Application Copper Wire. SPECIFICATION : BS 7884

advertisement
Application
Copper Wire.
SPECIFICATION
: BS 7884
Physical, Mechanical and Electrical Properties of Solid, Hard Drawn Copper Wire
Wire Diameter
Resistance at 20°C
Nominal Area of
Cross-Section
Nominal
Max
Min
Nominal
Mass Per
Length
mm²
mm
mm
mm
kg/km
1.43
1.35
1.364
1.337
12.73
12.41
12.66
583
2.01
1.60
1.616
1.584
17.87
8.838
9.018
818
2.27
1.70
1.717
1.683
20.18
7.829
7.988
923
2.54
1.80
1.818
1.782
22.62
6.983
7.125
1035
3.46
2.10
2.121
2.079
30.79
5.130
5.235
1409
3.98
2.25
2.273
2.228
35.35
4.469
4.558
1618
4.75
2.46
2.484
2.435
42.25
3.739
3.816
1932
4.91
2.50
2.525
2.475
43.64
3.620
3.694
1997
5.51
2.65
2.677
2.624
49.03
3.222
3.286
2244
6.16
2.80
2.828
2.772
54.74
2.886
2.944
2505
6.61
2.90
2.929
2.871
58.72
2.690
2.745
2687
7.07
3.00
3.030
2.970
62.84
2.514
2.565
2875
8.04
3.20
3.232
3.168
71.50
2.210
2.254
3271
9.90
3.55
3.586
3.515
87.99
1.795
1.831
4027
11.04
3.75
3.788
3.713
98.19
1.609
1.641
4494
14.52
4.30
4.350
4.250
129.10
1.224
1.253
5675
Nominal
Max
Minimum
Breaking Load
N
Note: Resistance values are calculated from a resistivity of 0.01777 µΩ.m at 20°C. This is equivalent to a conductivity of 97% IACS. Maximum values
of
resistance are calculated from minimum diameters.
Note: Minimum breaking loads for nominal diameters up to and including 4mm are based on the minimum diameter of conductor and a tensile strength
of 415 N/mm² and for nominal diameters greater than 4mm they are based on the minimum diameter of conductor and a tensile strength of 400 N/mm².
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and
reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of
any particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these
products
is
set
forth
in
our
standard
terms
and
conditions
of
sale.
Application
Stranded bare copper conductors are suitable for overhead transmission and distrubution application.
SPECIFICATION
Nominal
Area
: BS 7884
Number of Wires
in Conductor
Nominal Dia. of
Wires in
Conductor
Approx.
Conductor
Diameter
mm
mm
Nominal Weight
Breaking
Load (Min)
10
7
1.35
4.05
1.829
89.92
3752
14
7
1.60
4.80
1.303
126.2
5267
16
3
2.65
5.70
1.106
148.3
6194
16
7
1.70
5.10
1.154
142.4
5946
25
7
2.10
6.30
0.7563
217.3
9073
32
3
3.75
8.06
0.5520
296.9
12400
32
7
2.46
7.38
0.5497
298.2
12442
35
7
2.50
7.50
0.5337
308
12860
50
7
3.00
9.00
0.3706
433.5
18520
50
19
1.80
9.00
0.3819
435.8
17700
70
7
3.35
10.65
0.2646
621.1
25930
70
19
2.10
10.50
0.2806
593.2
24090
95
19
2.50
12.50
0.1980
840.7
34140
100
7
4.30
12.90
0.1810
911.2
36540
120
19
2.80
14.00
0.1578
1055
42830
125
19
2.90
14.50
0.1471
1131
45940
150
19
3.20
16.00
0.1208
1377
55940
150
37
2.25
15.75
0.1264
1334
53880
185
19
3.55
17.75
0.09815
1695
68860
185
37
2.50
17.50
0.1024
1647
66490
240
37
2.87
20.09
0.07878
2175
89477
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and
reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of
any particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these
products
is
set
forth
in
our
standard
terms
and
conditions
of
sale.
Download