ICM400 T HREE -P HASE V OLTAGE M ONITOR Stop Motor Burnouts! High performance, low cost model, front and back side protection, 7 bright fault LEDs, integral short-cycle protection, easy set up, fully adjustable features, 190 to 630 VAC... 3-Position Reset Switch, 50/60 Hz... • Choose from 3 easy-to-select reset modes – Full Manual, Full Automatic, Auto Front/Manual Back Features Specifications • Bright LEDs Show Modes and Identity Faults – Load energized LED – Lockout LED – Back fault LED – Low voltage LED – Control voltage LED – Front fault LED – High voltage LED • Knob-adjustable Variables –User may easily select and adjust setpoints on unit: • Line voltage: 190 to 600 VAC • Voltage unbalance: 2 to 25% • Delay on break period: .1 to 5 minutes • Fault interrogation: 1 to 15 seconds • Low Cost, High Performance –Full line protection and fault identification without costly LCD readout • Integral Delay on Break Timer –Knob-adjustable from .1 to 5 minutes, helps prevent rapid system recycling • Easy to Install and Configure –Wiring diagram on unit –Installation and application guide included Mode of Operation At power up, the ICM400 evaluates the incoming power for proper phase sequence, amplitude, and symmetry (voltage unbalance). If the three phase input at the line side connections is within user set parameters, the internal relay is energized and the load energize LED is turned on. Continuity will be across terminals 4 and 6. If connections are made to the load side terminals, the ICM400 will transfer monitoring over to the load side only. When a critical fault condition (phase loss or phase reversal) is present, the relay will immediately de-energize and the load energize LED will turn off. Continuity will be across terminals 4 and 5. If a non critical fault condition (unbalance, high or low voltage) is present, the ICM400 will ignore it for the interrogation delay time. If it is still present following the interrogation delay time, the relay will de-energize and the load energized LED will turn off. Continuity will be across terminals 4 and 5. The relay will not energize if any fault conditions exist. The integral adjustable delay on break timer will prevent short-cycling. LIS41-1 Phone 315.233.5266 Input • Line Voltage: Universal (190-630 VAC) • Frequency: 50/60 Hz Output • Type: Relay • Form: SPDT • Voltage Range: 240 VAC (maximum: 10 amps) • Frequency: 50/60 Hz Contactor Load Side (Back) • Line Voltage: Universal (190-630 VAC) • Frequency: 50/60 Hz • Load side monitoring is optional Control Operating Temperature • Operating Temperature: -40ºC to +75ºC (-40ºF to +167ºF) • Storage Temperature: -40ºC to +85ºC (-40ºF to +185ºF) Phase Unbalance Protection • Voltage Unbalance: 2 to 25% adjustable Over/Under Protection • Under: Fixed at ±12% • Over Voltage: Fixed at ±12% • Hysteresis: ±6% Phase Loss Protection • Phase Loss condition = <25% of nominal for any given phase. System will shut down should this condition occur. Delay on Break Timer • Control Voltage: 18-240 VAC • Time Delay: .1 to 5 minutes adjustable Fault Interrogation Delay • Time Delay: 1 to 15 seconds adjustable • Provides a delay between fault detection and system shutdown, eliminating nuisance trips/unnecessary shutdowns Mechanical • Mounting: Surface mount using (2) #8 screws • Termination: Screw terminals • Weight: 12 ounces (341 grams) • Dimensions: 6.5” x 4.25” x 1.4” (16.5 x 10.8 x 3.5 cm) Installation and Setup • Application Guide included with unit All features and specifications subject to change without notice. Application Assistance 800.365.5525 visit us at: www.icmcontrols.com Fax 315.233.5276 Wiring Diagram LI1 LI2 LI3 LINE LINE LINE 3 2 1 LOAD LOAD LOAD 3 2 1 Control Voltage L01 L02 L03 * Thermostat, pressure switch, etc. L0AD System Diagram Line Voltage Control Transformer * LI NE 0C 3 T MA HR DE EE P LI IN PH 1 /N NE 0B 2 TH A90-6 IC E SE 30 M40 US V V A OL A 0 1-80 TAC 5 0-36GE0-6 0H 5-55MO z 25 NIT LI 3 LI 2 LI 1 LR 30 32 0 LO 0C AD3 LI NE 0A 1 OR LO LO 0B AD2 1 LO IN TE IN RRFAUL SE OG T CO AT ND IO S N 2 LO 3 LO 0A AD1 48 0 38 5 E EN LO ER AD D GIZE AM P CO M AD 57 30 10 JU 5 ST 0 0 20 190 8 UN% VO BA LT LA AG NC E E CO VO 19 LTNTRO -24 AG 0 VA E L C 8% 25 % IN FO JUMSTAL 2% R 24 PER L AN CO VA TY TI OL C PE CIPA IN T’S TOG TA R T 1 Contactor 3 4 60 8 6% 4% .1 LT AG 0 23 4 LO CK 15 FR OU FA ON T UL T FABACK T 1 VO HI ULT LT GH AG VO LO E LT W AG E 3 VO 1 12 9 6 RE FR SE M ON T AU AN T BAMOD TO CK E M AU AN TO TI LO M CK MINE DE OU UT LA T ES Y IN 3 2 AL 5 RU 6 AR M N Thermostat Compressor * Install jumper for 24 VAC anticipator type thermostats.