Application Copper Wire. SPECIFICATION : BS 7884 Physical, Mechanical and Electrical Properties of Solid, Hard Drawn Copper Wire Wire Diameter Resistance at 20°C Nominal Area of Cross-Section Nominal Max Min Nominal Mass Per Length mm² mm mm mm kg/km 1.43 1.35 1.364 1.337 12.73 12.41 12.66 583 2.01 1.60 1.616 1.584 17.87 8.838 9.018 818 2.27 1.70 1.717 1.683 20.18 7.829 7.988 923 2.54 1.80 1.818 1.782 22.62 6.983 7.125 1035 3.46 2.10 2.121 2.079 30.79 5.130 5.235 1409 3.98 2.25 2.273 2.228 35.35 4.469 4.558 1618 4.75 2.46 2.484 2.435 42.25 3.739 3.816 1932 4.91 2.50 2.525 2.475 43.64 3.620 3.694 1997 5.51 2.65 2.677 2.624 49.03 3.222 3.286 2244 6.16 2.80 2.828 2.772 54.74 2.886 2.944 2505 6.61 2.90 2.929 2.871 58.72 2.690 2.745 2687 7.07 3.00 3.030 2.970 62.84 2.514 2.565 2875 8.04 3.20 3.232 3.168 71.50 2.210 2.254 3271 9.90 3.55 3.586 3.515 87.99 1.795 1.831 4027 11.04 3.75 3.788 3.713 98.19 1.609 1.641 4494 14.52 4.30 4.350 4.250 129.10 1.224 1.253 5675 Nominal Max Minimum Breaking Load N Note: Resistance values are calculated from a resistivity of 0.01777 µΩ.m at 20°C. This is equivalent to a conductivity of 97% IACS. Maximum values of resistance are calculated from minimum diameters. Note: Minimum breaking loads for nominal diameters up to and including 4mm are based on the minimum diameter of conductor and a tensile strength of 415 N/mm² and for nominal diameters greater than 4mm they are based on the minimum diameter of conductor and a tensile strength of 400 N/mm². All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale. Application Stranded bare copper conductors are suitable for overhead transmission and distrubution application. SPECIFICATION Nominal Area : BS 7884 Number of Wires in Conductor Nominal Dia. of Wires in Conductor Approx. Conductor Diameter mm mm Nominal Weight Breaking Load (Min) 10 7 1.35 4.05 1.829 89.92 3752 14 7 1.60 4.80 1.303 126.2 5267 16 3 2.65 5.70 1.106 148.3 6194 16 7 1.70 5.10 1.154 142.4 5946 25 7 2.10 6.30 0.7563 217.3 9073 32 3 3.75 8.06 0.5520 296.9 12400 32 7 2.46 7.38 0.5497 298.2 12442 35 7 2.50 7.50 0.5337 308 12860 50 7 3.00 9.00 0.3706 433.5 18520 50 19 1.80 9.00 0.3819 435.8 17700 70 7 3.35 10.65 0.2646 621.1 25930 70 19 2.10 10.50 0.2806 593.2 24090 95 19 2.50 12.50 0.1980 840.7 34140 100 7 4.30 12.90 0.1810 911.2 36540 120 19 2.80 14.00 0.1578 1055 42830 125 19 2.90 14.50 0.1471 1131 45940 150 19 3.20 16.00 0.1208 1377 55940 150 37 2.25 15.75 0.1264 1334 53880 185 19 3.55 17.75 0.09815 1695 68860 185 37 2.50 17.50 0.1024 1647 66490 240 37 2.87 20.09 0.07878 2175 89477 All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.