bending radius core identification

advertisement
65
BENDING RADIUS
Radius (R)
Outer
diameter (D)
During installation
During installation
During installation
Fixed instalation
Fixed instalation
(Unarmoured or unscreened cables)
R = 6x D
R = 6x D
R = 9x D
R = 4x D
R = 6x D
LKSM-HF
During installation
LKSM-EMC
Fixed instalation
LKSM-VFD
LKMSM-HF
LKAM-HF
LKSM-FRHF
LKAM-FRHF
RFE-HF
RFE-HF(i)
RFA-HF
RFA-HF(i)
RFE-FRHF
RFE-FRHF(i)
RFA-FRHF
RFA-FRHF(i)
PBS
(Armoured or screened cables)
R = 9x D
R = 6x D
Cable outer diameter, mm.
1 – 10
10,1 – 20
20,1 – 30
Tolerance
±0,5mm
±1,0mm
±1,5mm
Cable outer diameter, mm.
30,1 – 40
40,1 – 50
50,1 – 60
< 25mm
< 25mm
> 25mm
< 25mm
> 25mm
8/2010
DIAMETER TOLERANCE
LKM-HF
LKMM-HF
LKM-FRHF
LKEM-HF
Tolerance
±2,0mm
±2,5mm
±3,0mm
CORE IDENTIFICATION
0,6/1kV
Normal type
G-type
with earth
conductor)
1-core
BK
2-cores
BN BU
3-cores
BN BK
4-cores
5-cores
GY
Y/G BU
BN
BU BN
Y/G BN
GY BK
GY BK
1
3
Y/G
BU
GY
BN
BK
3
Y/G
4
6
5
4
2
2
7-cores
and above
7
6
1
2
5
Black numbers
on white base
3
1
4
5
Black numbers
on white base
Last core
yellow/green.
BU = Blue, BN = Brown, BK = Black, GY = Grey, Y/G = Yellow/Green
250V
Pair
number
1
2
3
4
5
6
etc.
60V
(PBS)
TECHNICAL INFORMATION
Recommended minimum bending
radius, ( R ) :
a
b
1
3
5
7
9
11
2
4
6
8
10
12
TECHNICAL INFORMATION
66
CURRENT RATING
"Current rating (A) at an ambient temperature of 45°C
according to the standard IEC 60092-352
0,6/1 kV +90°C marine cables."
Current carrying capacities in continous service at
maximum rated conductor temperature of +90°C.
For class 2 conductor cables
Size
N
Factor, n
mm2
8/2010
For continuous service. Continuous service for a cable is
to be considered as a current-carrying service (with
constant load) having a duration longer than three times
the thermal time constant of the cable, i.e. longer than
the critical duration(see short time duty).
1,5
2,5 mm2
4 mm2
6 mm2
10 mm2
16 mm2
25 mm2
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2
150 mm2
185 mm2
240 mm2
300 mm2
1
2
3
4
5
7
10
12
14
16
19
24
27
37
1
23
30
40
52
72
96
127
157
196
242
293
339
389
444
522
601
0,85
20
26
34
44
61
82
108
133
167
206
249
288
331
377
444
511
0,7
16
21
28
36
50
67
89
110
137
169
205
237
272
311
365
421
0,7
16
21
28
36
50
67
89
110
137
169
205
237
272
311
365
421
0,58
13
17
23
30
42
56
–
–
–
–
–
–
–
–
–
–
0,52
12
16
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0,46
11
14
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0,44
10
13
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0,41
9
12
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0,40
9
12
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0,37
9
11
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0,35
8
11
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0,33
8
10
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0,30
7
9
–
–
–
–
–
–
–
–
–
–
–
–
–
–
For class 5 conductor cables
Size
N
Factor, n
16mm2
25mm2
35mm2
50mm2
70mm2
95mm2
For class 5 conductor cables
1
2
3
4
5
1
94
123
153
196
240
284
0,85
80
105
130
167
204
241
0,7
66
86
107
137
168
199
0,7
66
86
107
137
168
199
0,58
55
–
–
–
–
–
Size
N
Factor, n
120mm2
150mm2
185mm2
240mm2
300mm2
1
2
3
4
5
1
331
381
429
507
582
0,85
281
324
365
431
495
0,7
232
267
300
355
407
0,7
232
267
300
355
407
0,58
–
–
–
–
–
SHORT CIRCUIT CURRENT
Maximum permissible short circuit current.
0,6/1 kV +90°C marine cables.
Based on formula:
Ik = 226
X
S
t
X
S
t
X
In
234 + Tk
234 + Tb
Formula 1:
Ik = 146
Ik
S
t
Tk
=
=
=
=
Maximum permissible short circuit current.
Cross-section of the conductor in mm2.
Duration of the short circuit in s.
Maximum rated conductor temperature,
short circuit, °C
Tb = Maximum rated conductor temperature,
normal, °C
Formula 1: For 0,6/1kV cable with XLPE or HF90 with
maximum operating temperature of +90°C (Tb) and
short circuit temperature of +250°C (Tk).
Cross-section of
the conductor
in mm2
1,5
2,5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
Duration of the short circuit in s.
0,2
0,5
0,8
1,3
2,0
3,3
5,2
8,2
11,4
16,3
22,9
31,0
39,2
49,0
60,4
78,4
97,9
0,5
1
2
3
0,3 0,2 0,2 0,1
0,5 0,4 0,3 0,2
0,8 0,6 0,4 0,3
1,2 0,9 0,6 0,5
2,1 1,5 1,0 0,8
3,3 2,3 1,7 1,3
5,2 3,7 2,6 2,1
7,2 5,1 3,6 3,0
10,3 7,3 5,2 4,2
14,5 10,2 7,2 5,9
19,6 13,9 9,8 8,0
24,8 17,5 12,4 10,1
31,0 21,9 15,5 12,6
38,2 27,0 19,1 15,6
49,6 35,0 24,8 20,2
61,9 43,8 31,0 25,3
Short circuit current in kA
10
0,1
0,1
0,2
0,3
0,5
0,7
1,2
1,6
2,3
3,2
4,4
5,5
6,9
8,5
11,1
13,9
67
SHORT TIME DUTY
If a cable is intended to supply motor
or equipment operating for periods of half an hour or
one hour, its current rating given in table “current
rating”, may be increased using the relevant
correction factors given by formula:
correction =
factor
1,12
1-exp(-ts/T)
( ts = service time, min. T = Time constant, min.)
T = 0,245 x d 1,35
(d = Overall diameter of the cable, mm.)
Overall
diameter of
the cable,
mm.
Service
time, min.
1
2
3
4
5
6
7
8
9
10
20
30
40
50
60
Time
Critical
constant, duration,
min.
min.
30
60
T
3x T
1,058
1,058
1,058
1,058
1,058
1,058
1,058
1,059
1,059
1,061
1,126
1,255
1,403
1,554
1,705
1,058
1,058
1,058
1,058
1,058
1,058
1,058
1,058
1,058
1,058
1,066
1,105
1,173
1,254
1,341
0,245
0,625
1,08
1,59
2,15
2,75
3,39
4,06
4,76
5,48
14,0
24,2
35,6
48,2
61,6
0,735
1,87
3,24
4,78
6,46
8,26
10,2
12,2
14,3
16,5
41,9
72,5
107
145
185
Intermittent service
Correction factor for intermittent service
according to the standard IEC 60092-352
The correction factor given hereby has been
roughly calculated for periods of 10 min,
of which 4 min are with a constant load and
6 min without load.
Intermittence period = 10min.
Intermittence ratio = 40%.
Fi=
1-exp(-10/T)
1-exp(-4/T)
8/2010
Correction factor.
TECHNICAL INFORMATION
Short time duty according to the standard
IEC 60092-352 0,6/1 kV +90°C
marine cables.
Overall diameter of
the cable, mm.
Correction
factor.
1
2
3
4
5
6
7
8
9
10
20
30
40
50
60
1,000
1,001
1,012
1,042
1,083
1,127
1,170
1,208
1,242
1,273
1,433
1,490
1,518
1,534
1,544
8/2010
TECHNICAL INFORMATION
68
SHORT CIRCUIT FACTORS
Short circuit factors for single (1) core cables
Cross-section of
the conductor
in mm2
1,5
2,5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
Duration of the short circuit in s.
0,2
0,5
1
2
3
23,3
27,2
32,6
38,4
46,0
55,0
65,3
73,7
85,9
95,2
106,9
115,2
127,2
137,3
150,7
166,0
14,7
17,2
20,6
24,3
29,1
34,8
41,3
46,6
54,3
60,2
67,6
72,9
80,4
86,8
95,3
105,0
10,4
12,2
14,6
17,2
20,6
24,6
29,2
33,0
38,4
42,6
47,8
51,5
56,9
61,4
67,4
74,2
7,4
8,6
10,3
12,1
14,5
17,4
20,6
23,3
27,2
30,1
33,8
36,4
40,2
43,4
47,6
52,5
6,0
7,0
8,4
9,9
11,9
14,2
16,9
19,0
22,2
24,6
27,6
29,8
32,8
35,4
38,9
42,9
Short circuit factors for two (2) core cables
Cross-section of
the conductor
in mm2
1,5
2,5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
Duration of the short circuit in s.
0,2
0,5
1
2
3
27,2
32,6
38,4
45,6
54,4
64,5
77,7
84,6
98,9
114,3
–
–
–
–
–
–
17,2
20,6
24,3
28,8
34,4
40,8
49,2
53,5
62,6
72,3
–
–
–
–
–
–
12,2
14,6
17,2
20,4
24,3
28,8
34,8
37,9
44,2
51,1
–
–
–
–
–
–
8,6
10,3
12,1
14,4
17,2
20,4
24,6
26,8
31,3
36,1
–
–
–
–
–
–
7,0
8,4
9,9
11,8
14,0
16,7
20,1
21,9
25,5
29,5
–
–
–
–
–
–
Short circuit factors for three (3) and
four (4) core cables
Short circuit factors for cables with a core no.
from five (5) to thirtyseven (37)
The conductor
in mm2
The conductor
in mm2
1,5
2,5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
Duration of the short circuit in s.
0,2
0,5
1
2
3
32,6
38,9
45,0
54,4
65,3
78,0
91,7
108,8
120,9
134,4
151,3
163,2
181,4
198,0
214,7
236,0
20,6
24,6
28,5
34,4
41,3
49,3
58,0
68,8
76,5
85,0
95,7
103,2
114,7
125,2
135,8
149,3
14,6
17,4
20,1
24,3
29,2
34,9
41,0
48,7
54,1
60,1
67,7
73,0
81,1
88,6
96,0
105,5
10,3
12,3
14,2
17,2
20,6
24,7
29,0
34,4
38,2
42,5
47,8
51,6
57,4
62,6
67,9
74,6
8,4
10,0
11,6
14,0
16,9
20,1
23,7
28,1
31,2
34,7
39,1
42,1
46,8
51,1
55,4
60,9
5x1,5
5x2,5
5x4
5x6
5x10
5x16
7x1,5
7x2,5
10x1,5
10x2,5
12x1,5
12x2,5
14x1,5
14x2,5
16x1,5
16x2,5
19x1,5
19x2,5
24x1,5
24x2,5
27x1,5
27x2,5
37x1,5
37x2,5
Duration of the short circuit in s.
0,2
0,5
1
35,0
45,3
52,2
65,3
74,2
93,3
40,8
51,0
44,5
58,3
49,0
62,8
49,0
62,8
54,4
68,0
54,4
74,2
61,2
81,6
61,2
81,6
70,0
90,7
22,1
28,7
33,0
41,3
46,9
59,0
25,8
32,3
28,2
36,9
31,0
39,7
31,0
39,7
34,4
43,0
34,4
46,9
38,7
51,6
38,7
51,6
44,2
57,4
15,6
20,3
23,4
29,2
33,2
41,7
18,3
22,8
19,9
26,1
21,9
28,1
21,9
28,1
24,3
30,4
24,3
33,2
27,4
36,5
27,4
36,5
31,3
40,6
2
3
11,1
14,3
16,5
20,6
23,5
29,5
12,9
16,1
14,1
18,4
15,5
19,9
15,5
19,9
17,2
21,5
17,2
23,5
19,4
25,8
19,4
25,8
22,1
28,7
9,0
11,7
13,5
16,9
19,2
24,1
10,5
13,2
11,5
15,1
12,6
16,2
12,6
16,2
14,0
17,6
14,0
19,2
15,8
21,1
15,8
21,1
18,1
23,4
69
VOLTAGE DROP
Size
1,5 mm2
2,5 mm2
4 mm2
6 mm2
10 mm2
16 mm2
25 mm2
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2
150 mm2
185 mm2
240 mm2
300 mm2
Resistance
at +20°C
ohm/km
Resistance
at +90°C
ohm/km
Voltage
reduction
mV/Am *)
Resistance
at +45°C
ohm/km
Current
rating
A **)
Voltage
reduction
mV/m ***)
12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
15,4
9,45
5,88
3,93
2,33
1,47
0,927
0,668
0,493
0,342
0,246
0,195
0,158
0,1264
0,0961
0,0766
30,9
18,9
11,8
7,85
4,67
2,93
1,85
1,34
0,99
0,68
0,49
0,39
0,32
0,25
0,19
0,15
13,3
8,14
5,06
3,38
2,01
1,26
0,798
0,575
0,425
0,294
0,212
0,168
0,136
0,1088
0,0828
0,0660
23
30
40
52
72
96
127
157
196
242
293
339
389
444
522
601
0,61
0,49
0,41
0,35
0,29
0,24
0,20
0,18
0,16
0,14
0,12
0,11
0,10
0,096
0,086
0,078
TECHNICAL INFORMATION
Cable types: LKM-HF, LKSM-HF, LKAM-HF, LKM-FRHF, LKSM-FRHF (Cables with class 2 conductor)
Cable types: LKM-HF FLEX, LKSM-HF FLEX, LKEM-HF (Cables with class 5 conductor)
0,75mm2
1,0mm2
1,5mm2
2,5mm2
4mm2
6mm2
10mm2
16mm2
25mm2
35mm2
50mm2
70mm2
95mm2
120mm2
150mm2
185mm2
240mm2
300mm2
Resistance
at +20°C
ohm/km
Resistance
at +90°C
ohm/km
Voltage
reduction
mV/Am *)
Resistance
at +45°C
ohm/km
Current
rating
A **)
Voltage
reduction
mV/m ***)
26,0
19,5
13,3
7,98
4,95
3,30
1,91
1,21
0,780
0,554
0,386
0,272
0,206
0,161
0,129
0,106
0,0801
0,0641
33,2
24,9
17,0
10,18
6,31
4,21
2,44
1,54
0,995
0,706
0,492
0,347
0,263
0,205
0,164
0,135
0,102
0,082
66,3
49,7
33,9
20,4
12,6
8,42
4,87
3,09
1,99
1,41
0,98
0,69
0,53
0,41
0,33
0,27
0,20
0,16
28,6
21,4
14,6
8,76
5,44
3,62
2,10
1,33
0,857
0,608
0,424
0,299
0,226
0,177
0,142
0,116
0,088
0,070
14
17
22
30
39
50
71
94
123
153
196
240
284
331
389
444
522
601
0,80
0,73
0,64
0,53
0,42
0,36
0,30
0,25
0,21
0,19
0,17
0,14
0,13
0,12
0,11
0,10
0,09
0,08
Cable types: LKSM-HF 250V, RFE-HF, RFE-HF(i), RFA-HF, RFA-HF(i), RFE-FRHF, RFE-FRHF(i), RFA-FRHF, RFA-FRHF(i)
Size
0,5 mm2
0,75 mm2
1,5 mm2
Resistance
at +20°C
ohm/km
Maximum
conductor
temperature, °C
Resistance
at +45°C
ohm/km
Voltage
reduction
mV/Am at +45°C
Resistance
at +90°C
ohm/km
Voltage
reduction
mV/Am at +90°C
40,4
26,0
12,8
90
90
90
44,4
28,6
14,1
88,7
57,1
28,1
51,5
33,2
16,3
103,0
66,3
32,6
*) at +90°C
**) For continuous service (single core, ambient temperature +45°C)
***) at maximum current rating for continuous service at +45°C
8/2010