amps)
SC
(amps)
Unit
Size
Max Air kW
Evap. PD
Conn
Flow
Rating temp through size
m3/s
R407C deg C Coil KPa
3
4
ESBHS3-ED
ESBHS3-E
ESBHS3-EC
5
27
3
1.0
19
5
18
2x12&22od
ESBHS4-ED
ESBHS4-E
ESBHS4-EC
57
7
4
1.4
27
5
15
2x12&28od
5
ESBHS5-ED
ESBHS5-E
ESBHS5-EC
83
8
5
1.9
37
5
13
2x22&35od
6
ESBHS6-ED
ESBHS6-E
ESBHS6-EC
83.5
8.5
6
2.5
48
5
11
2x22&35od
7
ESBHS7-ED
ESBHS7-E
ESBHS7-EC
86
11
7
3.5
68
5
11
2x22&42od
Z FAC TOR S FOR A N C I L L A R I E S
Casing Module
1
2
3
4
5
6
7
Unit
Size
Frost Coils
In
Out
Cooling Coils
In
Out
Heating Coils
In
Out
Silencer
102
41
20
11
8
3.1
2
3
1 BSP
1 BSP
1.25BSP
1.25BSP
1.25BSP
Damper
61
25
12
6.8
4.8
1.9
1.2
4
1 BSP
1 BSP
1.25BSP
1.25BSP
1.5BSP
1.5BSP
Frost coil LPHW
122
50
23
14
9.6
3.8
2.4
5
1.25BSP
1.25BSP
1.5BSP
1.5BSP
2 BSP
2 BSP
Frost coil electric
122
50
23
14
9.6
3.8
2.4
6
1.25BSP
1.25BSP
2 BSP
2 BSP
2 BSP
2 BSP
Weather cowl
61
25
12
6.8
4.8
1.9
1.2
7
1.5BSP
1.5BSP
2 BSP
2 BSP
2 BSP
2 BSP
Plate heat exchanger
612
148
117
68
48
1.9
12
H or V
For wiring diagrams refer to pages 110.
104
029 2085 8200
1.25BSP
Nuaire AHU_Layout 1 12/08/2011 10:30 Page 105
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMART B OXER
TEC H NI C A L I NF O R MATI O N
DIMENSIONS AND CONFIGURATIONS
B
Length
Ecosmart BOXER size 3 - 7
DI ME N S I ON S ( m m ) & W E I GH T S ( K G)
ESBHEX*
Size L
W
ESBHS*L/E ESBHS*
Heating & Cooling
L
W
L
W
B
C
E
F
G
H
3
1200 199
2400 402
3000 529
800
800
373
403
600
350
4
1200 243
2400 442
3000 590
1000 800
373
535
600
450
5
1200 255
2400 490
3000 600
1000 1000 373
535
600
450
6
1500 390
2700 702
3300 858
1300 1000 557
479
600
500
7
1500 507
2700 913
3300 1115 1300 1300 638
638
600
500
F
C
E
H
NB: Units are handed left hand side as standard. (L=Length, W=Weight).
Right hand side is available on request.
Airflow
Airflow
Model shown: size 7 (right hand with cooling coil).
Model shown: size 7 (left hand with cooling coil).
Model shown: size 7 (right hand with DX cooling coil).
Model shown: size 7 (left hand with DX cooling coil).
Model shown: size 7 (right hand supply with electric heater).
Model shown: size 7 (left hand supply with electric heater).
Download specification from www.nuaire.co.uk/specifications
G
nuaire.co.uk
105
Nuaire AHU_Layout 1 12/08/2011 10:30 Page 106
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMA RT B OXER
TEC H NI C A L I NF O R MATI O N
ECOSMART BOXER SIZES 3 - 7
Model shown: size 7 (right hand supply with electric heater and cooling coil).
Model shown: size 7 (left hand supply with electric heater and cooling coil).
Model shown: size 7 (right hand supply with electric heater and DX coil).
Model shown: size 7 (left hand supply with electric heater and DX coil).
Model shown: size 7 (right hand supply with LPHW heater).
Model shown: size 7 (left hand supply with LPHW heater).
Model shown: size 7 (right hand supply with LPHW heater and cooling coil).
Model shown: size 7 (left hand supply with LPHW heater and cooling coil).).
106
029 2085 8200
Nuaire AHU_Layout 1 12/08/2011 10:30 Page 107
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMART B OXER
TEC H NI C A L I NF O R MATI O N
ECOSMART BOXER SIZES 3 - 7
Model shown: size 7 (right hand supply with LPHW heater and DX cooling coil).
Model shown: size 7 (left hand supply with LPHW heater and DX cooling coil).
Model shown: size 7 (right hand with extract).
Model shown: size 7 (left hand with extract).
Please note: Sizes 3 - 7 do not have filters included as standard.
Download specification from www.nuaire.co.uk/specifications
nuaire.co.uk
107
Nuaire AHU_Layout 1 12/08/2011 10:30 Page 108
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMA RT B OXER C O I L S F O R L P H W
ECOSMART BOXER Size 1 and 2
Air Volume Flow rate (m3/s)
Water
Heat Air Off
on/off Air On
Output
C
C
C
(kW)
C
-3
25
31
3
11.5
35
82/71
9
21
38
15
19.2
41
60/40
2 ROW
0.6
Water flow
rate
(l/s)
0.556
0.514
0.472
0.428
Water dp
(kPa)
11.5
10
8.6
7.3
Heat Air Off
Output
C
(kW)
C
19
36
17.6
39
16
42
14.8
45
0.4
Water flow
rate
(l/s)
0.424
0.392
0.36
0.32
Water dp
(kPa)
7.1
6.3
5.4
4.6
Heat Air Off
Output
C
(kW)
C
10.8
41
10
44
9.2
47
8.4
50
0.2
Water flow
rate
(l/s)
0.242
0.224
0.206
0.188
Water dp
(kPa)
2.74
2.40
2.08
1.78
22
mm
-3
3
9
15
21.4
19.4
17.6
15.6
26
30
33
36
0.26
0.238
0.214
0.19
3.2
2.72
2.27
1.85
16
15
13.4
12
30
33
36
39
0.2
0.182
0.164
0.146
1.98
1.69
1.41
1.16
9.4
8.6
7.8
7
35
38
41
43
0.114
0.104
0.094
0.084
0.76
0.65
0.55
0.45
15
mm
-3
3
9
15
14
12
10
8
16
20
23
26
0.17
0.146
0.122
0.096
1.53
1.18
0.87
0.58
10.6
9.2
7.6
6
19
22
24
27
0.13
0.112
0.092
0.072
0.95
0.74
0.53
0.35
6
5
4
3.6
21
24
26
28
0.072
0.062
0.05
0.046
0.35
0.27
0.19
0.16
15
mm
ECOSMART BOXER Size 3
Air Volume Flow rate (m3/s)
Water
Heat Air Off
on/off Air On
Output
C
C
C
(kW)
C
-3
60
26
82/71
3
55
29
9
50
33
15
45
37
Connection size
80/60
Connection size
TEC H NI C A L I NF O R MATI O N
2 ROW
1.7
Water flow
rate
(l/s)
1.32
1.22
1.1
0.97
Water dp
(kPa)
11
9.6
8.2
7
Heat Air Off
Output
C
(kW)
C
54
31
50
35
46
38
41
41
1.3
Water flow
rate
(l/s)
1.2
1.1
1
0.92
Water dp
(kPa)
9.4
8.3
7.2
6.2
Heat Air Off
Output
C
(kW)
C
46
35
43
38
40
41
36
44
1
Water flow
rate
(l/s)
1
0.96
0.88
0.8
Water dp
(kPa)
7.4
6.6
5.8
5
1.25”
-3
3
9
15
50
45
40
35
21
25
28
32
0.61
0.55
0.49
0.43
3.4
2.83
2.37
1.93
45
41
37
33
26
29
32
36
0.56
0.5
0.45
0.4
2.9
2.42
2.06
1.71
39
36
32
28
29
32
35
38
0.48
0.44
0.39
0.35
2.33
2.07
1.72
1.45
1”
60/40
-3
3
9
15
32
27
22
17
12
16
20
23
0.39
0.33
0.27
0.2
1.66
1.28
0.94
0.59
29
25
20
15
15
19
22
24
0.35
0.3
0.24
0.19
1.39
1.10
0.78
0.54
25
21
17
14
17
20
23
26
0.3
0.26
0.21
0.16
1.14
0.92
0.66
0.43
1”
2 ROW
2.1
Water flow
rate
(l/s)
2.1
1.9
1.78
1.62
Water dp
(kPa)
12.9
11.3
9.8
8.4
Heat Air Off
Output
C
(kW)
C
86
36
79
39
73
42
67
45
1.8
Water flow
rate
(l/s)
1.9
1.77
1.63
1.48
Water dp
(kPa)
11
9.7
8.5
7.3
Heat Air Off
Output
C
(kW)
C
72
39
67
42
61
45
56
48
1.4
Water flow
rate
(l/s)
1.6
1.48
1.36
1.24
Water dp
(kPa)
8.2
7.3
6.4
5.5
80/60
-3
3
9
15
81
74
67
60
29
32
35
38
0.99
0.91
0.82
0.73
3.9
3.4
3.00
2.51
74
68
61
55
31
34
37
40
0.91
0.83
0.75
0.67
3.4
3.05
2.60
2.19
62
57
51
46
34
37
39
42
0.76
0.69
0.63
0.56
2.59
2.23
1.93
1.61
60/40
-3
3
9
15
54
47
39
32
18
21
24
27
0.66
0.57
0.48
0.38
2.15
1.71
1.31
0.91
49
43
36
29
19
22
25
28
0.6
0.52
0.43
0.35
1.84
1.48
1.10
0.80
41
36
30
24
21
24
26
29
0.5
0.43
0.36
0.29
1.35
1.07
0.81
0.58
ECOSMART BOXER Size 6
Air Volume Flow rate (m3/s)
Water
Heat Air Off
on/off Air On
Output
C
C
C
(kW)
C
-3
157
30
3
144
34
82/71
9
132
37
15
119
40
1.25”
1.25”
2 ROW
3.9
Water flow
rate
(l/s)
3.5
3.2
2.9
2.6
Water dp
(kPa)
11.8
10.4
9.1
7.9
Heat Air Off
Output
C
(kW)
C
139
35
128
38
117
41
106
44
3
Water flow
rate
(l/s)
3.1
2.85
2.61
2.36
Water dp
(kPa)
9.9
8.8
7.7
6.7
Heat Air Off
Output
C
(kW)
C
106
40
98
43
90
46
81
48
2
Water flow
rate
(l/s)
2.35
2.17
1.99
1.8
Water dp
(kPa)
6.6
5.9
5.3
4.6
80/60
-3
3
9
15
131
118
106
93
25
28
31
35
1.6
1.44
1.29
1.13
3.9
3.4
2.92
2.42
116
105
94
83
29
32
35
38
1.42
1.28
1.15
1
3.3
2.87
2.47
2.03
89
81
72
64
33
36
38
41
1.1
0.99
0.88
0.78
2.28
1.97
1.67
1.41
60/40
-3
3
9
15
83
70
56
42
14
18
21
24
1
0.85
0.68
0.51
2.04
1.63
1.19
0.80
73
62
50
37
17
20
23
25
0.89
0.75
0.61
0.45
1.73
1.36
1.02
0.66
56
47
37
25
20
22
24
25
0.67
0.57
0.45
0.31
1.14
0.91
0.65
0.39
ECOSMART BOXER Size 7
Air Volume Flow rate (m3/s)
Water
Heat Air Off
on/off Air On
Output
C
C
C
(kW)
C
-3
201
31
3
184
35
82/71
9
168
38
15
151
41
2”
2 ROW
4.8
Water flow
rate
(l/s)
4.5
4.1
3.7
3.4
Water dp
(kPa)
13
11.2
9.8
8.4
Heat Air Off
Output
C
(kW)
C
189
34
174
37
158
40
143
43
4.2
Water flow
rate
(l/s)
4.2
3.9
3.5
3.2
Water dp
(kPa)
11.7
10.3
9
7.7
Heat Air Off
Output
C
(kW)
C
166
40
153
42
139
45
125
47
3.2
Water flow
rate
(l/s)
3.7
3.4
3.1
2.8
Connection size
Air Volume Flow rate (m3/s)
Water
Heat Air Off
on/off Air On
Output
C
C
C
(kW)
C
-3
94
34
3
87
37
82/71
9
80
40
15
73
43
Water dp
(kPa)
9.6
8.5
7.5
6.4
80/60
-3
3
9
15
161
145
128
111
25
28
31
34
1.97
1.77
1.56
1.36
4
3.5
2.95
2.43
152
137
121
106
27
30
33
36
1.86
1.67
1.48
1.29
3.8
3.3
2.72
2.24
134
121
107
93
32
34
37
39
1.64
1.48
1.31
1.14
3.2
2.66
2.24
1.85
60/40
-3
3
9
15
96
79
61
39
13
16
19
22
1.16
0.96
0.74
0.48
1.95
1.49
1.04
0.57
91
75
58
36
15
18
20
22
1.1
0.91
0.7
0.43
1.79
1.37
0.95
0.48
80
66
50
29
18
20
22
23
0.97
0.8
0.61
0.35
1.47
1.12
0.77
0.35
2”
1.5”
1.5”
For further assistance
please call Nuaire. Note:
dp figures do not include
3 port valve.
Approximately double
these figures when valves
are included.
Connection size
ECOSMART BOXER Size 5
Connection size
80/60
2”
1.5”
1.5”
*Please note: above tables are based on indicative selections. For more specific selection, contact Nuaire.
108
029 2085 8200
Nuaire AHU_Layout 1 12/08/2011 10:30 Page 109
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMART B OXER A NC I L L A R I ES
TEC H NI C A L I NF O R MATI O N
SILENCER MODULES
MOTORISED DAMPERS
VERTICAL HEAT EXCHANGER
Splitters are faced with perforated sheet lined
to prevent particle migration and filled with
high density mineral wool.
Opposed blade design with quick fit flanges.
240V Open/Shut model (B) for efficient back
draught protection and 24V modulating
version (M) for balancing and control.
A plate exchanger core assembly providing
efficient heat transfer between supply and
extract air streams. An integral drip tray is
incorporated with a 22mm drain connection.
The tray is insulated to prevent secondary
condensation.
B
B
A
A
A
C
B
C
C
Unit Code
A
B
C
Weight (Kg)
Unit
A
Weight (Kg)
ESBSIL1
900
954
530
70
ESBD1
165
12
ESBSIL2
900
954
670
90
ESBD2
165
14
ESBSIL3
900
800
800
Length
Width
Height
A
B
C
Weight (Kg)
ESBHX1 1000
954
1060
150
ESBHX2 1130
954
1340
180
ESBHX3 1200
800
1600
210
ESBHX4 1400
1000
1600
263
ESBHX5 2200
1000
2000
360
ESBHX6 2200
1300
2000
440
Also available: motor open/spring return option.
Code: ESBD* MO/SR.
ESBHX7 2500
1300
2600
594
ESBD3
95
165
19
ESBSIL4
900
1000
800
96
ESBD4
165
23
ESBSIL5
900
1000
1000
124
ESBD5
165
28
ESBSIL6
900
ESBSIL7
900
1300
1000
1300
1300
ESBD6
150
ESBD7
192
165
165
Unit
30
34
Note: Dimensions B & C are to suit unit supplied.
DYNAMIC ATTENUATION VALUES
(at maximum velocity)
Length
125 250
500 1K
2K
4K
8K
900
6
8
18
22
20
16
15
FROST COIL = LPHW & ELECTRIC
HORIZONTAL HEAT EXCHANGER
1200
7
11
26
31
30
23
20
600mm long section to suit unit size selected.
For details contact Nuaire.
Heat exchanger complete with integral drop
tray with a 22mm drain connection.
Note: silencer cross sectional area matches the
Ecosmart Boxer unit.
A
WEATHER ROOF FOR ECOSMART BOXER
B
For further information please contact Nuaire.
C
Length
Width
Height
A
B
C
Weight (Kg)
ESBHX1H 1750
2000
530
150
ESBHX2H 1425
2000
670
180
ESBHX3H 1200
1600
800
200
ESBHX4H 1625
2000
800
280
ESBHX5H 2000
2000
1000
360
ESBHX6H 2200
2600
1000
600
ESBHX7H 2200
2600
1300
594
Unit
Example of horizontal
unit with weather kit.
Example of stacked
unit with weather kit.
ESBBF2* - Available in a variety of lengths to suit unit
sizes 1 - 7.
BASE FRAME
Z FAC TOR S FOR A N C I L L A R I E S
Casing Module
1
2
3
4
5
6
7
Silencer
102
41
20
11
8
3.1
2
Damper
61
25
12
6.8
4.8
1.9
1.2
Frost coil LPHW
122
50
23
14
9.6
3.8
2.4
Frost coil electric
122
50
23
14
9.6
3.8
2.4
Weather cowl
61
25
12
6.8
4.8
1.9
1.2
Plate heat exchanger
612
148
117
68
48
1.9
12
(Please contact Nuaire for further details).
Provided as standard on sizes 3 - 7.
Optional extras on sizes 1 and 2.
80mm
For further ancillaries please refer to Ducting and Ancillaries section or call Nuaire.
Download specification from www.nuaire.co.uk/specifications
nuaire.co.uk
109
Nuaire AHU_Layout 1 12/08/2011 10:30 Page 110
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMA RT B OXER W I R I NG
TEC H NI C A L I NF O R MATI O N
WIRING - ECOSMART BOXER SIZES 1 AND 2
WIRING - ECOSMART BOXER SIZES 1 AND 2
ESBHS1, ESBHS2, ESBHEX1 and ESBHEX2
ESBHS1-L, ESBHS2-L, ESBHS1-LD and ESBHS-2LD
BMS signal
Ecosmart
N
L
SL
Min
25
Fan 2
Coolin g
Connections
to Damper
Fault
Frost
Fault signal
Rx
ON OFF
Heat demand
signal
Run signal
Fault signal
NET connections for
ECOSMART devices
L
N
E
230V 50Hz
1ph mains
Fan 1
Max SL run on
Cooling Frost
demand alarm
signal
signal
Earth
Cooling
Fault
0
1
Frost
Tx
Trickle
Test
Rx
NET connections for
ECOSMART devices
L
N
E
230V 50Hz
1ph mains
Signal for
DX2 coil
if fitted
Signal for
DX1 coil
if fitted
Fan 2
Heating
HEAT
DEMAND
Test
Standby
Min
RET
Tx
Trickle
Pw r
FAULT RUN
1
AUTO
HEATER/COOL
Run signal
DP
CL
N
Heatin g
0
Ecosmart
N
L
0V
0-10V
SL
FAULT RUN
Heat demand
signal
Max SL run on
BMS signal
30
Fan 1
HEAT
DEMAND
Connections
to Damper
Pw r
Standby
DAMPER
DP
CL
N
RET
Speed
Controller
0V
0-10V
25
Speed
Controller
Remove this link wire if:
1. a switched live signal is connected.
2. an ES-PIR, ES-TC or BMS signal
is connected.
Set air off
temperature
of LPHW coil
DAMPER
Remove this link wire if:
1. a switched live signal is connected.
2. an ES-PIR, ES-TC or BMS signal
is connected.
Earth
ESBHS1-E and ESBHS2-E
Remove this link wire if:
1. a switched live signal is connected.
2. an ES-PIR, ES-TC or BMS signal
is connected.
Speed
Controller
BMS signal
N
L
Do not set temperature
above 30 OC
SL
DP
CL
N
Connections
to Damper
Electric heater control
230V 50Hz
1ph mains
L
N
E
Trickle
Test
0V
0-10V
Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx
5 6 7 8
9
10 11
12 13 14 15
Connections
to Damper
L3
L2
Brown
24 Vac
Green
0 - 10 Vac
Whi ite
Common
(U)
L1
(V)
(W)
DP
CL
N
RET
This contact is
not applicable
to BMS models
Run signal
Fault signal
NET connections for
ECOSMART devices
Earth
A1
3
(V)
4
5
(W)
6
Earth
Min
0
Max SL run on
1
Trickle
Test
Tx
Test
Rx
NET connections for
ECOSMART devices
Earth
0V
0-10V
Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx
24 Vac Warning: connect via safety
isolating transformer
~
1
L3
Y1 0...10V DC
Y2 0...20V
phase cut
U 2...10V DC
2 3
4 5
L2
L1
N
029 2085 8200
Frost
Trickle
NET connections for
ECOSMART devices
1
(U)
2
A2
110
1
Actuator head, type Belimo
model SM24-SR
Ecosmart
N
L
SL
12 13 14 15
DAMPER
FAULT RUN HEAT
DEMAND
Fault signal
1
Fault
L
N
E
230V 50Hz
1ph mains
Remove this link wire
L1 L2 L3 E
CONTACTER
This contact is
not applicable
to BMS models
Run signal
0
Max SL run on
Earth
BMS signal for fan speed
Note: Do not reverse the
polarity as it may cause
damage to the circuit
Actuator
DP
CL
N
RET
DAMPER
FAULT RUN HEAT
DEMAND
Connections
to Damper
Min
Cooling
0
E
400V 50Hz
3ph +N mains
T
Ecosmart
N
L
SL
L3
L2
L1
N
E
Fan 2
Heating
T
BMS signal for fan speed
Note: Do not reverse the
polarity as it may cause
damage to the circuit
Max SL run on
BMS MODES 3 TO 7
Actuator head, type Honeywell
model M7410E1028
Remove this link wire
Fan 1
HEAT
DEMAND
Fault signal
Speed
Controller
Standby
Min
FAULT RUN
Run signal
WIRING - ECOSMART BOXER SIZES 3 - 7
BMS MODES 1 AND 2
Pw r
RET
Heat demand
signal
400V 50Hz
3ph +N mains
supply for fan
and heater
Ecosmart
DAMPER
Adjustment for air off
temperature.
0V
0-10V
~
Y1 Y2 U
SM24-SR
Nuaire AHU_Layout 1 12/08/2011 10:30 Page 111
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMART B OXER W I R I NG
TEC H NI C A L I NF O R MATI O N
WIRING - ECOSMART BOXER SIZES 3 - 7
ESBHS3-L,ESBHS4-L, ESBHS5-L, ESBHS6-L AND ESBHS7,
ESBHS3-LD, ESBHS4-LD, ESBHS5-LD, ESBHS6-LD AND ESBHS7-LD
0-10V
Ecosmart
Pw r
L
10 11
N
Coolin g
1
L3
Run signal
Fault signal
(U)
(V)
Trickle
Test
(W)
7 8 9
10 11
N
Heat demand
signal
L3
Run signal
L2
(U)
L1
Max
SL run on
Fault signal
(V) (W)
Fan 2
Heatin g
Coolin g
Faul t
0
1
Frost
RET
12 13 14 15
Rx
FAULT
L2
L1
Tx
RU N HEAT
DEMAND
Heat demand
signal
5 6
Frost
CL
Connections
to Damper
Faul t
0
RET
12 13 14 15
12 13 14 15
Tx
RUN HEAT
DEMAND
7 8 9
Fan 1
Min
DP
Trickle
Test
Rx
NET connections for Ecosmart devices
NET connections for Ecosmart devices
A1
CONTACTER
CONTACTER
5
(W)
6
3
(V)
4
Set outlet air
temperature
of CW cooling
coil
25
A2
25
GREEN
BROWN
WHITE
3
2
1
Connect to LPHW
actuator motor
SM24
motor set at
position A
25
Set outlet air
temperature
of LPHW coil
5
(W)
6
25
25
Set air off
temperature
of LPHW coil
A2
1
(U)
2
30
3
(V)
4
25
1
(U)
2
30
A1
30
5 6
CL
Connections
to Damper
12 13 14 15
Pw r
Standby
Fan 2
SL run on
Heatin g
DAMPER
DP
Max
Ecosmart
N
SL
Fan 1
Min
0-10V
L
Standby
SL
0V
BMS signal
DAMPER
N
Remove this link wire if:
1. a switched live signal
is connected.
2. an ES-PIR, ES-TC or BMS
signal is connected.
L1 L2 L3 E
0V
BMS signal
FAULT
Remove this link wire if:
1. a switched live signal
is connected.
2. an ES-PIR, ES-TC or BMS
signal is connected.
L1 L2 L3 E
WIRING - ECOSMART BOXER SIZES 3 - 7
ESBHS3-LC, ESBHS4-LC, ESBHS5-LC, ESBHS6-LC
AND ESBHS7-LC
GREEN
3
BROWN
A
2
WHITE
1
GREEN
3
BROWN
2
WHITE
400V 50Hz
3ph +N mains
N
E
Earth
Frost
alarm
signal
Signal for
DX2 coil
if fitted
Signal for
DX1 coil
if fitted
L1
400V 50Hz
3ph +N mains
N
E
Inlet Outlet
sensor sensor
Cooling
demand
signal
L2
Connect to inlet
sensor after unit
is assembled
Inlet
sensor
Cooling
demand
signal
A
Frost
alarm
signal
Signal for
DX2 coil
if fitted
Signal for
DX1 coil
if fitted
1
ON OFF
L1
L3
AUTO
HEATER/COOL
L2
Earth
ON OFF
AUTO
HEATER/COOL
L3
Connect to LPHW
actuator motor
SM24
motor set at
position A
A
Connect to CW coil
actuator motor
SM24
motor set at
position A
A
Outlet
sensor
Connect to inlet
sensor after unit
is assembled
A
ESBHS3-E, ESBHS4-E, ESBHS5-E, ESBHS6-E AND ESBHS7-E
ESBHEX3, ESBHEX4, ESBHEX6 AND ESBHEX7
A
Remove this link wire if:
1. a switched live signal is connected
2. an ES-PIR, ES-TC or BMS signal
is connected.
0V
BMS signal
SL
DP
N
RET
(U)
(V) (W )
Heat demand
signal
Run signal
Fault signal
Frost
Test
L3
Coolin g
N
(U)
L1
(V)
Fault signal
5
L3
(W )
6
L2
L1
N
A2
E
400V 50Hz
3ph +N mains
1
Test
Rx
1
(U)
2
3
(V)
4
T
Adjustment for air off temperature.
Do not set temperature above 30OC
NET connections for
ECOSMART devices
5
(W)
6
LINE 1
LINE 2
L1
L2
LINE 3
Earth
L3
E
400V 50Hz 3ph supply for heater
B
A2
L3
L2
L1
N
E
Download specification from www.nuaire.co.uk/specifications
R
Frost
Tx
Trickle
HEAT
SENS
NET connections for
ECOSMART devices
Earth
3
(V)
4
Electric heater control
Fault
0
(W)
Run signal
1 2
Fan 2
Heating
Heat
demand
signal
L2
SL run on
CL
RET
Rx
CONTACTER
A1
CONTACTER
Trickle
Max
DP
Connections
to Damper
A1
1
(U)
2
Fan 1
Min
Faul t
1
Heater over-temperature stat
Standby
SL
10 11
12 13 14 15
Coolin g
0
Tx
HEAT
DEMAND
L2
5 6 7 8 9
Heatin g
RUN
L3
L1
CL
DAMPER
Connections
to Damper
Fan 2
FAULT
12 13 14 15
Max SL run on
Pw r
L
Fan 1
Min
10 11
DAMPER
9
Ecosmart
N
12 13 14 15
400V 50Hz
3ph +N mains
Make connection
after the unit has
been assembled
Note: these controls are located
in the electric heater section
nuaire.co.uk
111
Sensor
Standby
HEAT
DEMAND
7 8
Make connection
after the unit has
been assembled
BMS signal
Pwr
L
5 6
Remove this link wire if:
1. a switched live signal is connected HTR
2. an ES-PIR, ES-TC or BMS signal
0V
is connected.
0-10V
0-10V
Ecosmart
N
12 13 14 15
B
L1 L2 L3 E
FAULT RUN
L1 L2 L3 E
Nuaire AHU_Layout 1 12/08/2011 10:30 Page 112
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMA RT B OXER W I R I NG
TEC H NI C A L I NF O R MATI O N
ECOSMART BOXER WITH CONSTANT PRESSURE CONTROLS
Airflow
D
2D min
Silencer
Fan
Heater
Filter
Control
Locate Pressure Tapping here
EXTRACT FANS SIZE 1 AND 2
SUPPLY FANS SIZE 1 AND 2
Pressure Sensor
Pressure Sensor
Pressure setting pot
Pressure setting pot
Set differential
Pressure
Set differential
Pressure
High Low
Max SL run on
Connector
Min
0
Pre-wired in factory to
main control PCB via
PVC Tubing
connector labelled 'P in'
(supplied)
To fan outlet,
connection
to be made
on site
To atmosphere through
fan casing
1
Trickle
Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx
Test
Ecosmart
High Low
0
Pre-wired in factory to
main control PCB via
connector labelled 'P in'
Main control PCB
Test
Main control PCB
EXTRACT FANS SIZE 3 AND ABOVE
Pressure setting pot
Set differential
Pressure
Set differential
Pressure
Max SL run on
Connector
Min
0
1
Trickle
Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx
Ecosmart
Inverter
Max SL run on
0
1
Trickle
Test
Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx
Test
Main control PCB
Main control PCB
To fan outlet; connection
to be made on site
To atmosphere through
fan casing
Min
Connector
Ecosmart
Pre-wired in factory to
main control PCB via
connector labelled 'P in'
To atmosphere through
control casing
Pre-wired in factory to
main control PCB via
connector labelled 'P in'
To fan inlet chamber
Low High
Low High
Pressure Sensor
029 2085 8200
1
Trickle
To fan inlet chamber
Pressure setting pot
112
Max SL run on
Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx
To atmosphere through
fan casing
SUPPLY FANS SIZE 3 AND ABOVE
Inverter
Min
Connector
Ecosmart
Pressure Sensor
Nuaire AHU_Layout 1 12/08/2011 10:30 Page 113
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMART B OXER W I R I NG
TEC H NI C A L I NF O R MATI O N
i There are no inrush starting currents quoted because the Ecosmart control
incorporates a soft starting speed control feature.
ii. The inverters are preset to match the fan requirements. Under normal
circumstances it should not be necessary to adjust them.
iii. Pay particular attention to the model type, recorded on the product rating
plate and connect as follows.
ECOSMART BOXER FAN CONTROL ONLY
Power requirements
Model
Flc fan
only (1)
BHSEX1FC, BHS1FC-L
4.8A
BHS1FC-E
4.8A
BHSEX2FC,
7.3A
BHS2FC-E
7.2A
BHSEX3FC, BHS3FC-L
4.6A
6.1A
BHS4FC-E
6.1A
BHSEX5FC, BHS5FC-L
7.8A
BHS5FC-E
7.8A
BHSEX6FC, BHS6FC-L
8.2A
BHS6FC-E
8.2A
BHSEX7FC, BHS7FC-L
BHS7FC-E
18
25A
24
33A
27
38A
SIZES 1 AND 2
36
Note: Inter connections between circuit boards are made in the factory.
Remove this link wire if:
1. a switched live signal is connected.
2. A ES-PIR, ES-TC or BMS signal is connected.
Speed
Controller
50A
0V
BMS signal
54
75A
0-10V
Ecosmart
N
Pwr
L
Standby
SL
54
75A
11.4A
11.4A
54
Fan 1
Min
DP
Connections
to Damper
75A
N
RET
Heat demand
signal
Note: (1) Sizes 1 and 2 fans are rated at 230V ac, 50Hz single phase. All other
sizes are rated at 400V ac 50 Hz 3 phase.
(2) All electric heaters are rated at 400V ac 50 Hz 3 phase.
Max
Fan 2
SL run
on
Heating
Cooling
CL
Run signal
HEAT
DAMPER
DEMAND
4.6A
BHSEX4FC, BHS4FC-L
Flc
heater (2)
Fault
0
1
Frost
Tx
Trickle
Test
Rx
FAULT RUN
BHS3FC-E
Electric heater
max Kw
Fault signal
NET connections for
ECOSMART devices
L
230V 50Hz
1ph mains
N
Earth
E
SIZES 3 TO 7
TYPICAL ELECTRIC HEATER WIRING
Note: Inter connections between circuit boards and inverter/contactor are made in the factory.
Connect
over temperature
trip to control circuit
L1 L2 L3 E
Remove this link wire if:
1. a switched live signal is connected.
2. A ES-PIR, ES-TC or BMS signal
is connected.
Bus bar clamp
0V
BMS signal
12 13 14 15
7
8
9
L3
L2
Heat demand
signal
Max
SL run
on
N
Fan 2
Heating
Cooling
CL
RET
Fault
0
1
Frost
Tx
Trickle
Test
Rx
(V) (W)
Run signal
Fault signal
L3
FAULT RUN
(U)
Fan 1
Min
DP
Connections
to Damper
L1
Standby
SL
10 11
12 13 14 15
400V
50Hz
3 phase
Pwr
L
HEAT
DAMPER
DEMAND
5 6
L2
Ecosmart
N
L1
0-10V
A1
E
CONTACTER
NET connections for
ECOSMART devices
1
(U)
2
3
(V)
4
5
(W)
6
Earth
L3
L2
L1
N
A2
Download specification from www.nuaire.co.uk/specifications
400V 50Hz
3ph +N mains
E
nuaire.co.uk
113
Nuaire AHU_Layout 1 12/08/2011 10:30 Page 114
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMA RT B OXER
TEC H NI C A L I NF O R MATI O N
CO NSULTA NT S SP E CI F I C ATION
ECOSMART BOXER UNITS SIZE 3 TO 7
AIR HANDLING UNIT SPECIFICATION
The Air Handling Unit shall be configured and arranged as detailed on the
drawings and in accordance with the schedule of equipment. The units shall be
manufactured from a highly rigid pentapost framework with 25mm double
skinned infill panels. The panels shall contain inert high density infill.
Panel materials are heavy gauge Aluzinc corrosion resistant steel. The units shall
provide exceptional thermal and acoustic insertion. The general construction is
to class A leakage.
The fan impeller and motor shall be selected to provide the most energy
efficient solution conforming to part L regulations and shall be direct or belt
drive with IE2 high efficiency motors to BS5000 as standard. The fan impeller
shall be a high efficiency forward or backward curved centrifugal design,
manufactured in galvanised steel.
The Fan unit shall have a 5 year warranty.
The unit and ancillaries shall be of the Ecosmart Boxer type as manufactured by
Nuaire Ltd.
All other components shall be in accordance with the manufacturer’s
specification.
CONTROL SPECIFICATION
The Air Handling Unit shall be supplied with one of the following control
options:-
1. ECOSMART CONTROLS The compact Ecosmart control system complete with all necessary controls to
facilitate the operation of the ventilation system. It shall be come complete with
an integral factory fitted Ecosmart PCB which will control the fan unit within the
desired design parameters and provide the interface between all external control
devices and the unit itself.
ECOSMART SYSTEM OPERATION
The Ecosmart controls will enable the unit to automatically vary its speed as it
receives signals from one of the interconnected sensors. When the signal is
received the fan shall either increase speed gradually until the required level is
achieved or it will work on a trickle and boost principle. This will then and move
the fan duty point from trickle/background ventilation rate to the required boost
ventilation rate. Both the trickle and boost rates are infinitely variable, easy to
adjust and remove the need of a main balancing damper.
2. BMS INTERFACES
The fan unit shall be provided with the following integrated BMS interfaces
• 0 - 10 volt contacts to provide a full BMS interface. This will enable the
following functions:Switch the unit on/off.
Switch from low speed to high speed.
Full speed control facility.
Switch the heating function on/off.
Switch the cooling function on/off.
• 2 No. Volt free contacts to provide fan run and failure indication to provide
system status.
• An integrated commissioning/speed control to accurately commission the
system, with minimum and maximum speeds easily adjusted via a miniature
dial, as recommended in Part L. This will enable the unit to be configured to
run between set parameters thus saving motor power and limiting noise.
• Commissioning set up - The fan unit shall be provided with an integrated
commissioning/speed control to accurately commission the system, as
recommended in Part L, minimum and maximum speeds easily adjusted
via miniature dial. The commissioning set up facility directly controls the
integrated speed control/frequency inverter.
3. NO CONTROL IS AVAILABLE
(Example code BHS7NC-E).
The Air Handling Unit shall have the following energy saving components
integrally mounted, pre-wired to interface with the purpose made PCB, all
components pre-wired, configured and factory fitted by the manufacturer: • Integral Frequency inverter/speed controller.
• Integral maximum and minimum speed adjustment for commissioning.
• Integral adjustable run on timer.
• Integral BMS interfaces – summer/winter switching, heating control,
0-10V speed adjustment.
• Volt free failure and status indication.
• Integral air off temperature adjustment.
• Facility for remote temperature control.
• Integral background ventilation switch (trickle switch).
• Multiple IDC sockets for interconnection of sensors or fans using pre-plugged
4-core low voltage cable.
• Volt free frost alarm/heat demand interface.
• Frost protection/hold off stat.
114
029 2085 8200
COIL TYPES, HX AND CONTROLS
The control for the coils shall be fully integrated and shall maintain a constant
off coil temperature. The system shall have frost protection which shall, at
temperatures below 4 degrees C, fully open the 3-port valve and only start
the fan when the temperature at the filter has risen above the designated set
point. Unit to have contacts which will act as frost alarm and/or signal boiler
to switch on.
Nuaire AHU_Layout 1 12/08/2011 10:30 Page 115
A I R H A NDL I NG UNI TS ( A H U’S)
EC O SMART B OXER
TEC H NI C A L I NF O R MATI O N
CO NSULTA NT S SP E CI FIC ATION
HEATING COILS - LOW PRESSURE HOT WATER
The Low Pressure Hot Water heating coil shall be manufactured from copper
tubing with high efficiency aluminium fins contained within a galvanised steel
frame, shall be factory fitted with a 3-port motorised diverting valve assembly
comprising the 3-port valve, double regulating valve, drain cocks aactuator
controlling the 3-port valve shall be control via the on-board PCB by the off coil
temperature sensor. All components pre-piped, assembled and tested by the
manufacturers.
HEATING COILS - ELECTRIC
The Electric Heater Battery shall be factory fitted and pre-wired to an integral
closed loop thyristor control. The heat output can be configured on site to suit
the specific requirements.
COOLING COILS - CHILLED WATER
The Chilled Water Coil shall be manufactured from copper tubing with high
efficiency aluminium fins contained within a galvanised steel frame, it shall be
factory fitted with a 3-port motorised diverting valve assembly comprising the
3-port valve, drain cocks and air vents. The actuator controlling the 3-port valve
shall be control via the on-board PCB by the off coil temperature sensor.
Coil supplied complete with an insulated condensate tray and moisture
eliminator. All components pre-piped, assembled and tested by the
manufacturer.
COOLING COILS – DX COILS
The DX Coil shall be manufactured from copper tubing with high efficiency
aluminium fins and droplet eliminator contained within a galvanised steel frame.
The coil shall be filled with dry nitrogen with the pipe connections capped.
It shall be factory fitted and tested by the AHU manufacturer.
Note: Fan control only example code is BHS7FC-LD.
HEAT EXCHANGER
The cross flow heat exchanger shall be complete with a motorised summer
bypass; this will be activated when the heating, cooling or ventilation switch
on the user control is switched to the ventilation position.
The Ecosmart controlled fan unit shall have a 5 year warranty.
Non Ecosmart fan controlled units will have a 3 year warranty.
All equipment shall be as manufactured by Nuaire Ltd.
*Suitable for 95% RH non condensing.